LV circuit breakers and switch-disconnectors Compact Merlin Gerin 80 to 3200 A


S mpact N New Co

Catalogue

Building a New Electric World

046751

Compact NS 80 A

045345

Compact NS 100 to 250 A

053100

colibris

Things
Compact NS 400 to 630 A

will the

never be same
New Compact NS, setting the standard, once again...
The launch of Merlin Gerin Compact NS in 1994 revolutionised the world of moulded-case circuit breakers. Innovative, flexible and attractive, Compact NS rapidly set the standard in its field. Today, Schneider Electric continues to innovate, extending the Compact NS range to high power ratings to offer a comprehensive and consistent range from 80 to 3200 A. Equipped with the new generation of Micrologic control units, Compact NS630b to 3200 circuit breakers integrate electrical measurement and analysis functions. The communications option makes it possible to control power consumption, simplify maintenance and improve operating comfort. A wide range of optimised auxiliaries and accessories is also available to meet the needs of even more applications.

E45151

Compact NS 630 to 1600 A

E45178

Compact NS, simply a step ahead


Compact NS 1600 to 3200 A

Compact NS, even more applications...


Protection of LV distribution systems
E20999

p. 14
Protection for: b distribution systems supplied by transformers b distribution systems supplied by engine generator sets b long cables in IT and TN systems. Installation : b in power switchboards b on DIN rails (see page 42) Special applications: b single-phase and two-phase systems (see page 34) b 1000 V distribution systems (see page 36) b 400 Hz distribution systems (see page 38) b DC systems (see page 40). All circuit breakers in the Compact NS range offer positive contact indication and are suitable for isolation in compliance with standards IEC 60947-1 and 2.

push to trip

Protection of motor feeders


E26988

p. 44
When combined with a motor starter, Compact NS circuit breakers protect the cables and the starter against short-circuits. Equipped with an electronic trip unit, Compact NS circuit breakers also protect the cables, starter and motor against overloads. The exceptional current-limiting capacity of Compact NS circuit breakers automatically ensures type-2 coordination with the motor starter, in compliance with standard IEC 60947-4-1.

Protection of machines
E44356

p. 52
The different circuit-breaker versions in the Compact NS range are designed to meet the specific requirements of machines: b compliance with international standards IEC 60947-2 and UL 508 / CSA 22-2 No. 14 b compliance with U.S. standard UL 489 b protection against overloads and short-circuits b positive contact indication b installation in universal and functional enclosures.

Earth-leakage protection
E44357

p. 56
Additional earth-leakage protection protects life and property against the risks of faulty insulation in the installation. Depending on the circuit breaker, earth-leakage protection is provided by: b adding a Vigi module to the circuit breaker b using a specific Micrologic control unit b using a Vigirex relay and separate toroids.

M G

Schneider Electric

Switch-disconnectors
E21272

p. 60
A switch-disconnector version of Compact NS circuit breakers exists for circuit control and isolation. All the additional functions may be combined with the basic switch-disconnector function, including: b earth-leakage protection b motor mechanism b ammeter, etc. For information on other switch-disconnector ranges, see the Interpact (offering positive contact indication and visible break) and Fupact (fuse switch) catalogues.

push to trip

Service connection
E56631

p. xx
Compact NS service-connection circuit breakers are specially designed for the service-connection function: b lead seals and locking systems b tripping curves certified by utilities b fast overload curves to limit the power supplied, etc. Interpact INV switch-disconnectors offering visible break (see the corresponding catalogue) can be combined with Compact NS circuit breakers to constitute the various types of service connections and meet the needs of all installation configurations.
test

5...8

push to trip

STR
90 %Ir 105 alarm

22 DE

50/60Hz

Im Ir .9 .85 .8 .98 .7 .63 xIn 1 .95 3 8 2 1.5 xIr 10 4 5 6 Ir Im

push to trip

STR
90 %Ir 105 alarm

22 DE
test

50/60Hz

Im Ir .9 .85 .8 .98 .7 .63 xIn 1 .95 3 8 2 1.5 xIr 10 4 5 6 Ir Im

Source-changeover systems
E32454

p. 68 (see also the "Source-changeover systems" catalogue)


To ensure a continuous supply of power, some electrical installations are connected to two power sources: b a normal source b a replacement source on hand to supply the installation when the normal source is not available. A mechanical and/or electrical interlocking system between two Interpact, Compact or Masterpact devices avoids all risk of parallel connection of the sources during switching. A source-changeover system can be: b manual with mechanical interlocking between the devices b remote operated when an electrical interlocking function in added b automatic when a controller is added to manage switching from one source to the other on the basis of external parameters.

UL 489 applications
Compact NS circuit breakers also meet the requirements of applications governed by standard UL 489 (see the corresponding catalogue).

Schneider Electric

...a solution for all installation configurations


The Compact NS range now covers all ratings from 80 to 3200 A: b Compact NS80 to 1600 A, fixed, withdrawable, front or rear connections, manual or electrical operation. b Compact NS1600 to 3200 A, fixed, front connection, manual operation.
E27836

Compact NS100 to 630


Breaking capacity Icu at 415 V
E58549

compact

NS 250 N
Ui750V Uimp8kV

Ue (V)
220/240 380/415 440 500 525 660/690 250

Icu (kA)
85 36 35 30 22 8 50

The rating plates on the front panel of each device indicate the breaking capacity (N, H or L).

Ics = 100 % Icu

IEC 947-2

cat A

UTE VDE BS CEI UNE NEMA

N: standard breaking capacity


E27837

compact

NS 250 H
Ui750V Uimp8kV

Ue (V)
220/240 380/415 440 500 525 660/690 250

Icu (kA)
100 70 65 50 35 10 85

Ics = 100 % Icu

Compact NS630b to 1600


cat A

IEC 947-2

UTE VDE BS CEI UNE NEMA

H: high breaking capacity


E27838 E58550
compact

Breaking capacity Icu at 415 V

NS 250 L
Ui750V Uimp8kV

Ue (V)
220/240 380/415 440 500 525 660/690 250

Icu (kA)
150 150 130 70 50 20 100

Ics = 100 % Icu

IEC 947-2

cat A

UTE VDE BS CEI UNE NEMA

L: very high breaking capacity

Total discrimination as standard


E22051

Compact NS1600b to 3200


Breaking capacity Icu at 415 V
E58551
push to trip

Discrimination between Compact NS circuit breakers is total for all types of faults (overloads, high or low shortcircuits) and whatever the type of trip unit used with the circuit breaker.

Schneider Electric

041625

Compact NS400 with electronic trip unit

041879

Manual Compact NS250 with thermal-magnetic trip unit

053100

047313

Compact NS250 with motor mechanism

Plug-in Compact NS250 on base

Withdrawable Compact NS250 on chassis

E45151

Manually operated Compact NS800

E45163

Electrically operated Compact NS800

E45178

Compact NS2000 (manually operated only)


Schneider Electric

...simplified installation

Compact circuit breakers make it possible to standardise switchboards for faster installation and fewer errors. All type L Compact circuit breakers (150 kA) are housed in the same case as the type N and type H models with the same ratings. Compact circuit breakers up to 1600 A can be easily installed side-by-side in a minimum amount of space.

5 frame sizes from 80 to 3200 A


045345 053100 046751

80 A

100 to 250 A

400 to 630 A

E45151

630 to 1600 A

E45178

1600 to 3200 A

Many connection possibilities


Numerous connection possibilities, including front and rear connections for bare cables, cable lugs or bars, as well as plug-in or withdrawable versions, are available using accessories that can be rapidly added to the circuit breaker.
041650

Connection parts for Compact NS

Plug-in and withdrawable versions


Plug-in and withdrawable versions for: b fast removal or insertion of the circuit breaker without exposure to live parts b standby outgoing circuits ready for wiring and circuit breaker installation at a later date b visible break possibility.
042788 E32455

Busways
Compact NS circuit breakers up to 630 A can be installed in tap-off units of the Telemecanique Canalis range of busbar trunking.

Schneider Electric

...optimised protection and accurate measurements


Each Compact NS circuit breaker provides different types of protection, depending on the trip unit or control unit selected. Additional measurement and indication functions are available: b on Compact NS100 to 630, by adding an electrical auxiliary to the circuit breaker b on Compact NS630b to 3200, depending on the Micrologic control unit selected.
Compact NS100 to 630
On Compact NS100 to NS250 circuit breakers, the thermal-magnetic and electronic trip units are interchangeable and may be rapidly fitted to the circuit breakers. It is therefore easy to change the protection of a given circuit following a modification in an installation. On Compact NS400 and NS630 circuit breakers, the electronic trip units are interchangeable, plug-in modules. The STR53UE trip unit offers a large number of protection settings: standard: b specific indication of the different types of faults (overloads, short-circuits, etc.) optional: b built-in ammeter b earth-fault protection b communication: transmission of all information concerning circuit-breaker operation to an electrical distribution control, monitoring and automation system via Digipact modules (see page 72).
041625 048287 041638

TM thermal-magnetic trip unit


045212

Voltage presence indication module

Compact NS250

041641

STR electronic trip unit

Ammeter module

Compact NS630b to 3200


Compact NS630b to 3200 circuit breakers are equipped with Micrologic control units that are interchangeable on site. Micrologic 2.0 and 2.0 A control units offer standard protection. Micrologic 5.0 and 5.0 A control units offer selective protection that can be completed by earth-fault protection on Micrologic 6.0 A and earth-leakage protection on Micrologic 7.0 A control units. The ammeter version of Micrologic control units provides current measurements. These units are equipped with a digital display and bargraph, used in conjunction with simple navigation buttons. Access to the desired parameters and settings is direct and navigation between screens is intuitive. Settings are greatly simplified by direct display on the screen.
E45151

Micrologic 2.0, 5.0 Compact NS1600

056479

Micrologic 2.0 A, 5.0 A, 6.0 A, 7.0 A

056480

Schneider Electric

...an optimised range

A complete system of add-on modules for Compact NS: Fewer catalogue numbers means immediate availability of parts for all solutions. Trip units, control units, auxiliaries and installation and connection accessories are the same for a given frame size and often for a number of frame sizes (e.g. auxiliary contacts, MN and MX voltage releases, etc.): b Compact NS800 to NSA160 b Compact NS100 to NS250 b Compact NS400 to NS630 b Compact NS630b to 1600 b Compact 1600b to 3200.

16 15

E24603

12

1 7 9 10 8 11

13

2 2 4 3 6 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Breaking unit Trip units or control units Vigi earth-leakage protection module Insulation monitoring module Voltage presence indicator Ammeter module MN and MX voltage releases Multifunction auxiliary contact Direct rotary handle Extended rotary handle Motor mechanism Plug-in base Connection of auxiliary circuits to plug-in base or withdrawable chassis Connection accessories Short terminal shields Long terminal shields

Schneider Electric

...modern products
Open communication ...
Equipped with a communications option, Compact NS circuit breakers fit perfectly in the Digipact installationmanagement system or other supervision systems. Via a PC or a PLC, the operator can: b display the status of each circuit breaker and its settings b control the circuit breakers b display faults b access measurements supplied by the electronic control units.
E37615

s PM150 power s management

meter

s circuit breaker

or other power actuator

s ModBus / JBus

s CLS150 indication

and local-control module


s Digipact internal bus

s Multi 9 control s DC150 data concentrator

device and ATB 1S interface

s UA150 automatic

source-changeover controller

s RHU residualcurrent relay with separate toroid s RMH earthleakage monitor

Digipact installation-management system

... and protection of the environment


oiseaux

Schneider Electric fully takes into account environmental requirements, starting right from the design stage of products through to the end of their service life: b the materials used for Compact NS are not dangerous for the environment b the production facilities are non-polluting in compliance with the ISO 14001 standard b filtered breaking for the high ratings eliminates pollution in the switchboard b the energy dissipated per pole is low, making energy losses insignificant b the materials are marked to facilitate sorting for recycling at the end of product service life.

Schneider Electric

10

Schneider Electric

Compact NS

Functions and characteristics

Selection of a Compact NS circuit breaker depends on the application requiring protection (distribution systems, motor feeders, etc.) and on the prescribed installation conditions (see section Installation, connection and accessories).

Presentation

General characteristics Protection of distribution systems


Overview of solutions Compact NB circuit breakers up to 600 A Compact NS circuit breakers up to 630 A Compact NS circuit breakers from 630 up to 3200 A TM and STR trip units for Compact NS100 to 250 MP and STR trip units for Compact NS400 to 630 Micrologic control units for Compact NS630b to 3200 Special cases: b single-phase and two-phase systems b 1000 V systems b 400 Hz applications b circuit breaker selection for DC applications b incoming circuit breakers in final distribution NSA160

12 14
14 16 18 20 22 24 28 34 36 38 40 42

Motor protection
Overview of solutions Compact NS80H-MA NS100 to 630 circuit breakers with MA magnetic trip units NS100 to 250 circuit breakers with STR22ME electronic trip unit NS400 to 630 circuit breakers with STR43ME electronic trip unit

44
44 46 47 48 50

Protection of industrial control panels


Overview of solutions Circuit breaker NSC100N Trip units, auxiliaries, installation enclosures UL508 / CSA 22-2 no. 14 marking

52
52 53 54 55

Earth-leakage protection
Overview of solutions Add-on Vigi module (Vigicompact) for Compact NS100 to 630

56
56 57

Control and isolation


Overview of solutions Compact NSA125NA and NSA160NA switch-disconnectors Compact NSC100 and NS100 to 630NA switch-disconnectors Compact NS630bNA to 1600NA switch-disconnectors Compact NS1600b to 3200NA switch-disconnectors

58
58 60 62 64 66

Source-changeover systems
Presentation Manual source-changeover systems Remote-operated systems Controllers

68
68 69 70 71

Communication
Compact NS100 to 630 COM option in Compact Compact in a communication network

72
72 74, 78 76

Electrical and mechanical accessories

80

Compact NB50 and 100 80, 82 Compact NB250 to 600 81, 84 Compact NS80H-MA, NSC100N 88, 90 Compact NSA160 89, 90 Compact NS100 to 630 (fixed version) 94,96 Compact NS100 to 630 (plug-in and withdrawable version) 95, 96 Compact NS630b to 1600 (fixed version) 114, 116 Compact NS630b to 1600 (withdrawable version) 115, 116 Compact NS1600b to 3200 (fixed version) 134

Test equipment Display modules


Installation recommendations Dimensions, volumes Connection Electrical diagrams Additional characteristics Catalogue numbers
Schneider Electric

139 140
143 165 205 221 251 267
11

Functions and characteristics

General characteristics

E18567

Compliance with standards


compact NS160 H
Ui 750V. Uimp 8kV.
Ue (V) 220/240 380/415 440 500/525 660/690 250 Icu (kA) 100 70 65 50 10 85

Ics = 100% Icu cat A IEC 947.2


UTE VDE BS CEI UNE NEMA

Standardised characteristics indicated on the rating plate: Ui: rated insulation voltage Uimp: rated impulse withstand voltage Icu: ultimate breaking capacity, for various values of the rated operational voltage Ue cat: utilisation category Icw: rated short-time withstand current Ics: service breaking capacity suitable for isolation

Compact NS circuit breakers and auxiliaries comply with the following: b international recommendations: v IEC 60947-1 - general rules v IEC 60947-2 - circuit breakers v IEC 60947-3 - switches, disconnectors, switch-disconnectors, etc. v IEC 60947-4 - contactors and motor starters v IEC 60947-5.1 and following - control circuit devices and switching elements; automatic control components b European (EN 60947-1 and EN 60947-2) and the corresponding national standards: v France NF v Germany VDE v U.K. BS v Australia AS v Italy CEI b the specifications of the marine classification companies (Veritas, Lloyds Register of Shipping, Det Norske Veritas, etc.) b French standard NF C 79-130 and the recommendations issued by the CNOMO organisation for the protection of machine tools. For U.S. UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please consult us.

Pollution degree
Compact NS circuit breakers are certified for operation in pollution-degree III environments as defined by IEC standard 60947 (industrial environments).

Tropicalisation
Compact NS circuit breakers have successfully passed the tests prescribed by the following standards for extreme atmospheric conditions: b IEC 68-2-1 - dry cold (-55 C) b IEC 68-2-2 - dry heat (+85 C) b IEC 68-2-30 - damp heat (95 % relative humidity at 55 C) b IEC 68-2-52 - salt mist (severity level 2).

Environmental protection
Compact NS circuit breakers take into account important concerns for environmental protection. Most components are recyclable and the parts of Compact NS630b to NS3200 circuit breakers are marked as specified in applicable standards.

Ambient temperature

b Compact NS circuit breakers may be used between -25 C and +70 C. For temperatures higher than 40 C (65 C for circuit breakers used to protect motor feeders), devices must be derated as indicated in the documentation. b circuit-breakers should be put into service under normal ambient operatingtemperature conditions. Exceptionally, the circuit breaker may be put into service when the ambient temperature is between -35 C and -25 C. b the permissible storage-temperature range for Compact NS circuit breakers in the original packing is -50 C (1) to +85 C.

Discrimination
As standard, the Compact NS range ensures discrimination between two circuit breakers positioned in series in an installation.
E22037

CB1

CB2

(1) -40 C for Micrologic control units with an LCD screen.

12

Schneider Electric

044 334

Positive contact indication


All Compact NS circuit breakers are suitable for isolation as defined in IEC standard 60947-2: b the isolation position corresponds to the O (OFF) position b the operating handle cannot indicate the OFF position unless the contacts are effectively open b padlocks may not be installed unless the contacts are open. Installation of a rotary handle or a motor mechanism does not alter the reliability of the position-indication system. The isolation function is certified by tests guaranteeing: b the mechanical reliability of the position indication system b the absence of leakage currents b overvoltage withstand capacity between upstream and downstream connections.

E18569

Installation in class II switchboards


All Compact NS circuit breakers are class II front face devices. They may be installed through the door of class II switchboards (as per IEC standard 60664), without downgrading switchboard insulation. Installation requires no special operations, even when the circuit breaker is equipped with a rotary handle or a motor mechanism.

Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102 (IK degree of protection against external mechanical impacts).

Bare circuit breaker with terminal shields


E18570

With toggle

IP40

IK07

push to trip

E28439

With direct rotary handle standard / VDE


ON I

IP40

IK07

push to trip

O OFF

Circuit breaker installed in a switchboard


With toggle
E21277

IP40

IK07

push to trip

ON I

With direct rotary handle standard / VDE MCC CNOMO

E28440

IP40 IP435 IP547

IK07

push to trip

O OFF

With extended rotary handle


E28441

IP55

IK08

ON I

push to trip

O OFF

ON I

OFF

E28442

With motor mechanism

IP40

IK07

push to trip

1 manu /auto

O
push OFF

I
push ON

Schneider Electric

13

Functions and characteristics

Protection of distribution systems Overview of solutions

Protection of distribution systems means protection of: b systems supplied by a transformer b systems supplied by an engine generator set b long cables in IT and TN systems.

E58563

E43842

Power distribution
Selection of circuit breakers up to 630 A
Rated current (A)
E20999
push to trip

page 18
60 400
NS400
053100

12.5 12.5 125 100


NS125E NS100

12.5 12.5 160 250


NS160 NS250

250 630
NS630

Compact

Breaking capacity (kA rms) 380/415 V

E N H L

045345

16 25 70 150 36 70 150 36 70 150 45 70 150 45 70 150

Accompanying trip units up to 630 A

page 22

Interchangeable thermal-magnetic and electronic trip units for NS100 to 630 and built-in thermal-magnetic trip unit for Compact NS125E

+
E43843

Selection of circuit breakers from 630 to 3200 A page 20


Rated current (A)
Compact
E45151

250 320 630 800


NS630b NS800

400 1000
NS1000

500 1250
NS1250

640 1600
NS1600

Special case of DC systems: TM thermal-magnetic trip units for Compact NS100 to 250 and MP magnetic trip units for Compact NS400 and 630 may be used to protect DC distribution systems.

Breaking capacity (kA rms) 380/415 V

N H L

50 70 150

50 70 150

50 70 150

50 70 -

50 70 -

Rated current (A)


Compact
E45178

640 800 ... 1600 2000


NS1600b NS2000

1000 1250 2500 3200


NS2500 NS3200

Breaking capacity (kA rms) 380/415 V

N H

70 85

70 85

70 85

Accompanying control units up to 3200 A

page 28

Micrologic electronic control units may be used on all Compact NS630b to NS3200 circuit breakers and can be changed on site.

14

Schneider Electric

Power distribution (cont.)


Single-phase or two-phase distribution
Rated current (A)
Compact
86099

page 34
160 250

16 100
NS100 1P/2P
86101

125 160

NS160 1P/2P NS250 1P Built-in thermal-magnetic trip units

Breaking capacity (kA rms) 220 V

N H

1P 25 40

2P 85 100

1P 25 40

2P 85 100

1P 25 -

1000 V distribution
Rated current (A)
Compact
053182

page 36
60 400
NS400 1000V Breaking capacity: 10 kA rms at 1000 V STR23SP electronic trip unit specially designed for 1000 V applications

E21000

Incoming circuit breakers in final distribution


Rated current (A)
048016

page 42

16 160
NSA160 Breaking capacity (kA rms) 380/415 V: E : 16 kA N : 30 kA Built-in trip unit

Compact installation on a DIN rail

Schneider Electric

15

Functions and characteristics

Protection of distribution systems Compact NS circuit breakers up to 630 A


Compact circuit breakers
Number of poles Control manual electric fixed plug-in (on base) withdrawable (on chassis) Electrical characteristics as per IEC 60947-2 and EN 60947-2 Rated current (A) In 40 C 65 C Rated insulation voltage (V) Ui Rated impulse withstand voltage kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Type of circuit breaker Ultimate breaking capacity (kA rms) lcu AC 50/60 Hz 220/240 V 380/415 V 440 V 500 V 525 V 660/690 V 250 V (1P) 500 V (2P in series) toggle direct or extended rotary handle front connection rear connection front connection rear connection front connection rear connection

045345

Connections

Compact NS250H

048286

DC Service breaking capacity Suitability for isolation Utilisation category Durability (C-O cycles) lcs % Icu

mechanical electrical

440 V

In/2 In

Electrical characteristics as per NEMA AB1 Breaking capacity (kA)

240 V 480 V 600 V 240 V 480 V 600 V

Compact NS630L

Electrical characteristics as per UL508 Breaking capacity (kA)

Protection Trip units Overload protection Short-circuit protection Earth-fault protection Zone selective interlocking Add-on earth-leakage protection Current measurements

long time Ir (In x ) short time lsd (Ir x ) instantaneous Ii (In x ) lg (In x ) ZSI add-on Vigi module combination with Vigirex relay

Additional measurement, indication and control auxiliaries Indication contacts MX shunt and MN undervoltage releases Voltage-presence indicator Current-transformer module and ammeter module Insulation-monitoring module Remote communication by bus Device-status indication Device remote operation Transmission of settings Indication and identification of protection devices and alarms Transmission of measured current values Installation Accessories terminal extensions and spreaders terminal shields and interphase barriers escutcheons fixed, front connections 2-3P / 4P fixed, front connections 3P / 4P

(1) 2P in 3P case for type N only (2) specific trip units are available for operational voltages > 525 V (3) operational voltage y 500 V.

Dimensions (mm) W x H x D Weight (kg)

Source changeover system (see section on source changeover systems) Manual, remote-operated and automatic source changeover systems

18

Schneider Electric

NS125E
3, 4 b b b 125 750 8 500 E 25 16/10 10 6 -

NS100
2 (1), 3, 4 b b b b b b b b b 100 100 750 8 690 500 N 85 25 25 18 18 8 50 50 100 % b A 50000 50000 30000 N 85 25 10 N 85 25 10 H 100 70 65 50 35 10 85 85 L 150 150 130 100 100 75 100 100

NS160
2 (1), 3, 4 b b b b b b b b b 160 150 750 8 690 500 N 85 36 35 30 22 8 50 50 100 % b A 40000 40000 20000 N 85 35 20 N 85 35 10 H 100 70 65 50 35 10 85 85 L 150 150 130 70 50 20 100 100

NS250
2 (1), 3, 4 b b b b b b b b b 250 220 750 8 690 500 N 85 36 35 30 22 8 50 50 100 % b A 20000 20000 10000 N 85 35 20 N 85 35 18 H 100 70 65 50 35 10 85 85 L 150 150 130 70 50 20 100 100

NS400
3, 4 b b b b b b b b b 400 320 750 8 690 500 N 85 45 42 30 22 10 (2) 100 % b A 15000 12000 6000 N 85 42 20 N H 100 70 65 50 35 20 (2) 85 85 L 150 150 130 100 100 75 (2) -

NS630
3, 4 b b b b b b b b b 630 500 750 8 690 500 N H 85 100 45 70 42 65 30 50 22 35 10 (2) 20 (2) 85 85 100 % (3) b A 15000 8000 4000 N 85 42 20 N H 100 65 35 H L 150 150 130 70 50 35 (2) -

50 % b A 10000 6000 6000 E 5 5 E non interchangeable 12.5 125 (A) b b b b b b b 105 x 161 x 86 1.7 / 2.3 -

H 100 65 35 H 85 65 10

L 200 130 50 L -

H 100 65 35 H 85 65 10

L 200 130 50 L -

H 100 65 35 H 85 65 18

L 200 130 50 L -

H 100 65 35 H -

L 200 130 50 L -

L 200 130 50 L -

TM (thermal-magnetic) b b b b b b b b b b b b b b 105 x 161 x 86 / 140 x 161 x 86 1.6 to 1.9 / 2.1 to 2.3 b

STR22 (electronic) b b b b b -

STR23 (electronic) b b b b b b b b b b

STR53 (electronic) b b b b b b b b

b b -

b b b b b 140 x 255 x 110 / 185 x 255 x 110 6.0 / 7.8 b

b b b b b

Schneider Electric

19

Functions and characteristics

Protection of distribution systems Compact NS circuit breakers from 630 up to 3200 A


Compact circuit breakers
Number of poles Control manual electric Type of circuit breaker Connections fixed withdrawable (on chassis) front connection rear connection front connection rear connection toggle direct or extended rotary handle

E45151

Compact NS800H

Electrical characteristics as per IEC 60947-2 and EN 60947-2 Rated current (A) In 50 C 65 C (1) Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Type of circuit breaker Ultimate breaking capacity (kA rms) lcu AC 50/60 Hz 220/240 V 380/415 V 440 V 500/525 V 660/690 V 250 V 500 V

E45178

DC Service breaking capacity (kA rms) Short-time withstand current (kA rms) V AC 50/60 Hz V AC 50/60 Hz Integrated instantaneous protection Suitability for isolation Utilisation category Durability (C-O cycles) mechanical electrical lcs lcw

Value or % Icu 0.5 s 1s 3s kA peak 10 %

440 V 690 V

Compact NS2000H Compact NS1600bN


Pollution degree Electrical characteristics as per Nema AB1 Breaking capacity at 60 Hz (kA)

In/2 In In/2 In

240 V 480 V 600 V

Protection and measurements Interchangeable control units Overload protection Short-circuit protection Earth-fault protection Residual earth-leakage protection Zone selective interlocking Protection of the fourth pole Current measurements Additional indication and control auxiliaries Indication contacts Voltage releases

long time Ir (In x ) short time Isd (Ir x ) instantaneous Ii (In x ) lg (In x ) In ZSI

MX shunt release MN undervoltage release

Remote communication by bus Device-status indication Device remote operation Transmission of settings Indication and identification of protection devices and alarms Transmission of measured current values terminal extensions and spreaders terminal shields and interphase barriers escutcheons Dimensions fixed devices, front connections (mm) 3P HxWxD 4P Weight fixed devices, front connections (kg) 3P 4P Source changeover system (see section on "source changeover systems") Manual, remote-operated and automatic source changeover systems Installation Accessories

(1) 65 C with vertical connections. See the temperature derating tables for other types of connections. (2) Ics : 100 % Icu for breaking capacity 440V/500V/660V Ics : 75 % Icu for breaking capacity 220V/380V.

20

Schneider Electric

NS630b NS800
3, 4 b b b N b b b b 630 630 750 8 690 500 N H 50 70 50 70 50 65 40 50 30 42 75 % 50 % 25 25 17 17 55 b B B 10000 6000 5000 4000 2000 III N 50 35 25 H 65 50 50 H b b b b L b b b b 800 800

NS1000

NS1250 NS1600
3, 4 b b b N b b b b H b b b b 1600 1510

NS1600b NS2000 NS2500 NS3200


3, 4 b N b 1600 1550 750 8 690 500 N 85 70 65 65 65 100 % (2) 32 130 b B 5000 3000 2000 2000 1000 III N 85 65 50 H 125 85 85 75 % 32 130 B H b 2000 1900 2500 2500 3200 2970

1000 1000

1250 1250 750 8 690 500 N 50 50 50 40 30 75 % 25 17 55 b B 10000 5000 4000 3000 2000 III N 50 35 25 H 70 70 65 50 42 50 % 25 17 -

L 150 150 130 100 25 100 % 10 7 -

B 5000 2000 2000 1000 H 65 50 50 Micrologic 5.0 A

L 125 100 Micrologic 5.0 b b b b b b b b b b b b b

H 125 85 -

Micrologic 2.0 b b b b b b b b b b b b b b b b b b b b b b b b

Micrologic 2.0 A b b b b b b b

Micrologic 6.0 A Micrologic 7.0 A

b b b b b b b b b b b b b b b b b 350 x 420 x 160 350 x 535 x 160 24 36

b b b 327 x 210 x 147 327 x 280 x 147 14 18 b

Schneider Electric

21

Functions and characteristics

Protection of distribution systems TM and STR trip units for Compact NS100 to 250
13
E23160

Compact NS100 to 250 circuit breakers, types N, H and L, may be equipped with either a TM thermal-magnetic trip unit or an STR22 electronic trip unit. A mechanical mismatch-protection system avoids breaker and trip unit mismatches.

16 TM-D

25

40

63

80

100

125

200

250

STR22SE TM-G STR22GE TM-D TM-G

Standard protection

Protection of systems supplied by generators. Protection of long cables

Protection of DC distribution systems

TM thermal-magnetic trip units


E58564

t 1
E19528

Ir

Im

10 9

5 6

TM 250 D 250A / 40C

.9

.8

x 250A
0 Ir Im I

x 250A

Ir

Im

1 2

overload protection threshold short-circuit protection pick-up

Protection
The protection functions may be set using the adjustment dials. Overload protection Thermal protection with an adjustable threshold. Short-circuit protection Magnetic protection with a fixed or adjustable pick-up, depending on the rating. Protection of the fourth pole On four-pole circuit breakers, the trip units can be of the: 4P 3d type (neutral unprotected), 4P 3d + N/2 type (neutral protection at 0.5 In) or 4P 4d type (neutral protection at In).

TM thermal-magnetic trip units


Ratings (A) Circuit breaker In at 40 C Compact NS125 E Compact NS100 Compact NS160 Compact NS250 Ir Im Compact NS100 Compact NS160/250 4P 3d 4P 3d + N/2 4P 4d

TM16D to 250D
16 b b b b 25 b b b b 32 b b b b 40 b b b b 50 b b b b 63 b b b b 80 b b b b 100 b b b b 125 b b b 160 b b 200 b 250 b

TM16G to 63G
16 b b b b 25 b b b b 40 b b b b 63 b b b b

Overload protection (thermal)


Current setting (A) Current setting (A) adjustable from 0.8 to 1 x In adjustable from 0.8 to 1 x In

Short-circuit protection (magnetic)


fixed adjustable fixed 190 300 400 500 500 500 640 800 63 80 190 300 400 500 500 500 1000 1250 1250 1250 5 to 10 x In 63 80 no protection 56 1 x Ir 56 63 0.5 x Ir 1 x Ir 80 80 125 125

Protection of the fourth pole


Neutral unprotected Neutral protection at 0.5 In Neutral protection at In no protection

22

Schneider Electric

STR22 electronic trip units


E58565

t 1
E24096

2 3

In=100A
.8 .7

STR 22 SE
Io Ir
.9 1 .88 .85 .5 .8
x In x Io

alarm

%Ir 90 105

.9

.93 .95 .98 1

Im
5 4 3 2
x Ir

6 7 8 10

4 5
Ir Im

.63

test

Ir Im

1 2 3 4 5 6 7

long-time threshold (overload protection) long-time tripping delay short-time pick-up (short-circuit protection) short-time tripping delay instantaneous pick-up (short-circuit protection) test connector percent load indication

Protection
The protection functions may be set using the adjustment dials. Overload protection True rms long-time protection with an adjustable threshold. Short-circuit protection Short-time and instantaneous protection: b short-time protection with an adjustable pick-up and fixed tripping delay b instantaneous protection with fixed pick-up. Protection of the fourth pole On four-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d (neutral protection at In).

E58711

4P 4d

Indications
Protection of the fourth pole

A LED on the front indicates the percent load: b ON - load is > 90 % of Ir setting b flashing - load is > 105 % of Ir setting.

Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.

STR electronic trip units


Ratings (A) Circuit breaker In 20 to 70 C (1) Compact NS100 N/H/L Compact NS160 N/H/L Compact NS250 N/H/L Ir = In x at 1.5 x Ir at 6 x Ir at 7.2 x Ir Im = Ir x

STR22SE
40 b b b 80 b b 100 b b b 160 b b 250 (1) b

STR22GE
40 b b b 100 b b b 160 b b 250 (1) b

Overload protection (Long Time)


Current setting Time delay (s) (min.max.) 0.4...1 48 settings 90...180 5...7.5 3.2...5.0 2...10 8 settings fixed y 40 y 60 fixed u 11 x In 0.4...1 48 settings 1215 2...10 8 settings fixed y 40 y 60 fixed u 11 x In

Short-circuit protection (Short Time)


Pick-up (A) Accuracy 15 % Time delay (ms)

max. resettable time max. break time

Short-circuit protection (Instantaneous)


Pick-up (A) Ii

Protection of the fourth pole


Neutral unprotected 4P 3d no protection Neutral protection at 0.5 In 4P 3d + N/2 0.5 x Ir Neutral protection at In 4P 4d 1 x Ir (1) If the STR22SE and STR22GE 250 A trip units are used in high-temperature environments, the setting must take into account the thermal limitations of the circuit breaker. The overload protection setting may not exceed 0.95 at 60 C or 0.9 at 70 C.

What is the overload-protection threshold of a Compact NS250 circuit breaker equipped with an STR22SE 160 A trip unit set to Io = 0.5 and Ir = 0.8 ? Answer: In x Io x Ir = 160 x 0.5 x 0.8 = 64 A.

E25979

Setting example

Io
.8 .9

Ir
.9 .93 1 .88 .95 .98 .85 .8 1
x Io

.7 .63 .5
x In

Schneider Electric

23

Functions and characteristics

Protection of distribution systems MP and STR trip units for Compact NS400 to 630
60
E23161

Compact NS400 to 630 circuit breakers, types N, H and L, 3-pole and 4-pole, may be equipped with any of the STR23SE, STR23SV, STR53UE and STR53SV electronic trip units. The STR53UE and STR53SV trip units offer a wider range of settings and the STR53UE offers a number of optional protection, measurement and communications functions. For DC applications, the Compact NS400H and 630H circuit breakers are equipped with a built-in MP magnetic trip unit.

250

400

500

630

STR23SE / STR53UE STR23SE / STR53UE STR23SV / STR53SV MP

Standard protection with selectivity Protection of DC distribution systems

Protection of systems supplied by generators. Protection of long cables Protection of systems U > 525 V

Selection of the trip unit depends on the type of distribution system protected and the operational voltage of the circuit breaker. Protection for all types of circuits, from 60 to 630 A, is possible with only four tripunit catalogue numbers, whatever the circuit-breaker operational voltage: b U y 525 V: STR23SE or STR53UE b U > 525 V: STR23SV or STR53SV. Trip units do not have a predefined rating. The tripping threshold depends on the circuit breaker rating and the LT (long time) current setting. For example, for an STR23SE trip unit set to the maximum value, the tripping threshold is: v 250 A, when installed on a Compact NS400 250 A v 630 A, when installed on a Compact NS630.

STR23SE (U y 525 V) and STR23SV (U > 525 V) electronic trip units


E21003

t 1
E24094

2 3 4 5

STR 23 SE
Io
.8 .9

alarm

90 105 %Ir

Ir
1 .88 .85 .8 .9 .93 .95 .98 1
x Io

Isd
5 4 3 2
x Ir

6 7 8 10
Ir Isd

.7 .63 .5
x In

Ir Im

test

1 2 3 4 5 6 7

long-time threshold (overload protection) long-time tripping delay short-time pick-up (short-circuit protection) short-time tripping delay instantaneous pick-up (short-circuit protection) test connector percent load indication

Protection
The protection functions may be set using the adjustment dials. Overload protection Long-time protection with an adjustable threshold and fixed tripping delay: b Io base setting (6-position dial from 0.5 to 1) b Ir fine adjustment (8-position dial from 0.8 to 1). Short-circuit protection Short-time and instantaneous protection: b short-time protection with an adjustable pick-up and fixed tripping delay b instantaneous protection with fixed pick-up. Protection of the fourth pole On four-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d (neutral protection at In).

Indications
A LED on the front indicates the percent load: b ON - load is > 90 % of Ir setting b flashing - load is > 105 % of Ir setting.

Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.

24

Schneider Electric

STR53UE (U y 525 V) and STR53SV (U > 525 V) electronic trip units


E21004

t 1
E33944

(*)

7 (*)

2 3 4 7 5 Ir Isd Ii I

STR 53 UE
Io
.7 .6 .5 1 .8 .9 1

%Ir

>Ir

>Isd

>Ig

test

fault

Ir
.88 .85 .8 .9 .93 .95 .98 1

Isd
4 5 3 2 1.5 6 8 10

Ii
4 6 3 2 1.5 8 10 11

Ig
.5 .6 .4 .3 .2 .7 .8 1

P > Ir

A
> Im > Ih
tr tsd

x In

x Io

x Ir
.3 .3 .2 .1 0

x In

x In
.4 .4 .3 .2 .1

test

tr +

4 2 0,5

8 16

tsd (s).2
.1 16 0
on

tg (s) .3
.2 .1
on

In

I1

I2

I3

Ir Isd li

1 2 3 4 5 6 7 8 9

long-time threshold (overload protection) long-time tripping delay short-time pick-up (short-circuit protection) short-time tripping delay instantaneous pick-up (short-circuit protection) optional earth-fault pick-up optional earth-fault tripping delay test connector battery and lamp test pushbutton

(s) @ 6 Ir

I2t

off

I2t

off

Protection
The protection functions may be set using the adjustment dials. Overload protection Long-time protection with adjustable threshold and tripping delay: b Io base setting (6-position dial from 0.5 to 1) b Ir fine adjustment (8-position dial from 0.8 to 1). Short-circuit protection Short-time and instantaneous protection: b short-time protection with adjustable pick-up and tripping delay, with or without constant I2t b instantaneous protection with adjustable pick-up. Protection of the fourth pole On four-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d (neutral protection at In).

Earth-fault protection (T) (see the Options for the STR53UE electronic trip unit section on the following pages). With the earth-fault option (T) on the STR53UE electronic trip unit, an external neutral sensor can be installed (situation for a three-pole circuit breaker in a distribution system with a neutral). Available ratings of external neutral sensors: 150, 250, 400, 630 A.

Overload LED (%Ir)


A LED on the front indicates the percent load: b when ON, the load is > 90 % of Ir setting b when flashing, the load is > 105 % of Ir setting.

Fault indications
A LED signals the type of fault: b overload (long-time protection) or abnormal internal temperature (> Ir) b short-circuit (short-time protection) or instantaneous (> Isd) b earth fault (if earth-fault protection option installed) (> Ig) b microprocessor malfunction: v both (> Ig) and (> Isd) LEDs ON v (> Ig) LED ON (if earth-fault protection option (T) installed). Battery powered. Spare batteries are supplied in an adapter box. The LED indicating the type of fault goes OFF after approximately ten minutes to conserve battery power. The information is however stored in memory and the LED can be turned back ON by pressing the battery/LED test pushbutton. The LED automatically goes OFF and the memory is cleared when the circuit breaker is reset.

Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories. The test pushbutton tests the battery and the (%Ir), (> Ir), (> Isd) and (> Ig) LEDs.

Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature is detected.

Options
Four options are available: b earth-fault protection T b ammeter I b zone selective interlocking ZSI b communications option COM.
Schneider Electric

25

Functions and characteristics

Protection of distribution systems MP and STR trip units for Compact NS400 to 630 (cont.)
STR23SE (U y 525V) STR23SV (U > 525V) STR53UE (U y 525V) STR53SV (U > 525V)
150 b 250 b 400 b 630 b

Trip units
Ratings (A) Circuit breaker In 20 to 70 C (1) Compact NS400 N/H/L Compact NS630 N/H/L Ir = In x

150 b -

250 b -

400 b -

630 b

Overload protection (Long time)


Current setting Time delay (s) (min.max.) 0.4...1 adjustable, 48 settings fixed 90...180 5...7.5 3.2...5.0 2...10 adjustable, 8 settings fixed y 40 y 60 11 fixed no protection 0.5 x Ir 1 x Ir 0.4...1 adjustable, 48 settings adjustable 8...15 34...50 69...100 0.4...0.5 1.5...2 3...4 0.2...0.74 1...1.4 2...2.8

at 1.5 x Ir at 6 x Ir at 7.2 Ir Isd = Ir x

138...200 277...400 6...8 12...16 4...5.5 8.2...11

Short-circuit protection (Short time)


Pick-up (A) accuracy 15 % Time delay (ms) 1.5...10 adjustable, 8 settings adjustable, 4 settings + "constant I2t" option y 15 y 60 y 140 y 230 y 60 y 140 y 230 y 350 1.5...11 adjustable, 8 settings no protection 0.5 x Ir 1 x Ir b (standard) b (2) b (2) b (2) b (2)

max. resettable time max. break time

Short-circuit protection (instantaneous)


Pick-up (A) Ii = In x

Protection of the fourth pole


Neutral unprotected Neutral protection at 0.5 In Neutral protection at In 4P 3d 4P 3d + N/2 4P 4d

Options
Indication of fault type Zone selective interlocking Communications Built-in ammeter Earth-fault protection ZSI COM I T

(1) If the trip units are used in high-temperature environments, the setting must take into account the thermal limitations of the circuit breaker. The overload protection setting may not exceed 0.95 at 60 C or 0.9 at 70 C for the Compact NS400, and 0.95 at 50 C, 0.9 at 60 C or 0.85 at 70 C for the Compact NS630. (2) This option is not available for the STR53SV trip unit.
E25979

Setting example
What is the overload-protection threshold of a Compact NS400 circuit breaker equipped with an STR23SE (or STR23SV) trip unit set to Io = 0.5 and Ir = 0.8 ? Answer. In x Io x Ir = 400 x 0.5 x 0.8 = 160 A. The identical trip unit, with identical settings but installed on a Compact NS630 circuit breaker, will have an overload-protection threshold of: 630 x 0.5 x 0.8 = 250 A.

Io
.8 .9

Ir
1 .88 .85 .8 .9 .93 .95 .98 1
x Io

.7 .63 .5
x In

26

Schneider Electric

Possible combinations: bI bT bI+T b I + COM b I + T + COM b ZSI b ZSI + I b ZSI + T b ZSI + I + T b ZSI +I + COM b ZSI + I + T + COM

Options for the STR53UE electronic trip unit


Earth-fault protection (T)
Type
Pick-up Accuracy 15 % Time delay constant I2t function Ig = In x

Residual
0.2 to 1 adjustable, 8 settings adjustable, 4 settings 60 140 230 350 y 140 y 230 y 350 y 500

max. resettable time max. break time

Ammeter (I)
A digital display continuously indicates the current of the phase with the greatest load. The value of each current (I1, I2, I3, Ineutral) may be successively displayed by pressing a scroll button. LEDs indicate the phase for which the current is displayed. Ammeter display limits: b minimum current u 0.2 x In. Lower currents are not displayed b maximum current y 10 x In.

Zone selective interlocking (ZSI)


A number of circuit breakers are interconnected one after another by a pilot wire. In the event of a short-time or earth fault: b if a given STR53UE trip unit detects the fault, it informs the upstream circuit breaker, which applies the set time delay b if the STR53UE trip unit does not detect the fault, the upstream circuit breaker trips after its shortest time delay. In this manner, the fault is cleared rapidly by the nearest circuit breaker. The thermal stresses on the circuits are minimised and time discrimination is maintained throughout the installation. The STR53UE trip unit can handle only the downstream end of a zone selective interlocking function. Consequently, the ZSI option cannot be implemented between two Compact NS circuit breakers. Opto-electronic outputs Using opto-transistors, these outputs ensure total isolation between the internal circuits of the trip unit and the circuits wired by the user.

Communications option (COM)


This option transmits data to Digipact distribution monitoring and control modules. Transmitted data: b settings b phase and neutral currents (rms values) b highest current of the three phases b overload-condition alarm b cause of tripping (overload, short-circuit, etc.).

MP DC trip units
E26028

Im(A)
3000 4400 5000 2500 3500 3800 5700 2000 4000
In Im

Magnetic trip units for Compact NS400/630 three-pole, type H circuit breakers. These trip units are specifically designed to protect DC distribution systems. They are not interchangeable. The circuit breaker and trip unit are supplied fully assembled. Built-in trip units
Circuit breaker Compact NS400H Compact NS630H

MP1
b b adjustable 800...1600

MP2
b b adjustable 1250...2500

MP3
b adjustable 2000...4000

Short-circuit protection (magnetic) Pick-up (A) Im

Schneider Electric

27

Functions and characteristics

Protection of distribution systems Micrologic control units for Compact NS630b to 3200
Protection
Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection can be cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I2t type (ON or OFF) for short-time delay. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P 3d + N/2) or neutral protection at In (4P 4d).

Micrologic 2.0 and 5.0 control units protect power circuits. Micrologic 5.0 offers time discrimination for short-circuits as well.

E46026A

Micrologic 5.0

Indications
Overload indication by alarm LED on the front; the LED goes on when the current exceeds the long-time trip threshold.

Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.

long time

2
alarm

Ir .7 .6 .5 .4

.8

x In

tr 8 (s) 4 .9 12 16 .95 2 .98 1 20 24 1 .5


@ 6 Ir

short time

instantaneous

Isd 4 5 3 2.5 6 2 8 1.5 10 x Ir


setting

tsd
(s)

.4 .4 .3 .2 .1
I t
delay 2

Ii 3 2.5 2 1.5

.3 .2 .1
on

5 6 8 10

0 off

x In

1 2 3 4 5 6

long-time threshold and tripping delay overload alarm (LED) short-time pick-up and tripping delay instantaneous pick-up fixing screw for long-time rating plug test connector

Note. Micrologic control units are equipped with a transparent leadseal cover as standard.

28

Schneider Electric

Protection
Long time Current setting (A) Ir = In x tripping between 1.05 and 1.20 x Ir Time setting (s) Time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Instantaneous Pick-up (A) accuracy: 10 % Time delay Isd = Ir x

Micrologic 2.0
0.4 0.5 0.6 0.7 0.8 0.9 0.95 other ranges or disable by changing rating plug 0.5 1 2 4 8 12 16 12.5 25 50 100 200 300 400 0.7 (1) 1 2 4 8 12 16 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 20 minutes before and after tripping 0.98 20 500 20 13.8 1 24 600 24 16.6
E46022

t Ir

tr at 1.5 x Ir tr at 6 x Ir tr at 7.2 x Ir

tr

Isd 0
1.5 2 2.5 3 4 5 6 8 10

max resettable time: 20 ms; max break time: 80 ms

Protection
Long time Current setting (A) Ir = In x tripping between 1.05 and 1.20 x Ir Time setting (s) Time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time Pick-up (A) accuracy: 10 % Time setting (s) Time delay (ms) at 10 Ir Instantaneous Pick-up (A) accuracy: 10 % Time delay Isd = Ir x I2t Off I2t On tsd (max resettable time) tsd (max break time) settings Ii = In x

Micrologic 5.0
Micrologic 5.0 0.4 0.5 0.6 0.7 0.8 0.9 0.95 other ranges or disable by changing rating plug 0.5 1 2 4 8 12 16 12.5 25 50 100 200 300 400 0.7 (1) 1 2 4 8 12 16 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 20 minutes before and after tripping 0.98 20 500 20 13.8 1 24 600 24 16.6
E46023

Ir tr Isd tsd Ii

tr at 1.5 x Ir tr at 6 x Ir tr at 7.2 x Ir

1.5 0 20 80 2

2 0.1 0.1 80 140 3

2.5 0.2 0.2 140 200 4

3 0.3 0.3 230 320 6

4 0.4 0.4 350 500 8

10

10

12

15

off

max resettable time: 20 ms; max break time: 50 ms

Schneider Electric

29

Functions and characteristics

Protection of distribution systems Micrologic A control units for Compact NS630b to 3200 (cont.)
Protection
Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection can be cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I2t type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of I2t type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. q Protected against nuisance tripping. kDC-component withstand class A up to 10 A. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P 3d + N/2), neutral protection at In (4P 4d). Zone selective interlocking (ZSI) A ZSI terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.

Micrologic A control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection, version 7 provides earthleakage protection.
E46028

Micrologic 6.0 A

9 10
t= In= tsd= tr= Isd= Ii= Ir= Ig= tg=

MAX s kA

11

100 % 12 40 % 13

Overload alarm
A red alarm LED goes on when the current exceeds the long-time trip threshold.

menu

"Ammeter" measurements
long time

Ir .7

.8

tr
(s) 4 .9 .95 2 .98 1 1 .5

alarm

2 7

.6 .5 .4

x In

@ 6 Ir

12 16 20 24
instantaneous

short time

Isd 4 5 3 2.5 6 2 8 1.5 10 x Ir


setting

tsd
(s)

on tg

.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
delay

Ii 4 3

off

6 8 10 12 15 off 2 x In
test

Micrologic A control units measure the true (rms) value of currents. A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I1, I2, I3, IN, Ig,In, stored-current (maximeter) and setting values by successively pressing the navigation button. The load on each phase is indicated continuously by bargraphs. The optional external power supply makes it possible to display currents < 20% In.

Ig

D C B A

F G H J

(s)

.4 .4 .3 .2 .1
I t
2

6 8

Communication option
In conjunction with the COM communication option, the control unit transmits the following: b settings b all ammeter measurements b tripping causes b maximeter readings.

.3 .2 .1
on

0 off

ground fault

1 2 3 4 5 6 7 8 9 10 11 12 13

long-time threshold and tripping delay overload alarm (LED) short-time pick-up and tripping delay instantaneous pick-up earth-leakage or earth-fault pick-up and tripping delay earth-leakage or earth-fault test button long-time rating plug screw test connector lamp test, reset and battery test indication of tripping cause digital display three-phase bargraph and ammeter navigation buttons

Fault indications
LEDs indicate the type of fault: b overload (long-time protection) or abnormal internal temperature (Ir) b short-circuit (short-time protection) or instantaneous (Isd) b earth fault or earth leakage (Ig or In) b microprocessor malfunction (Ap). Battery power The fault indication LEDs remain on until the test/reset button is pressed. Under normal operating conditions, the battery supplying the LEDs has a service life of approximately 10 years.

Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units, the operation of earth-fault or earth-leakage protection can be checked by pressing the test button located above the test connector.
Note. Micrologic A control units come with a transparent lead-seal cover as standard.

30

Schneider Electric

Protection
Long time Current setting (A) Ir = In x tripping between 1.05 and 1.20 x Ir Time setting (s) Time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Instantaneous Pick-up (A) accuracy: 10 % Time delay Isd = Ir x

Micrologic 2.0 A
0.4 0.5 0.6 0.7 0.8 0.9 0.95 other ranges or disable by changing rating plug 0.5 1 2 4 8 12 16 12.5 25 50 100 200 300 400 0.7(1) 1 2 4 8 12 16 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 20 minutes before and after tripping
E46022

0.98 20 500 20 13.8

1 24 600 24 16.6

t Ir

tr at 1.5 x Ir tr at 6 x Ir tr at 7.2 x Ir

tr

Isd
1.5 2 2.5 3 4 5 6 8 10

max resettable time: 20 ms; max break time: 80 ms

Ammeter
Continuous current measurements Display from 20 to 200 % of In accuracy: 1.5 % (including sensors) Maximeters

Micrologic 2.0 A
I2 I3 IN I1 no auxiliary source (where I > 20 % In) I1 max I2 max I3 max IN max

menu

Protection
Long time Current setting (A) Ir = In x tripping between 1.05 and 1.20 x Ir Time setting (s) Time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time Pick-up (A) accuracy: 10 % Time setting (s) Time delay (ms) at 10 Ir Instantaneous Pick-up (A) accuracy: 10 % Time delay Earth fault Pick up (A) accuracy: 10 % Isd = Ir x settings I2t Off I2t On tsd (max resettable time) tsd (max break time) Ii = In x

Micrologic 5.0 / 6.0 / 7.0 A


Micrologic 5.0 / 6.0 / 7.0 A 0.4 0.5 0.6 0.7 0.8 0.9 0.95 other ranges or disable by changing rating plug 0.5 1 2 4 8 12 16 12.5 25 50 100 200 300 400 0.7(1) 1 2 4 8 12 16 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 20 minutes before and after tripping
E46023

0.98 20 500 20 13.8

1 24 600 24 16.6

Ir tr Isd tsd Ii

tr at 1.5 x Ir tr at 6 x Ir tr at 7.2 x Ir

1.5 0 20 80 2

2 0.1 0.1 80 140 3

2.5 0.2 0.2 140 200 4

3 0.3 0.3 230 320 6

4 0.4 0.4 350 500 8

10

10

12

15

off

max resettable time: 20 ms ; max break time: 50 ms Ig = In x In y 400 A 400 A < In y 1200 A In > 1200 A settings I2t Off I2t On tg (max resettable time) tg (max break time) A 0.3 0.2 500 0 20 80 2 60 60 140 Micrologic 6.0 A B C D 0.3 0.4 0.5 0.3 0.4 0.5 640 720 800 0.1 0.2 0.3 0.1 0.2 0.3 80 140 230 140 200 320 Micrologic 7.0 A 3 5 140 140 200 230 230 320 350 350 500 E 0.6 0.6 880 0.4 0.4 350 500 7 800 800 1000 F 0.7 0.7 960 G 0.8 0.8 1040 H 0.9 0.9 1120 J 1 1 1200
E46024

t Ig tg

I t on I t off
2

Time setting (s) Time delay (ms) at In or 1200 A

0
t

Residual earth leakage (Vigi) Sensitivity (A) In 0.5 1 accuracy: 0 to -20 % Time delay (ms) settings t (max resettable time) t (max break time)

10

20

30

E46243

In t

0
menu

Ammeter
Continuous current measurements Display from 20 to 200 % of In accuracy: 1.5 % (including sensors) Maximeters

Micrologic 5.0 / 6.0 / 7.0 A


I1 I2 I3 IN Ig In no auxiliary source (where I > 20 % In) I1 max I2 max I3 max IN max Ig max In max

Note. All current-based protection functions require no auxiliary source. The test / reset button resets maximeters, clears the tripping indication and tests the battery.

Schneider Electric

31

Functions and characteristics

Protection of distribution systems Micrologic A control units for Compact NS630b to 3200 (cont.)
Accessories for Micrologic control units

E47477

External sensors
External sensor for earth-fault protection The sensor is used with 3P circuit breakers and the Micrologic 6.0 A control unit. It is installed on the neutral conductor for residual type earth-fault protection. The rating of the sensor (CT) must be compatible with the rating of the circuit breaker: b NS630b to NS1600 - 400/1600 CT b NS1600b to NS3200 - 1000/4000 CT. Rectangular sensor for earth-leakage protection The sensor is installed around the busbars (phases + neutral) to detect the zerophase sequence current required for the earth-leakage protection. Rectangular sensors are available in two sizes. Inside dimensions (mm) b 280 x 115 up to 1600 A b 470 x 160 up to 3200 A. External sensor for source ground return protection The sensor is installed around the connection of the transformer neutral point to earth and connects to the Micrologic 6.0 A control unit to provide the source ground return (SGR) protection.

External sensor (CT)

056467

External sensor for source ground return protection

Long-time rating plug


Four interchangeable plugs may be used to limit the long-time threshold setting range for higher accuracy. As standard, control units are equipped with the 0.4 to 1 plug. Setting ranges
Standard Low-setting option High-setting option Off plug Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 Ir = In x 0.4 0.45 0.50 0.55 0.60 0.65 Ir = In x 0.80 0.82 0.85 0.88 0.90 0.92 no long-time protection - Ir = In for Isd settings 0.95 0.70 0.95 0.98 0.75 0.98 1 0.8 1

056412

External power-supply module


Used in conjunction with the Micrologic A control units, this module maintains three functions when the circuit breaker is OFF or the current is less than 20 % In: b display of measurements b screen backlighting b operation of maximeters. Characteristics: b power supply: v 110/130, 200/240, 380/415 V AC (+10 % -15 %), consumption 10 VA v 24/30, 48/60, 100/125 V DC (+20 % -20 %), consumption 10 W b output voltage: 24 V DC; power delivered: 5 W / 5 VA b ripple < 5 % b class 2 isolation.
025173

32

Schneider Electric

056429

Spare parts for Micrologic control units


Lead-seal cover for Micrologic A
A transparent, lead-seal cover controls access to the adjustment dials. When the cover is closed, it is still possible to access: b the test connector b the test button for the earth-fault and earth-leakage protection function.

Spare battery
Lead-seal cover for Micrologic A

A battery supplies power to the LEDs identifying the tripping causes. Battery service life is approximately ten years. A test button on the front of the control unit is used to check the battery condition. The battery may be replaced on site when discharged.

Schneider Electric

33

Functions and characteristics

Protection of distribution systems Single-phase and two-phase systems


Compact circuit breakers
Number of poles Control manual electric fixed withdrawable toggle direct or extended rotary handle front connection rear connection front connection rear connection

86099

Connections

Compact NS160H single-pole

Electrical characteristics as per IEC 60947-2 and EN 60947-2 Rated current (A) In 40 C Rated insulation voltage (V) Ui Rated impulse withstand voltage kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Type of circuit breaker Ultimate breaking capacity (kA rms) lcu AC 50/60 Hz 220 V 277 V 380/415 V 440 V 500 V 525 V 660/690 V 250 V (1P) 500 V (2P)

86101

DC Service breaking capacity (kA rms) Suitability for isolation Utilisation category Durability (C-O cycles) mechanical electrical Electrical characteristics as per NEMA AB1 Breaking capacity (kA) V AC 50/60 Hz lcs % Icu

277 V

In/2 In

Compact NS100N two-pole

240 V 277 V 480 V 600 V

Protection and measurements Type of trip units Ratings Overload protection (thermal) Short-circuit protection (magnetic) Add-on earth-leakage protection Additional indication and control auxiliaries Indication contacts Voltages releases

In long time Ir threshold instantaneous lm pickup add-on Vigi module combination with Vigirex relay

MX shunt release MN undervoltage release

Remote communication by bus Device status indication via communicating auxiliary contacts Installation Accessories terminal extensions and spreaders terminal shields and interphase barriers escutcheons WxHxD

Dimensions (mm) Weight (kg) Source changeover system Interlocking systems

34

Schneider Electric

NS100
1 b b b 100 750 8 277 250 N 25 25 25 100 % b A 20000 20000 10000 N 25 25 H 40 40 40 100 750 8 690 500 N 85 25 25 18 18 8 50 50 100 % b A 20000 20000 10000 N 85 25 10 H 100 70 65 50 35 10 85 85 2 b b b -

NS160
1 b b b 160 750 8 277 250 N 25 25 25 100 % b A 20000 20000 10000 N 25 25 H 40 40 40 160 750 8 690 500 N 85 36 35 30 22 8 50 50 100 % b A 20000 20000 10000 N 85 25 10 H 100 70 65 50 35 10 85 85 2 b b b -

NS250
1 b b b 250 750 8 277 250 N 25 25 25 100 % b A 10000 10000 5000 N 25 25 built-in thermal-magnetic 160 200 250 fixed 160 200 250 fixed 850 850 850 b b b b b b b b 70 x 161 x 86 1.2 b b b 35 x 161 x 86 0.7 -

H 40 40 -

H 100 65 35

H 40 40 -

H 100 65 35

built-in thermal-magnetic 16 20 25 30 fixed 16 20 25 30 fixed 190 300 300 300 b b b b 35 x 161 x 86 0.7 -

40 40 500

50 50 500

63 63 500

80 80 640

100 100 800

built-in thermal-magnetic 125 160 fixed 125 160 fixed 1000 1250 b b b b 35 x 161 x 86 0.7 -

b b b b b b b 70 x 161 x 86 1.2 -

Schneider Electric

35

Functions and characteristics

Protection of distribution systems 1000 V systems

053182

Compact circuit breakers


Number of poles Rating of sensors (A) Control manual electric fixed plug-in (on base) withdrawable (on chassis) Electrical characteristics Rated operational voltage (V) Ultimate breaking capacity (kA rms) Service breaking capacity toggle direct or extended rotary handle front connection rear connection front connection rear connection front connection rear connection AC 50/60 Hz AC 1000 V % Icu

Connections

Ue lcu lcs

1000 V Compact NS400

For ratings above 400 A, see the Masterpact catalogue.

Electrical characteristics as per IEC 60947-2 and EN 60947-2 Rated current (A) In 40 C Rated insulation voltage (V) Ui Rated impulse withstand voltage kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz Ultimate breaking capacity (kA rms) lcu AC 1000 V Service breaking capacity lcs % Icu Suitability for isolation Short-time withstand current (kA rms) lcw 0.5 s V AC 50/60 Hz 1s Utilisation category Durability (C-O cycles) mechanical electrical 1000 V In/2 In Pollution degree Protection and measurements Interchangeable trip units Overload protection Short-circuit protection Earth-fault protection Residual earth-leakage protection Zone selective interlocking Protection of the fourth pole Add-on earth-leakage protection Current measurements Additional indication and control auxiliaries Indication contacts Voltage releases

long time Ir (In x ) short time Isd (Ir x ) instantaneous Ii (In x ) lg (In x ) In ZSI combination with Vigirex relay

MX shunt release MN undervoltage release

Remote communication by bus Device-status indication Device remote operation Transmission of settings Indication and identification of protection devices and alarms Transmission of measured current values Installation Accessories terminal extensions and spreaders terminal shields and interphase barriers escutcheons fixed 3P 4P fixed 3P 4P

Dimensions (mm) WxHxD Weight (kg) Source changeover system Interlocking systems

36

Schneider Electric

NS400 1000V
3 150, 250, 400 b b b b consult us consult us consult us consult us consult us 1150 10 100 % 150, 250, 400 1250 8 1000 10 100 % b standardised standardised A 15000 4000 2000 III STR23SP b b b b b b b b b b b b b 480 x 140 x 110 13 consult us

For ratings above 400 A, see the Masterpact catalogue

Schneider Electric

37

Functions and characteristics

Protection of distribution systems 400 Hz applications

Tripping thresholds
The 400 Hz current settings are obtained by multiplying the 50 Hz values by the following coefficient: b K1 for thermal trip units; b K2 for magnetic trip units. On adjustable trip units, these adaptation coefficients are independent of the unit adjustment knob position. Thermal trip units The current settings are lower at 400 Hz than at 50 Hz (K1 < 1). Magnetic trip units The current settings are conversely higher at 400 Hz than at 50 Hz (K2 > 1). Adjustable trip units should be set to minimum, or use Compact circuit breakers equipped with low magnetic trip units (type G). Electronic trip units The use of electronics offers the advantage of greater operating stability when the frequency is varied. However, the devices are still subjected to frequency related temperature effects which may sometimes pose restrictions on their use. Column K1 of the table gives the maximum permissible current to be used for the current setting (knob position).

Thermal-magnetic trip units


Circuit breaker
NS100N

Trip unit
TM16G TM25G TM40G TM63G TM16D TM25D TM40D TM63D TM80D TM100D TM125D TM160D TM200D TM250D

at 40 C 16 25 40 63 16 25 40 63 80 100 125 160 200 250

Thermal setting K1
0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.9 0.9 0.9 0.9 0.9 0.9

Magnetic setting
63 80 80 125 240 300 500 500 650 800 1000 1250 1000 (1) 1250 (1)

K2
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

NS250N

(1) for TM200D and TM250D, Im must be set to its maximum

Electronic trip units Compact adaptation coefficients


Circuit breaker Trip unit Rating
Ir at 50 Hz (A at 40 C) NS100N NS250N NS400N NS630N NS400N NS630N C801N C1001N C1251N STR22SE STR22SE STR23SE STR23SE STR53SE STR53SE STR25DE STR35SE/GE STR25DE STR35SE/GE STR25DE STR35SE/GE 40...100 100...250 400 630 400 630 800 800 1000 1000 1250 1250

Long-time
Ir maxi K1 0.4 to 1 0.4 to 0.9 0.4 to 0.8 0.4 to 0.8 0.4 to 0.8 0.4 to 0.8 0.4 to 0.75 0.4 to 0.75 0.4 to 0.75 0.4 to 0.75 0.4 to 0.75 0.4 to 0.75

Short-time
Irm at 50 Hz (A) 2 to 10 Ir 2 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir 1.5 to 10 Ir

K2

1 1 1 1 1 1 0.97 0.97 0.97 0.97 0.97 0.97

38

Schneider Electric

Breaking capacity of Compact NS and Compact circuit breakers at 400 Hz


At 440 V, 400 Hz
Circuit breaker
NS100N NS250N NS400N NS630N C801N C1001N C1251N

Breaking capacity
12 kA 4,5 kA 10 kA 10 kA 25 kA 25 kA 25 kA

E22347

R MN/MX U volt 400 Hz 125 V CC

MN or MX auxiliary releases
For Compact NS100-630 For circuit breakers on 400 Hz systems, only 125 V DC rated releases can be used. The release must be supplied by the 400 Hz system via a rectifier bridge (to be selected from the table below) and an additional resistor with characteristics depending on the system voltage and the type of circuit breaker. U (V) 400 Hz
220/240 V

Connection

Rectifier
Thomson 110 BHz or General Instrument W06 or Semikron SKB at 1,2/1,3 Semikron SKB at 1,2/1,3

Additional resistor
4.2 k-5 W

380/420 V

10.7 k-10 W

Note : other models of rectifier bridges can be used if their characteristics are at least equivalent to those stated above.

For Compact C801-1251 The following auxiliary releases are designed to operate at 400 Hz. U (V) 400 Hz
MN 110/130 V MN 208/250 V MN 380/415 V MX 380/415 V

Catalogue number
44925 44926 44932 44914

For Compact NS630b-3200 The standard auxiliary releases can be used at 400 Hz, up to an ambiant temperature of 55 C.

Schneider Electric

39

Functions and characteristics

Protection of distribution systems Circuit breaker selection for DC applications


Selection criteria
The selection of the type of circuit breaker most suitable for protection of a DC installation depends mainly on the following criteria: b the rated current, which determines the rating of the equipment b the rated voltage, which determines the number of poles in series necessary for breaking b the maximum short-circuit current at the point of installation, which determines the breaking capacity b the type of network (see below).

Type of system Diagrams and various cases of faults

E22350

E22349

E22348

Earthed systems one polarity of the DC supply is earthed i a


+

Insulated systems a centre point of the DC supply is earthed i a


+

i
+

a R B b C A

R B b C A

U/2 + U/2 b

R B C A

Fault effect

fault A fault B fault C

max. Isc the positive polarity is the only one involved max. Isc both polarities are involved no effect fault A the poles required to perform the break are in series on the positive polarity

Most unfavorable case Distribution of the breaking poles

Isc close to max. Isc the positive polarity is the only one involved, voltage U/2 max. Isc both polarities are involved same as fault A but this is the negative polarity which is involved faults A and C on each polarity there must be the number of poles required to perform the break of max. Isc at U/2

no effect max. Isc both polarities are involved no effect fault B the poles required to perform the break are shared between the 2 polarities

E79370

Isc

240 V DC 300 A 500 Ah Ri = 0.5 m/cell

Calculation the short-circuit current (Isc) across the terminals of a battery When a short-circuit occurs across its terminals, a battery discharges a current given by Ohm's law:
Isc = Vb Ri

where Vb = the maximum discharge voltage (battery 100 % charged). and Ri = the internal resistance equivalent to the sum of the cell resistances (figure generally given by the manufacturer according to the capacity of the battery). Example What is the short-circuit current at the terminals of a standing battery with the following characteristics: b capacity: 500 Ah b max. discharge voltage: 240 V (110 cells of 2.2 V) b discharge current: 300 A b autonomy: 1/2 hour b internal resistance: 0.5 m per cell. Ri = 110 x 0.5 10-3 = 55 10-3
Isc = 240 = 4.4kA 55 103

As the above calculation shows, the short-circuit current is relatively weak.


Note: If the internal resistance is not known, the following approximate formula can be used: Isc = kC, where C is the capacity of the battery expressed in Ampere-hours, and k is a coefficient close to 10 but in any case always lower than 20.

40

Schneider Electric

E79371

+ 125 V = -

NC100 H 3P 80 A load

Example 1 Determine the protection required for a 80 A feeder on a 125 V DC network with an earthed negative pole and an Isc of 15 kA. The table below indicates that a NC100H circuit breaker (30 kA, 2P, 125 V) should be used. The table opposite indicates that both circuit breaker poles should be fitted on the positive pole of the network. An additional circuit breaker pole can be fitted on the negative pole of the network for isolation purposes. Example 2 Determine the protection required for a 100 A feeder on a 250 V DC network with an earthed middle point and an Isc of 15 kA. Each pole will be exposed to a maximum of U/2 = 125 V. The table below indicates that NC100H (30 kA, 2P, 125 V), NS100N (50 kA, 1P, 125 V) or NS160N (50 kA, 1P, 125 V) circuit breakers should be used. The table opposite indicates that both circuit breaker poles must take part in the breaking at a voltage of 125 V. Example 3 Determine the protection required for a 400 A feeder on an unearthed 250 V DC network with an Isc of 35 kA. The table above indicates that NS400H circuit breakers (85 kA, 1P, 250 V) should be used. At least 2 poles must take part in breaking. The table opposite indicates that the half the number of circuit breaker poles required for breaking should be fitted on the positive pole of the network and the other half on the negative pole.

E79372

+ 250 V = -

NC100 H 4P 100 A load


E79373

+ 250 V = -

NS400H 2P 400 A load

selection table of DC circuit breakers


Type Rated current (A) and trip units 16-25-40-63-80-100 16-25-40-63-80-100 16-25-40-63-80-100 80-100-125-160 80-100-125-160 80-100-125-160 160-200-250 160-200-250 160-200-250 MP1/MP2/MP3 MP1/MP2/MP3 P21/P41-1250 Breaking capacity (kA) (L/R y 0.015 s) (and number of poles required to perform the break) 24/48 V 125 V 250 V 500 V 750 V 50 (1P) 50 (1P) 50 (1P) 50 (2P) 85 (1P) 85 (1P) 85 (1P) 85 (2P) 100 (1P) 100 (1P) 100 (1P) 100 (2P) 50 (1P) 50 (1P) 50 (1P) 50 (2P) 85 (1P) 85 (1P) 85 (1P) 85 (2P) 100 (1P) 100 (1P) 100 (1P) 100 (2P) 50 (1P) 50 (1P) 50 (1P) 50 (2P) 85 (1P) 85 (1P) 85 (1P) 85 (2P) 100 (1P) 100 (1P) 100 (1P) 100 (2P) 85 (1P) 85 (1P) 85 (1P) 85 (2P) 85 (1P) 85 (1P) 85 (1P) 85 (2P) 50 (1P) 50 (1P) 50 (2P) 50 (3P) 25 (3P) Protection against Protection against overloads (thermal) short-circuits (magnetic) same as for trip units used on AC systems

NS100N NS100H NS100L NS160N NS160H NS160L NS250N NS250H NS250L NS400H NS630H C1251N-DC

no thermal protection: specially designed for DC an external relay must be provided

Schneider Electric

41

Functions and characteristics

Protection of distribution systems Incoming circuit breakers in final distribution


Compact circuit breakers
Number of poles Control manual (toggle, direct or extended rotary handle) electric fixed front connection rear connection withdrawable front connection rear connection

These are incoming circuit breakers, specially designed to operate upstream of Multi 9 modular circuit breakers. Features include: b reinforced breaking capacity at 380/415 V, by cascading up to 25 kA b easy installation in Pragma and Prisma G enclosures: v standard 45 mm front cut-out v circuit breaker clips onto a DIN rail v reduced depth (82.5 mm). A switch-disconnector version is also available (NSA125NA and NSA160NA).
048016

NSA160
3, 4 b b b b height 45 mm 160 500 8 500 250 E 25 16 10 5 5 50 % A b 10000 5000 N 70 36 18 10 10 100 %

Connections

Mounting on DIN rail Front-panel cut-out Electrical characteristics as per IEC 60947-2 Rated current (A) In 40 C Rated insulation voltage (V) Ui Rated impulse withstand volt. (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Type of circuit breaker Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz DC % Icu 220 / 240 V 380 / 415 V 440 V 125 V 250 V (2P)

Service breaking capacity Utilisation category Suitability for isolation Durability (C-O cycles)

Ics

mechanical electrical (In - 440 V)

Compact NSA160

Protection Built-in thermal-magnetic trip unit Ratings In 16 25 32 40 50 63 80 100 125 160 Thermal overload protection Ir fixed threshold 16 25 32 40 50 63 80 100 125 160 Magnetic short-circuit fixed pick-up protection lm 600 600 600 600 1000 1000 1000 1250 1250 1250 Add-on earth-leakage add-on Vigi module protection combination with Vigirex relay Indication and control auxiliaries Indication contacts Voltage releases Installation and connections Connections terminals Accessories terminal shields depth adjuster Dimensions (mm) Compact 3-poles WxHxD 4-poles Vigicompact 3-poles 4-poles Weight (kg) Compact 3-poles 4-poles Vigicompact 3-poles 4-poles Source changeover system Interlocking systems 1 OF + 1 SD MN or MX 1.5 to 70 mm2 cables b b 90 x 120 x 82.5 120 x 120 x 82.5 210 x 120 x 82.5 240 x 120 x 82.5 1.1 1.4 2.6 3.1 -

42

Schneider Electric

048018

Vigi earth-leakage protection module


The Vigi earth-leakage protection module may be installed to the right of the circuit breaker. Connections with the circuit breaker are possible to the top or bottom of the Vigi module (two versions). The connection is supplied with the Vigi module. Characteristics
Number of poles Sensitivity (A) Time delay 3, 4 0.03 / 0.3 / 1 / 3 intentional (ms) 0 60 (1) 150 (1) max. break time < 40 < 140 < 150 Rated voltage (V) 50/60 Hz 200 to 440 V Reset pushbutton Test pushbutton Protection against nuisance tripping b DC-component withstand class A (1) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.

Vigicompact NSA

Auxiliaries and accessories


Available auxiliaries include: b 1 ON/OFF indication contact (OF) b 1 trip-indication contact (SD) b 1 voltage release (MN undervoltage release or MX shunt trip) b 1 extended rotary handle with door locking, directly accessible from outside the enclosure. Depth adjuster This accessory is required to align the front of Multi 9 devices when they are installed next to a Compact NSA125 or NSA160. Maximum width 324 mm (36 modules).

Schneider Electric

43

Functions and characteristics

Motor protection Overview of solutions

The circuit breakers presented here provide protection against short circuits and are suitable for isolation as defined by standard IEC 60947-2. For complete protection of the motor and its control device, overload protection may be provided by either the circuit breaker or a separate Telemecanique thermal relay. The control device may be of the direct on-line type (with or without reversing) or of the star-delta type. Combinations are governed by standard IEC 60947-4.1.
E26988

Motor protection up to 37 kW
Motor rating (kW)
Compact
046751

0.37 37
NS80

Breaking capacity (kA rms) 380/415 V

70

General circuit-breaker characteristics page 46 The Compact NS80H-MA circuit breaker is specially designed for motor protection. Accompanying trip unit A built-in MA magnetic trip unit provides short-circuit protection. page 46

Motor protection up to 250 kW


Motor rating (kW)
Compact

1.1 110
NS100 NS160/250
045198

18.5250
NS400/630

Breaking capacity (kA rms) 380/415 V

N H L

041624

25 70 150

36 70 150

45 70 150

General circuit-breaker characteristics page 18 Compact NS100 to 630 circuit breakers for motor protection are the same as those for distribution systems, but are fitted with specific motor trip units. Accompanying trip units pages 47 to 51 MA magnetic trip units provide short-circuit protection. Interchangeable ME electronic trip units provide protection against short-circuits, overloads and phase unbalance.

Motor protection up to 750 kW


Motor rating (kW) Protection coordination (as defined by IEC 60947-4) Whatever the power of the motor, the coordination between the circuit breaker, contactor and relay can be of either type 1 or 2. Selection depends on operational requirements concerning continuity of service and the technical skills of servicing personnel. All type 2 Merlin Gerin/Telemecanique combinations have been tested under the conditions defined by standards and they are certified ASEFA/LOVAG.
Compact
E45151

160750
NS630b to 1600

Breaking capacity (kA rms) 380/415 V

N H L

50 70 150

General circuit-breaker characteristics page 20 Compact NS630b to 1600 circuit breakers equipped with Micrologic control units are the same as those for distribution systems. Accompanying control units page 28 Micrologic electronic control units may be used on all Compact NS630b to 1600 circuit breakers. Micrologic 2.0 A and 5.0 A electronic control units provide protection against short-circuits and overloads. Micrologic 7.0 A provides the same protection functions, plus earth-leakage protection.

44

Schneider Electric

Selection of a trip unit or Micrologic control unit


E26530

P (kW) (400 V, 50 Hz) Ir (A) Compact NS80H-MA Compact NS100 NS250

0.37 1.5 MA

1.1 2.5

5.5 12

18.5 40

50

37 80

100

160

200

110 220

160 320

250 500

800

560 1000

750 1350

MA STR22ME MA STR43ME

Compact NS400 NS630

Compact NS630b NS1600

Micrologic 2.0 A / 5.0 A / 7.0 A

Schneider Electric

45

Functions and characteristics

Motor protection Compact NS80H-MA

This circuit breaker is specially designed for the protection of motors rated up to 37 kW: b due to its high current-limiting capacity, it effectively protects motor starters (type-2 coordination as per IEC 60947-4, with contactors) b small size for easy installation in motor control centre (MCC) switchboards.

Compact circuit breakers


Number of poles Control manual (toggle, direct or extended rotary handle) electric fixed front connection rear connection withdrawable front connection rear connection

NS80H-MA
3 b b b 80 750 8 690 100 70 65 25 25 6 100 % A b 20000 10000 7000 100 65 10

Connections

Compact NS80 H-MA

Electrical characteristics as per IEC 60947-2 Rated current (A) In 65 C Rated insulation Ui voltage (V) Rated impulse Uimp withstand voltage (kV) Rated operational voltage (V) Ue AC 50/60 Hz Ultimate breaking Icu AC 50/60 Hz 220 / 240 V capacity (kA rms) 380 / 415 V 440 V 500 V 525 V 660/690 V Service breaking capacity Ics % Icu Utilisation category Suitability for isolation Durability (C-O cycles) mechanical electrical 440 V In/2 In Electrical characteristics as per Nema AB1 Breaking capacity (kA) 240 V 480 V 600 V

046751

Protection Magnetic trip unit Rating In Instantaneous short-circuit lm protection Earth-leakage protection

built-in 1.5 2.5 6.3 12.5 25 adjustable pick-up 6 14 x In combination with Vigirex relay

50

80

Indication and control auxiliaries Indication contacts Voltage releases Installation and connections Connections Terminal extensions and spreaders Terminal shields Interphase barriers DIN rail plate Dimensions (mm) WxHxD Weight (kg)

1 OF + 1 SD MN or MX built-in terminals b b 90 x 120 x 80 1.0

46

Schneider Electric

Compact NS100 to 630 circuit breakers with MA magnetic trip units


Compact NS100 to 630 circuit breakers, equipped with an MA magnetic trip unit with adjustable thresholds, offer: b short-circuit protection b suitability for isolation. Compact NS100 to 630 circuit breakers and the trip unit are supplied already assembled.
041624

General circuit-breaker characteristics MA trip units


Rating (A) at 65 C In Compact N/H/L NS100 circuit breaker NS160 NS250 H/L NS400 NS630 Pick-up Im 2.5 b 6.3 b 12.5 b 25 b b 50 b b 100 b b b 150 b b -

page 18

220 b -

320 b -

500 b

Short-circuit protection (magnetic)


setting 6...14 x In setting setting 9...14 x In 9...14 x In

Compact NS250H

045198

Compact NS400H-MA

Schneider Electric

47

Functions and characteristics

Motor protection Compact NS100 to 250 circuit breakers with STR22ME electronic trip unit
Compact NS100 to 250 circuit breakers
See the circuit breakers for distribution systems on page 18.

Compact NS100 to 250 circuit breakers, equipped with an STR22ME electronic trip unit with adjustable thresholds, offer: b short-circuit protection b phase-unbalance protection b overload protection b suitability for isolation.
052163

STR22ME electronic trip unit


Protection
Overload protection LT (long time) protection with adjustable Ir threshold, in compliance with tripping class 10 as defined by IEC 60947-4. Short-circuit protection Short-time and instantaneous protection: b short-time protection with fixed pick-up (Im = 13 x Ir) and tripping delay b instantaneous protection with fixed pick-up (15 x In). Phase-unbalance protection This function complies with the stipulations of standard IEC 60947-4.1 and trips the circuit breaker whenever a phase-current unbalance of 40 % or more occurs. The circuit-breaker opening time is between 3.5 and 6 seconds.

Overload LED (%Ir)


Compact NS250 equipped with an STR22ME electronic trip unit

A LED on the front indicates the percent load: b OFF: I < 1.05 Ir b flashing: I u 1.05 Ir.

Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.

Optional SDTAM contactor tripping module


(Early-break thermal-fault signal) This module can be installed in place of the MN or MX release. It operates 300 ms before the circuit breaker trips on an overload. The SDTAM module can be used to open a contactor when an overload occurs, thereby avoiding the opening of the circuit breaker. It can also be used without a contactor to provide an overload indication on the STR22ME trip unit, thereby making it possible to differentiate between tripping on overloads and short-circuits. Characteristics b compatible with the following control voltages: v 24 to 72 V DC and 24 to 48 V AC v 110 to 240 V AC / DC b replaces the MN and MX voltage releases.

48

Schneider Electric

E26985

t 1
E94521

Ir In=50A
Ir
37.5 40 35.5 42.5 45 47.5 30 50

ImSTR 22 ME
7,2Ir 7,0s

u1,05 Ir IEC 947.4 / cl.10

3 4 5 0 Ir 13Ir I

33.5 31.5

Ir

13 Ir

test

1 2 3 4 5 6 7

long-time threshold tripping class 10 as defined by IEC 60947-4 short-time pick-up short-time tripping delay instantaneous pick-up test connector percent load indication

STR22ME trip unit


Ratings (A) 20 to 70 C NS100N/H/L NS160N/H/L NS250N/H/L Ir 20100 b b b 150 b b 220 b

Overload protection (Long Time)


Current setting Tripping class (IEC 60947-4) Time delay (s) (minmax.) adjustable, 10 settings 0.6...1 x In 10 fixed 120320 615 410 LED u 40 % unbalance 3.5 to 6 seconds Isd fixed 13 x Ir 20 % fixed 10 60 fixed 15 x In b

at 1.5 x Ir at 6 x Ir at 7.2 Ir

Motor-overload indication Tripping threshold Time delay

Phase-unbalance protection in compliance with IEC 60947-4.1

Short-circuit protection (Short Time)


Pick-up Accuracy Max. resettable time (ms) Max. break time

Short-circuit protection (Instantaneous)


Pick-up Ii

Options
SDTAM module

Overload protection settings (A)


rating (A) 20 25 40 50 80 100 150 220 thresholds (A) 12 12.6 13.4 15 15.7 16.7 24 25.5 27 30 31.5 33.5 48 51 54 60 63 67 90 95 101 132 140 148 14.2 17.7 28.5 35.5 57 71 107 157 15 18.7 30 37.5 60 75 113 166 16 20 32 40 64 80 120 177 17 21.2 34 42.5 68 85 127 187 18 22.5 36 45 72 90 135 198 19 23.7 38 47.5 76 95 142 209 20 25 40 50 80 100 150 220

Schneider Electric

49

Functions and characteristics

Motor protection Compact NS400 to 630 circuit breakers with STR43ME electronic trip unit
Compact NS400 to 630 circuit breakers
See the circuit breakers for distribution systems on page 18.

Compact NS400 to 630 circuit breakers, equipped with an STR43ME electronic trip unit with adjustable thresholds, offer: b short-circuit protection b phase-unbalance protection b overload protection b suitability for isolation.

STR43ME electronic trip unit


Protection
Overload protection True (rms) long-time protection with an adjustable threshold: b Io base setting (5 settings from 0.5 to 0.8) and Ir fine adjustment (8 settings from 0.8 to 1) b adjustable tripping delay, in compliance with tripping classes 10A, 10 and 20 as defined by IEC 60947-4. The STR43ME offers two motor-cooling time constants, associated with the motor starting class: b short cooling time constant (the same as the heating time constant), providing maximum continuity of service and satisfactory motor protection b long cooling time constant (four times the heating time constant), providing maximum motor protection. Short-circuit protection Short-time and instantaneous protection: b short-time protection with adjustable pick-up and fixed tripping delay b instantaneous protection with fixed pick-up. Phase-unbalance protection This function complies with the stipulations of standard IEC 60947-4.1 and trips the circuit breaker whenever a phase-current unbalance of 40 % or more occurs. The circuit-breaker opening time is 4 seconds 10 %.

053192

Compact NS630 equipped with an STR43ME electronic trip unit

Indications: Overload LED (%Ir)


A LED on the front indicates the percent load: b OFF: I < 1.05 Ir b flashing: I u 1.05 Ir

Fault indications
LEDs indicate the type of fault that caused tripping: b overload (long-time protection) or abnormal component temperature (> Ir) b short-circuit (short-time protection) or instantaneous (> Isd) b phase unbalance (LED on the right) b microprocessor malfunction: v all four (%Ir), (> Ir), (> Isd) and (phase unbalance) LEDs ON. Battery powered. Spare batteries are supplied in an adapter box. When a fault occurs, the LED indicating the type of fault goes OFF after approximately ten minutes to conserve battery power. The information is however stored in memory and the LED can be turned back ON by pressing the battery/LED test pushbutton. The LED automatically goes OFF and the memory is cleared when the circuit breaker is reset.

Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories. The test pushbutton tests the battery and the LEDs.

Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature is detected.

Options
Three options are available: b ammeter (I) b contactor tripping module (SDTAM) b communication (COM).

50

Schneider Electric

E26987

t 1 2
E32566

STR 43 ME
Io
.63 .56 .71 .8

%Ir

>Ir

>Isd

test

fault

3 4 5 0 Ir Isd Ii I

Ir
.88 .85 .8 .8 .90 .93 .95 .98 1

Isd
9 10 8 7 6 11 12 13

P > Ir

A
> Im > Ih
tr tsd

.5

x In

x Io

x Ir

test

tr
+

20 20 10 10 10A

Ir

I1

I2

I3

Ir Isd li

10A

1 2 3 4 5 6 7

long-time threshold tripping class short-time pick-up short-time tripping delay instantaneous pick-up test connector percent load indication

class

IEC 947-4-1

STR43ME trip unit


Ratings (A) Circuit breakers 20 to 70 C NS400N/H/L NS630N/H/L Ir 120 b 200 b 320 b 500 b

Overload protection (Long Time)


Current setting Tripping class (IEC 60947-4) Time delay (s) (min. ... max.) at 1.5 x Ir at 6 x Ir at 7.2 Ir Tripping threshold Time delay Pick-up Isd Accuracy Time delay (ms) max. resettable time max. break time Pick-up Ii adjustable, 40 settings - 0.4...0.8 x In 10A, 10, 20 adjustable 144198 5.87.3 45 u 40 % unbalance 4 s 10 % adjustable, 8 settings - 6...13 x Ir 15 % fixed 10 60 fixed - 13 x Ir max. b b b b b

270357 10.913.1 7.39.1

433595 17.421.8 1215

Phase-unbalance protection in compliance with IEC 60947-4.1

Short-circuit protection (Short Time)

Short-circuit protection (Instantaneous) Other functions


Motor-overload LED Indications module

Options
Ammeter (I) SDTAM module Communication (COM)

Options for STR43ME trip unit


Possible combinations: bI b I + COM b SDTAM b SDTAM + I b SDTAM + I + COM

Ammeter (I)
A digital display continuously indicates the current of the phase with the greatest load. The value of each current I1, I2, I3 and the long-time current setting Ir may be successively displayed by pressing a scroll button. LEDs indicate the phase for which the current is displayed. Ammeter display limits b minimum current u 0.2 x In. Lower currents are not displayed b maximum current y 10 x In.

Optional SDTAM contactor tripping module


(Early-break thermal-fault signal) See the information on this optional module on page 44.

Communication (COM)
This option transmits data to Digipact distribution monitoring and control modules. Transmitted data: b settings b phase currents (rms values) b highest current of the three phases b overload-condition alarm b cause of tripping (overload, short-circuit, etc.).

Schneider Electric

51

Functions and characteristics

Protection of industrial control panels Overview of solutions


Compact NSC100
Rated current (A)
054556

Compact NS circuit breakers are specially designed to protect incoming feeders and groups of outgoing circuits on industrial control panels: b compliance with standards applicable worldwide including IEC 60947-2 and UL 508 / CSA 22-2 no. 14 b overload and short-circuit protection b isolation with positive contact indication, making it possible to service machines safely by isolating them from all power sources b installation in universal and functional type enclosures b NA switch-disconnector version.
E44356

12.5100

UL 508 / IEC 60947-2 / CSA22-2

Breaking capacity (kA rms) 380/480 V

18

General circuit-breaker characteristics page 53 Compact NSC100 circuit breakers are specially designed to protect industrial control panels. Accompanying trip unit The built-in TMD thermal-magnetic trip unit provides: b overload protection (adjustable-threshold thermal device) b short-circuit protection (fixed-pick-up magnetic device). page 54

Compact NS100 to 630


Rated current (A)
Compact

12.5 12.5 ... 100 160


NS100 NS160

12.5 ... 250


NS250
045198

60... 400
NS400

250... 630
NS630

041624

push to trip

UL 508 / IEC 60947-2 / CSA22-2

IEC 60947-2

Breaking capacity (kA rms) 380/480 V

N H

25 65

35 65

35 65

42 65

42 65

General circuit-breaker characteristics page 18 Compact NS100 to 630 circuit breakers are designed for protection of distribution systems and are also suitable for protection of industrial control panels. Accompanying trip unit page 22 to 27 The trip units are interchangeable. Compact NS100 to 250 circuit breakers are equipped with TMD thermal-magnetic or STR electronic trip units. Compact NS400 to 630 circuit breakers are equipped exclusively with STR electronic trip units.

52

Schneider Electric

Circuit breaker NSC100N


Compact NS100N circuit breakers are specially designed to protect incoming feeders and groups of outgoing circuits on industrial control panels. The NSC100NA switch-disconnector version is also available.
054556

Compact circuit breaker


Number of poles Control manual (toggle, direct or extended rotary handle) electric fixed front connection rear connection withfront connection drawable rear connection

NSC100N
3, 4 b b b b 100 750 8 690 250 42 18 18 10 10 5 5 100 % A b 20000 10000 7000 42 18 10

Connections

Mounting on DIN rail Electrical characteristics as per IEC 60947-2 Rated current (A) In 40 C Rated insulation Ui voltage (V) Rated impulse Uimp withstand voltage (kV) Rated operational voltage (V) Ue AC 50/60 Hz DC Ultimate breaking capacity Icu AC 220/240 V (kA rms) 50/60 380/415 V Hz 440 V 500 V 525 V DC 125 V 250 V (2P) Service breaking capacity Ics % Icu Utilisation category Suitability for isolation Durability (C-O cycles) mechanical electrical 440 V In/2 In Electrical characteristics as per UL 508 Breaking capacity (kA) AC 50/60 Hz 240 V 480 V 600 V

Compact NSC100N

Protection Built-in thermal-magnetic trip unit Ratings In 16 20 25 32 40 50 63 70 80 100 Instantaneous short-circuit lm fixed pick-up protection (A) 600 600 600 600 1000 1000 1000 1000 1000 1250 Add-on earth-leakage add-on Vigi module protection combination with Vigirex relay Indication and control auxiliaries Auxiliary contacts Early-make or early-break contact Voltage releases Installation and connections Connection built-in terminals Accessories terminal shields interphase barriers escutcheons Dimensions (mm) 3P WxHxD 4P Weight (kg) 3P 4P
054556

b b MN or MX

b b 90 x 120 x 80 120 x 120 x 80 1.0 1.3

Vigi earth-leakage protection module


The Vigi earth-leakage protection module may be installed to the right of the circuit breaker. Connections with the circuit breaker are possible to the top or bottom of the Vigi module (two versions). The connection is supplied with the Vigi module. Characteristics
Number of poles Sensitivity (A) Time delay 3, 4 0.03 / 0.3 / 1 / 3 intentional (ms) 0 60 (1) 150 (1) max. break time < 40 < 140 < 150 Rated voltage (V) 50/60 Hz 200 to 440 V Reset pushbutton Test pushbutton Protection against nuisance tripping b DC-component withstand class A (1) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.

Vigicompact NSC100N

Schneider Electric

53

Functions and characteristics

Protection of industrial control panels Trip units, auxiliaries, installation enclosures


Trip-unit selection
10 16 TMD 15 25 20 32 30 40 30 48 40 63 50 70 60 80 75 100 125 160 150 205 150 220 250 320 400 500

P (hp) (480 V, 3P) Ir (A)


E58713

3 12

Compact NSC100N Compact NS100 NS250

STR22ME

Compact NS400 NS630

STR43ME / STR23SE / STR53UE

STR electronic trip units are designed for: b short-circuit protection b overload protection b phase-failure protection (STR22ME and STR43ME). TMD thermal-magnetic trip units are designed for: b short-circuit protection b overload protection. Type NA devices are switch-disconnectors which must always be protected upstream in accordance with applicable installation standards. Circuit breakers
NSC100N

trip units
TMD NA STR22ME NA TMD STR22SE/GE STR43ME NA STR23SE STR53UE

UL/CSA approvals
Manual Motor Controller: Across the line starter & General use Manual Motor Controller: Across the line starter Manual Motor Controller: General Use

NS100/160/250 N/H

NS400/630 N/H

Auxiliaries
All auxiliaries can be added to the circuit breaker by the user: b padlocking devices (in the OFF position) b rotary handle b status-indication auxiliary contacts (ON, OFF and tripped) b shunt (MX) or undervoltage (MN) releases b early-make or early-break contacts. Rotary handle Available in direct or extended versions for mounting up to 590 mm behind front. Versions include: b black front with black handle b yellow front with red handle (for machine tools or emergency off as per IEC 204 / VDE 0013). All rotary handles can be padlocked in the OFF position. Optional door interlock, recommended for MCC panels (motor control centres). Early-make or early-break contacts These auxiliary contacts make it possible to de-energise the downstream auxiliary circuits of the control panel as well as the auxiliary circuits supplying the MN release, if applicable.
W
E44458

Installation in an enclosure
Compact circuit breakers can be installed in a metal enclosure together with other devices (contactors, motor-protection circuit breakers, LEDs, etc.) Minimum enclosure dimensions
Circuit breakers NSC100N NS100 N/H NS160 N/H NS250 N/H NS400 N/H NS630 N/H Height (mm) 300 457 457 457 Depth (mm) 150 130 130 130 Width (mm) 200 208 208 208 -

Installation enclosure

54

Schneider Electric

UL 508 / CSA 22-2 no. 14 marking


The UL 508 / CSA 22-2 no. 14 approval is for a Manual Motor Controller (across the line starter or general use). The circuit breakers are 100 % rated.
E42651

LISTED MAN. MOTOR. CTRL. 34XL NSC100N-NA


R

UL / CSA logo

This MMC is suitable for use on a circuit capable of delivering not more than the short-circuit current rating of this MMC indicated here below, or the upstream protective device interrupting capability, whichever is less, when protected by any protective device for Group fusing or Group installation. SC current rating kA 50/60 Hz Vac 240 42 480 25 600 10 Vac 115 230 460 575 1 ph 3 ph 1 ph 3 ph 1 ph 3 ph 1 ph 3 ph hp ratings (A) 2 2 5 5 1 16 10 7.5 10 5 1.5 15 20 7.5 10 10 3 3 10 15 20 3 3 7.5 10 2 25 10 2 20 15 32 5 5 30 10 5 7.5 10 3 30 20 30 40 15 7.5 10 15 20 30 40 3 25 50 10 40 10 20 30 60 5 25 63 5 40 70 50 15 25 60 10 30 7.5 10 80 15 40 75 60 30 30 10 40 75 50 100 100 20 15 30 tripping current 125% 100% rated temperature rating tightening torque 75C wire size Nm lb-inch 14 AWG to 3/0 AWG Cu 50 5.5 12 AWG to 4/0 AWG Al

Breaking capacity

Horsepower rating

Cable cross-section and tightening torques

NSC100 device marking (circuit breaker with built-in trip unit)

E42650

LISTED MAN. MOTOR. CTRL. 34XL NS100-160-250 N/H/NA


R

UL / CSA logo

Equipped with TMD/DE or STR trip unit This MMC is suitable for use on a circuit capable of delivering not more than the short-circuit current rating of this MMC indicated here below, or the upstream protective device interrupting capability, whichever is less, when protected by any protective device for Group fusing or Group installation. SC current rating kA 50/60 Hz NS100 NS160 NS250 Vac N H N H N H 240 85 85 85 85 85 85 480 25 65 65 35 65 35 600 10 10 18 10 10 18 tripping current 125% 100% rated temperature rating Terminal kit tightening torque reference 75C wire size 4P Nm 3P lb-inch 14 AWG to 3/0 AWG Cu 29242 29243 130 11.3 12 AWG to 4/0 AWG Al 4 AWG to 2 AWG Cu,Al 1 AWG to 350 kcmil Cu,Al 180 230 20 29259 26 29260

Breaking capacity

Cable cross-section and tightening torques

NS100 to 250 device marking (circuit breaker with interchangeable trip unit)

E42651

In=220A Ir 166 177


157 148 140 132 187 198 209 220

STR 22 ME
7,2 Ir 7,0 s

> 1,05 Ir
IEC 947.4 / cl.10

A
Trip-unit marking

Ir

13Ir

220A 1ph 3ph hp Vac 115 15 40 230 50 75 460 50 150 575 50 200 100% rated

test

Schneider Electric

55

Functions and characteristics

Earth-leakage protection Overview of solutions

Earth-leakage protection is obtained by: b fitting a Vigi module on the circuit breaker (Compact NS100 to 630) b installing a Micrologic 7.0 A control unit (Compact NS630b to 3200) b using a Vigirex relay and separate toroids (all Compact circuit breakers).

Circuit breakers equipped with an add-on Vigi module (Vigicompact)


Rated current (A)
Vigicompact

100 630
NSC100 N NSA160 N/E NS125 E
044333

NS100 to 250 N/H/L NS400 and 630 N/H/L

General circuit-breaker characteristics pages 18, 42 and 53 Compact NS100 to 630 and NSA160 circuit breakers are presented in the Protection of distribution systems section and the Compact NSC100 circuit breaker is presented in the Protection of industrial control panels section. Accompanying Vigi modules Earth-leakage protection is achieved by installing a Vigi module directly on the circuit-breaker terminals.

Circuit breakers equipped with a control unit offering integrated earth-leakage protection and an external rectangular sensor
Rated current (A)
Compact
E45151

054556

630 3200
NS630b to 1000 N/H/L NS1250 and 1600 N/H
E45178

NS1600b to 3200

General circuit-breaker characteristics page 20 Compact NS630b to 3200 circuit breakers are presented in the Protection of distribution systems section. Accompanying control units page 30 Micrologic 7.0 A electronic control units offer earth-leakage protection as standard.

Earth-leakage protection using a Vigirex relay


Vigirex Earth-leakage relay
051352

Separate toroids

Compact circuit breaker + Vigirex relay combination


Vigirex relays may be used to add external earth-leakage protection to Compact NS circuit breakers. The circuit breakers must be equipped with an MN or MX voltage release. Vigirex relays are very useful when special time-delay or tripping-threshold values are required, or when there are major installation constraints (circuit breaker already installed and connected, limited space available, etc.). Vigirex-relay characteristics: b sensitivity adjustable from 30 mA to 250 mA and eight time-delay settings (0 to 1 second) b closed toroids (30 to 300 mm in diameter) or split toroids (46 to 110 mm in diameter). Options: b trip alarm by a fail-safe contact b pre-alarm LED and contact (threshold = 0.5 x In) b 400 Hz distribution systems, etc. Compliance with standards: b IEC 60947-2, appendix B b French decree dated 14 November 1988 b IEC 60255-4 and IEC 60801-2 to 5 covering protection against nuisance tripping due to transient overvoltages, lightning strikes, switching of devices on the distribution system, electrostatic discharges, radiofrequency interference. b IEC 60755, class A, immunity to DC components up to 6 mA b VDE 664, operation down to -25 C.

56

044322

Schneider Electric

Add-on Vigi module (Vigicompact) for Compact NS100 to 630


Vigicompact NSA160 and NSC100 circuit breakers with earth-leakage protection
See pages 43 and 53, respectively.
044333

Vigicompact NS100 to 630 circuit breakers with earth-leakage protection


Addition of the Vigi module does not alter circuit-breaker characteristics: b compliance with standards b degree of protection, class II front-face isolation b positive contact indication b electrical characteristics b trip-unit characteristics b installation and connection modes b indication, measurement and control auxiliaries b installation and connection accessories.
Vigicompact NS250N
Dimensions and weights Dimensions 3 poles W x H x D (mm) 4 poles Weight (kg) 3 poles 4 poles NS100/160 105 x 236 x 86 140 x 236 x 86 2.5 3.2 NS250 NS400/630 135 x 355 x 110 180 x 355 x 110 8.8 10.8

2.8 3.4

E21007

Vigi earth-leakage protection module


310 150 60 0
avant test dilectrique enlever ce couvercle before dielectric test remove this cover

t(ms)

T R

vigi
NS 250 200 / 440 V - 50 / 60 Hz

vigi MH
3 1 0,3 10
N 1 3 5

In(A)
2 4 6

HS 0,03 ( t = 0 )

1 2 3 4 5 6 7

sensitivity setting time-delay setting (for selective earth-fault protection) lead-seal fixture for controlled access to settings test button simulating an earth-fault for regular checks on the tripping function reset button (reset required after earth-fault tripping) rating plate housing for SDV auxiliary contact

Compliance with standards: b IEC 60947-2, appendix B b French decree dated 14 November 1988 b IEC 60255-4 and IEC 60801-2 to 5 covering protection against nuisance tripping due to transient overvoltages, lightning strikes, switching of devices on the distribution system, electrostatic discharges, radiofrequency interference. b IEC 60755, class A, immunity to DC components up to 6 mA b VDE 664, operation down to -25 C. Remote indications Vigi modules may be equipped with an auxiliary contact (SDV) to remotely signal tripping due to an earth fault. Power supply Vigi modules are self-supplied internally by the distribution-system voltage and therefore do not require any external source. They continue to function even when supplied by only two phases.

Plug-in circuit breaker The Vigi module can be installed on a plug-in base. Special accessories are required (see the section on part numbers).

Vigi module selection table


Vigi ME Vigi MH
Number of poles NS125 E NS100 N/H/L NS160 N/H/L NS250 N/H/L NS400 N/H/L NS630 N/H/L 3, 4 (1) b b b 3, 4 (1) b b b b -

Vigi MB
3, 4 (1) b b

Protection characteristics
Sensitivity fixed adjustable adjustable In (A) 0.3 0.03 - 0.3 - 1 - 3 - 10 0.3 - 1 - 3 - 10 - 30 Time delay Intentional fixed adjustable adjustable delay (ms) < 40 0 60 (2) 150 (2) 310 (2) 0 60 150 310 Max. breaking < 40 < 40 <140 <300 <800 < 40 < 140 < 300 < 800 time (ms) Rated voltage 200...440 200... 440 - 440...550 200...440 - 440...550 V AC 50/60 Hz (1) Vigi 3P modules may also be used on 3P circuit breakers used for single-phase or twophase protection. (2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.

Note. The Vigi module for the Compact NSA160 circuit breaker is presented on page 43.

Schneider Electric

57

Functions and characteristics

Control and isolation Overview of solutions

Masterpact NT

E94915

Masterpact NW

source coupling switch-disconnector

Masterpact NW or NT

main power distribution board for commercial applications

main power distribution board for industrial applications

y 1000 A

15 -40 kA

y 1600 A

20 -80 kA

replacement source modular subdistribution board industrial distribution board y 160 A : 15 - 25 kA y 400 A : 20 - 80 kA
automatic control panel

y 160 A

15 - 25 kA

y 400 A

source changeover system

local isolation enclosure

final distribution enclosure for commercial applications y 10 kA y 63 A y 10 kA

local isolation enclosure y 25 kA

control panel

local isolation enclosure

y 40 A y 630 A

y 5 kA

5-15 kA

y 63 A

y 125 A

M
N.B. adjacent to or built into the machine

Circuit breakerdisconnector

building utilities

building final distribution

continuous processes

manufacturing processes and individual machines


Switchdisconnector standardised symbols

Switch-disconnectors
E58880 056470 052164 86087 086106

Masterpact
E45182

Compact NS

Interpact INS

Compact NS

Vario

056385

054361

035050

Compact NS

Interpact IN

Interpact INS

NG125

054629

Multi 9

58

Schneider Electric

Compact switch-disconnectors are used to control and isolate electrical distribution circuits. In addition to these basic functions, other functions for safety, remote control and convenience include: b earth-leakage protection b auxiliary MN/MX releases b remote operation b ammeter, etc. Compact switch-disconnectors may be interlocked with another Compact switchdisconnector or circuit breaker to constitute a source-changeover system.

86087

Compact NS250 switch-disconnector

053039

053041

Compact switch-disconnector equipped with a Vigi earthleakage module

Compact switch-disconnector equipped with a motor mechanism

044313

MN/MX voltage release

Schneider Electric

59

Functions and characteristics

Control and disconnection Compact NSA125NA and NSA160NA switch-disconnectors


Compact switch-disconnectors
Number of poles Control manual electric fixed withdrawable Built-in connectors Mounting Front-panel cutout for 1.5 to 90 mm2 cables on DIN rail 45 mm high toggle direct or extended rotary handle front connection rear connection front connection rear connection

Installation standards require upstream protection. However, due to their high-set magnetic release, Compact NSA125NA and NSA160NA switch-disconnectors are self protected.
86085

Connections

Compact NSA125NA

Electrical characteristics as per IEC 60947-3 and EN 60947-3 Conventional thermal current (A) Ith 60 C Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational current le AC 50/60 Hz 220/240 V 380/415 V 440/480 V 500 V minimum (switch-disconnector alone) maximum (with protection circuit breaker upstream) 1s 3s 20 s

Short-circuit making capacity

lcm

(kA peak)

Short-time withstand current

lcw

(A rms)

Suitability for isolation Durability (C-O cycles)

mechanical electrical electrical

AC AC

690 V 440 V 250 V

AC22A AC23A AC23A

Positive contact indication Pollution degree Protection Add-on earth-leakage protection Additional indication and control auxiliaries Indication contacts Voltage releases Installation and connection Accessories Dimensions (mm) WxHxD Weight (kg) fixed, front connection fixed, front connection 2/3P 4P 3P 4P add-on Vigi module combination with Vigirex relay

Source-changeover system (see section on "source-changeover systems") Manual source-changeover systems

60

Schneider Electric

NSA125NA
3, 4 b b b b b b 125 500 8 500 250 AC22A 125 125 125 125 2.1 330 1500 1500 580 b 10000 5000 5000 5000 b III b b 1 OF + 1 SD MN or MX terminal shields depth adjuster 90 x 120 x 82.5 120 x 120 x 80 1.1 1.4 b

NSA160NA
3, 4 b b b b b b 160 500 8 500 250 AC22A 160 160 160 160

AC23A 125 125 125 100

AC23A 160 160 160 125

Schneider Electric

61

Functions and characteristics

Control and disconnection Compact NSC100NA and NS100NA to 630NA switchdisconnectors


Compact switch-disconnectors
Number of poles Control manual electric fixed plug-in (on base) toggle direct or extended rotary handle front connection rear connection front connection rear connection front connection rear connection

Installation standards require upstream protection. However, due to their high-set magnetic release, Compact NSC100NA and NS100NA to 630NA switchdisconnectors are self protected.
86087

Connections

withdrawable (on chassis) Electrical characteristics as per IEC 60947-3 and EN 60947-3 Conventional thermal current (A) Ith 60 C Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational current le AC 50/60 Hz

Compact NS100NA

220/240 V 380/415 V 440/480 V (2) 500/525 V 660/690

Short-circuit making capacit

lc

(kA peak

Short-time withstand curren

lc

(A rms

250 V (1 P 500 V (2 P in series minimum (switch-disconnector alone maximum (with protectio circuit breaker upstream 1 3 20

Suitability for isolatio Durability (C-O cycles

mechanica electrica

A D

690 440 250

AC22 AC23 DC23

Positive contact indicatio Pollution degre Protectio Add-on earth-leakage protectio Additional indication and control auxiliarie Indication contact V oltage release V oltage-presence indicato Current-transformer modul Ammeter modul Insulation-monitoring modul Remote communication by bu Device status indications (communicating auxiliary contacts Device remote operation (communicating motor mechanism Installatio Accessorie terminal extensions and spreader terminal shields and interphase barrier escutcheon fixed, front connectio 2/3 4 fixed, front connectio 3 4 add-on Vigi modul combination with Vigirex rela

MX shunt releas MN undervoltage releas

Dimensions (mm W x H x W eight (kg

Source-changeover system (see section "on source-changeover systems" Manual source-changeover system Remote-operated and automatic source-changeover system

(1) 2P in 3P case (2) Suitable for 480 V NEMA

62

Schneider Electric

NSC100NA
3, 4 b b b 100 750 8 690 250 AC22A 100 100 100 100 DC22A 2.1 330 1500 1500 580 b 20000 7000 7000 7000 b III b b b b b b b b b 90 x 120 x 80 120 x 120 x 80 0.9 1.2 b (locking)

NS100NA
2 (1), 3, 4 b b b b b b b b b 100 750 8 690 500 AC22A 100 100 100 100 100 DC22A 100 100 2.6 330

NS160NA
2 (1), 3, 4 b b b b b b b b b 160 750 8 690 500 AC22A 160 160 160 160 160 DC22A 160 160 3.6 330

NS250NA
2 (1), 3, 4 b b b b b b b b b 250 750 8 690 500 AC22A 250 250 250 250 250 DC22A 250 250 4.9 330

NS400NA
3, 4 b b b b b b b b b 400 750 8 690 500 AC22A 400 400 400 400 400 DC22A 400 400 7.1 330

NS630NA
3, 4 b b b b b b b b b 630 750 8 690 500 AC22A 630 630 630 630 630 DC22A 630 630 8.5 330

AC23A 100 100 100 100 DC23A -

AC23A 100 100 100 100 100 DC23A 100 100

AC23A 160 160 160 160 160 DC23A 160 160

AC23A 250 250 250 250 250 DC23A 250 250

AC23A 400 400 400 400 400 DC23A 400 400

AC23A 630 630 630 630 630 DC23A 630 630

1800 1800 690 b 50000 50000 30000 (50000 - In/2) 30000 (50000 - In/2) b III b b b b b b b b b b b b b b 105 x 161 x 86 140 x 161 x 86 1.5 to 1.8 2.0 to 2.2 b b

2500 2500 960 b 40000 40000 20000 (40000 - In/2) 20000 (40000 - In/2) b III

3500 3500 1350 b 20000 20000 10000 (20000 - In/2) 10000 (20000 - In/2) b III

5000 5000 1930 b 15000 15000 6000 (12000 - In/2) 6000 (12000 - In/2) b III b b b b b b b b b b b b b b 140 x 255 x 110 185 x 255 x 110 5.2 6.8 b b

6000 6000 2320 b 15000 15000 4000 (8000 - In/2) 4000 (8000 - In/2) b III

Schneider Electric

63

Functions and characteristics

Control and disconnection Compact NS630bNA to NS1600NA switch-disconnectors


Compact switch-disconnectors
Number of poles Control manual electric fixed withdrawable (on chassis) Electrical characteristics as per IEC 60947-3 and EN 60947-3 Conventional thermal current (A) Ith 60 C Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational current le AC 50/60 Hz 220/240 V 380/415 V 440/480 V (1) 500/525 V 660/690 V toggle direct or extended rotary handle front connection rear connection front connection rear connection

Installation standards require upstream protection.


E45179

Connections

Compact NS800NA

DC 250 V (1P) 500 V (2P in series) minimum (switch-disconnector alone) maximum (with protection circuit breaker upstream) (2) 0.5 s 1s 20 s

Short-circuit making capacity

lcm

(kA peak)

Short-time withstand current

lcw

(A rms)

Suitability for isolation Durability (C-O cycles)

mechanical electrical

AC

690 V 440 V

AC22A/In AC23A/In

Positive contact indication Pollution degree Protection Add-on earth-leakage protection Additional indication and control auxiliaries Indication contacts Voltage releases combination with Vigirex relay

MX shunt release MN undervoltage release

Remote communication by bus Device status indications (communicating auxiliary contacts) Device remote operation (communicating motor mechanism) Installation Accessories terminal extensions and spreaders terminal shields and interphase barriers escutcheons fixed 3P 4P fixed 3P 4P

Dimensions (mm) WxHxD Weight (kg)

Source-changeover system (see section "on source-changeover systems") Manual source-changeover systems, remote-operated and automatic

(1) Suitable for 480 V NEMA. (2) Protection by upstream type NS, NT or NW circuit breaker: see additional technical information.

64

Schneider Electric

NS630bNA
3, 4 b b b b b b b 630 750 8 690 500 AC22A 630 630 630 630 630 DC22A 50 330 25 17 4 b 10000 2000 2000 b III b b b b b b b b b 327 x 210 x 147 327 x 280 x 147 14 18 b

NS800NA
3, 4 b b b b b b b 800 750 8 690 500 AC22A 800 800 800 800 800 DC22A 50 330 25 17 4 b 10000 2000 2000 b III

NS1000NA
3, 4 b b b b b b b 1000 750 8 690 500 AC22A 1000 1000 1000 1000 1000 DC22A 50 330 25 17 4 b 10000 2000 2000 b III

NS1250NA
3, 4 b b b b b b b 1250 750 8 690 500 AC22A 1250 1250 1250 1250 1250 DC22A 50 330 25 17 4 b 10000 2000 2000 b III

NS1600NA
3, 4 b b b b b b b 1600 750 8 690 500 AC22A 1600 1600 1600 1600 1600 DC22A 50 330 25 17 4 b 10000 1000 1000 b III

AC23A 630 630 630 630 630 DC23A -

AC23A 800 800 800 800 800 DC23A -

AC23A 1000 1000 1000 1000 1000 DC23A -

AC23A 1250 1250 1250 1250 1250 DC23A -

AC23A 1600 1600 1600 1600 1520 DC23A -

Schneider Electric

65

Functions and characteristics

Control and disconnection Compact NS1600b to 3200NA switch-disconnectors


Compact switch-disconnectors
Number of poles Control manual electric fixed withdrawable (on chassis) Electrical characteristics as per IEC 60947-3 and EN 60947-3 Conventional thermal current (A) Ith 60 C Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational current le AC 50/60 Hz 220/240 V 380/415 V 440/480 V (1) 500/525 V 660/690 V minimum (switch-disconnector alone) maximum (with protection circuit breaker upstream) (2) 3s toggle direct or extended rotary handle front connection rear connection front connection rear connection

Installation standards require upstream protection. However, Compact NS1600b to 3200NA switch-disconnectors are selfprotected for all currents higher than 130 kA peak.

Connections

E45182

Short-circuit making capacity

lcm

(kA peak)

Compact NS2000NA

Short-time withstand current lcw (A rms) Integrated instantaneous protection (kA peak 10 %) 0 %) 130 solation 130 1 b b b 000 b 60

60 1000

600 1000

n 1000 ication II III III

1000 b III

1000

Prot Additi

ion Add-on earth-leakage prot

ination with Vigirex relay b nal indication and dication contact undervoltage release b ccessories esc (mm) fi 0 W x H

b MX shunt release b

cheon D 3 P 5

Weight (kg) fixed 3P 23 4P 36 Source-changeover system (see ection "on source-changeover systems")Manual source-changeover

(1) Suitable for 480 V NEMA. (2) Protection by upstream type NS, NT or NW circuit breaker: see additional technical information.

66

Schneider Electric

NS1600bNA
3, 4 b b 1600 750 8 690 500 AC22A 1600 1600 1600 1600 1600 135 178 32 130 b 6000 1000 1000 b III b b b b b 350 x 420 x 160 350 x 535 x 160 23 36 -

NS2000NA
3, 4 b b 2000 750 8 690 500 AC22A 2000 2000 2000 2000 2000 135 178 32 130 b 6000 1000 1000 b III

NS2500NA
3, 4 b b 2500 750 8 690 500 AC22A 2500 2500 2500 2500 2500 135 178 32 130 b 6000 1000 1000 b III

NS3200NA
3, 4 b b 3200 750 8 690 500 AC22A 3200 3200 3200 3200 3200 135 178 32 130 b 6000 4000 2000 b III

AC23A 1600 1600 1600 1600 1600

AC23A 2000 2000 2000 2000 2000

AC23A 2500 2500 2500 2500 2500

AC23A 3200 3200 3200 3200 3200

Schneider Electric

67

Functions and characteristics

Source-changeover systems Presentation

For complete, in-depth information, see the Interpact, Compact, Masterpact sourcechangeover systems catalogue.
87921

Manual source-changeover systems


This is the most simple type. Intervention by technical personnel is required, i.e. transfer from the normal source to the replacement source is not immediate. A manual source-changeover system can be installed on two to three manuallycontrolled circuit breakers or switch-disconnectors. Interlocking is mechanical. Interlocks prevent connection to both sources at the same time, even momentarily.

Remote-operated source-changeover systems


This is the most commonly employed system. No human intervention is required. Switching from the normal to the replacement source is controlled electrically. A remote-operated source-changeover system is made up of two or three circuit breakers or switch-disconnectors linked by an electrical interlocking system (different configurations possible). Device operation is backed up by a mechanical interlocking fixture that prevents parallel connection if the electrical system malfunctions or if an incorrect manual operation is attempted.

Automatic source-changeover systems


An automatic controller may be added to the remote-operated source-changeover system for automatic source control according to programmable operating modes. This solution ensures optimum energy management: b switching to a replacement source depending on external requirements b management of power sources b regulation b emergency source replacement, etc. The automatic controller may be fitted with an option for communication with a supervisor.

Service sector b hospital operating rooms b safety systems for tall buildings b computer rooms (banks, insurance companies, etc.) b lighting systems in shopping centres

029693

Industry b assembly lines b engine rooms on ships b critical auxiliaries in thermal power stations

IMG0021

Infrastructure b port and railway installations b runway lighting systems b control systems for military installations

68

Schneider Electric

Manual source-changeover systems

A manual source-changeover system can be installed on two to three manuallyoperated circuit breakers or switchdisconnectors. Interlocking is mechanical. Interlocks prevent connection to both sources at the same time, even momentarily.

Interlocking of two or three toggle-controlled devices


Two devices can be interlocked using this system. Two identical interlocking systems can be used to interlock three devices installed side by side, in which case one device is in the ON position and the two others are in the OFF position. The system is locked using one or two padlocks (shackle diameter 5 to 8 mm). Combinations of Normal and Replacement devices There are two interlocking-system models: b Compact NS100 to 250 b Compact NS400 to 630 (can also be used for a Compact NS100 to 250). Devices must be either all fixed or all withdrawable.

Interlocking of two devices with rotary handles


E21287

The rotary handles are padlocked with the devices in the OFF position. The mechanism inhibits the two devices being closed at the same time, but does allow for both to be open (OFF) at the same time. Combinations of Normal and Replacement devices All Compact NS100 to 1600 circuit breakers and switch-disconnectors with rotary handles can be interlocked. Interlocking of a Compact NS100 to 630 with a Compact NS630b to 1600 is not possible.
Interlocking of two toggle-controlled devices

Interlocking of a number of devices using keylocks (captive keys)


ON I
ON I

ON I
ON I
reset tripped

O OFF
tripped

O O FF
O OFF

reset

O O FF

Interlocking uses two identical keylocks with a single key. This solution enables interlocking between two devices that are physically distant or that have significantly different characteristics, for example between a low and a mediumvoltage device, or between Compact NS circuit breakers and switch-disconnectors. A system of wall-mounted units with captive keys makes possible a large number of combinations between many devices. Combinations of Normal and Replacement devices All Compact NS100 to 1600 circuit breakers and switch-disconnectors with rotary handles or motor mechanisms can be interlocked.

E21399

Interlocking of two devices with rotary handles

Interlocking of two devices on a base plate


A base plate designed for two Compact devices can be installed horizontally or vertically on a mounting rail. Interlocking is carried out on the base plate by a mechanism located behind the devices. Access to the device controls and trip units is not blocked. Combinations of Normal and Replacement devices All manually operated Compact NS100 to 630 circuit breakers and switchdisconnectors can be interlocked. Devices must be fixed or plug-in versions, with or without earth-leakage protection or measurement modules.

E26766

ON

ON I

reset

O
OFF

O OFF

Interlocking with keylocks

E33943

push to trip

push to trip

Interlocking on base plates

Schneider Electric

69

Functions and characteristics

Source-changeover systems Remote-operated systems

053042

Source-changeover system without a controller


In this case, the automatic-control system to initiate changeovers between the Normal and Replacement sources under predefined conditions must be provided by the installation designer.

Remote-operated source-changeover system


QR QN
053060

E32699

3
053058

2 1

Auxiliary control plate

Controller

Source-changeover system with a controller


In this case, changeovers between the Normal and Replacement sources under predefined conditions are initiated by a Merlin Gerin controller.

E79368

E79369

E32700

0 . OFF 0 . OFF

IN LIN GER MER

N R N
Test

UN =

UR

0,5s
I /O UN = 1

UN ON / ON / OFF fault I /O fault OFF

0,5s

Test

FFO hsup

I NO

FFO hsup

stop

manu
NO h sup

test

hsup

R N

FFO

O
d e gr ahcs id

FFO

O
degr ahcs id

352

10

352

10

IN LIN GER MER

N R
UR

UN =

UN ON / ON / OFF fault auto I /O fault OFF I /O UN = 1

5
FFO hsup

stop

manu

test
STOP

rator gene

R N

6
NO h sup

FFO hsup

NO h sup

FFO

O
d e gr ahcs id

FFO

O
degr ahcs id

352

10
352

Coupling accessory
10

This accessory may be used with the source-changeover system (with or without a controller) to facilitate connections.

Compact NS630b to 1600 Interlocking by rods

Interlocking by cables
E32701

7
A remote-operated source-changeover system is made up of: 1 circuit breaker QN equipped with a motor mechanism and auxiliary contacts, connected to the Normal source 2 circuit breaker QR equipped with a motor mechanism and auxiliary contacts, connected to the Replacement source 3 mounting base plate with mechanical interlocking (NS100 to 630) or an interlocking system using rods or cables (NS630b to 1600) 4 electrical interlocking unit. IVE for NS100 to 630 or an electrical system provided by the installer for NS630b to 1600. Electrical interlocking system example: part no. 51156903 in the source-changeover system catalogue. Switching between sources can be automated by adding: 5 ACP auxiliary control plate 6 BA or UA controller, or an electrical system provided by the installer for NS630b to 1600. Electrical system example: part no. 51156904 and 51156904 in the sourcechangeover system catalogue. Accessory: 7 coupling accessory (downstream connection) for NS100 to 630.

70

B US

Schneider Electric

Controllers

When used with a remote-operated sourcechangeover system, the BA or UA controllers initiate the automatic changeover operations according to userdefined sequences.

Controller
Four-position switch
Automatic operation Forced operation on Normal source Forced operation on Replacement source Stop (both Normal and Replacement sources OFF)

BA
b b b b b

UA
b b b b b b b b b

Automatic operation
Monitoring of the Normal source and automatic changeover Engine generator set start-up control Delayed shutdown (adjustable) of engine generator set Load shedding and reconnection of non-priority loads Changeover to Replacement source if one of the Normalsource phases is absent
053058R

Test
By opening of the P25M circuit breaker upstream of the controller By pressing the test button on the front of the controller b b b b b b b b b

Indications
Circuit-breaker status indication on the front of the controller: ON, OFF, fault trip Automatic-mode indication contact

Other functions
BA controller
Selection of type of Normal source (single-phase or three-phase) Voluntary transfer to Replacement source b (e.g. energy-management commands) During peak-tariff periods (energy-management commands), forced operation on Normal source if Replacement source is not operational Additional control contact (not in controller). b Transfer to Replacement source only if contact closed (e.g. UR frequency check) Replacement-source maximum start-up time setting

053058

Options
Communications option b 220 to 240 V 50/60 Hz 380 to 415 V 50/60 Hz 440 V 60 Hz b b b b b b b b b

Power supply
Control voltages (1)

Operating thresholds
UA controller
Undervoltage Phase failure Voltage presence 0.35 Un y voltage y 0.7 Un b 0.5 Un y voltage y 0.7 Un voltage u 0.85 Un b

IP degree of protection against penetration of solid bodies and liquids (EN 60529) and IK degree of protection against external mechanical impacts (EN 50102)
Front Side Connectors Front Rated thermal current (A) Minimum load IP40 IP30 IP20 IK07 8 10 mA at 12 V b b b b b b b b

Characteristics of output contacts

AC DC Utilisation category (IEC 60947-5-1) AC12 AC13 AC14 AC15 DC12 DC13 Operational current (A) 24 V 8 7 5 6 8 2 48 V 8 7 5 5 2 110 V 8 6 4 4 0.6 220/240 V 8 6 4 3 250 V 0.4 380/415 V 5 440 V 4 660/690 V (1) Power supplied by the ACP auxiliary control plate. The supply voltage must be the same for the ACP plate, the IVE unit and the circuit breaker operating mechanisms. If this voltage is the same as the distribution-system voltage, the Normal and Replacement sources can be used directly for the power supply. If not, a BC-type or equivalent isolation transformer must be used.

Schneider Electric

71

Functions and characteristics

Communication Compact NS100 to 630

Integration of the circuit breaker or the switch-disconnector in a supervison system requires either the communicating auxiliaries or the SC150 interface. Compact devices fit perfectly in the SMS Powerlogic electrical installation management system by communicating using Digipact protocols. An external gateway offers communication via other networks including: b Profibus b Ethernet
053172

There are two possibilities for the 100 to 630 A range: b communicating auxiliaries They replace the standard auxiliaries and connect directly to the Digipact bus. Three equipment levels: v communicating auxiliary contacts, comprising: - OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts - electronic module - prefabricated wiring. v communicating auxiliary contacts and motor-mechanism module, comprising: - OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts - motor-mechanism module (220 V AC) (1) - electronic module - prefabricated wiring. v communicating carriage switches for the chassis, comprising: - CE / CD (connected/disconnected position) contacts - electronic module - wiring connector. b SC150 interface Using the SC150 interface, it is possible to integrate a device equipped with noncommunicating auxiliaries into a supervison system. The SC150 interface is used to connect: v the auxiliary contacts on the circuit breaker (OF, SD, SDE, SDV, CD, CE) v the remote-operation system (on, off, reset) v the communication output for the STR53UE and STR43ME electronic trip units equipped with the COM option v an unassigned digital input.

Compact NS equipped with communicating auxiliary contacts and motor-mechanism module


054481

Withdrawable Compact NS on its chassis equipped with communicating auxiliary contacts


054516

SC150 indication and control interface

(1) For voltages other than 220 V AC, use a standard motor-mechanism module (noncommunicating) together with an SC150 indication and control interface.

72

Schneider Electric

Overview of functions
E94526

Software

Communication interface Communication bus


IN LIN GER MER SV
pulsar

RS 232C,Ethernet RS 485

JBus BBus com 24V

com error

OK error

1
N1

3
N1

Data concentrator DC150

Device
SC150 indication and control interface

comp

act

NB25 Uimp 8kV. Icu (kA) Ue 100 (V) 0 70 220/245 65 380/41 50 440 5 10 500/520 85 660/69 250 0% Icu Ics=10 cat A
Ui 750V.

0NH

2
ed discharg
compact L NS250 Uimp 8kV. Ui 750V. Icu(kA) 150 Ue(V) 150 220/240 130 380/415 70 440 20 500 100 600/690

O OFF
5...8

Digipact Bus

-2 IEC947BS CEI VDE


UTE

UNE

NEMA

0 125/16
push to trip

250 250 cat A TM Icu C 100% Ics = 250A/40

Im 10 Ir
.8 .9 9 8

5 6 7

VDE UTE NEMA 947-2 UNE IEC CEI BS

Ir

Im

1
auto manu

x 250A

x 250A

O
push OFF

I
push ON

Compact NS with communicating auxiliary contacts and motor mechanism

comp

act

NB25 Uimp 8kV. Icu Ui 750V. (kA) Ue 100 (V) 0 70 220/245 65 380/41 50 440 5 10 500/520 85 660/69 250 0% Icu Ics=10 cat A
-2 IEC947BS CEI VDE
UTE UNE NEMA

0NH

2
ed discharg
compact L NS250 Uimp 8kV. Ui 750V. Icu(kA) 150 Ue(V) 150 220/240 130 380/415 70 440 20 500 100 600/690

O OFF
5...8

0 125/16
push to trip

250 250 cat A TM Icu C 100% Ics = 250A/40

Im 10 Ir
.8 .9 9 8

5 6 7

VDE UTE NEMA 947-2 UNE IEC CEI BS

Ir

Im

1
auto manu

x 250A

x 250A

O
push OFF

I
push ON

Compact circuit breaker with standard auxiliary contacts and motor mechanism. Trip unit with the COM option.

: hard wire : communication bus

Compact with communicating SC150 auxiliaries Device identification


Address Rating b b b b b b b b b b b b b b b b b b

Indication of status conditions


OF (on/off) SD (trip indication) SDE (fault-trip indication) CE/CD (connected/disconnected position)

Controls
ON/OFF LED reset

Protection settings
Reading of the protection settings

Operating and maintenance aids


Measurements: Fault readings: Indications: currents type of fault operation counter

Schneider Electric

73

Functions and characteristics

Communication Compact NS630b to 1600 COM option in Compact


For fixed circuit breakers, the COM option is made up of: b a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SD, SDE micro-contacts for manually operated devices; OF, SDE micro-contacts for electrically operated devices) and its kit for connection to a communicating motor-mechanism module. For withdrawable circuit breakers, the COM option is made up of: b a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SD, SDE micro-contacts for manually operated devices; OF, SDE micro-contacts for electrically operated devices) and its kit for connection to a communicating motor-mechanism module b a "chassis" communication module supplied separately with its set of sensors (CE, CD and CT contacts). Status indication by the COM option is independent of the circuit breaker indication contacts. These contacts remain available for conventional uses. Digipact or Modbus "device" communication module This module is independent of the control unit. It receives and transmits information on the communication network. An infra-red link transmits data between the control unit and the communication module. Consumption: 30 mA, 24 V. Digipact or Modbus "chassis" communication module This module is independent of the control unit. The Modbus "chassis" communication module makes it possible to address the chassis and to maintain the address when the circuit breaker is in the disconnected position. Consumption: 30 mA, 24 V. Communicating motor-mechanism module A bus link is used to transmit remote ON/OFF orders to the circuit breaker. A communicating motor-mechanism module must be used. The remote-tripping function (MX or MN) is independent of the communication option.
E59437A

The COM option is required for integration of the circuit breaker or switchdisconnector in a supervision system. Compact uses the Digipact or Modbus communications protocol for full compatibility with the SMS PowerLogic electrical-installation management systems. An external gateway is available for communication on other networks: b Profibus b Ethernet The eco COM is limited to the transmission of metering data and does not allow the control of the circuit breaker.
056431

Digipact "device" communication module.

Communication bus

Communication bus

056401

Digipact "chassis" communication module


OF SD SDE OF SDE

3 1

3 5

I on

tripped

reset

056431

Modbus "device" communication module

Manually operated fixed device

0 OF

Electrically operated fixed device

Communication bus
CCM

++
modb us

Communication bus 2
CCM

++
modb us

2
CE

CD

CE

+
CT CD

CT

CD

C CE

C CT OF SD SDE

4
C CD C CE

C CT OF SDE

1
E45183

3 5

Modbus "chassis" communication module


Manually operated drawout device Electrically operated drawout device

1 2 3

"device" communication module "chassis" communication module OF, SD, SDE "device" sensors

4 5

CE, CD and CT "chassis" sensors communicating motor-mechanism module

Note. eco COM The eco COM Modbus is intended to fit the circuit breaker with a module display (DMB300, DMC300).

74

Schneider Electric

Overview of functions
File

POWERLOGIC System Manager Demo Edit View Setup Control Display Reports

Tools Window Help 5 seconds

Sampling Mode : MANUAL

Time

Event

Module

Phase A-N Voltage - Harmonics Analysis 1,20


Phase 1-N
Harmonics(RMS)

Fundamental:

1,00

RMS: RMS-H:

0,80
% Fundamental

Peak: CF: THD:

H1: 118.09 H2: 0.01 H3: 0.45 H4: 0.03 H5: 0.45 H6: 0.04 H7: 1.27 H8: 0.05 H9: 0.42 H10: 0.01 H11: 1.03 H12: 0.07

0,60
OK

0,40

Compact circuit breakers and switch-disconnectors are compatible with the Digipact or Modbus COM option. The COM option may be used with all types of control units to: b identify the device b indicate status conditions b control the device. Depending on the different types of Micrologic (S, A) control units, the COM option also offers: b setting of the protections functions b analysis of the AC-power parameters for operating-assistance and maintenance purposes Switch-disconnector with Circuit breaker with communication bus communication bus
Digipact Modbus b b b b b Digipact S A A A A S S S S A A A A S S S S Modbus S A A A A A A A A

E47071

0,20 0,00 H2 H3 H4 H5 H6 H7
Harmonics

H8

H9

H10

H11

H12

Ready

ONLINE: DEMO

No working system

9:30

Device identification
Address Rating Type of device Type of control unit Type of long-time rating plug b b b b b

Status indications
OF (on/off) SD (trip indication) SDE (fault-trip indication) CE/CD (connected/ disconnected position)

Controls
MX/XF ON/OFF Spring charging Reset of the mechanical indicator b b S A S A

Protections settings
Reading of protections settings A A

Operating and maintenance aids


Measurements current A Fault readings type of fault Note. S = Micrologic 2.0 and 5.0 A = Micrologic with ammeter See the description of the Micrologic control units for further details on protection. A A

Schneider Electric

75

Functions and characteristics

Communication Compact NS630b to 1600 (cont.) Compact in a communication network

E94525

Software

Communication interface Communication bus


IN LIN GER MER SV
pulsar

RS 232C, Ethernet RS 485

JBus BBus com 24V

com error

OK error

1
N1

3
N1

Data concentrator DC150

Device

Digipact Bus Compact Compact

Modbus Bus

Devices
Circuit breakers equipped with Micrologic control units may be connected to either a Digipact or Modbus communication bus. The information made available depends on the type of Micrologic control unit (S, A) and on the type of communication bus (Digipact or Modbus). Switch-disconnectors may be connected exclusively to the Digipact communication bus.

Communication bus Digipact bus


The Digipact bus is the internal bus of the low-voltage switchboard in which the Digipact communicating devices are installed (Compact with Digipact COM, PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data concentrator (see the Powerlogic System catalogue). Addresses Addressing is carried out by the DC150 data concentrator. Number of devices The maximum number of devices that may be connected to the Digipact bus is calculated in terms of communication points. These points correspond to the amount of traffic the bus can handle. The total number of points for the various devices connected to a single bus must not exceed 100. If the required devices represent more than 100 points, add a second Digipact internal bus. Communicating device
DC150 data concentrator Micrologic + Digipact COM PM150 SC150 UA150

Number of points
4 4 4 4 4

Length of bus The maximum recommended length for the Digipact internal bus is 200 meters. Bus power source Power is supplied by the DC150 data concentrator (24 V).

76

Schneider Electric

Modbus bus
The Modbus RS 485 (JBus) system is an open bus on which communicating Modbus devices (Compact with Modbus COM, PM300, Sepam, Vigilohm, etc.) are installed. All types of PLCs and microcomputers may be connected to the bus. Addresses The software layer of the Modbus protocol can manage up to 255 addresses (1 to 255). The device communication module comprises three addresses linked to: b circuit-breaker manager b measurement manager b protection manager. The chassis communication module comprises one address linked to: b the chassis manager. The division of the system into four managers secures data exchange with the supervision system and the circuit-breaker actuators. The manager addresses are automatically derived from the circuit-breaker address @xx entered via the Micrologic control unit (the default address is 47). logic addresses
@xx @xx + 50 @xx + 200 @xx + 100 Circuit-breaker manager Chassis manager Measurement manager Protection manager (1 to 47) (51 to 97) (201 to 247) (101 to 147)

Number of devices The maximum number of devices that may be connected to the Modbus bus depends on the type of device (Compact with Modbus COM, PM300, Sepam, Vigilohm, etc.), the baud rate (19200 is recommended), the volume of data exchanged and the desired response time. The RS 485 physical layer offers up to 32 connection points on the bus (1 master, 31 slaves). A fixed device requires only one connection point (communication module on the device). A drawout device uses two connection points (communication modules on the device and on the chassis). The number must never exceed 31 fixed devices or 15 drawout devices. Length of bus The maximum recommended length for the Modbus bus is 1200 meters. Bus power source A 24 V DC power supply is required (less than 20 % ripple, insulation class II).

Communication interface
The Modbus bus may be connected to the central processing device in any of three manners: b direct link to a PLC. The communication interface is not required if the PLC is equipped with a Modbus port; b direct link to a computer. The Modbus (RS 485) / Serial port (RS 232) communication interface is required; b connection to a TCP/IP (Ethernet) network. The Modbus (RS 485) / TCP/IP (Ethernet) communication interface is required.

Software
To make use of the information provided by the communicating devices, software with a Modbus driver must be used.

Micrologic utilities
This is a set of Modbus drivers that may be used with a PC to: b display the variables (I, U, P, E, etc.) with the RDU (Remote Display Utility) b read/write the settings with the RSU (Remote Setting Utility) b remotely control (ON / OFF) the device with the RCU (Remote Control Utility) These utilities are available on request.

System Manager Software (SMS)


SMS is a power management software for the control and monitoring of LV and MV electrical installations. The SMS family includes a number of products for all types of applications, from standalone systems to networked power management of multiple buildings. SMS can communicate with all intelligent devices of the electrical installation including: b Power Meter and Circuit Monitor products b LV circuit breakers and switch-disconnectors b Sepam units.

Schneider Electric

77

Functions and characteristics

Communication Compact NS1600b to 3200 COM option in Compact


For fixed circuit breakers, the COM option is made up of: b a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SD, SDE micro-contacts). Status indication by the COM option is independent of the circuit breaker indication contacts. These contacts remain available for conventional uses. Digipact or Modbus "device" communication module This module is independent of the control unit. It receives and transmits information on the communication network. An infra-red link transmits data between the control unit and the communication module. Consumption: 30 mA, 24 V.
E59438

The COM option is required for integration of the circuit breaker or switchdisconnector in a supervision system. Compact uses the Digipact or Modbus communications protocol for full compatibility with the SMS PowerLogic electrical-installation management systems. An external gateway is available for communication on other networks: b Profibus b Ethernet
056431

Communication bus

Digipact "device" communication module.


OF SD SDE

2 1
COM module
OFF OFF

056431

Modbus "device" communication module

1 2

"Device" communication module OF, SD, SDE "device" sensors

78

Schneider Electric

Overview of functions
File

POWERLOGIC System Manager Demo Edit View Setup Control Display Reports

Tools Window Help 5 seconds

Sampling Mode : MANUAL

Time

Event

Module

Phase A-N Voltage - Harmonics Analysis 1,20


Phase 1-N
Harmonics(RMS)

Fundamental:

1,00

RMS: RMS-H:

0,80
% Fundamental

Peak: CF: THD:

H1: 118.09 H2: 0.01 H3: 0.45 H4: 0.03 H5: 0.45 H6: 0.04 H7: 1.27 H8: 0.05 H9: 0.42 H10: 0.01 H11: 1.03 H12: 0.07

0,60
OK

0,40

Compact circuit breakers and switch-disconnectors are compatible with the Digipact or Modbus COM option. The COM option may be used with all types of control units to: b identify the device b indicate status conditions b control the device. Depending on the different types of Micrologic (S, A) control units, the COM option also offers: b setting of the protections functions b analysis of the AC-power parameters for operating-assistance and maintenance purposes Switch-disconnector with Circuit breaker with communication bus communication bus
Digipact Modbus b b b b Digipact S A A A A S S S A A A A S S S Modbus S A A A A A A A A

E47071

0,20 0,00 H2 H3 H4 H5 H6 H7
Harmonics

H8

H9

H10

H11

H12

Ready

ONLINE: DEMO

No working system

9:30

Device identification
Address Rating Type of device Type of control unit Type of long-time rating plug b b b b

Status indications
OF (on/off) SD (trip indication) SDE (fault-trip indication)

Protections settings
Reading of protections settings

Operating and maintenance aids


Measurements current A Fault readings type of fault Note. See the description of the Micrologic control units for further details on protection. A A

Schneider Electric

79

Functions and characteristics

Electrical and mechanical accessories Compact NS80H-MA


E58516

Sealable terminal shield

Direct rotary handle


com A H-M . NS 80 Uimp 8kV 0V. Icu (kA) 100 Ue (V) 70 220/240 65 380/415 25 440 6 500/525 10 660/690 250 pact

Ui75

Auxiliary contact
ON I
push to trip

cat A Icu 100% Ics =

DIN-rail plate

IEC
UTE

2 UNE 947. BS CEI


VDE

push to trip

O OFF

push to trip

C2 C1 SHT z MX/ /50-60H 240V 220-

Voltage release

Sealable terminal shield

88

2
ON I
ed tripp
5...8

t rese

O OFF

Extended rotary handle

Auxiliary contact

Schneider Electric

Compact NSC100N, NSA160


Front accessory for NSC100N (45 mm standard door cutout)

E58517

Ue (V) 220/240 380/415 440 125 Ics =


UTE

com . 125E p 6kV NSA V. Uim (kA) U 500 Icu 25 16 10 5

pact

50%

Icu
UNE

CEI 947.2 IEC VDE BS

45 mm front

E58518

Sealable terminal shield

. 125E p 6kV NSA V. Uim (kA) U 500 Icu 25 Ue (V) 16 220/240 10 380/415 5 440 125 Ics
UTE

pact com

Auxiliary contact

= 50%

Icu
UNE

CEI 947.2 IEC VDE BS

ON I

ed tripp
C2 C1 SHT z MX/ /50-60H 240V 220-

5...8

Voltage release

t rese

O OFF

Extended rotary handle

Sealable terminal shield

Schneider Electric

89

Functions and characteristics

Electrical and mechanical accessories Compact NS80H-MA, NSC100N and NSA160


Installation
Compact NS80H-MA and NSC100N circuit breakers may be mounted vertically, horizontally or flat on their back without any derating of characteristics. They are designed for easy installation in the various types of switchboards of each market and country. Mounting on a DIN rail is possible using a special adapter. The NSA160 circuit breaker may be mounted exclusively on a DIN rail. These three circuit breakers are available in the fixed, front-connection version.
E43595 E43596 E43597

E59278

Installation positions

OFF

push to trip

NS80H-MA and NSC100N: mounting on backplate or mounting plate.

NS80H-MA and NSC100N: mounting on DIN rail (optional). NSA160: mounting on DIN rail (standard).

Standard 45 mm front, optional on NSC100N, standard on NSA160.

E54455

Front connection of bare cables


Compact NS80H-MA, NSC100N and NSA160 circuit breakers are equipped as standard with connectors for bare copper or aluminium cables from 1.5 to 70 mm2. Distribution connector This connector screws directly to the standard connectors. It is used to connect up to three cables: b flexible cables from 1 to 10 mm2 b rigid cables from 1.5 to 16 mm2 b with crimped or self-crimping ferrules from 1.5 to 4 mm2.
E39432

Distribution connector

Insulation of live parts


Terminal shields Insulating accessories used for protection against direct contact with power circuits (degree of protection IP40, IK07). They are supplied with sealing accessories. For voltages u 500 V, terminal shields are mandatory.
E58553

Terminal shields

90

Schneider Electric

044314

Indication contacts
A single type of contact, complying with the IEC 60947-5 international recommendation, provides different indication functions, depending on where it is inserted in the device. b OF (ON/OFF) - indicates the position of the circuit breaker contacts b SD (trip indication) - indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth-leakage fault (Compact NSC100N and NSA160) v operation of a voltage release. Returns to de-energised state when the circuit breaker is reset. b SDV (earth-leakage fault indication) - inserted in the Vigi module on Compact NSC100N and NSA160 devices, it indicates that the circuit breaker has tripped due to an earth fault. Returns to de-energised state when the circuit breaker is reset. All the above auxiliary contacts are also available in low-level versions capable of switching very low loads (e.g. for the control of PLCs or electronic circuits). Characteristics Contacts
Rated thermal current (A) Minimum load Utilisation category (IEC 60947-5-1) Operational 24 V current (A) 48 V 110 V 220/240 V 250 V 380/440 V

Indication contacts Common-point changeover contacts provide remote circuitbreaker status information. They can be used for indications, electrical locking, relaying, etc.

Standard
6 100 mA at 24 V AC12 AC15 DC12 6 6 2.5 6 6 2.5 6 5 0.8 6 4 0.3 6 3 -

Low level
5 2 mA at 15 V DC AC12 AC15 DC12 5 3 5 5 3 2.5 5 2.5 0.8 5 2 5 0.3 5 1.5 -

DC14 1 0.2 0.05 0.03 -

DC14 1 0.2 0.05 0.03 -

054550

Remote tripping
MX or MN voltage releases are used to trip the circuit breaker. MN undervoltage release This release trips the circuit breaker when the control voltage drops below a tripping threshold: b tripping threshold between 0.35 and 0.7 times the rated voltage b circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage. Circuit breaker tripping by an MN release meets the requirements of standard IEC 60947-2. Time-delay unit for an MN release (Compact NS80H-MA) Eliminates nuisance tripping due to transient voltage dips lasting y 200 ms: It is used in conjunction with: b a 250 V DC MN release, control voltage 220/240 V AC b a 48 V DC MN release, control voltage 48 V AC. MX shunt release Trips the circuit breaker when the control voltage rises above 0.7 x Un. Control signals can be of the impulse type (u 20 ms) or maintained. Operation When the circuit breaker has been tripped by an MN or MX release, it must be reset locally. MN or MX tripping takes priority over manual closing. In the presence of a standing trip order, closing of the contacts, even temporary, is not possible. Mechanical characteristics b endurance is equal to 50 % of the mechanical endurance of the circuit breaker b the releases clip in behind the front cover b connection using wires up to 1.5 mm2 to integrated terminal blocks. Electrical characteristics b consumption: v pick-up (MX): < 5 VA v seal-in (MN): < 5 VA b response time: < 50 ms.

MX or MN voltage release

Schneider Electric

91

Functions and characteristics

Electrical and mechanical accessories Compact NS80H-MA, NSC100N and NSA160 (cont.)
Rotary handles
There are two types of rotary handle: b direct rotary handle b extended rotary handle. There are two models: b standard with a black handle b VDE with a red handle and yellow front for machine-tool control. Direct rotary handle (NS80H-MA and NSC100N) Degree of protection IP40, IK07. The direct rotary handle maintains: b visibility of and access to trip unit settings b suitability for isolation b indication of the three positions O (OFF), I (ON) and tripped b access to the push to trip button b circuit breaker locking capability in the OFF position by one to three padlocks, shackle diameter 5 to 8 mm (not supplied). It replaces the circuit-breaker front cover. Accessories transform the standard direct rotary handle for the following situations: b motor control centre (MCC) switchboards: v door opening disabled when the circuit breaker is ON v circuit-breaker closing is disabled if the door is open b a higher degree of protection (IP43, IK07) b machine-tool control, complying with CNOMO E03.81.501, IP54, IK08. Extended rotary handle Degree of protection IP55, IK08. This handle makes it possible to operate circuit breakers installed at the back of switchboards, from the switchboard front. It maintains: b suitability for isolation b indication of the three positions O (OFF), I (ON) and tripped b access to trip unit settings, when the switchboard door is open b circuit breaker locking capability in the OFF position by one to three padlocks, shackle diameter 5 to 8 mm (not supplied). The door cannot be opened if the circuit breaker is ON or locked. The extended rotary handle is made up of: b a unit that replaces the front cover of the circuit breaker (secured by screws) b an assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontally b an extension shaft that must be adjusted to the distance (min/max distance between back of circuit breaker and door is 185/600 mm).

054558

Compact NS80H-MA with a direct rotary handle

054563

Compact NS80H-MA with an extended rotary handle

92

Schneider Electric

Locking systems
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking systems can receive up to three padlocks with shackle diameters ranging from 5 to 8 mm (padlocks not supplied).
E58552

Toggle locking using a removable device

Outgoing-circuit identification
Compact NS80H-MA and NSC100N devices come with clip-in labels for handwritten indications. It is also possible to use pre-printed Telemecanique labels (part number AB1-** (8 digits).
E18595

P D E P. P O M
Identification accessories

.P DE P
push to trip

Schneider Electric

93

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (fixed version)


E58523

Sealable terminal shield


que dilectri rnes test avant ce cache-bo c test enlever dielectri shield before terminal this L3 remove L2

L1

0V 220/60

z 50/60H

Voltage-presence indicator

Rear connector Connectors One-piece spreader

Interphase barriers
2
arged disch
ct compa L 0 NS25 Uimp 8kV. Ui 750V. Icu(kA) 150 Ue(V) 0 150 220/245 130 380/41 70 440 20 500 0 100 600/69 250 Icu cat A 100% Ics =
VDE UTE NEMA 947-2 UNE IEC CEI BS

O OFF
5...8

ON I

1
5..
ct compa L

.8
manu

auto

O
push OFF

I
push ON

Ui 750V

com 50NH NB2 . Uimp 8kV.

pact

ON I

Ue (V) 40 220/2 15 380/4 440 25 500/5 90 660/6 250 Icu 00% Ics=1 cat A 47-2 IEC9 BS CEI VDE
UTE

Icu (kA) 100 70 65 50 10 85

NS25 Uimp 8kV. Ui 750V. Icu(kA) 150 Ue(V) 0 150 220/245 130 380/41 70 440 20 500 0 100 600/69 250 Icu cat A 100% Ics =
VDE UTE NEMA 947-2 UNE IEC CEI BS

reset
push to trip

OFF

UNE

NEMA

125/
push to trip

160

D TM 250 40C 250A/

Im 10 Ir
.8 .9 9 8

5 6 7

Ir

Im

act comp L 0 NS25 Uimp 8kV. Ui 750V. Icu(kA) 150 Ue(V) 0 150 220/245 130 380/41 70 440 20 500 0 100 600/69 250 Icu cat A 100% Ics =
VDE UTE NEMA 947-2 UNE IEC CEI BS

reset
push to trip

OFF

Direct rotary handle


ON I

Motor-mechanism module

x 250A

Rear insulating screens

x 250A

Auxiliary contact
tripped
5.. .8

reset

O OFF

Extended rotary handle

Voltage release

80 40 0 120

que dilectri le test avant ce couverc enlever c test dilectri cover before this remove

Ammeter module Current-transformer module

vigi
NS 250 V-50/60
200/525 Hz
-25

310 50 60 0
5

t(ms)

H vigiM
10
6 2 4

3 1

In(A) 0,3

HS

t=0) 0,03(

0A 160/25
90 %Ir 105

STR

22 SE
test

Im Ir
0A In=25
.8 .98 .7 .63 xIn 1 .9 .85 .95 3 8 2 1.5 xIr 10 4 5 6 Ir Im

alarm

Insulation-monitoring module

Trip unit

Sealable terminal shield

94

Schneider Electric

Compact NS100 to 630 (plug-in and withdrawable versions)


E58715

Sealable terminal shield


que dilectri rnes test avant ce cache-bo c test enlever dielectri shield before terminal this L3 remove L2

L1

0V 220/60

z 50/60H

Voltage-presence indicator

Terminal extensions and spreaders

Rear connectors Connectors for withdrawable devices One-piece spreader Connectors

Plug-in base

Interphase barriers
2
arged disch
ct compa L 0 NS25 Uimp 8kV. Ui 750V. Icu(kA) 150 150 130 70 20 100 Ue(V) 0 220/245 380/41 440 500 0 600/69 250 Icu cat A 100% Ics =
VDE UTE NEMA 947-2 UNE IEC CEI BS

O OFF
5...8

ON I

Chassis side plate


4 5 6 7 8 9

Control-wire connection plate

1
5..
ct

.8
manu

auto

O
push OFF

I
push ON

50N NB2 . Uimp 8kV. Icu Ui 750V (kA) Ue 100 (V) 40 70 220/2 15 65 380/4 50 440 25 10 500/5 90 85 660/6 250 Icu 00% Ics=1 A cat
47-2 IEC9 BS CEI VDE
UTE UNE NEMA

pact com H

ON I

Ui 750V. Icu(kA 150 Ue(V) 0 150 220/245 130 380/41 70 440 20 500 0 100 600/69 250 Icu cat A 100% Ics =

compa L 0 NS25 Uimp 8kV. )

reset
push to trip

OFF

VDE UTE NEMA 947-2 UNE IEC CEI BS

125/
push to trip

160

D TM 250 40C 250A/

Im 10 Ir
.8 .9 9 8

5 6 7

Ir

Im

act comp L 0 NS25 Uimp 8kV. Ui 750V. Icu(kA) 150 Ue(V) 0 150 220/245 130 380/41 70 440 20 500 0 100 600/69 250 Icu cat A 100% Ics =
VDE UTE NEMA 947-2 UNE IEC CEI BS

reset
push to trip

OFF

Direct rotary handle


ON I

Motor-mechanism module

Control-wire connection on chassis


80 40 0 120

Schneider Electric

1 2 3

x 250A

x 250A

Auxiliary contact Circuit-breaker side plate Voltage release

tripped

5..

.8

reset

O OFF

Extended rotary handle

que dilectri le test avant ce couverc enlever c test dilectri cover before this remove

Ammeter module Current-transformer module

vigi
NS 250 V-50/60
200/525 Hz
-25

310 50 60 0
5

t(ms)

H vigiM
10
6 2 4

3 1

In(A) 0,3

HS

t=0) 0,03(

0A 160/25
90 %Ir 105

STR

22 SE
test

Im Ir
0A In=25
.8 .98 .7 .63 xIn 1 .9 .85 .95 3 8 2 1.5 xIr 10 4 5 6 Ir Im

alarm

Insulation-monitoring module

Trip unit

Sealable terminal shield

95

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630


Installation
Fixed circuit breakers
Compact circuit breakers may be mounted vertically, horizontally or flat on their back without any derating of characteristics. They are designed for easy installation in the various types of switchboards of each market and country.

045345

E58529

Fixed Compact NS250H

E59278

Installation positions

Mounting on a backplate (solid or slotted)

E58530

Mounting on rails

Mounting on DIN rail (with adapter)

E18850

Mounting on a Prisma functional mounting plate.

Circuit breaker on a plug-in base

The plug-in configuration makes it possible to: b extract and/or rapidly replace the circuit breaker without having to touch connections b allow for the addition of future circuits at a later date.
041632

E21017

E21018

Mounting on a backplate

Mounting through a front panel

E21019

Mounting on rails

Compact NS250H on a plug-in base

Installation positions

Protection against direct contacts with power circuits b circuit breaker plugged in = IP4 b circuit breaker removed = IP2 b circuit breaker removed, base equipped with shutters = IP4 Parts of a plug-in configuration b Compact circuit breaker b set of power connectors added to the circuit breaker b plug-in base for mounting on a backplate or on rails b insulating screen, for use when the circuit breaker is installed on a backplate with front connections b safety trip, installed on the circuit breaker, that causes automatic tripping if the circuit breaker is ON, before engaging or withdrawing it. The safety trip does not prevent circuit breaker operation, even when it has been removed. b mandatory short terminal shields. Accessories Insulating accessories can be used to: b protect against direct contact b increase insulation between phases.
Schneider Electric

E59279

96

E58714

b disconnected position - the power circuits are disconnected, but the circuit breaker is still on the chassis and may still be operated (ON, OFF, push-to-trip). b the circuit breaker may be locked using 1 to 3 padlocks (shackle diameter 5 to 8 mm), to prevent connection. b the auxiliaries can be tested (with manual auxiliary connector).
041879

Circuit breaker on a withdrawable chassis


E21282

Connected

Disconnected

Removed

The chassis is made up of two side plates installed on the base and two other plates mounted on the circuit breaker. Accessories b auxiliary contacts for installation on the fixed part, indicating the connected and disconnected positions b toggle collar for circuit breakers with a toggle mounted through a front panel, intended to maintain the degree of protection whatever the position of the circuit breaker (supplied with a toggle extension) b keylock which, depending on the bolt fitted, can be used to: v prevent insertion for connection v lock the circuit breaker in the connected or disconnected positions. b telescopic shaft for extended rotary handles.

Compact NS250H on a withdrawable chassis

E59279

Installation positions

Front and rear connections


Fixed, plug-in and withdrawable Compact devices may all be equipped with front and rear connections. Fixed device

E58733

Front connection

Rear connection

Plug-in and withdrawable devices

E58716

E58717

Front connection

E58718

Rear connection

E58719

Rear connection through a backplate

Schneider Electric

97

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (cont.)


Connection of fixed devices
Front connection of bars or cables with lugs
The Compact NS100 to NS630 devices are equipped as standard with terminals comprising snap-in nuts with screws (M8 for NS100 to 250, M10 for NS400 to 630) for direct connection to insulated bars or cables with lugs. Additional terminal extensions (right-angle, edgewise, spreaders) are available for all connection requirements. Spreaders (52.5 or 70 mm pitch) may be fitted on the Compact NS400 to 630. Lugs Lugs are different for copper and aluminium cables. They are supplied with interphase barriers and are compatible with the long terminal shields. b the small lugs for copper cables may be used for cables with the following cross-sectional areas: v 120, 150 or 185 mm2 (NS100 to 250) v 240 or 300 mm2 (NS400 to 630). Crimping by hexagonal barrels or punching. b the small lugs for aluminium cables may be used for cables with the following cross-sectional areas: v 150 or 185 mm2 (NS100 to 250) v 240 or 300 mm2 (NS400 to 630). Crimping by hexagonal barrels. Spreaders Spreaders increase the pitch of the terminals. They are not compatible with terminal shields on the Compact NS100 to 250. The one-piece spreader increases the pitch, thus making it possible to use the connection accessories of a larger device (e.g. a Compact NS100 to 250 can be fitted with the accessories of a Compact NS400 to 630). The one-piece spreader also provides protection against direct contact (see page 101).

E54456

E58531

E58534

Right-angle terminal extensions

E58535

Straight terminal extensions for NS100 to 250

E58536

E58720

Edgewise terminal extensions for NS400 to 630

E58537

Small lug for copper cables

E58532

E58538

Small lug for aluminium cables

E58539

Spreaders

E58533

E58721

One-piece spreader

98

Schneider Electric

E54457

Bare-cable connectors for Compact NS devices may be used for both copper and aluminium cables. 1-cable connectors for Compact NS100 to 250 The connectors snap directly on to the device terminals or clip onto right-angle and straight terminal extensions as well as spreaders. 1-cable and 2-cable connectors for Compact NS400 to 630 The connectors are screwed to device terminals or right-angle terminal extensions. Distribution connectors for Compact NS100 to 250 These connectors are screwed directly to device terminals. Interphase barriers are supplied with distribution connectors, but may be replaced by long terminal shields. Each connector can receive six cables with cross-sectional areas ranging from 1.5 to 35 mm2 each. Polybloc distribution block for Compact NS100 to 630 The Polybloc connects directly to the device terminals and is used to connect up to six or nine flexible or rigid cables with cross-sectional areas not exceeding 10 mm2, to each pole. Connection is made to spring terminals without screws.

E54468

Front connection of bare cables

1-cable connector for NS100 to 250


E54469

E58540

1-cable connector for NS400 to 630


E54470

2-cable connector for NS400 to 630


E54471

E58722

Distribution connector for NS100 to 250


E54472

Polybloc distribution block for NS100 to 250

E54456

Rear connections for bars or cables with lugs are available in two lengths. Bars may be positioned flat, on edge or at 45 angles depending on how the rear connections are positioned. The rear connections are simply fitted to the device connection terminals. All combinations of rear connection lengths and positions are possible on a given device. The device is mounted on a backplate. For the connection of cables without lugs, the 1-cable connectors for Compact NS100 to 250 may be simply clipped onto the rear connections.

E58724

Rear connection

E58723

Two lengths

E58725

Four positions

E58726

Connection of bare cables to NS100 to 250.

Schneider Electric

99

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (cont.)


Connection of plug-in devices
Connection of bars or cables with lugs
The plug-in base is equipped with terminals which, depending on their orientation, serve for front and rear connection. For rear connection of a base mounted on a backplate, the terminals must be replaced by insulated, long right-angle terminal extensions. For Compact NS630 devices, connection most often requires the 52.5 or 70 mm pitch spreaders. Connection accessories See the Connection of fixed devices section.

E54456

E58717

E58727

Front connection

Front connection with spreaders

E58718

Rear connection

E58719

Rear connection of a base mounted on a backplate


E54457

Connection of bare cables


All terminals may be equipped with bare-cable connectors. See the Connection of fixed devices section.

E58728

Plug-in base for Compact NS100 to 250 equipped with 1-cable connectors

E58729

Plug-in base for Compact NS400 to 630 equipped with 2-cable connectors

100

Schneider Electric

056384

One-piece spreader
Connection of large cables may require an increase in the distance between the device terminals. The onepiece spreader is an accessory that can also be fitted on Interpact INS switch-disconnectors. It offers the following features: b increases the pitch of the circuit-breaker terminals to correspond to that of the next largest frame size b compatible with all the connection accessories available for the next largest frame size (connectors, terminal extensions, etc.) b enhances insulation between phases in comparison with standard spreaders. NS100 to 250 NS400 to 630
Pitch without spreaders (mm) Pitch with standard spreaders (mm) Pitch with one-piece spreader (mm) 35 45 45 45 52.5 or 70 70
E58730

One-piece spreader

Mounting
When equipped with a one-piece spreader, Compact NS circuit breakers may be installed either at the back of a switchboard or on the front panel with a raiser. b devices with different frame sizes can thus be aligned in the switchboard b the same mounting plate can be used for all devices (including Interpact INS switch-disconnectors).

E58731

E58732

Connection and insulation accessories are identical to those for Interpact INS switch-disconnectors

Mounting at the back of a switchboard

Mounting behind the front panel with a raiser

Schneider Electric

101

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (cont.)


Insulation of live parts
Terminal shields
Terminal shields are sealable insulating accessories used for protection against direct contact with power circuits (degree of protection IP40, IK07). They are supplied with sealing accessories. Terminal-shield selection b fixed circuit breaker, front connection - long terminal shields b fixed circuit breaker, rear connection - short terminal shields b for voltages u 500 V, terminal shields are mandatory b for voltages > 600 V, special connection kit with terminal shields and insulating screens b for Compact NS400 to 630 with spreaders, special terminal shields for spreaders b for withdrawable circuit breaker (plug-in and chassis type), short terminal shields on the device are mandatory. Terminal shields on the base are possible. Long terminal shields for plug-in bases are used to: b protect against direct contact with power circuits (degree of protection IP40, IK07) b increase insulation between phases. Insulating accessories for plug-in bases include: b an adapter offering the same connection possibilities as the circuit breaker b long terminal shields for the plug-in base.
E58541

049221

Terminal shields

Compact NS equipped with terminal shields.

E58542

Interphase barriers

Interphase barriers
Safety accessories for maximum insulation at the power-connection points: b they clip easily onto the circuit breaker b not compatible with terminal shields b special version for plug-in bases.
E58543

Rear insulating screens


Safety accessories for insulation between connections and the backplate. Compatible with terminal shields or interphase barriers.

Rear insulating screens

102

Schneider Electric

E28443

OF1

SD

SDE OF2

Connection of electrical auxiliaries


Fixed configuration
Auxiliary circuits exit the device through a knock-out in the front cover.

MN/MX

motor mechanism

OR

rotary handle

SDV

Compact NS100/160/250

E28444

OF1 OF2 OF3

SD

SDE

E18585

Plug-in and withdrawable configurations


MN/MX motor mechanism rotary handle
E18586

OR

SDV

Compact NS400 to 630

Automatic auxiliary connectors Auxiliary circuits exit the circuit breaker via one to three automatic auxiliary connectors (nine wires each). These are made up of: b a moving part, connected to the circuit breaker via a support (one support per circuit breaker) b a fixed part, mounted on the plug-in base, equipped with connectors for bare cables up to 2.5 mm2. Selection of automatic auxiliary connectors. For Compact NS400 to 630, connection wires for the options installed with trip unit STR53UE also exit via the automatic auxiliary connectors.
E21397

E21398

connector 2 connector 1 OF2/SDV OF1 SDE/MT SD MT MN/MX

connector 3 OF3/SDV connector 2 COM connector 1 OF2 T OF1 SDE/MT SD MT MN/MX

Compact NS100 to 250

Compact NS400 to 630

Manual auxiliary connector for withdrawable configurations Withdrawable circuit breakers may be equipped with one to three plugs with nine wires each. In disconnected position, the auxiliaries remain connected and can therefore be tested by operating the circuit breaker.
E18587

Each auxiliary is equipped with a terminal block with numbered terminals for connection of wires up to: b 1.5 mm2 for auxiliary contacts and voltage releases b 2.5 mm2 for the motor-mechanism module.

Nine-wire manual auxiliary connector

Schneider Electric

103

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (cont.)


Indication contacts
Common-point changeover contacts are used to remote circuit-breaker status information and can thus be used for indications, electrical locking, relaying, etc. They comply with the IEC 60947-5 international recommendation. Functions b OF (ON/OFF) - indicates the position of the circuit breaker contacts b SD (trip indication) - indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth-leakage fault v operation of a voltage release v operation of the push to trip button v disconnection when the device is ON. Returns to de-energised state when the circuit breaker is reset. b SDE (fault indication) - indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth-leakage fault. Returns to de-energised state when the circuit breaker is reset. b SDV (Earth-leakage fault indication) - indicates that the circuit breaker has tripped due to an earth fault. Returns to de-energised state when the circuit breaker is reset. b CAM (early-make or early-break function) - indicates the position of the rotary handle. Used in particular for advanced opening of safety trip devices (early break) or to energise a control device prior to circuit-breaker closing (early make) b CE / CD (connected/disconnected position) - microswitch type carriage switches for withdrawable circuit breakers Installation b OF, SD, SDE and SDV functions - a single type of contact provides all these different indication functions, depending on where it is inserted in the device. The contacts clip into slots behind the front cover of the circuit breaker (or the Vigi module for the SDV function). The SDE function on a circuit breaker equipped with a thermal-magnetic trip unit requires the SDE actuator. b CAM function - the contact fits into the rotary-handle unit (direct or extended). b CE / CD (connected/disconnected) function - two parts must be fitted on the fixed and moving parts of the chassis. Electrical characteristics of auxiliary contacts Contacts
Rated thermal current (A) Minimum load Utilisation cat. (IEC 60947-5-1) Operational 24 V current (A) 48 V 110 V 220/240 V 250 V 380/440 V 660/690 V

044314

Changeover contacts

All the auxiliary contacts opposite are also available in low-level versions capable of switching very low loads (e.g. for the control of PLCs or electronic circuits).

Standard
6 100 mA at 24 V AC12 AC15 DC12 6 6 2.5 6 6 2.5 6 5 0.8 6 4 0.3 6 3 6 0.1 -

Low level
5 2 mA at 15 V DC AC12 AC15 DC12 5 3 5 5 3 2.5 5 2.5 0.8 5 2 5 0.3 5 1.5 -

DC14 1 0.2 0.05 0.03 -

DC14 1 0.2 0.05 0.03 -

104

Schneider Electric

045349

Rotary handles
There are two types of rotary handle: b direct rotary handle b extended rotary handle. There are two models: b standard with a black handle b VDE with a red handle and yellow front for machine-tool control.

Direct rotary handle


Compact NS250L with a direct rotary handle

Degree of protection IP40, IK07. The direct rotary handle maintains: b visibility of and access to trip unit settings b suitability for isolation b indication of the three positions O (OFF), I (ON) and tripped b access to the push to trip button b circuit breaker locking capability in the OFF position by one to three padlocks, shackle diameter 5 to 8 mm (not supplied). It replaces the circuit-breaker front cover. Accessories transform the standard direct rotary handle for the following situations: b motor control centre (MCC) switchboards: v door opening disabled when the circuit breaker is ON v circuit-breaker closing is disabled if the door is open b a higher degree of protection (IP43, IK07) b machine-tool control, complying with CNOMO E03.81.501, IP54, IK08.

044316

Extended rotary handle


Compact NS250L with an extended rotary handle

Degree of protection IP 55, IK08. This handle makes it possible to operate circuit breakers installed at the back of switchboards, from the switchboard front. It maintains: b suitability for isolation b indication of the three positions O (OFF), I (ON) and tripped b access to trip unit settings, when the switchboard door is open b circuit breaker locking capability in the OFF position by one to three padlocks, shackle diameter 5 to 8 mm (not supplied). The door cannot be opened if the circuit breaker is ON or locked. The extended rotary handle is made up of: b a unit that replaces the front cover of the circuit breaker (secured by screws) b an assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontally b an extension shaft that must be adjusted to the distance. The min/max distance between the back of circuit breaker and door is: v 185 to 600 mm for Compact NS100 to 250 v 210 to 625 mm for Compact NS400 to 630. For withdrawable configurations, the extended rotary handle is also available with a telescopic shaft with two stable positions.

Schneider Electric

105

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (cont.)


Remote tripping
MX or MN voltage releases are used to trip the circuit breaker. MN undervoltage release This release trips the circuit breaker when the control voltage drops below a tripping threshold: b tripping threshold between 0.35 and 0.7 times the rated voltage b circuit breaker closing is possible if the voltage exceeds 0.85 times the rated voltage. For a lower value, circuit breaker closing cannot be guaranteed. Circuit breaker tripping by an MN release meets the requirements of standard IEC 60947-2. Time-delay unit for an MN release Eliminates nuisance tripping due to transient voltage dips lasting 200 ms. It is used in conjunction with: b a 250 V DC MN release, control voltage 220/240 V AC b a 48 V DC MN release, control voltage 48 V AC. MX shunt release Trips the circuit breaker when the control voltage rises above 0.7 x Un. Control signals can be of the impulse type (u 20 ms) or maintained. Operation When the circuit breaker has been tripped by an MN or MX release, it must be reset locally. MN or MX tripping takes priority over manual closing. In the presence of a standing trip order, closing of the contacts, even temporary, is not possible. Mechanical characteristics b endurance is equal to 50 % of the mechanical endurance of the circuit breaker b the releases clip in behind the front cover b connection using wires up to 1.5 mm2, to integrated terminal blocks. Electrical characteristics b consumption: v pick-up (MX): < 10 VA v seal-in (MN and MNR): < 5 VA. b response time: < 50 ms.

044313

MX or MN voltage release

106

Schneider Electric

047313

Motor-mechanism module
When equipped with a motor-mechanism module, Compact NS circuit breakers feature very high mechanical endurance as well as easy and sure operation: b all circuit-breaker indications and information remain visible and accessible, including trip-unit settings and indications b suitability for isolation is maintained and padlocking remains possible b double insulation of the front face. Applications b local motor-driven operation, centralised operation, automatic distribution control b normal/standby source changeover or switching to a replacement source to optimise energy costs b load shedding and reconnection to optimise energy costs b synchrocoupling. Automatic operation b circuit-breaker ON and OFF controlled by two impulse-type or maintained control signals b automatic spring charging following voluntary tripping (by MN or MX), with standard wiring b mandatory manual reset following tripping due to an electrical fault. Manual operation b transfer to manual mode using a switch (9) with possibility of remote mode indication b circuit-breaker ON and OFF controlled by 2 pushbuttons b recharging of stored-energy system by pumping the lever 9 times b padlocking in OFF position. Installation and connection All installation (fixed, plug-in/withdrawable) and connection possibilities are maintained. Motor-mechanism module connections are made behind its front cover to integrated terminals, for cables up to 2.5 mm2. Accessories b keylock for locking in OFF position b operations counter for the Compact NS400 and NS630, indicating the number of ON and OFF cycles. The counter must be installed on the front of the motormechanism module. Characteristics Motor mechanism
contact position indicator (suitability for isolation) outgoing-circuit identification labels spring status indicator (charged, discharged) locking device (keylock) locking device (OFF position), using 1 to 3 padlocks, shackle diameter 5 to 8 mm, not supplied 6 manual spring-charging lever 7 I (ON) pushbutton 8 O (OFF) pushbutton 9 manual/auto mode selection switch. The position of this switch can be indicated remotely 10 operations counter (Compact NS400/630) 1 2 3 4 5
Response time (ms) Rate Control voltage (V) opening closing cycles/minute max. DC AC 50/60 Hz Consumption
(1)

Compact NS250H with motor mechanism

1
E21006

compact

NS400 H
Ui 750V. Uimp 8kV. Ue Icu (V) (kA) 220/240 380/415 440 500/525 600/690 100 70 65 50 20

cat A Ics = 100% Icu IEC 947-2


UTE VDE BS UNE NEMA CEI

O OFF

charged

In = 400A

manu

auto

O
push OFF

I
push ON

10

MT100 to MT630
< 600 < 80 4 24/30 - 48/60 110/130 - 250 48 (50 Hz) - 110/130 220/240 - 380/440 y 500 y 500 y 500 y 500

DC (W) AC (VA)

opening closing opening closing

Electrical endurance Circuit breaker + motor-mechanism module, in thousands of operations (IEC 60947-2), at 440 V.
E21300

50 40 30 20 15 10 NS250 NS400 NS630 0,2 0,3 0,5 0,7 1 I/In NS100 NS160

6 4 0,1

(1) For NS100/250, motor "vibratory" type consider inrush current as 2 In during 10 ms cycling.
Schneider Electric

107

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (cont.)


Indications and measurement
Voltage presence indicator
The indicator detects and indicates that circuit breaker terminals are supplied with power. Installation b in the long or short terminal shields, via the knockouts b not compatible with the motor-mechanism module b upstream or downstream of the circuit breaker b degree of protection IP40, IK04. Electrical characteristics Operates on all networks with voltages ranging from 220 to 550 V AC.

048287

Current-transformer module
Compact NS630L with voltage-presence indicator

This module enables direct connection of a measurement device such as an ammeter or a Digipact power meter (not supplied). Installation b directly on the downstream circuit-breaker terminals b degree of protection IP40, IK04 b class II insulation between front and the power circuits b connection to 6 integrated connectors for cables up to 2.5 mm2. Electrical characteristics b transformer with 5 A secondary winding. b accuracy class 3 for the following output-power consumptions: v rating 100 A: 1.6 VA v rating 150 A: 3 VA v rating 250 A: 5 VA v rating 400/630A: 8 VA.

041892

Ammeter and Imax ammeter modules


Ammeter module Measures and displays (dial-type ammeter) the current of each phase (selection of phases by 3-position switch in front). Imax ammeter module Measures and displays (dial-type ammeter) the maximum current flowing in the middle phase. The Imax value can be reset on the front. Installation b identical for both types of ammeter module b directly on the downstream circuit-breaker terminals b ammeter clips into module in any of four 90 positions, i.e. can be installed of devices mounted both vertically and horizontally b degree of protection IP40, IK04 b class II insulation between front and the power circuits. Electrical characteristics b ammeter module: accuracy class 4.5 b Imax ammeter module: v accuracy 6 % v maximum currents are displayed only if they last at least 15 minutes.

Compact NS630H with current-transformer module

045212

Compact NS250L with ammeter module

108

Schneider Electric

041896

Insulation-monitoring module
This module detects and indicates an insulation drop on a load circuit (TN-S or TT systems). Operation is identical to that of a Vigi module, but without circuit-breaker tripping. Indication by a red LED in front. An auxiliary contact may be installed for remote insulation-drop indications. Installation b directly on the downstream circuit-breaker terminals b degree of protection: IP40, IK04 b double insulation of the front face. Electrical characteristics b settings: 100, 200, 500 and 1000 mA b accuracy: -50 +0 % b time delay following drop: 5 to 10 seconds b AC-system voltage: 200 to 440 V AC and 440 to 550 V AC.

Compact NS250H with insulation-monitoring module

053172

Communication
Communicating versions of the auxiliary contacts and the motor-mechanism module also exist for integration in a Digipact communications system. They simply replace the standard electrical auxiliaries. Using the STR53UE and STR43ME trip units equipped with the COM communications option, it is possible to transmit data to Digipact modules: b settings b rms values of phase and neutral currents b current of the most heavily loaded phase b overload alarm in progress b tripping cause (overload, short-circuit, etc.).
Compact NS equipped with communicating auxiliary contacts and motor-mechanism module

054481

Withdrawable Compact NS equipped with communicating auxiliary contacts

Schneider Electric

109

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (cont.)


Locking systems
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking systems can receive up to three padlocks with shackle diameters ranging from 5 to 8 mm (padlocks not supplied). Control device
Toggle

Function
lock in OFF position lock in OFF or ON position lock in OFF position

Means
padlock padlock padlock keylock padlock padlock keylock padlock keylock

Required accessories
removable device fixed device

Direct rotary handle

locking device + keylock

MCC rotary handle Rotary handle Extended rotary handle Motor mechanism

lock in OFF position lock in OFF position lock in OFF position, door opening prevented lock in OFF position, motor mechanism locked out

keylock

locking device (keylock incorporated)

E58544

E58545

E18620

ON I

pr of al ux

O OFF

Locking of the toggle using a removable device

Locking of the toggle using a fixed device

Locking of the rotary handle using a padlock or a keylock.

110

Schneider Electric

048803

Individual enclosures
Compact NS and Vigicompact NS devices with two, three or four poles may be installed in individual enclosures. All fixed, front connections are possible, except right-angle and edgewise terminal extensions. Spreaders may be installed in the enclosures intended for Interpact Compact and Vigicompact NS250 to 630 devices. There are two models of enclosures: b heavy-duty metal individual enclosure, with: v metal enclosure v door with keylock and cut-out for rotary handle v direct rotary handle (CNOMO, IP55, IK08) v device mounting plate v removable plate (without holes) for cable entry through bottom b heavy-duty insulating individual enclosure, with: v insulating enclosure v transparent cover, screwed, lead sealable, with cut-out for rotary handle v extended rotary handle v device mounting plate v removable plates (without holes) for cable entry through bottom and/or top. Dimensions (W x H x D in mm) b metal enclosures: W D v Compact NS100 to 160: 300 x 400 x 200 v Vigicompact NS100 to 160: 400 x 500 x 200 v Compact NS250 to 400: 400 x 600 x 200 v Compact NS630: 600 x 800 x 275 v Vigicompact NS250 to 630: 600 x 800 x 275 b insulating enclosures: H v Compact/Vigicompact NS100 to 160: 270 x 360 x 235 v Compact NS250: 270 x 540 x 235 v Compact NS400 to 630: 360 x 720 x 235 v Vigicompact NS250 to 630: 360 x 720 x 235
E44458

Heavy-duty insulating individual enclosure for Compact NS

Schneider Electric

111

Functions and characteristics

Electrical and mechanical accessories Compact NS100 to 630 (cont.)


Escutcheons
Escutcheons are an optional feature mounted on the switchboard door. They increase the degree of protection to at least IP40, IK07.
E21265 E23938

E23935

E23936

ON I

push to trip

O OFF

Front-panel escutcheons for toggle and Vigi module (NSA160). Secures to the panel, from the front.

Toggle cover b degree of protection IP43, IK07 b fits on the front of the circuit breaker.

E22039

Front-panel escutcheon for rotary handle. Secures to the panel by four screws, from the front. For circuit breaker with motor mechanism and Vigi module, use the protection collar for front panel mounting (see below).

80 40 0 120

Front-panel escutcheons for ammeter module. Secures to the panel by four screws, from the front.

Protection collar for toggle and Vigi module on withdrawable devices


Protection collars maintain the degree of protection, whatever the position of the device (connected, disconnected). b front-panel escutcheons are mandatory (same as those for rotary handles and ammeter modules) b collars are mounted on the device using two screws b escutcheons are attached to the switchboard b a toggle extension is supplied with the collar. For the insulation-monitoring module, use the same elements as for the Vigi module. Front-panel escutcheons for motor mechanism, rotary handles, ammeter modules Same as for fixed devices.

112

E21267

Schneider Electric

Outgoing-circuit identification
Compact NS100 to 630 devices come with clip-in labels for hand-written indications. It is also possible to use pre-printed Telemecanique labels part number AB1-**: v Compact NS100 to 250: 8 digits v Compact NS400 to 630: 16 digits.
E18595

P D E P. P O M
Identification accessories

.P DE P
push to trip

Sealing accessories
This option includes the elements required to fit lead seals to prevent: b front removal b rotary-handle removal b opening of the motor-mechanism module b access to auxiliaries b access to trip-unit settings b trip-unit removal b access to earth-leakage protection settings b terminal-shield removal b access to power connections.
E18596

Sealing accessories

Schneider Electric

113

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (fixed version)


E59224

Sealable terminal shield

Terminal extension for cables with lugs Interphase barriers

Connection kit for connectors


Spreader

Vertical connection adapter

Phase barriers Rear connectors Spreader

Auxiliary contact

Voltage release

I on

I O
push push OFF

ON

arged disch

O OFF

Manual control with front connection


I on

trippe

reset

0 OF

012

53

Manual control with rear connection

trippe

reset

0 OF

Direct rotary handle


tripped reset

Electrical control with mixed connection Extended rotary handle Communications module

Connection kit for connectors

Sealable terminal shield Escutcheon

114

Schneider Electric

Compact NS630 to 1600 (withdrawable version)


E59225

Interphase barriers

Terminal extention for cables with lugs

Vertical connection adapter Spreader Rear connectors

Spreader

Auxiliary contact

Chassis with front or rear connection

Voltage release

I on

I O
push push OFF

ON

Manual operation
trippe d reset

arged disch

O OFF

I on

0 OF

012

53

trippe

reset

0 OF

Electrical operation
tripped reset

Direct rotary handle

Communications module

Extended rotary handle

Escutcheon

Transparent cover

Schneider Electric

115

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600


Installation
Fixed configuration
Compact NS630b to 1600 circuit breakers may be installed vertically, horizontally or flat on their back.

E45151

E59226A

Fixed Compact NS800H

E59278

Mounting on a backplate

E59227A

Mounting on rails

The withdrawable configuration makes it possible to: b extract and/or rapidly replace the circuit breaker without having to touch connections; b allow for the addition of future circuits at a later date.
E45176

Withdrawable configuration
Compact NS630b to 1600 circuit breakers should be installed vertically only.

E59228A

Mounting on a backplate

E59229A

Rear mounting on rails

E59230

Withdrawable Compact NS800H

E59281A

Device on mounting plate

E59231

Device on rails

116

Schneider Electric

The device may be in one of four positions on the chassis: b connected position. The power circuits and auxiliary contacts are all connected b test position. The power circuits are disconnected. The auxiliary contacts are still connected and the device can be operated electrically b disconnected position. The power circuits and auxiliary contacts are all disconnected, however the device is still mounted on the chassis. It can be operated manually (ON, OFF, "push to trip"). b removed position. All circuits are disconnected. The device simply rests on the chassis rails and can be removed.

E59232A

Connected

Test

Disconnected

Removed

The multifunctional chassis for Compact NS630b to 1600 devices is particularly suited for incoming circuit breakers. Features include: b device connection and disconnection through a door, using a crank that can be stored in the chassis b three positions (connected, test and disconnected) that are indicated: v locally by a position indicator v remotely by carriage switches (3 for the connected position, 2 for the disconnected position and 1 for the test position) b circuit-breaker ON/OFF commands through a switchboard front panel. Locking There are extensive locking possibilities: b chassis locking in connected, disconnected and test positions using three padlocks and two keylocks, on the switchboard front panel b door interlock (inhibits door opening with breaker in connected position) b racking interlock (inhibits racking with door open) b locking in each of the connected, disconnected and test positions during device connection or disconnection. Continuation to the next position requires pressing a release button to free the crank. Other safety function Mismatch protection ensures that a circuit breaker is installed only in a chassis with compatible characteristics.

E59267A

3 4 5 6 7 8 9 10 2

1 2 3 4 5 6 7 8 9 10

mismatch protection door interlock racking interlock keylock locking padlock locking position indicator chassis front plate (accessible with cubicle door closed) crank entry reset button crank storage

Schneider Electric

117

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (cont.)


Types of connection
Front connection
E59235

Compact NS630b to 1600 fixed and withdrawable devices can be connected using: b horizontal or vertical rear connections b front connections b mixed connections b a combination of front and rear connections.

Rear connection
Horizontal Vertical

E59233A

Simply turn a horizontal rear connector 90 to make it a vertical connector.

Combination of front and rear connections

Note. Compact circuit breakers can be connected indifferently with bare-copper, tinned-copper and tinned-aluminium conductors, requiring no particular treatment.

118

E59236

E59237

E59234A

Schneider Electric

Front connection of fixed devices


E54540

Bars
Fixed, front-connection Compact NS630b to 1600 devices are equipped with terminals comprising captive screws for direct connection of bars. Other connection possibilities for bars include verticalconnection adapters for edgewise bars and spreaders to increase the pole pitch to 95 mm. If the vertical connection adapters are front oriented, then it is mandatory to install the arc chute screen in order to comply with the safety clearances.
E46426A

E59235

Vertical-connection adapters

E59238A

E59239A

E46431A

Spreaders.

E59240A

E54457

Bare cables
Special sets of connectors and terminal shields may be used to connect up to four 240 mm2 copper or aluminium cables for each phase.
E46887A

E59241A

E70750

4-cable connectors

E54456

Cables with lugs


Cable lug adapters are combined with the verticalconnection adapters. One to four cables with crimped lugs (y 300 mm2) may be connected. To ensure stability, spacers must be positioned between the terminal extensions. If the cable lug adapters are installed over the top of the arc chute chambers, then it is mandatory to install the arc chute screen in order to comply with the safety clearances.
E46427A

Cable lug adapters

E59242A

E59243A

E70751

Schneider Electric

119

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (cont.)


Rear connection of fixed devices

E54540

Bars
Fixed, rear-connection Compact NS630b to 1600 devices equipped with horizontal or vertical connectors may be directly connected to flat or edgewise bars, depending on the position of the connectors. Spreaders are available to increase the pole pitch to 95 mm.
E46431A

E59236

Spreaders.

E59257A

E54456

E59247A

Cables with lugs


Cable lug adapters enable connection of one to four cables with crimped lugs (y 300 mm2). To ensure stability, spacers must be positioned between the terminal extensions.
E46427A

E59248A

Cable lug adapters

120

E59250A

E59249A

Schneider Electric

Front connection of withdrawable devices


Bars
E54540

Withdrawable, front-connection Compact NS630b to 1600 devices are suitable for direct connection of bars. Other connection possibilities for bars include verticalconnection adapters for edgewise bars and spreaders to increase the pole pitch to 95 mm.
E59252A E59253A

E59280

E46426A

Vertical-connection adapters

E46431A E59254A

Spreaders

Cables with lugs


Cable lug adapters enable connection of one to four cables with crimped lugs (y 300 mm2). To ensure stability, spacers must be positioned between the terminal extensions.
E54456 E46427A

Cable lug adapters

E59255A

E59253A

Schneider Electric

121

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (cont.)


Rear connection of withdrawable devices

E54540

Bars
Withdrawable, rear-connection Compact NS630b to 1600 devices equipped with horizontal or vertical connectors may be directly connected to flat or edgewise bars, depending on the position of the connectors. Spreaders are available to increase the pole pitch to 95 mm.
E46431A

E59282A

Spreaders

E59258A

E54456

E59260A

Cable lug adapters enable connection of one to four cables with crimped lugs (y 300 mm2). To ensure stability, spacers must be positioned between the terminal extensions.

E46427A

Cables with lugs

E59259A

Cable lug adapters


E59261A

122

E59262A

Schneider Electric

Insulation of live parts


E45190

Connection shield
Mounted on fixed, front-connection devices, this shield insulates power-connection points, particularly when cables with lugs are used
E59263A

Connection shield

Interphase barriers
These barriers are flexible insulated partitions used to reinforce isolation of connection points in installations with busbars, whether insulated or not. Barriers are installed vertically between front or rear connection terminals.
E79056

Compact NS equipped with connection shield

Interphase barriers for fixed device, front connection

E79057

Interphase barriers for fixed device, rear connection

E59264A

Interphase barriers for withdrawable device, rear connection

Safety shutters
Mounted on the chassis, the safety shutters automatically block access to the disconnecting contact cluster when the device is in the disconnected or test positions (degree of protection IP20). When the device is removed from its chassis, no live parts are accessible. The shutters can be padlocked (padlock not supplied) to: b prevent connection of the device b lock the shutters in the closed position.
E59265A

Safety shutters

Schneider Electric

123

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (cont.)


Connection of electrical auxiliaries

E59283A

Fixed devices
CAO1 CAO2 CAF1 CAF2 OF1 OF2 SD SDE COM MN or MX
E59286A

Connections are made directly to the auxiliaries once the front has been removed. Wires exit the circuit breaker through a knock-out in the top.

rotary handle

OF3

Manually operated device

E59284A

SDE

OF3

OF2

COM

MN or ou MX

OF1

Withdrawable devices
Auxiliary circuits are connected to terminal blocks located in the top part of the chassis. The auxiliary terminal block is made up of a fixed and moving part. The two parts are in contact when the device is in the test and connected positions.
E59287A

Electrically operated device

E59285A

CD2

CD1

CE3

CE2

CE1

Withdrawable device

124

CT1

Schneider Electric

044314

Indication contacts
Contacts installed in the device
Changeover contacts are used to remote circuit-breaker status information and can thus be used for indications, electrical locking, relaying, etc. They comply with the IEC 60947-5 international recommendation. Functions b OF (ON/OFF) - indicates the position of the main circuit breaker contacts b SD (trip indication) - indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth-leakage fault. v operation of a voltage release v operation of the "push to trip" button v disconnection when the device is ON. Returns to de-energised state when the circuit breaker is reset. b SDE (fault indication) - indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth-leakage fault. Returns to de-energised state when the circuit breaker is reset. b CAF / CAO (early-make or early-break function) - indicates the position of the rotary handle. Used in particular for advanced opening of safety trip devices (early break) or to energise a control device prior to circuit-breaker closing (early make). Installation b OF, SD and SDE functions - a single type of contact provides all these different indication functions, depending on where it is inserted in the device. The contacts clip into slots behind the front cover of the circuit breaker b CAF / CAO function - the contact fits into the rotary-handle unit (direct or extended). Electrical characteristics of the OF/SD/SDE/CAF/CAO auxiliary contacts Contacts
Rated thermal current (A) Minimum load Utilisation cat. (IEC 60947-5-1) Operational 24 V current (A) 48 V 110 V 220/240 V 250 V 380/440 V 660/690 V

OF, SD and SDE changeover contacts

All the auxiliary contacts opposite are also available in "low-level" versions capable of switching very low loads (e.g. for the control of PLCs or electronic circuits).

Standard
6 100 mA at 24 V AC12 AC15 DC12 6 6 2.5 6 6 2.5 6 5 0.8 6 4 0.3 6 3 6 0.1 -

Low level
5 2 mA at 15 V DC AC12 AC15 DC12 5 3 5 5 3 2.5 5 2.5 0.8 5 2 5 0.3 5 1.5 -

DC14 1 0.2 0.05 0.03 -

DC14 1 0.2 0.05 0.03 -

056456

Connected, disconnected, test position carriage switches


A single type of changeover contact can be mounted optionally on the chassis to indicate, depending on the slot where it is installed: b the connected (CE) position b the disconnected (CD) position. This position is indicated when the required clearance for isolation of the power and auxiliary circuits is reached b the test (CT) position. In this position, the power circuits are disconnected and the auxiliary circuits are connected. Installation b contacts for the connected (CE), disconnected (CD) and test (CT) positions clip into the upper front section of the chassis. Electrical characteristics of the CE/CD/CT auxiliary contacts Contacts
Rated thermal current (A) Minimum load Utilisation cat. (IEC 60947-5-1) Operational 24 V current (A) 48 V 110 V 220/240 V 250 V 380/440 V 660/690 V

Carriage switches for connected (CE), disconnected (CD) and test (CT) positions

Standard
8 100 mA at 24 V AC12 AC15 DC12 8 6 2.5 8 6 2.5 8 5 0.8 8 4 0.3 8 3 6 0.1 -

Low level
5 2 mA at 15 V DC AC12 AC15 DC12 5 3 5 5 3 2.5 5 2.5 0.8 5 2 5 0.3 5 1.5 -

DC14 1 0.2 0.05 0.03 -

DC14 1 0.2 0.05 0.03 -

Schneider Electric

125

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (cont.)


Rotary handles
There are two types of rotary handle: b direct rotary handle b extended rotary handle. There are two models: b standard with a black handle b VDE with a red handle and yellow front for machine-tool control.

E45159

Direct rotary handle


Degree of protection IP40, IK07. The direct rotary handle maintains: b visibility of and access to trip unit settings b suitability for isolation b indication of the three positions O (OFF), I (ON) and tripped b access to the "push to trip" button b circuit breaker locking capability in the OFF position by one to three padlocks, shackle diameter 5 to 8 mm (not supplied). It replaces the circuit-breaker front cover. Accessories transform the standard direct rotary handle for the following situations: b motor control centre (MCC) switchboards: v door opening disabled when the circuit breaker is ON; v circuit-breaker closing is disabled if the door is open; b a higher degree of protection (IP43, IK07) b machine-tool control, complying with CNOMO E03.81.501, IP54, IK07.

Compact NS with a direct rotary handle

E45161

Extended rotary handle


Compact NS with an extended rotary handle

Degree of protection IP55, IK07. This handle makes it possible to operate circuit breakers installed at the back of switchboards, from the switchboard front. It maintains: b suitability for isolation b indication of the three positions O (OFF), I (ON) and tripped b access to trip unit settings, when the switchboard door is open b circuit breaker locking capability in the OFF position by one to three padlocks, shackle diameter 5 to 8 mm (not supplied). The door cannot be opened if the circuit breaker is ON or locked. The extended rotary handle is made up of: b a unit that replaces the front cover of the circuit breaker (secured by screws) b an assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontally b an extension shaft that must be adjusted to the distance. The min/max distance between the back of circuit breaker and door is 218/605 mm.

126

Schneider Electric

Manually operated circuit breakers may be equipped with an MX shunt release, an MN undervoltage release or a delayed undervoltage release (MN + delay unit). Electrically operated circuit breakers are equipped as standard with a remoteoperating mechanism to remotely open or close the circuit breaker. An MX shunt release or an MN undervoltage release (instantaneous or delayed) may be added.
056421

Remote tripping
This function opens the circuit breaker via an electrical order. It is made up of: b a shunt release (MX) b or an undervoltage release (MN) b or a delayed undervoltage release (MN + delay unit). These releases (MX or MN) cannot be operated by the communication bus. The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain instantaneous opening of the circuit breaker. Wiring diagram for the remote-tripping function
E59433A E46553A E46554A

opening order

opening order

delayed opening order delay unit

10

12

MX voltage release

3 instantaneous opening order MN D1 D1

C2

D2

D2

MX C1

MN

Voltage releases (MX)


When energised, the MX voltage release instantaneously opens the circuit breaker. A continuous supply of power to the MX locks the circuit breaker in the OFF position. Characteristics
Power supply V AC 50/60 Hz V DC Operating threshold Permanent locking function Consumption (VA or W) Circuit-breaker response time at Un 24 - 48 - 100/130 - 200/250 - 277 - 380/480 12 - 24/30 - 48/60 - 100/130 - 200/250 0.7 to 1.1 Un 0.85 to 1.1 Un pick-up: 200 (200 ms) hold: 4.5 50 ms 10

Instantaneous voltage releases (MN)


The MN release instantaneously opens the circuit breaker when its supply voltage drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on the release, it is impossible to close the circuit breaker, either manually or electrically. Any attempt to close the circuit breaker has no effect on the main contacts. Circuit-breaker closing is enabled again when the supply voltage of the release returns to 85 % of its rated value. Characteristics
Power supply V AC 50/60 Hz V DC Operating opening threshold closing Consumption (VA or W) MN consumption with delay unit (VA or W) Circuit-breaker response time at Un 24 - 48 - 100/130 - 200/250 - 380/480 24/30 - 48/60 - 100/130 - 200/250 0.35 to 0.7 Un 0.85 Un pick-up: 200 (200 ms) hold: 4.5 pick-up: 400 (200 ms) hold: 4.5 90 ms 5

MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of the MN release can be delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions are available, adjustable and non-adjustable. Characteristics
Power supply V AC 50-60 Hz /DC Operating threshold Consumption of delay unit alone (VA or W) Circuit-breaker response time at Un non-adjustable 100/130 - 200/250 adjustable 48/60 - 100/130 - 200/250 - 380/480 opening 0.35 to 0.7 Un closing 0.85 Un pick-up: 200 (200 ms) hold: 4.5 non-adjustable adjustable 0.25 s 0.5 s - 0.9 s - 1.5 s - 3 s

Schneider Electric

127

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (cont.)


Electrically operated circuit breaker
The motor mechanism module is used to remotely open and close the circuit breaker. It is made up of a spring-charging motor equipped with an opening release and a closing release. An electrical operation function is generally combined with: b device ON/OFF indication (OF) b "fault-trip" indication (SDE). Wiring diagram of a point-to-point electrical operation solution
E59434A

Electrically operated circuit breakers are equipped as standard with a motor mechanism module. Two solutions are available for electrical operation: b a point-to-point solution b a bus solution with the COM communication option.
E45163

opening order A4

closing order A2 B4

fault 82

open 84 12

closed 14

motor mechanism module

OF1 SDE

A1

81

11

Electrically operated Compact NS circuit breaker

Wiring diagram of a bus-type electrical operation solution


E59435A

opening order A4

closing order A2 B4

motor mechanism module

A1

COM supervisor

OF SDE

In the event of simultaneous opening and closing orders, the mechanism discharges without any movement of the main contacts. In the event of maintained opening and closing orders, the standard electrical operation solution provides an antipumping function by blocking the main contacts in open position.

128

Schneider Electric

Motor mechanism module


Power supply V AC 50/60 Hz V DC Operating threshold Consumption (VA or W) Motor overcurrent Charging time Operating frequency 48/60 - 100/130 - 200/240 - 277- 380/415 24/30 - 48/60 - 100/125 - 200/250 0.85 to 1.1 Un 180 2 to 3 In for 0.1 second maximum 4 seconds maximum 3 cycles per minute

Electrical closing order The release remotely closes the circuit breaker if the spring mechanism is charged. Release electrical characteristics are identical to those of an MX release (see above), the operating threshold is from 0.85 to 1.1 Un and the circuit-breaker response time at Un is 60 ms 10. The Compact NS electrical operation function can be used to implement a synchrocoupling system. Electrical opening order The release instantaneously opens the circuit breaker when energised. The supply can be impulse-type or maintained. Release electrical characteristics are identical to those of an MX release (see above).

Schneider Electric

129

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (cont.)

E45194

Toggle locked by removable padlocking device

Locking on manually operated devices


Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking systems can receive up to three padlocks with shackle diameters ranging from 5 to 8 mm (padlocks not supplied). Control device
Toggle

Function
lock in OFF position lock in OFF or ON position lock in b OFF position b OFF or ON position lock in b OFF position b OFF or ON position lock in OFF position, door opening prevented

Means
padlock padlock padlock keylock padlock keylock padlock keylock

Required accessories
removable device fixed device

Direct rotary handle

Rotary handle locked by a keylock

E45159

locking device + keylock locking device + keylock keylock

CNOMO direct rotary handle

Extended rotary handle

Locking in ON position does not prevent the device from tripping in the event of a fault or remote tripping order.

E59436A

Access to pushbuttons protected by transparent cover

056447

Locking on electrically operated devices


1 reset of mechanical trip indicator 2 OFF pushbutton 3 OFF position locking 4 ON pushbutton 5 springs charged indication 6 pushbutton locking 7 contact position indication 8 operation counter

1
056446

4
I O
push push OFF ON

Pushbutton locking using a padlock

5 6 7

ed harg disc

O OFF

012

53

Pushbutton locking
OFF position locking using padlocks

The transparent cover blocks access to the pushbuttons used to open and close the device. It is possible to independently lock the opening OFF button and the closing ON button. The pushbuttons may be locked using either: b three padlocks (not supplied) b lead seal b two screws.

056448

Device locking in the OFF position


The circuit breaker is locked in the OFF position by physically maintaining the opening pushbutton pressed down: b using padlocks (one to three padlocks, not supplied) b using a keylock (supplied). Keys may be removed only when locking is effective (Profalux or Ronis type locks). The keylocks are available in any of the following configurations: b one keylock b one keylock mounted on the device + one identical keylock supplied separately for interlocking with another device. A locking kit (without lock) is available for installation of a keylock (Ronis, Profalux, Kirk or Castell).

OFF position locking using a keylock and padlocks

056449

130

Schneider Electric

Chassis locking
mismatch protection door interlock racking interlock keylock locking padlock locking position indicator chassis front plate (accessible with cubicle door closed) 8 crank entry 9 reset button 10 crank storage 1 2 3 4 5 6 7
E59267A

3 4 5 6 7 8 9 10 2

056450

056451

Disconnected position locking


Mounted on the chassis and accessible with the door closed, these devices lock the circuit breaker in the disconnected position in two manners: b using padlocks (standard), up to three padlocks (not supplied) b using keylocks (optional), one or two different keylocks are available. Profalux and Ronis keylocks are available in different options: b one keylock b one keylock mounted on the device + one identical keylock supplied separately, using the same key, for interlocking with another device b one (or two) keylocks mounted on the device + one (or two) identical keylocks supplied separately, for interlocking with another device. A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell).
Disconnected position locking by keylocks

Disconnected position locking by padlocks

Connected, disconnected and test position locking


The connected, disconnected and test positions are shown by an indicator. The racking crank blocks when the exact position is obtained. A release button is used to free it. On request, the disconnected position locking system may be modified to lock the circuit breaker in any of the three positions, connected, disconnected and test.

056417

Door interlock

Door interlock
Mounted on the right or left-hand side of the chassis, this device inhibits opening of the cubicle door when the circuit breaker is in connected or test position. It the breaker is put in the connected position with the door open, the door may be closed without having to disconnect the circuit breaker.
056452

Racking interlock

Racking interlock
This device prevents insertion of the crank when the cubicle door is open (device cannot be connected).

Mismatch protection
Mismatch protection ensures that a circuit breaker is installed only in a chassis with compatible characteristics. It is made up of two parts (one on the chassis and one on the circuit breaker) offering twenty different combinations that the user may select.
056453

Mismatch protection

Schneider Electric

131

Functions and characteristics

Electrical and mechanical accessories Compact NS630b to 1600 (cont.)


Other accessories
Auxiliary terminal shield (CB)
Optional equipment mounted on the chassis, the shield prevents access to the terminal block of the electrical auxiliaries.

056463

Auxiliary terminal shield

Operation counter (CDM)


056464

Operation counter

The operation counter sums the number of operating cycles and is visible on the front panel. It is compatible with electrically operated devices.

Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases the degree of protection to IP40. It is available in fixed and withdrawable versions.

Transparent cover (CCP) for escutcheon


E45184

Escutcheon

Optional equipment mounted on the escutcheon, the cover is hinged and secured by a screw. It increases the degree of protection to IP54 and the degree of protection against mechanical impacts to IK10. It may be used for withdrawable devices only.

Blanking plate (OP) for escutcheon


Used with the escutcheon, this option closes off the door cutout of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and withdrawable devices.
E45187

Transparent cover

E59987

Blanking plate

132

Schneider Electric

Schneider Electric

133

Functions and characteristics

Electrical and mechanical accessories Compact NS1600b to 3200 (fixed version)

OFF OFF

OFF OFF

134

Schneider Electric

Installation
E45178

Fixed circuit breakers


Compact NS1600b to 3200 circuit breakers should be installed vertically only.

E59271A

OFF OFF

Fixed Compact NS Mounting on rails


E59281A

Connection
Front connection
NS1600 to 2500 NS3200

E59272A

OFF OFF

E59726A

OFF OFF

Bars
Bars may be directly connected to the terminals of Compact NS1600b to 3200 circuit breakers. NS1600b to 2500
E59275A

E59273

OFF OFF

NS1600b to 2500 with connection for vertical-connection adapters or NS3200

E59727A

E59274A

OFF OFF

E59728A

OFF OFF

Schneider Electric

135

Functions and characteristics

Electrical and mechanical accessories Compact NS1600b to 3200 (cont.)


Indication contacts
Contacts installed in the device
Changeover contacts are used to remote circuit-breaker status information and can thus be used for indications, electrical locking, relaying, etc. They comply with the IEC 60947-5 international recommendation. Functions b OF (ON/OFF) - indicates the position of the main circuit breaker contacts b SD (trip indication) - indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth-leakage fault v operation of a voltage release v operation of the "push to trip" button Returns to de-energised state when the circuit breaker is reset. b SDE (fault indication) - indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth-leakage fault. Returns to de-energised state when the circuit breaker is reset. Installation b OF, SD and SDE functions - a single type of contact provides all these different indication functions, depending on the position where it is inserted in the device. The contacts clip into slots behind the front cover of the circuit breaker. Electrical characteristics of the OF/SD/SDE auxiliary contacts Contacts
Rated thermal current (A) Minimum load Utilisation category (IEC 60947-5-1) Operational 24 V current (A) 48 V 110 V 220/240 V 250 V 380/440 V 660/690 V

044314

OF, SD and SDE changeover contacts

All the auxiliary contacts opposite are also available in "low-level" versions capable of switching very low loads (e.g. for the control of PLCs or electronic circuits).

Standard
6 100 mA at 24 V AC12 AC15 DC12 6 6 2.5 6 6 2.5 6 5 0.8 6 4 0.3 6 3 6 0.1 -

Low level
5 2 mA at 15 V DC DC14 AC12 AC15 DC12 1 5 3 5 0.2 5 3 2.5 0.05 5 2.5 0.8 5 2 0.03 5 0.3 5 1.5 -

DC14 1 0.2 0.05 0.03 -

136

Schneider Electric

Compact NS1600b to 3200 circuit breakers may be equipped with an MX shunt release, an MN undervoltage release or a delayed undervoltage release (MN + delay unit).
056421

Remote tripping
This function opens the circuit breaker via an electrical order. It is made up of: b a shunt release (MX) b or an undervoltage release (MN) b or a delayed undervoltage release (MN + delay unit). These releases (MX or MN) cannot be operated by the communication bus. The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain instantaneous opening of the circuit breaker. Wiring diagram for the remote-tripping function
E59433A E46553A E46554A

MX voltage release

opening order

opening order

delayed opening order delay unit

10

12

3 instantaneous opening order MN D1 D1

C2

D2

D2

MX C1

MN

Voltage releases (MX)


When energised, the MX voltage release instantaneously opens the circuit breaker. A continuous supply of power to the MX locks the circuit breaker in the OFF position. Characteristics
Power supply V AC 50/60 Hz V DC Operating threshold Permanent locking function Consumption (VA or W) Circuit-breaker response time at Un 24 - 48 - 100/130 - 200/250 - 277 - 380/480 12 - 24/30 - 48/60 - 100/130 - 200/250 0.7 to 1.1 Un 0.85 to 1.1 Un pick-up: 200 (200 ms) hold: 4.5 50 ms 10

Instantaneous voltage releases (MN)


The MN release instantaneously opens the circuit breaker when its supply voltage drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on the release, it is impossible to close the circuit breaker, either manually or electrically. Any attempt to close the circuit breaker has no effect on the main contacts. Circuit-breaker closing is enabled again when the supply voltage of the release returns to 85 % of its rated value. Characteristics
Power supply V AC 50/60 Hz V DC Operating opening threshold closing Consumption (VA or W) MN consumption with delay unit (VA or W) Circuit-breaker response time at Un 24 - 48 - 100/130 - 200/250 - 380/480 24/30 - 48/60 - 100/130 - 200/250 0.35 to 0.7 Un 0.85 Un pick-up: 200 (200 ms) hold: 4.5 pick-up: 400 (200 ms) hold: 4.5 90 ms 5

MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of the MN release can be delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions are available, adjustable and non-adjustable. Characteristics
Power supply V AC 50-60 Hz /DC Operating threshold Consumption of delay unit alone (VA or W) Circuit-breaker response time at Un non-adjustable 100/130 - 200/250 adjustable 48/60 - 100/130 - 200/250 - 380/480 opening 0.35 to 0.7 Un closing 0.85 Un pick-up: 200 (200 ms) hold: 4.5 non-adjustable adjustable 0.25 s 0.5 s - 0.9 s - 1.5 s - 3 s

Schneider Electric

137

Functions and characteristics

Electrical and mechanical accessories Compact NS1600b to 3200 (cont.)


Device locking
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking systems can receive up to three padlocks with shackle diameters ranging from 5 to 8 mm (padlocks not supplied). Control device
Toggle

62191

Function
lock in OFF position lock in OFF or ON position

Means
padlock padlock

Required accessories
removable device fixed device

Interphase barriers
Compact NS with toggle locked using a fixed device and padlocks
62190

These barriers are flexible insulated partitions used to reinforce isolation of connection points in installations with busbars, whether insulated or not. Barriers are installed vertically between front connection terminals.

Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases the degree of protection to IP40.

Compact NS with toggle locked using a removable device and padlocks

E79056

Interphase barriers

E94383

Escutcheon

138

Schneider Electric

Test equipment

Compact NS100 to 630 test equipment for STR electronic trip units
047035 052172

Mini test kit


The mini test kit is a portable unit requiring no external power supply, used to check operation of the electronic trip unit and circuit-breaker tripping. It connects to the test connector on the front of the circuit breaker. Required power source: five 9 V alkaline batteries (not supplied).

Portable test kit


The portable test kit is used to check all aspects of the protection functions: b long time protection b short time protection b instantaneous protection b earth-fault protection. Required power source: 110 or 220 V AC, 50/60 Hz.

Mini test kit

Portable test kit

Compact NS630b to 3200 test equipment for Micrologic control units


Mini test kit
The autonomous hand-held mini test kit may be used to: b check operation of the control unit and the tripping and pole-opening system by sending a signal simulating a short-circuit b supply power to the control units for settings via the keypad when the circuitbreaker is open (Micrologic P and H control units). Required power source: standard LR6-AA battery.
056466

Portable test kit


The portable test kit is may be used to check: b the mechanical operation of the circuit breaker b the electrical continuity of the connection between the circuit breaker and the control unit b operation of the control unit: v display of settings v operating tests on the ASIC electronic component v automatic and manual tests on protection functions v test on the zone-selective interlocking (ZSI) function v inhibition of the earth-fault protection v inhibition of the thermal memory. Note. These test kits are identical for all Compact NS630b to 3200 circuit breakers and all Masterpact NT and NW circuit breakers. Required power source: 110 or 220 V AC, 50/60 Hz.

Portable test kit

Schneider Electric

139

Functions and characteristics

Display modules

Perfectly integrated in the Compact and Masterpact ranges, Display modules are designed for use with Micrologic control units to provide instant and highly intuitive access to all the information provided by the circuit breakers, including device status, current, voltage and power values, etc.
057454

DMB300 and DMC300 display modules use the power and communications capabilities of the Micrologic control units to centralise the display of electrical values, status conditions and alarms of one or more Compact or Compact circuit breakers. The mounting and cabling system for the display modules ensures fast, easy and reliable installation. Start-up is immediate with no configuration or programming required. Display modules are high-performance devices combining: b simple and easy-to-read dials b powerful and accurate digital processing. Their small size and extensive communications capabilities make for easy and flexible installation and operation.

Display modules
Associated circuit breakers
Type Number

DMB300

DMC300

Compact or Masterpact equipped with Micrologic control units 1 to 4 1 to 16 Black and white 240 x 64 pixels 5 buttons Colour, touch screen 5, 320 x 240 pixels Touch screen

Display
DMB300 display module: basic and harmonic measurements
Screen type Screen size Entry

Information displayed
Currents (per phase) Currents I1, I2, I3, IN Maximum current Earth-fault and earth-leakage currents Demand current Maximum demand current Total harmonic distortion (THD) Maximum total harmonic distortion Amplitudes of individual harmonics Waveform capture Voltages Phase-to-phase voltages (U1-2, U2-3, U3-1) Minimum/maximum phase-to-phase voltages Phase-to-neutral voltages (V1-N, V2-N, V3-N) Minimum/maximum phase-to-neutral voltages Frequency Voltage unbalance (% per phase) Total harmonic distortion (% per phase) Maximum total harmonic distortion (% per phase) Amplitudes of individual harmonics Power Active (P), reactive (Q) and apparent (S) power Power factor and cos Maximum power (P, Q, S) Demand power (P, Q, S) Maximum demand power (P, Q, S) Metering Active, reactive and apparent energy On-line help On-line help is available for each type of information supplied by the module Circuit-breaker diagnostics Identification of control units Reading of protections Circuit-breaker status Type of trip Current alarms Maintenance indicator Installation diagnosis Indication of faulty devices Fault log A A A A P P P P P H H H H H A A A A P P P P P P P H H H H H H H H
E79078

A A A

P P P P P

H H H H H H H

A A A

P P P P P

H H H H H H H H H H H H H H H H H H H H H H H

DMC300 display module: measurements, harmonic analysis, diagnosis

P P P P P P

H H H H H H H H H H H H H H H

P P P P P

P P P P P P

P P P P P P

Associated Micrologic control unit A = Micrologic A P = Micrologic P H = Micrologic H

A P

Installation and start-up


Mounting Connection Mounted through door, without tools, using 6 spring-clips supplied with the mod. Prefabricated wiring systems

140

Schneider Electric

Wiring system The wiring system is designed for low-voltage power switchboards. Installation requires no tools or special skills. The prefabricated wiring ensures both data transmission (Modbus protocol) and 24V DC power distribution for the display module and the communications modules on the Micrologic control units.

E59178

Connection of DMB300 display module


24 V DC power 2
ON ON

E59081

ON n 4n 4 4 ON n n 3n 3 n 4 n 2n 2 n 3 n 3 n 1n 1 n 2 n 2 OUT OUT n 1 IN IN T

ON

IN

OU

3
Reset
push
reset

push OFF

ON

NX 32

H2
Icu (kA) 100 100 85 Icw 85kA/1s Icu
50/60Hz

70 Micrologic Ap

Ue (V) 220/440 525 690

Ir

Ig Isd I n Ii

d discharge

cat.B Ics = 100%

O OFF

947-2 AS NEMA IEC UNE EN 60947-2 CEI BS


UTE VDE

012

53

com

CDM 303: Connection cable between display module and junction block
E59180A

DMB300 Digipact
volets shutters

Test

1 2 3
select

2
ON

NW

1251

H1
12kV

Uimp Icu (kA) 100 85

Ui 1000V 8kV Uimp Ue (V) 220/240 480/690

70 Micrologic Ap reset

Ir

Ig Isd I n Ii

push

O OFF

push

I ON

discharged

O OFF

Ics =

100%

Icu

IEC

947-2

UTE VDE

BS CEI

UNE

NEMA

012

53

IN

OUT

n 1

n 2

n 3

n 4

ON

NW

1251

H1
12kV

Uimp Icu (kA) 100 85

Ui 1000V 8kV Uimp Ue (V) 220/240 480/690

70 Micrologic Ap reset

Ir

Ig Isd I n Ii

push

O OFF

push

I ON

discharged

O OFF

Ics =

100%

Icu

IEC

947-2

UTE VDE

BS CEI

UNE

NEMA

012

53

CJB 306 junction block


E59179

Compact circuit breakers equipped with Micrologic control units and the Modbus eco COM option

Connection of DMC300 display module


Maximum distance between module and circuit breaker: 1200 m
5 4

CCP 303: Connection cable between Masterpact or Compact and junction block
E59176A

E59082

2 1

NW
Uimp

1251

H1
12kV

Uimp Icu (kA) 100 85

NW
Uimp

1251

H1
12kV

Uimp Icu (kA) 100 85

Ui 1000V 8kV Ue (V) 220/240 480/690

Ui 1000V 8kV Ue (V) 220/240 480/690

70 Micrologic Ap reset

70 Micrologic Ap reset

Ir

Ig Isd I n Ii

push

O OFF

push

I ON

Ir

Ig Isd I n Ii

push

O OFF

push

I ON

discharged

discharged

O OFF

O OFF

Ics =

100%

Icu Ics =

100%

Icu

IEC

947-2

UTE VDE

BS CEI

UNE

NEMA

IEC

947-2

UTE VDE

BS CEI

UNE

NEMA

Reset
push
reset

push OFF

ON

NX 32

H2
Icu (kA) 100 100 85 Icw 85kA/1s Icu
50/60Hz

012

53

012

53

70 Micrologic Ap

Ue (V) 220/440 25 525 690

Ir

Ig Isd I n Ii

d discharge

cat.B Ics = 100%

O OFF

947-2 AS NEMA IEC UNE EN 60947-2 CEI BS


UTE VDE

NW
Uimp

1251

H1
12kV

Uimp Icu (kA) 100 85

NW
Uimp

1251

H1
12kV

CCR 301: Roll of RS 485 cable (2 RS 485 wires + 2 power supply wires)
E59177

Uimp Icu (kA) 100 85

Ui 1000V 8kV Ue (V) 220/240 480/690

Ui 1000V 8kV Ue (V) 220/240 480/690

70 Micrologic Ap reset

70 Micrologic Ap reset

Ir

Ig Isd I n Ii

push

O OFF

push

I ON

Ir

Ig Isd I n Ii

push

O OFF

push

I ON

discharged

discharged

O OFF

O OFF

Ics =

100%

Icu Ics =

100%

Icu

IEC

947-2

UTE VDE

BS CEI

UNE

NEMA

IEC

947-2

UTE VDE

BS CEI

UNE

NEMA

012

53

012

53

Reset
push
70 Micrologic Ap reset

push OFF

ON

NX 32

H2
Icu (kA) 100 100 85 Icw 85kA/1s Icu
50/60Hz

Ue (V) 220/440 525 690

d discharge

cat.B Ics = 100%

Ir

Ig Isd I n Ii

NW
Uimp

1251

H1
12kV

O OFF

Uimp Icu (kA) 100 85

NW
Uimp

1251

H1
12kV

Uimp Icu (kA) 100 85

947-2 AS NEMA IEC UNE EN 60947-2 CEI BS


UTE VDE

Ui 1000V 8kV Ue (V) 220/240 480/690

Ui 1000V 8kV Ue (V) 220/240 480/690

70 Micrologic Ap reset

70 Micrologic Ap reset

Ir

Ig Isd I n Ii

push

O OFF

push

I ON

Ir

Ig Isd I n Ii

push

O OFF

push

I ON

discharged

discharged

O OFF

O OFF

Ics =

100%

Icu Ics =

100%

Icu

IEC

947-2

UTE VDE

BS CEI

UNE

NEMA

IEC

947-2

UTE VDE

BS CEI

UNE

NEMA

012

53

012

53

CSD 309: SubD 9-pin connector for colour-coded connection of wires to screw terminals

Compact circuit breakers equipped with Micrologic control units and the Modbus eco COM option
Schneider Electric

141

142

Schneider Electric

Compact NS

Installation recommendations

Presentation Functions and characteristics

2 11

Operating conditions Installation in switchboards


Power supply and weights Safety clearances and minimum distances Installation example

144 145
145 146 148

Door interlock for Compact NS630b to 1600 Connection of MN and MX voltage releases for Compact NS630b to 3200 Power connections for Compact NS80H-MA NSC100N, NSA160 Power connections for Compact NS100 to 630
Connection of insulated bars or cables with lugs Connection of bare cables Insulation of live parts

149 150 151 152


152 153 154

Power connections for Compact NS630b to 3200


Sizing of bars Recommended drilling dimensions

155
157 159

Temperature derating Power dissipation / Resistance


Dimensions, volumes Connection Electrical diagrams Additional characteristics Catalogue numbers

161 163
165 205 221 251 267

Schneider Electric

143

Installation recommendations

Operating conditions

E59432A

Altitude derating
Altitude does not significantly affect circuit-breaker characteristics up to 2000 m. Above this altitude, it is necessary to take into account the decrease in the dielectric strength and cooling capacity of air. The following table gives the corrections to be applied for altitudes above 2000 metres. The breaking capacities remain unchanged. Compact NS80 to 630 Altitude (m)
Dielectric resistance voltage (V) 3000 Average insulation level (V) Maximum utilisation voltage (V) 690 Average thermal current (A) at 40 C

2000 m

2000
2500 2100 750 700 550 480 1 x In

3000
1800 600 420 0.96 x In

4000
500 0.93 x In

5000

0.9 x In

Compact NS630b to 3200 Altitude (m)


Dielectric resistance voltage (V) 3000 Average insulation level (V) Maximum utilisation voltage (V) 690 Average thermal current (A) at 40 C
E59571A

2000
2500 2100 750 750 590 520 1 x In

3000
1800 700 460 0.99 x In

4000
600 0.96 x In

5000

0.94 x In

Vibrations
Compact NS devices resist electromagnetic or mechanical vibrations. Tests are carried out in compliance with standard IEC 68-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyds, etc.): b 2 13.2 Hz: amplitude 1 mm b 13.2 100 Hz: constant acceleration 0.7 g. Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts.

Electromagnetic disturbances
Compact NS devices are protected against: b overvoltages caused by devices that generate electromagnetic disturbances b overvoltages caused by an atmospheric disturbances or by a distribution-system outage (e.g. failure of a lighting system) b devices emitting radio waves (radios, walkie-talkies, radar, etc.) b electrostatic discharges produced by users. Compact NS devices have successfully passed the electromagnetic-compatibility tests (EMC) defined by the following international standards: b IEC 60947-2, appendix F b IEC 60947-2, appendix B (trip units with Vigi earth-leakage function). The above tests guarantee that: b no nuisance tripping occurs b tripping times are respected.
E59572A

144

Schneider Electric

Installation in switchboards Power supply and weights

Power supply
E23947

Compact NS circuit breakers can be supplied from either the top or the bottom without any reduction in performance. This capability facilitates connection when installed in a switchboard.

push to trip

Weights
Circuit breaker
NS80H-MA NSC100N 3P/3D 3P/3D 4P/4D NS100N/H 1P/1D 2P/2D NS100N 3P/2D NS100N/H/L 3P/3D 4P/4D NS125E 3P/3D 4P/4D NS160N/H 1P/1D 2P/2D NS160N 3P/2D NS160N/H/L 3P/3D 4P/4D NS250N 3P/2D NS250N/H/L 3P/3D 4P/4D NS400/630N/H/L 3P/3D 4P/4D NS630b to 1600 3P manual operation 4P NS630b to 1600 3P electrical operation 4P NS1600b to 3200 3P 4P NSA NB50N NB100F/N NB250N NB400/600N 3P/3D 4P/4D 3P/3D 3P/3D 3P/3D 3P/3D 1.09 1 1.3 0.5 1.45 1.79 2.05 2.57 1.8 2.3 0.5 1.45 1.85 2.10 2.58 1.94 2.2 2.78 6.19 8.13 14 18 14 18 24 36 1.1 1.4 0.7 1.2 1.94 6.19

Plug-in base

Chassis

Vigi module

Fully visible break block (Interpact INV)

Motor-mechanism module

1.5 1.7

0.8 0.8 1.05 0.8 1.1

2.2 2.2 2.2

0.87 0.87 1.13 0.9 1.2

2 2 2.2

1.2 1.2 1.2

0.8 0.8 1.05 0.8 0.8 1.05 2.4 2.8

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 14 18 16 21

0.87 0.87 1.13 0.87 0.87 1.13 2.8 3

2 2 2.2 2 2 2.2 4.6 4.9

1.2 1.2 1.2 1.2 1.2 1.2 2.8 2.8

1.5 1.7

The table above presents the weights (in kg) of the circuit breakers and the main accessories, which must be summed to obtain the total weight of complete configurations.

Schneider Electric

145

Installation recommendations

Installation in switchboards Safety clearances and minimum distances


Compact NS80 to 630
When installing a circuit breaker, minimum distances (safety clearances) must be maintained between the device and panels, bars and other protection devices installed nearby. These distances, which depend on the ultimate breaking capacity, are defined by tests carried out in accordance with standard IEC 60947-2. If installation conformity is not checked by type tests, it is also necessary to: b use insulated bars for circuit-breaker connections b block off the busbars using insulating screens. For Compact NS80 to 630 devices, terminal shields, interphase barriers and the insulation kit are recommended and may be mandatory depending on the utilisation voltage and the type of installation (fixed, withdrawable). (See page 147.) Minimal distance between two adjacent circuit breakers
A1 A2
E23942

Minimal distance between the circuit breaker and top, bottom or side panels
E50701

Minimal distance between the circuit breaker and front or rear panels
front panel

E50700

F if F < 8 mm : an insulating screen is mandatory

D1

D2

C1 C2

bare or painted sheetmetal; insulation or insulated bars


Dimensions (mm) Insulation, insulated bars or painted sheet metal Bare sheetmetal

Compact circuit breaker C1 D1 D2 C2 D1 D2 A1 (2) A2 (3) B NS80H-MA U y 440 V 0 30 30 5 35 35 0 10 0 NSC100N U < 600 V 0 30 30 10 (1) 35 35 0 20 0 U u 600 V 0 30 30 20 (1) 35 35 0 40 0 NS100-250 U y 440 V 0 30 30 5 35 35 0 10 0 U < 600 V 0 30 30 10 (1) 35 35 0 20 0 U u 600 V 0 30 30 20 (1) 35 35 0 40 0 NS400-630 U y 440 V 0 30 30 5 60 60 0 10 0 U < 600 V 0 30 30 10 (1) 60 60 0 20 0 U u 600 V 0 30 30 20 (1) 100 100 0 40 0 (1) Distance must be doubled with interphase barriers. (2) For Compact NS with long or short terminal shields. (3) For Compact NS without terminal shields. The mandatory distances when installing Compact NS circuit breakers are calculated from the device case, not taking into account the terminal shields or the interphase barriers.

146

Schneider Electric

Fixed Compact NS400 1000 V AC, front connection


Power supply from the top or bottom. Connection by cables or busbars.
E50781

insulation

E94502

150

side panel 30

40

insulating kit

40
150

B=0

bare or painted sheetmetal ; insulation or insulated bars

30

Insulating kit is standard.

Compact NS630b to 3200 (fixed devices)


A (*)
E59717A

B
E59718A

A (*)

146,5 F

(*) An overhead clearance of 50 mm is required to remove the arc chutes.

Insulated parts
NS630b to 1600 A 0 B 0 NS1600b to 3200 A 0 B 0

Metal parts
120 10 120 30

Live parts
180 60 180 60

Compact NS630b to 1600 (withdrawable devices)


A
E59719A E59720A

B C C

40 180 F

Insulated parts
A B C 0 10 0

Metal parts
0 10 0

Live parts
30 60 90

F Datum

Schneider Electric

147

Installation recommendations

Installation in switchboards Installation example

painted sheetmetal
E50704

Direct connection by bare cables, devices with terminal shields.

Connection by cables with lugs, devices with terminal shields.

Connection by insulated bars, devices with terminal shields.

Rear connection or plug-in base, devices with terminal shields.

Minimum dimensions (mm) Compact circuit breaker NS80H-MA/NSC100N NS100-630 NS630b-1600 NS1600b-3200

A 0 0 250 300

148

Schneider Electric

Door interlock for Compact NS630b to 1600

Mounted on the left or right-hand side of the chassis, this locking device prevents opening of the door if the circuit breaker is in the connected or test positions. If the circuit breaker was connected with the door open, the door may be closed without having to disconnect the circuit breaker.

E59429A

4 61 2 11 (1) (2)

Dimensions (mm)
Type NS630b to 1600 (3P) NS630b to 1600 (4P) (1) 135 205 (2) 168 168

Device in the connected or test positions


Door locked
E59430A

door

F 5 23

Device in the disconnected position


Door not locked
E59431A

Note. The door interlock may be mounted on either the left or right-hand side of the chassis. F Datum

Schneider Electric

149

Installation recommendations

Connection of MN and MX voltage releases for Compact NS630b to 3200


Release wiring
During pick-up, the power drawn is approximately 150 to 200 VA. For low supply voltages (12, 24, 48 V), the maximum cable length therefore depends on the supply voltage and the size of the cables. Indicative values for maximum wire lengths (in metres)
12 V 24 V 48 V 2.5 mm2 280 75 550 350 1.5 mm2 165 45 330 210 2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2 MN 100 % U source 58 35 85 % U source 16 10 MX 100 % U source 21 12 115 70 85 % U source 10 6 75 44 Note. The lengths mentioned are for each of the two supply wires.

150

Schneider Electric

Power connections for Compact NS80H-MA, NSC100N, NSA160


Standard device
E54545 E59291A

With distribution connector


y 10 1.5 to 16 rigid 1.5 to 10 flexible (1) 2

L (mm) S (mm2) Cu / Al Tightening torque (Nm)

18 1.5 to 70 rigid 1.5 to 50 flexible 5

OFF

S
push to trip

(1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrule.

E39432

Distribution connector

Schneider Electric

151

Installation recommendations

Power connections for Compact NS100 to 630 Connection of insulated bars or cables with lugs
NS100
Bars L (mm) I (mm) d (mm) e (mm) (mm)
L e

NS160/250
y 25 d + 10 y 10 y6 8.5

NS400/630
y 32 d + 15 y 15 3 y e y 10 10.5

400 l L

y 25 d + 10 y 10 y6 6.5

E59292A

push to trip

E50702

L (mm) y 25 y 25 y 32 (mm) 6.5 8.5 10.5 Tightening torque (Nm) (1) 10 15 50 Tightening torque (Nm) (2) 5 5 20 (1) Tightening torque for lugs or bars on the circuit breaker. (2) Tightening torque for rear connections or terminal extensions on plug-in base.

Lugs

Connections with accessories - IEC228


NS100 to 250
Spreader Separate parts Tinned copper
E18599 E55599

NS100 to 250
Pole pitch One-piece spreader
Without spreaders With spreaders 35 mm 45 mm

Dimensions
E50702

With spreaders or terminal extensions NS100 NS160/250


Bars L (mm) l (mm) d (mm) e (mm) (mm) L (mm) (mm) (Nm) y 25 20 y I y 25 y 10 y6 6.5 y 25 6.5 10 (1), 5 (2) y 25 20 y I y 25 y 10 y6 8.5 y 25 8.5 15 (1), 5 (2)

Where U > 600 V, the mandatory insulation kit means separate spreaders cannot be used. The one-piece spreader must be used. Straight terminal extensions Tinned copper.
E18601

400 l L e

d
Lugs

Right-angle terminal extensions Tinned copper. Upstream side.

Tighten. torque (1) Tightening torque for spreaders or terminal extensions on the circuit breaker. (2) Tightening torque for spreaders or terminal extensions on plug-in base.

E18600

Spreaders, straight and right-angle terminal extensions are supplied with flexible interphase barriers.

NS400 and 600


Separate spreaders with 52.5 and 70 mm pole pitches Tinned copper Where U > 600 V, use of the 52.5 mm spreaders requires a specific insulation kit. The 70 mm spreaders may not be used. Right-angle terminal Edgewise terminal extensions extension Tinned copper Tinned copper Upstream side
E18600

NS400 and 630


Pole pitch
Without spreaders With spreaders
E50702

45 mm 52.5 ou 70 mm

Dimensions
Bars L (mm) l (mm) d (mm) e (mm) (mm) L (mm) (mm) (Nm)

With spreaders
y 40 d + 15 y 20 3 y e y 10 12,5 y 40 12,5 50 (1), 20 (2)

With terminal extensions


y 32 30 y I y 34 y 15 3 y e y 10 10,5 y 32 10,5 50 (1), 20 (2)

E18599

400 l L e

d L
Lugs

E21276

Tighten. torque (1) Tightening torque for spreaders or terminal extensions on the circuit breaker. (2) Tightening torque for spreaders or terminal extensions on plug-in base.

Spreaders, straight and right-angle terminal extensions are supplied with flexible interphase barriers.

E25961

Close-up view of two cables with lugs.

152

Schneider Electric

Connection of bare cables


NS100 to 250

E59293A

E54471

E58540

E54468

E54472

1-cable connector

Distribution connector

Polybloc distribution block

1-cable connector
E54545

Steel y 160A
20 1.5 to 95 (1) 12

Aluminium y 250A
20 1016 15 2535 20 50185 150 max. flex. 26

L (mm) S (mm2) Cu / Al Tightening torque (Nm)

6-cable distribution connector (copper or aluminium)


L (mm) S (mm2) Cu / Al Tightening torque (Nm) 15 or 30 1.5 to 6 (1) 8 to 35 4 6

Polybloc distribution block (6 or 9 cables)


L (mm) 12 S (mm2) Cu / Al 1.5 to 10 (1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrule.

NS400 and 630


E54470

E54469

1-cable connector

2-cable connector

1-cable connector 1 cable


E54545

2-cable connector 2 cables


30 or 60 2 x 85 to 2 x 240 rigid 240 max. flexible 31

L (mm) S (mm2) Cu / Al Tightening torque (Nm)

20 35 to 300 rigid 240 max. flexible 31

Conductor materials and electrodynamic stresses


See page 155.

Ties for flexible bars and cables


See page 155.

Schneider Electric

153

Installation recommendations

Power connections for Compact NS100 to 630 (cont.) Insulation of live parts
Fixed Compact NS, front connections
NS100/250N/H/L
U < 500 V

NS400/630N/H

NS400/630L

Interphase barriers Interphase barriers or long terminal or long terminal shields recommended. shields recommended. Insulated bars Insulated bars are mandatory. are mandatory. 500 V y U y 600 V Interphase barriers Interphase barriers Interphase barriers or long terminal or long terminal or long terminal shields are shields are shields are mandatory. mandatory. mandatory. Insulated bars Insulated bars Insulated bars are mandatory. are mandatory. are mandatory. U > 600 V Insulation kit Insulation kit Insulation kit and insulated bars and insulated bars and insulated bars are mandatory. are mandatory. are mandatory. The insulation kit is not compatible with: b separate spreaders for Compact NS100 to 250. The one-piece spreader must be used b separate spreaders (70 mm) for Compact NS400 and 630. For the 52.5 mm spreaders, there is a specific insulation kit.

Fixed Compact NS, rear connections


NS100/250N/H/L
All voltage levels Short terminal shields recommended.

NS400/630N/H
Short terminal shields recommended.

NS400/630L
Short terminal shields recommended.

Withdrawable Compact NS, front and rear connections


NS100/250N/H/L
All voltage levels Short terminal shields are mandatory. Insulated bars are mandatory.

NS400/630N/H

NS400/630L

Short terminal shields Short terminal shields are mandatory. are mandatory. Insulated bars Insulated bars are mandatory are mandatory. for U u 500 V. Use of an insulating screen (supplied with the plug-in base) is mandatory.

154

Schneider Electric

Power connections for Compact NS630b to 3200

Conductor materials and electrodynamic stresses


Compact circuit breakers can be connected indifferently with bare-copper, tinnedcopper and tinned-aluminium conductors (flexible or rigid bars, cables. In the event of a short-circuit, thermal and electrodynamic stresses will be exerted on the conductors. They must therefore be correctly sized and maintained in place using supports. Electrical connection points on all types of devices (switch-disconnectors, contactors, circuit breakers, etc.) should not be used for mechanical support. Any partition between upstream and downstream connections of the device must be made of non-magnetic material.
E59565A

Ties for flexible bars and cables


The table below indicates the maximum distance between ties depending on the prospective short-circuit current. The maximum distance between ties attached to the switchboard frame is 400 mm. Type of tie
Maximum distance between ties (mm) Short-circuit current (kA rms)

"Panduit" ties Width: 4.5 mm Maximum load: 22 kg Colour: white


200 10 100 15 50 20

"Sarel" ties Width: 9 mm Maximum load: 90 kg Colour: black


350 20 200 27 100 35 70 45 50 (double ties) 100

Note. For cables u 50 mm2, use 9 mm-wide ties.


E59566A E59567A

C
B

E59568A

Connection of bars
Bars must be adjusted to ensure correct positioning on the terminals before bolting (B). Bars must rest on a support firmly attached to the switchboard frame, such that the circuit-breaker terminals do not bear any weight (C). Electrodynamic forces The first spacer between bars must be positioned within a maximum distance (see table below) of the connection point to the circuit breaker. This distance is calculated to resist the electrodynamic stresses exerted between the bars of each phase during a short-circuit.
Maximum distance A between the circuit-breaker connection and the first spacer between bars, depending on the short-circuit current Isc (kA) 30 50 65 80 100 Distance (mm) 350 300 250 150 150

150 150

B
E59569A

C
E59570A

Schneider Electric

155

Installation recommendations

Power connections for Compact NS630b to 3200

E47678A

Connections
The quality of bar connections depends, among other things, on the tightening torques used for the nuts and bolts. Over-tightening may have the same consequences as under-tightening. The correct tightening torques for the connection of bars to the circuit-breaker terminals are indicated in the table below. The values below are for copper bars (Cu ETP-NFA51-100) and steel nuts and bolts (class 8.8). The same values apply to AGS-T52 quality aluminium bars (French standard NFA 02-104 and American National Standard H-35-1). Examples of bar connections
E47667B E47665 E47668

6
1 terminal screws, factory tightened to 13 Nm 2 circuit-breaker terminal 3 bars 4 bolt 5 washer 6 nut

Tightening torque for bars Rated diameter (mm) Drilling (mm) diameter 10 11

Tightening torque (Nm) with flat or grower washers 37.5

Tightening torque (Nm) with contact or split washers 50

Bar drilling
Examples
E47329A E47330A E47331A

Insulation distance

E47680A

X
Dimensions (mm)
Utilisation voltage Ui y 600 V Ui y 1000 V X minimum 8 mm 14 mm

Bar bending
Bars must be bent according to the table below. A tighter bend may cause cracks.

E47679A

r e

Dimensions (mm)
e 5 10 Radius r Minimum 5 15 Recommended 7.5 18 to 20

156

Schneider Electric

Sizing of bars
The following tables are based on the following assumptions: b maximum permissible temperature of bars is 100 C b Ti: temperature around the circuit breaker and its connections b busbars made of copper and not painted.
Note. The values presented in the tables are the result of trials and theoretical calculations on the basis of the assumptions mentioned above. These tables are intended as an aid in designing connections, however, the actual values must be confirmed by tests on the installation.

Front or horizontal rear connections


E59294A

Compact

Maximum service current


400 630 800 1000 1250 1400 1600 1800 2000 2200 2500 2800 3000 3200

Ti : 40 C Number of bars 5 mm thick 10 mm thick


2b.30 x 5 2b.40 x 5 2b.50 x 5 3b.50 x 5 3b.50 x 5 2b.80 x 5 2b.80 x 5 3b.80 x 5 3b.80 x 5 3b.100 x 5 3b.100 x 5 4b.100 x 5 4b.100 x 5 5b.100 x 5 6b.100 x 5 1b.30 x 10 1b.40 x 10 1b.50 x 10 1b.63 x 10 2b.40 x 10 2b.40 x 10 2b.40 x 10 2b.63 x 10 2b.63 x 10 2b.80 x 10 2b.80 x 10 2b.100 x 10 3b.80 x 10 3b.80 x 10 3b.100 x 10

Ti : 50 C Number of bars 5 mm thick 10 mm thick


2b.30 x 5 2b.40 x 5 2b.50 x 5 3b.50 x 5 3b.50 x 5 2b.80 x 5 2b.80 x 5 3b.80 x 5 3b.80 x 5 3b.100 x 5 3b.100 x 5 4b.100 x 5 4b.100 x 5 6b.100 x 5 8b.100 x 5 1b.30 x 10 1b.40 x 10 1b.50 x 10 2b.50 x 10 2b.50 x 10 2b.50 x 10 2b.63 x 10 2b.63 x 10 2b.80 x 10 2b.80 x 10 2b.100 x 10 3b.80 x 10 3b.100 x 10 3b.100 x 10

Ti : 60 C Number of bars 5 mm thick 10 mm thick


2b.30 x 5 2b.40 x 5 2b.50 x 5 3b.63 x 5 3b.63 x 5 3b.80 x 5 3b.80 x 5 3b.100 x 5 3b.100 x 5 4b.80 x 5 4b.100 x 5 5b.100 x 5 8b.100 x 5 1b.30 x 10 1b.40 x 10 1b.63 x 10 2b.50 x 10 2b.50 x 10 2b.63 x 10 3b.50 x 10 2b.80 x 10 3b.63 x 10 2b.100 x 10 3b.80 x 10 3b.100 x 10 4b.80 x 10 4b.100 x 10

NS630b NS630b NS800 NS1000 NS1250 NS1600 / 1600b NS1600 / 1600b NS2000 NS2000 NS2500 NS2500 NS3200 NS3200 NS3200

Note. With Compact NS630b to NS1600, it is recommended to use 50 mm wideness bars (see "Recommanded busbars drilling").

Schneider Electric

157

Installation recommendations

Power connections for Compact NS630b to 3200 Sizing of bars


Vertical rear connections
E59422A

Compact

Maximum service current


400 630 800 1000 1250 1400 1600

Ti : 40 C Number of bars 5 mm thick 10 mm thick


2b.30 x 5 2b.40 x 5 2b.50 x 5 2b.50 x 5 2b.63 x 5 2b.80 x 5 3b.63 x 5 1b.30 x 10 1b.40 x 10 1b.50 x 10 1b.50 x 10 1b.63 x 10 1b.80 x 10 2b.50 x 10

Ti : 50 C Number of bars 5 mm thick 10 mm thick


2b.30 x 5 2b.40 x 5 2b.50 x 5 2b.50 x 5 3b.50 x 5 2b.80 x 5 3b.63 x 5 1b.30 x 10 1b.40 x 10 1b.50 x 10 1b.50 x 10 2b.40 x 10 2b.50 x 10 2b.50 x 10

Ti : 60 C Number of bars 5 mm thick 10 mm thick


2b.30 x 5 2b.40 x 5 2b.50 x 5 2b.63 x 5 3b.50 x 5 3b.63 x 5 3b.80 x 5 1b.30 x 10 1b.40 x 10 1b.50 x 10 1b.63 x 10 2b.40 x 10 2b.50 x 10 2b.63 x 10

NS630b NS630b NS800 NS1000 NS1250 NS1600 NS1600

158

Schneider Electric

Power connections for Compact NS630b to 1600 Recommended drilling dimensions


Rear connection
E59308A E59308A

Rear connection with spreaders


E59309A E59310A

50 12,5 12,5 12 maxi

50 12,5 12,5 12 maxi

63 25,5 12,5 12 maxi

80 15 15 12 maxi

25

12,5

25

12,5

25

12,5

25 25

12,5

Middle left or middle right spreader for 4P


E59325A E59326A

Middle spreader for 3P

Left or right spreader for 4P


E59327A E59328A

Left or right spreader for 3P


77 38,5 25 30 = = 30 82 52 15 5 11 25 52 13,5

77 38,5 25 = = 30 82 52 15 5 11 25 52 13,5

77 38,5 25 = = 30 13,5

77 38,5 25 = = 13,5

E59324B

44 25 9,5 12,5 60 12,5 2 11

82 52

15 5 11 25 52

82 52

15 5 11 25 52

Vertical rear connection


32

40

50

63

E59315 A

E59311A

E59312A

E59313A

E59314A

80

25 12,5

12 maxi

25 12,5

12 maxi

25 12,5

12 maxi

25

12 maxi

25 12,5

12 maxi

12,5

12,5

12,5

12,5 12,5

12,5

E59329B

60 12,5 12,5 9,5 25 44

2 11

Front connection
E59308A E59308A

Front connection with vertical-connection adapter


E59309A E59310A

50 12,5 12,5 12 maxi

50 12,5 12,5 12 maxi

63 25,5 12,5 12 maxi

80 15 15 12 maxi

25

12,5

25

12,5

25

12,5

25 25

12,5

Top terminal
E94518

Bottom terminal
2 M10 screws 15

E59332A

44 25

25 21 101

89 = =

12,5 15

9,5 15

21 3 11

2 M10 screws

15

25 44

15 9,5
15 20

Schneider Electric

159

Installation recommendations

Power connections for Compact NS1600b to 3200 Recommended drilling dimensions

Front connection (NS1600b to 2500)


E59308A E59309A

50 12,5 12,5 12 maxi

63 25,5 12,5 12 maxi

E59310A

80 15 15 12 maxi

25

12,5

25

12,5

25 25

12,5

E59462B

13

76 = =

25 = =

3 11 15

Front connection with vertical-connection adapter (NS1600b to 2500)


E59731A E59732A E59733A

63 12 maxi 25 25 25 12,5 12,5

80 12 maxi 25 25 25 12,5 12,5

100 12 maxi 25 25 25 12,5 12,5


12,5
E59734A

12 maxi 25 100 25 25 12,5

4 11
E59735A

25 25 25 20 45 60 12,5 15 20 25 25 80 60 100 20

Front connection (NS3200)


E59733A

100 12 maxi 25 25 25
12,5
E59734A

12 maxi 25 100 25 25 12,5

12,5
4 11
E59735A

12,5

25 25 25 20 45 60 12,5 15 20 25 25 80 60 100 20

160

Schneider Electric

Temperature derating Compact NS devices equipped with thermal-magnetic trip units


The values opposite are valid for fixed circuit breakers equipped with one of the following modules: b Vigi module b ammeter module b insulation-monitoring module b current-transformer module. They also apply to plug-in / withdrawable circuit breakers equipped with one of the following modules: b ammeter module b current-transformer module. However, for plug-in / withdrawable circuit breakers equipped with a Vigi module or an insulationmonitoring module, the coefficients in the table below must be applied. Trip unit
TM16 to TM125 TM160 to TM250

When the ambient temperature is greater than 40 C, overload-protection characteristics are slightly modified. To determine tripping times using time/current curves, use Ir values corresponding to the thermal setting on the device, corrected as indicated in the tables below.

Single-pole and two-pole Compact NS


Rating (A)
16 25 40 63 80 100 125 160 200 250

40 C
16 25 40 63 80 100 125 160 200 250

45 C
15.6 24.5 39 61.5 78 97.5 122 156 195 244

50 C
15.2 24 38 60 76 95 119 152 190 238

55 C
14.8 23.5 37 58 74 92.5 116 147.2 185 231

60 C
14.5 23 36 57 72 90 113 144 180 225

65 C
14 22 35 55 70 87.5 109 140 175 219

70 C
13.8 21 34 54 68 85 106 136 170 213

Coefficient
1 0.9

Compact NS100 to 250 equipped with TM-D and TM-G trip units
Rating (A)
16 25 32 40 50 63 80 100 125 160 200 250

40 C
16 25 32 40 50 63 80 100 125 160 200 250

45 C
15.6 24.5 31.3 39 49 61.5 78 97.5 122 156 195 244

50 C
15.2 24 30.5 38 48 60 76 95 119 152 190 238

55 C
14.8 23.5 30 37 47 58 74 92.5 116 147.2 185 231

60 C
14.5 23 29.5 36 46 57 72 90 113 144 180 225

65 C
14 22 29 35 45 55 70 87.5 109 140 175 219

70 C
13.8 21 28.5 34 44 54 68 85 106 136 170 213

Compact NSA160
Rating (A)
16 25 32 40 50 63 80 100 125 160

40 C
16 25 32 40 50 63 80 100 125 160

45 C
15.6 24.5 31.3 39 49 61.5 78 97.5 122 156

50 C
15.2 24 30.5 38 48 60 76 95 119 152

55 C
14.8 23.5 30 37 47 58 74 92.5 116 147.2

60 C
14.5 23 29.5 36 46 57 72 90 113 144

65 C
14 22 29 35 45 55 70 87.5 109 140

70 C
13.8 21 28.5 34 44 54 68 85 106 136

Compact NB50NB600
NB50 / NB100
NB50N NB100F/N

40 C
1 1

45 C
1 1

50 C
1 1

55 C
1 1

60 C
1 1

NB250N Rating (A)


125 150 175 200 225

50 C
125 150 175 200 225

55 C
122 146 171 195 220

60 C
119 143 166 190 214

65 C
116 139 162 185 208

70 C
113 135 158 180 203

NB400N Rating (A)


400

50 C
400

55 C
390

60 C
380

65 C
370

70 C
360

NB600N Rating (A)


600

50 C
600

55 C
585

60 C
570

65 C
550

70 C
535

Schneider Electric

161

Installation recommendations

Temperature derating Compact NS devices equipped with electronic trip units


Electronic trip units are not affected by variations in temperature. However, the maximum permissible current in the circuit breaker still depends on the ambient temperature.

The values opposite are valid for fixed circuit breakers equipped with one of the following modules: b Vigi module b ammeter module b insulation-monitoring module b current-transformer module. They also apply to plug-in / withdrawable circuit breakers equipped with one of the following modules: b ammeter module b current-transformer module. However, for plug-in / withdrawable circuit breakers equipped with a Vigi module or an insulationmonitoring module, the coefficients in the table below must be applied. Circuit breaker Trip unit
NS100N/H/L NS160N/H/L NS250N/H/L NS250N/H/L STR22SE/GE 40 to 100 STR22SE/GE 40 to 160 STR22SE/GE 100 and 160 STR22SE/GE 250

Compact NS100...NS250
The table below indicates the maximum long-time (LT) protection setting depending on the ambient temperature. NS100-160N/H/L
In: 40 to 160 A Ir max

40 C 40 C

45 C 45 C

50 C
1

55 C
1

60 C
1

65 C
1

70 C
1

no derating 1 1 no derating 1 1 250 250 1 1

NS250N/H/L
In: 100 to 160A Ir max In: 250A Ir max

50 C
1 250 1

55 C
1 237.5 0.95

60 C
1 237.5 0.95

65 C
1 225 0.90

70 C
1 225 0.90

Coeff.
1 1 1 0.86

Compact NS400 and NS630


The table below indicates the maximum long-time (LT) protection setting depending on the ambient temperature. NS400N/H/L
Fixed In: 400A Io/Ir max Plug-in / In: 400 withdrawable Io/Ir max

The values opposite are valid for fixed or plug-in / withdrawable circuit breakers equipped with one of the following modules: b ammeter module b current-transformer module. However, for fixed or plug-in / withdrawable circuit breakers equipped with a Vigi module or an insulationmonitoring module, the coefficients in the table below must be applied. Circuit breaker Trip unit
NS400N/H/L

40 C
400 1/1 400 1/1

45 C
400 1/1 390 1/0.98

50 C
400 1/1 380 1/0.95

55 C
390 1/0.98 370 1/0.93

60 C
380 1/0.95 360 1/0.9

65 C
370 1/0.93 350 1/0.88

70 C
360 1/0.9 340 1/0.85

NS630N/H/L
Fixed In: 630A Io/Ir max Plug-in / In: 570A withdrawable Io/Ir max

40 C
630 1/1 570 1/0.9

45 C
615 1/0.98 550 1/0.88

50 C
600 1/0.95 535 1/0.85

55 C
585 1/0.93 520 1/0.83

60 C
570 1/0.9 505 1/0.8

65 C
550 1/0.88 490 0.8/0.98

70 C
535 1/0.85 475 0.8/0.95

Coeff.

STR23SE and 53UE 0.97 STR23SV and 53SV NS630N/H/L STR23SE and 53UE 0.9 STR23SV and 53SV Note. To provide the Visu function, Compact NS circuit breakers, with or without a Vigi module, are combined with INV switch-disconnectors. Tripping values for the selected combination are indicated in the Interpact catalogue.

Compact NS630b to NS1600 (1)


The table below indicates the maximum rated-current value for each type of connection, depending on the ambient temperature. For mixed connections, use the same derating values as for horizontal connections. Version Connection temp. Ti (2)
NS630b N/H/L NS800 N/H/L NS1000 N/H/L NS1250 N/H NS1600 N/H

Fixed device Front or horizontal rear 40 45 50 55


630 800 1000 1250 1600 630 800 1000 1250 1600 630 800 1000 1250 1560 630 800 1000 1250 1510

60
630 800 1000 1250 1470

65
630 800 1000 1240 1420

70
630 800 1000 1090 1360

Vertical rear 40 45
630 800 1000 1250 1600 630 800 1000 1250 1600

50
630 800 1000 1250 1600

55
630 800 1000 1250 1600

60
630 800 1000 1250 1600

65
630 800 1000 1250 1510

70
630 800 1000 1180 1460

Version Connection temp. Ti (2)


NS630b N/H/L NS800 N/H/L NS1000 N/H/L NS1250 N/H NS1600 N/H

Withdrawable device Front or horizontal rear 40 45 50 55


630 800 1000 1250 1600 630 800 1000 1250 1600 630 800 1000 1250 1520 630 800 1000 1250 1480

60
630 800 1000 1250 1430

65
630 800 1000 1170 1330

70
630 800 920 1000 1160

Vertical rear 40 45
630 800 1000 1250 1600 630 800 1000 1250 1600

50
630 800 1000 1250 1600

55
630 800 1000 1250 1560

60
630 800 1000 1250 1510

65
630 800 1000 1250 1420

70
630 800 990 1090 1250

Compact NS1600b to 3200


Version Connection temp. Ti (2) Fixed device Front or horizontal rear 40 45 50 55 Vertical rear 40 45

60

65

70

50

55

60

65

70

NS1600b N/H 1600 1600 1600 1600 1500 1450 1400 1600 1600 1600 1600 1600 1550 1500 NS2000 N/H 2000 2000 2000 2000 1900 1800 1700 2000 2000 2000 2000 2000 1900 1800 NS2500 N/H 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 NS3200 N/H 3200 3200 3200 3180 3080 2970 2860 (1) For a circuit breaker mounted in horizontal position, the derating to be applied is equivalent to that of a front or horizontal rear connected circuit breaker. (2) Ti: temperature around the circuit breaker and its connections.

162

Schneider Electric

Power dissipation / Resistance Compact NS devices equipped with thermal-magnetic trip units
Power dissipated per pole (P/pole) in Watts (W). Resistance per pole (R/pole) in milliohms (m). Total power dissipation is the value measured at In, 50/60 Hz, for a three-pole or four-pole circuit breaker (values above power P = 3RI2).

Compact NSC100N
Fixed device 3/4 poles NSC100N Rat. (A) 16 20 25 32 40 50 63 70 80 100 100 R/pole 15 11.2 8 5.4 3.7 2.8 2 2 1.4 1 0.6 P/pole 4 4.5 5 5.5 6 7 8 10 9 10 6 Additional modules Vigi (N, L3) 0.06 0.1 0.16 0.26 0.4 0.63 1 1.3 1.6 2.5 2.5 Vigi (L1, L2) 0.06 0.1 0.16 0.26 0.4 0.63 1 1.3 1.6 2.5 2.5

NSC100NA

Compact NS100 to 250 equipped with TM-D and TM-G trip units
Fixed device 3/4 poles Rat. (A) R/pole 11.42 6.42 3.94 3.42 1.64 2.17 1.37 0.88 1.26 0.77 0.69 0.55 0.61 0.46 0.39 0.3 P/pole 2.92 4.01 4.03 5.47 4.11 8.61 8.77 8.8 8.06 7.7 10.78 13.95 9.45 11.78 15.4 18.75 Additional modules Vigi (N, L3) 0 0 0.06 0.10 0.15 0.3 0.4 0.7 0.4 0.7 1.1 1.8 1.1 1.8 2.8 4.4 Vigi (L1, L2) 0 0 0.03 0.05 0.08 0.15 0.2 0.35 0.2 0.35 0.55 0.9 0.55 0.9 1.4 2.2 WithAmmeter Transfo. module 0 0 0.1 0.1 0.1 0.1 0.1 0.2 0.1 0.2 0.3 0.5 0.3 0.5 0.8 1.3 drawable module 0 0 0.1 0 0.15 0.1 0.2 0.1 0.3 0.1 0.4 0.1 0.6 0.1 1 0.2 0.6 0.1 1 0.2 1.6 0.3 2.6 0.5 1.6 0.3 2.6 0.5 4 0.8 6.3 1.3

NS100N/H/L 16 25 32 40 50 63 80 100 NS160N/H/L 80 100 125 160 NS250N/H/L 125 160 200 250

Compact NS80 and NS100 to 630 equipped with MA trip units


Fixed device 3 poles NS80H Rat. (A) R/pole 93.3 89.6 75.6 12.8 2.24 1.04 0.94 148.42 99.02 4.05 1.66 0.67 0.52 0.38 0.3 0.12 0.1 P/pole 0.21 0.56 3 2 1.4 2.6 6.02 0.93 3.93 0.63 1.04 1.66 5.2 8.55 14.52 12.29 25 Additional modules Vigi (N, L3) 1.5 2.5 6.3 12.5 25 50 80 NS100N/H/L 2.5 6.3 12.5 25 50 100 NS160N/H/L 150 NS250N/H/L 220 NS400H/L 320 NS630H/L 500 Vigi WithAmmeter Transfo. (L1, L2) drawable module module

0 0 0 0 0.2 0.7 1.35 2.9 3.2 13.99

0 0 0 0 0.1 0.35 0.68 1.45 1.6 7

0 0 0 0.1 0.3 1 2.6 4.89 6.14 15

0 0 0 0 0.1 0.2 0.45 0.97 1.54 3.75

0 0 0 0 0.1 0.2 0.45 0.97 1.54 3.75

Single-pole and two-pole Compact NS100 to 160


Fixed device 1/2 poles NS100N/H Rat. (A) 16 20 30 40 50 63 80 100 125 160 R/pole 11.3 6.3 2.9 2.9 1.4 1.4 1.25 0.76 0.63 0.48 P/pole 2.89 2.52 2.61 4.64 3.5 5.56 8 7.6 9.84 12.29

NS160N/H

Schneider Electric

163

Installation recommendations

Power dissipation / Resistance Compact NS devices equipped with electronic trip units
Compact NS100 to NS630
Fixed device 3/4 poles Rat. (A) R/pole P/pole Additional modules Vigi Vigi WithAmmeter Transfo.

Power dissipated per pole (P/pole) in Watts (W). Resistance per pole (R/pole) in milliohms (m) (measured cold). Total power dissipation is the value measured at In, 50/60 Hz, for a three-pole or fourpole circuit breaker (values above power P = 3RI2).

(N, L3) (L1, L2) drawable module module NS100N/H/L 40 0.84 1.34 0.1 0.05 0.2 0.1 0.1 100 0.468 4.68 0.7 0.35 1 0.2 0.2 NS160N/H/L 40 0.73 1.17 0.4 0.2 0.6 0.1 0.1 100 0.36 3.58 0.7 0.35 1 0.2 0.2 160 0.36 9.16 1.8 0.9 2.6 0.5 0.5 NS250N/H/L 100 0.27 2.73 1.1 0.55 1.6 0.2 0.2 250 0.28 17.56 4.4 2.2 6.3 1.3 1.3 NS400N/H/L 400 0.12 19.2 3.2 1.6 9.6 2.4 2.4 NS630N/H/L 630 (1) 0.1 39.69 6.5 3.25 19.49 5.95 5.95 (1) The dissipation values for the Vigi modules and withdrawable circuit breakers are given for 570 A

Compact NSA160
Fixed device 3/4 poles NSA160 Rat. (A) R/pole 16 25 32 40 50 63 80 100 125 160 125 160 15 8 5.4 3.7 2.8 2 1.4 1 0.8 0.6 0.7 0.6 P/pole 4 5 5.5 6 7 8 9 10 12.5 15.4 11 15.4 Additional modules Vigi (N, L3) 0.06 0.16 0.26 0.4 0.63 1 1.6 2.5 3.9 6.4 Vigi (L1, L2) 0.06 0.16 0.26 0.4 0.63 1 1.6 2.5 3.9 6.4

NSA125NA NSA160NA

Compact NS630b to 1600


Version Fixed device Dissipated power N/H NS630b N/H/L NS800 N/H/L NS1000 N/H/L NS1250 N/H NS1600 N/H Version 30 45 65 130 220 L 45 60 100 Input/output resistance N/H 0.026 0.026 0.026 0.026 0.026 L 0.039 0.039 0.039

Withdrawable device Dissipated power N/H L 115 120 230 Input/output resistance N/H 0.038 0.038 0.038 0.036 0.036 L 0.072 0.072 0.072

NS630 N/H/L NS800 N/H/L NS1000 N/H/L NS1250 N/H NS1600 N/H

55 90 150 250 460

Compact NS1600b 3200


Version NS1600b N/H NS2000 N/H NS2500 N/H NS3200 N/H Fixed device Dissipated power 250 250 300 680 Input/output resistance 0.019 0.013 0.008 0.008

164

Schneider Electric

Compact NS

Dimensions, volumes

Presentation Functions and characteristics Installation recommendations

2 11 143

Compact NB Compact NS80H-MA Compact NSC100 Compact NSA160 Compact NS100 to 630 (fixed version) Vigicompact NS100 to 630 (fixed version) Compact NS100 to 630 (plug-in and withdrawable versions) Vigicompact NS100 to 630 (plug-in and withdrawable versions) Compact NS100 to 250 (single-pole and two-pole versions) Visu function for Compact NS100 to 630 (combination with Interpact INV) Motor-mechanism module for Compact NS100 to 630 Rotary handle for Compact NS100 to 630 Indication and measurement modules for Compact NS100 to 630 Front accessories for Compact NS100 to 630 Compact NS630b to 1600 (fixed version)
Dimensions Mounting Front-panel cutouts Rotary handle

166 168 170 171 172 174 176 178 180 182 184 186 188 190 192
192 193 194 195

Compact NS630b to 1600 (withdrawable version)


Dimensions, mounting and cutouts Rotary handle

196
196 197

Compact NS1600b to 3200 (fixed version)


Dimensions

198
198

Compact NS630b to 3200


External modules

200
200

Accessories NS630b to 3200


Connection Electrical diagrams Additional characteristics Catalogue numbers

204
205 221 251 267

Schneider Electric

165

Dimensions, volumes

Compact NS80H-MA

Dimensions
E21874 E21875

Mounting
On backplate
15
E94522

On rails
30

30 15
u 32

103 120 X 60 206

E21873

100 48,5

100 48,5

(a) Y

64,5 70 80 84 100 Z

45 90

(a) long terminal shields

Front-panel cutouts
Cutout A
E21881 E21882 E21883

Cutout B
E21884

Cutout C

60,5 26

68,5 30

68,5 30

B/C 71 81 Z

Y 14,5 29

Y 46 92

168

Schneider Electric

Standard direct rotary handle


Front-panel cutout
E21888 E21885

7,5
E21887

65,5 X 28,5

60
tripped

ON I

4,2 X X
O OFF

E21886

68,5 30

60

Y
82,5 112 Z

47,5 45 80 90 Z 85

Y 43 86

Extended rotary handle


Front-panel cutout
75 37,5
E21891 E21889

E21890

45

7,5

7,5

60 4,2
X

50

75
X

4,2

X 60 Y
Z mini 175 L ( maxi 590 )
shaft length = L _ 109

37,5

4,2 36 Y

72

MCC direct rotary handle


Front-panel cutout
120 69,2 7,5
E21893 E21892 E21894

4,2 120

X
X 60

100

45,8

1 to 3 maxi 116 2
Y

Y 51,7 100

Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.
Schneider Electric

E22046

169

Dimensions, volumes

Compact NSC100

Dimensions
Compact NSC100 3 poles
E43398 E43399 E43400

4 poles

103 120 X 60 90 206

(a)
15 70 80 84 100 Z

(a) Y

Y 45 90

45 120

(a) long terminal shields

Vigicompact NSC
E43401

101,2
E43402

3 poles
E43403

4 poles

103 120

X
X 60 90 206

(a)
15 70 80 84 100 Z

(a) Y 75

Y 45 210

240

(a) long terminal shields.

Extended rotary handle


Front-panel cutout
75 37,5
E21891 E21889

E21890

45

7,5

7,5

60 4,2
X

50

75
X

4,2

X 60 Y
Z mini 175 L ( maxi 590 )
shaft length = L _ 109

37,5

4,2 36 Y

72

Note. Centre line X indicates the centre of the mounting r ail.

170

Schneider Electric

Compact NSA160

Dimensions
Compact NSA160 3 poles
E21897 E21895 E21896

4 poles

98,5 120 X 64,5 90 206 X 45

(a) 15 72,5 82,5 89,5 102,5 Z Y 45 90 120 Y 45

(a)

Vigicompact NSA160 3 poles


E21903

4 poles
E21902

101,2
E21901

98,5 120

X 64,5 90 206

45

(a)

(a) Y 75

15

72,5 82,5 89,5 102,5 Z

Y 45 210

240

Extended rotary handle


Dimensions
E31295

Front-panel cutout
75
E31296

37,5 5

45

E31294

83

60

50

X
X 60 Y
Z

3 37,5

75

X
4,2 36

72

mini 122 maxi 147

Note. Centre line X indicates the centre of the mounting r ail.

Schneider Electric

171

Dimensions, volumes

Compact NS100 to 630 (fixed version)

Dimensions
2 poles or 3 poles
E21504 E21502 E21503

4 poles

H1 X H

H3

H5

H7

H2

H4

H6

(a) (b) (c) L

P1 P2 P4 Z

L1

(a) short terminal shields. (b) long terminal shields (available for spreaders on NS400 to 630, pitch 52.5 : L1 = 157.5 mm, L2 = 210 mm). (c) interphase barriers.

Y L L2

Mounting
On backplate 2 poles or 3 poles
E21507

4 poles
K1 K
E21508

K1

K1

K1

K1 K2

K1 K

G1 G

X T

G5

G4

T4 (d)

(d) for rear connection only. For two-pole circuit breakers, the centre hole is not necessary.

On rails 2 poles or 3 poles


U (e) K1 K
E21511 E21512

4 poles
K2 K

G1 G T

On DIN rail with adapter plate


E49738

G50 G51

G49
X

G48 G47 Z

172

Schneider Electric

Front-panel cutouts
Fixed or plug-in circuit breaker Cutout A
E21600 E21601 E21603

Cutout B
E21604

Cutout C

X C

C1

C3
X

C3 C2

C2

B/C P5 P6

Y R R1

Y R2 R4(3P) R5(4P)

With escutcheon

With toggle cover

E21609

E21608

C7

E21602

X C6

X C21
C20

P6 Z

Y R6 R7

Y R12 R13

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L C 29 41.5 G5 140 227 H5 321 480 C1 76 116 G47 95 C2 54 92.5 G48 75 C3 108 184 G49 13.5 C6 43 56.5 G50 23 C7 104 146 G51 17.5 C20 34 46.5 H 80.5 127.5 L 52.5 70 R4 108 143 C21 86 126 H1 161 255 L1 105 140 R5 143 188 G 62.5 100 H2 94 142.5 L2 140 185 R6 29 46.5 G1 125 200 H3 188 285 P1 81 95.5 R7 58 93 G4 70 113.5 H4 160.5 240 P2 86 110 R12 43 63

H6 178.5 237

H7 357 474 P6 88 112

K 17.5 22.5 R 14.5 31.5

K1 35 45 R1 29 63

K2 70 90 R2 54 71.5

Type P4 P5 NS100/160/250N/H/L 111 (1) 83 NS400/630N/H/L 168 107 (1) : P4 = 126 mm for Compact NS250N/H/L.

Type R13 T T4 U(e) NS100/160/250N/H/L 86 6 22 y 32 NS400/630N/H/L 126 6 32 y 32 (e) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.

E22046

Schneider Electric

173

Dimensions, volumes

Vigicompact NS100 to 630 (fixed version)

Dimensions
2 poles or 3 poles
E21515 E21513 E21514

4 poles

X H9 H11 H13 H15 H8 H10 H12 H14

(a) (b) (c) Y Y L L1

P1 P2 P4

(a) short terminal shields. (b) long terminal shields. (c) interphase barriers.

L L2

Mounting
On backplate 2 poles or 3 poles
E21518

4 poles
K1 K
E21519

K1

K1

K1

K1 K1 K2 K

G7

G1 X G

G9 X

G6 T T4 (d)

G8

(d) for rear connection only. For two-pole circuit breakers, the centre hole is not necessary.

On rails 2 poles or 3 poles


U (e) K1 K
E21520 E21521

4 poles
K2 K

G7

G1 X G X

G6 T

174

Schneider Electric

Front-panel cutouts
Fixed or plug-in circuit breaker Cutout A
E21605 E21795

Cutout B
E21796

R1 R C1 C C4

X C3 C2

C5

R28

B P5 P6

Y R28 R26

Y R4 (3P) R5 (4P) R26 R2

With escutcheons
E21800

R7 R6

E21610

C7
X

X C6 C18

C19

Y
P6 Z

R27 R11

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L C 29 41.5 C1 76 116 C2 130 192 C3 184 276 C4 C5 86 37 147.5 37 H12 H13 235.5 396 340 580 C6 43 56.5 C7 104 146 C18 71 132 K 17.5 22.5 C19 68 68 K1 35 45 C20 34 46.5 K2 70 90 C21 86 126 L 52.5 70 G 62.5 100 L1 105 140 G1 125 200 L2 140 185 G6 G7 137.5 200 200 300 P1 81 95.5 P2 86 110 G8 G9 145 215 213.5 327 P4 P5 111 (1) 83 168 107

Type H8 H9 H10 H11 NS100/160/250N/H/L 155.5 236 169 263 NS400/630N/H/L 227.5 355 242.5 385 (1) P4 = 126 mm for Compact NS250N/H/L.

H14 H15 253.5 432 337 574

Type P6 R R1 R2 R4 R5 R6 NS100/160/250N/H/L 88 14.5 29 54 108 143 29 NS400/630N/H/L 112 31.5 29 71.5 143 188 46.5 (e) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

R7 58 93

R11 58 58

R12 43 63

R13 86 126

R26 14.5 32

R27 29 47

T 6 6

T4 22 32

U(e) y 32 y 32

Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.

E22046

Schneider Electric

175

Dimensions, volumes

Compact NS100 to 630 (plug-in and withdrawable versions)

Dimensions
Plug-in base
N M Z

2 poles or 3 poles

4 poles

(*)

K1
E21524 E21522 E21523

K1

K1

H17

G11

X
H16

X G10

(*)

L L2

P7 P8 P9

L1

P4

Chassis
N M

2 poles or 3 poles

4 poles

E21586

E21584

H19 X
X X

H18
(*) (*)

Z P7 P8 P9

Y L6 L7 L8

E21585

Y L6 L9 L10

P2 P4

P12

Mounting
Through panel M (plug-in base) K1 2P, 3P
K
E21525 E21526

4P

K2 K

Through panel M (chassis) K1 2P, 3P


K
E21587

4P
E21588

K2 K

G11 X

G13 X G12

G11 X

G13 X G12

G10

G10

Y K5 K6 K7

Y K5

Y K11 K12 K13

Y K11

On rails (plug-in base or chassis) 2P, 3P


U
E21533

K21 K20

4P
E21534

K22 K20

G21

G20 Y T

(*) short terminal shields are mandatory. Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.

176

Schneider Electric

E21589

On backplate N (plug-in base or chassis) Front connection (insulating screen is mandatory between the backplate and the base, supplied with the base) 2P, 3P 4P
E21590

K1 K

K2 K

G15 X G14

Interior rear connection 2P, 3P


K1 K K
E21591

4P
K2 K K
E21592

Exterior rear connection 2P, 3P


K1 K K
E21593 E21594

4P
K2 K K

T6

G16 X G14

G18

G15
X T X

G15
X

G17

G14

G19

K1

Y K1

K1 K1

Y K1

T5

K1

Y K1

K1 K1

Y K1

Front-panel cutouts
Plug-in base
E21619

Chassis with protection collar and escutcheons


E21620

C11

C17

P44 Z
Y R8

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L C11 103 155 G25 380 567 K21 70 100 C17 42.5 56 G10 95 150 G11 190 300 G12 87 137 G13 174 274 G14 77.5 125 G15 155 250 K 17.5 22.5 L8 216 250 G16 66 101 K1 35 45 L9 220 265 G17 132 202 K2 70 90 L10 251 295 G18 82 126 K5 54.5 71.5 P2 86 110 G19 164 252 K6 109 143 G20 37.5 75 K7 144 188 G21 75 150 K11 74 91.5 P8 45 45

R9
G22 G23 111 222 170.5 341 K12 148 183 P9 75 100 K13 183 228 P10 64 86 G24 190 283.5 K20 35 50 P12 32 32

G26 G27 208 416 318.5 637 K22 105 145 L 52.5 70

H16 H17 102.5 205 157.5 315 L1 105 140 L2 140 185

H18 H19 103.5 210 140 280 L6 92.5 110 L7 185 220 T6 30 33

P4 P7 111 (1) 27 168 27

Type P44 R8 R9 U (2) T T5 NS100/160/250N/H/L 123 74 148 y 32 6 24 NS400/630N/H/L 147 90 180 y 32 6 33 (1) P4 = 126 mm for Compact NS250N/H/L (2) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250). Schneider Electric

177

Dimensions, volumes

Vigicompact NS100 to 630 (plug-in and withdrawable versions)

Dimensions
Plug-in base 2 poles or 3 poles
E21537

4 poles
K1
E21536

(*)
E21535

K1

K1

H17 X
X

G11

H16

G10

(*)

P7 P8 P9

Y L2

L1

P4

Chassis See withdrawable Compact, page 176.

Mounting
Through panel M (plug-in base) 2P, 3P
K1 K
E21526 E21525

4P
E21587

Through panel M (chassis) 2P, 3P


K2 K K1 K
E21588

4P
K2 K

G11 X

G13 X G12

G11 X

G13 X G12

G10

G10

Y K5 K6 K7

Y K5

Y K11 K12 K13

Y K11

On rails (plug-in base or chassis) 2P, 3P


U K21 K20
E21533

4P
E21534

K22 K20

G21

G20 Y T

(*) short terminal shields are mandatory

178

Schneider Electric

Front-panel cutouts
Plug-in base See fixed Compact, page 175. Chassis with protection collar and escutcheons
E21813

R9 R8

E21623

C11

C17

C16

C13

P44 Z
R34

R33

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L C11 103 155 H17 205 315 C13 84 84 K 17.5 22.5 C16 55 116.5 K1 35 45 L 52.5 70 C17 42.5 56 K2 70 90 L1 105 140 G10 95 150 K5 54.5 71.5 L2 140 185 G11 190 300 K6 109 143 P4 111 (1) 168 G12 87 137 K7 144 188 P7 27 27 G13 174 274 K11 74 91.5 P8 45 45 G20 37.5 75 K12 148 183 P9 75 100 G21 75 150 K13 183 228 P44 123 147 H16 102.5 157.5 K20 35 50 R8 74 90

Type K21 K22 NS100/160/250N/H/L 70 105 NS400/630N/H/L 100 145 (1) P4 = 126 mm for Compact NS250N/H/L.

Type R9 R33 R34 T NS100/160/250N/H/L 148 74 148 6 NS400/630N/H/L 180 91.5 148 6 (2) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

U (2) y 32 y 32

Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.

E22046

Schneider Electric

179

Dimensions, volumes

Compact NS100 to 250 (single-pole and two-pole versions)

Dimensions
1 pole
E29213

2 poles

E29214

H1 X H

H3

H7
X

E29215

H2

H6
(a) (b)
Y L3

Y L3 L4

P1 P2 P4 Z

L5

(a) short terminal shields (b) interphase barriers

Mounting
On backplate 1 pole
E29216 E21506

2 poles
K1 K
K1 K

G1

G5
X
X

G T T4 (c)
Y

G4

(c) for rear connection only

On rails 1 pole
E29217 E21510

2 poles
K1 K

U (d)

G1

X G T

(d) U y 20 mm if automatic auxiliary connectors are used

180

Schneider Electric

Front-panel cutout
E21600 E21601 E29218 E21604

X C

C1

C3

X
C2

C3 C2

B/C P5 P6

Y R R1

Y R4(1P) R5(2P) R2

With escutcheon
E21609

E21608

C7
X

X C6

P6 Z

Y R6 R7

Dimensions (mm)
Type NS100/160/250 Type NS100/160/250 Type NS100/160/250 C 29 H1 161 P1 81 C1 76 H2 94 P2 86 C2 54 H3 188 P4 111 C3 108 H4 160.5 P5 83 U(d) y 32 C6 43 H6 178.5 P6 88 C7 104 H7 357 R 14.5 G 62.5 K 17.5 R1 29 G1 125 K1 35 R2 19 G4 70 L3 17.5 R4 38 G5 140 L4 70 R5 73 H 80.5 L5 35 R6 29

Type R7 T T4 NS100/160/250 58 6 22 (d) U y 20 mm if automatic auxiliary connectors are used

Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.

E22046

Schneider Electric

181

Dimensions, volumes

Visu function for Compact NS100 to 630 (combination with Interpact INV)

Fixed Compact NS100 to 250 with Visu function Interpact INV100 to 250
3 poles
138 131 96 86
E62427

4 poles

510 474 (a)

(a) 314 for front connection. 316.5 for rear connection. 322.5 with connectors. (b) 80.5 for front connection. 83 for rear connection. 89 with connectors.

E62428

E62429

140 52,5 35 35 35

140 52,5 35 35 35

215 277,5
X 93,7 (b)

215 277,5 X

178,5 160,5

Y 52,5
Z

Y 52,5 140

105

Mounting on rails 3 poles


E62431 E62430

4 poles
70 35
70 35 9 6 17,5

7 6

17,5

100

X 50

100

X 50

22,3 157,5

22,3 157,5

125

X 62,5

125

X 62,5

Front-panel cutout
E62432A

86

E62433A

132 65,5

84

17,5 115,5

X 29

76

14,5 29

182

Schneider Electric

Fixed Compact NS400 to 630 with Visu function


3 poles
162 160,4 120 110
E62434

4 poles
E62436

522,5 717,5 (a)


X

142,5 240

(b)

(a) 492.5 for front connection 493.5 for rear connection 512.5 with right-angle terminal extensions 536.5 with edgewise terminal extensions 532.5 with spreaders 525 with 2-cable connectors. (b) 127.5 for front connection 128.5 for rear connection 147.5 with right-angle terminal extensions 171.5 with edgewise terminal extensions 167.5 with spreaders 160 with 2-cable connectors.

E62435

185 70 45 45 45

185 70 45 45 45

241

241

341

341

70
Z

70 185

140

Mounting on rails 3 poles


E62437

4 poles
90 45
E62438

90 45 7 6 22,5

7 6

22,5

75 150 X
150 X

75

33

241

33

241

200

X 100

200

X 100

Front-panel cutout
E62439 E62440

172 86

110

127

22,5 177,5

116

41,5

Y
Z

31,5 63

Schneider Electric

183

Dimensions, volumes

Motor-mechanism module for Compact NS100 to 630

Dimensions
3 poles
E21599

4 poles

H22 X

H20 H21

E21597

E21598

H23

Y L L12 L11 L1
L2

Y L

P33 P32 Z

Front-panel cutouts
With IP40, IK07 escutcheons and protection collar for Vigi module
E21813

R9 R8

E21614

E21612

E21621

C23

C11

C22 Y R14 R15


P45 Z

C17

C16

C13

P45 Z

Y R33 R34

Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.

E22046

h
Schneider Electric

184

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L C11 103 155 L2 140 185 C13 84 84 L11 91 123 C16 56 116.5 L12 45.5 61.5 C17 42.5 56 P32 178 250 C22 29 41.5 P33 143 215 C23 76 126 P45 145 217 H20 62.5 100 R8 74 90 H21 97 152 R9 148 180 H22 45.5 83 R14 48.5 64.5 H23 73 123 R15 97 129 L 52.5 70 R33 74 91.5 L1 105 140 R34 148 148

Schneider Electric

185

Dimensions, volumes

Rotary handle for Compact NS100 to 630

direct rotary handle


3 poles
E21627 E21625

4 poles
L12
E21626

H23 X H20
(a) sans se (b) avec se (c) avec se

60
DD

H24 X

60
DD

X
O

60

60

Y L15 L L11 L1
L2

Y L

P34 P35 (a) Z P36 (b) P37 (c)

(a) without keylock (b) with Ronis keylock (c) with Profalux keylock

Front-panel cutouts
Fixed or plug-in circuit breaker

Compact
E21614

Vigicompact

E21613

E21615

E21805

C23

C23 C22

C22 Y R14 R15

C4

C5

P43 Z

Y
Z

P43

R28 R26

R14 R15

Withdrawable circuit breaker

Compact
E21618

Vigicompact
E21813

R9 R8

E21620

C11

E21622

C11

C17

C17

C16

C13

P44 Z
Y R8 R9 Y

P44 Z
R34

R33

An escutcheon is mandatory

Protection collar for Vigi module is mandatory. Escutcheons are mandatory for rotary handles and Vigi protection collars.

186

Schneider Electric

MCC direct rotary handle


E21632

L8 L7 L12
E21634

Front-panel cutout

E21633

H24 H10 X X H9

G39

G38

1 to 3 maxi P422 Z Y

Y K14 K15

Extended rotary handle


Fixed or plug-in circuit breaker Cut shaft at length: P38-126 mm (NS100 to 250) P38-150 mm (NS400 to 630)
E21629

E21628

Withdrawable circuit breaker Cut shaft at length: P40-122 mm (NS100 to 250) P40-150 mm (NS400 to 630)

L14 L13 L12

E21630

10

60
I

X
O

H24 H26 X H25

60

Y P38 Z

E21631

Front-panel cutout
45 L12

T7 H24 X T6 G36 G37 Y

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L C4 C5 86 37 147.5 37 H25 37.5 37.5 P37 164 188 H26 75 75 C11 103 155 K14 50 72.5 C13 84 84 K15 100 145 C16 C17 55 42,5 116.5 56 L 52.5 70 P43 89 112 L1 105 140 P44 123 147 C22 29 41.5 L2 140 185 R1 29 29 C23 76 126 L7 69 85 R8 74 90 G36 36 36 L8 120 160 R9 148 180 G37 72 72 L11 91 123 R14 48.5 64.5 G38 41 51 L12 9.25 5 R15 97 129 G39 100 145 L13 37.5 37.5 R26 14.5 32 H9 60 83 L14 75 75 R33 74 91.5 H10 120 160 L15 55 66.5 R34 148 148 H20 28 40 P34 121 145 T6 4.2 4.2 H23 73 123 P35 155 179 T7 50 50 H24 9 24.5 P36 156 180

P38(1) P40(1) P42 u 185 u 248 125 u 209 u 272 149

(1) y 600 mm. Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.
Schneider Electric

187

Dimensions, volumes

Indication and measurement modules for Compact NS100 to 630

Dimensions
Circuit breaker with ammeter module
E21517 E21516

Circuit breaker with current-transformer module

X H9 H11 H13 H15 H8 H10 H12 H14

X H9 H11 H13 H15 H8 H10 H12 H14

P1 P2 P47

P1 P2 P4

Mounting
On backplate 2 poles or 3 poles
E21518

4 poles
E21519

K1

K1 K1 K

K1

K1 K1 K2 K

G7

G1 X G

G9 X

G6 T T4 (d)

G8

(d) for rear connection only. For two-pole circuit breakers, the centre hole is not necessary.

On rails 2 poles or 3 poles


U (e) K1 K
E21520 E21521

4 poles
K2 K

G7

G1 X G X

G6 T

188

Schneider Electric

Front-panel cutout
Circuit breaker with ammeter module and voltage-presence indicator
T8
E21673 E21674

C30

X C

C1

C28 C27

P6

Y R R1 R16 R17

E21677

E21678

T8

C30

C23 C22 C28 C27

P43 Z

Y R16 R17 R14 R15

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L Type NS100/160/250N/H/L NS400/630N/H/L C 28 41.5 H11 263 385 R14 48.5 64.5 C1 76 116 C22 28 41.5 C23 76 126 C27 56.5 56.5 C28 C29 124 30 185.5 30 K 17.5 22.5 T4 22 32 K1 35 45 U (2) y 32 y 32 C30 78.5 122 K2 70 90 G 62.5 100 P1 81 95.5 G1 125 200 P2 86 110 G6 G7 137.5 200 200 300 P4 P6 111 (1) 88 168 112 G8 G9 145 215 213.5 327 P43 89 112 P47 137 162 H8 H9 155.5 236 227.5 355 P48 128 154 R 14.5 31.5 H10 169 242.5 R1 29 63

H12 H13 235.5 396 340 580 R15 97 129 R16 46.5 64.5

H14 H15 253.5 432 337 574 R17 93 93 T 6 6

(1) P4 = 126 mm for Compact NS 250N/H/L (2) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

Schneider Electric

189

Dimensions, volumes

Front accessories for Compact NS100 to 630

Protection collar
Toggle protection collar
E21636 E21637

E21635

Vigi-module protection collar

Circuit breaker with toggle or rotary handle


E21639 E21640 E21464

Circuit breaker with motor-mechanism module

E21638

52,4

91

35

53

Toggle cover
E21654 E21655

E21653

M8

A3

D3

Front-panel escutcheons
For toggle
E21642 E21643

E21641

M2

M3

A1

D1

D2

For Vigi module


E21645 E21646

E21644

79

64

69

3,5

6,5

190

Schneider Electric

Front-panel escutcheons
For protection collar, motor mechanism or rotary handle
E21648 E21649

E21647

M6

M7

A2

D1

D2

For Vigi module with protection collar or ammeter module


E21651 E21652

E21650

93,5

80,5

157

3,5

6,5

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L A 91 123 A1 69 102 A2 157 189 A3 94 35 D 35 134 D1 3.5 3.5 D2 6.5 6.5 D3 40 60 M 73 123 M2 115 155 M3 102 142 M6 114 164 M7 101 151 M8 94 134

Schneider Electric

191

Dimensions, volumes

Compact NS630b to 1600 (fixed version) Dimensions

Manual control
Front connection
E47972B E47973A

(1)

163,5

254

327

508

200 100

107,5 205

Z
F

99,5 (3P) 169,5 (4P)

Y
99,5

(1) terminal shields are optional

Rear connection
E47914A

105 (3P) 175 (4P) 188

105 94

Y
E47913A

123 105 234 117 210

113 92,5

123

Z
107,5 140,5 146,5 205

35 70

14

Electrical control
Front and rear connection
E47897A

105 (3P) 175 (4P) 188

105 94

Y
E47896A

123 105

210

234

200 100

X
123

117

F : Datum
107,5 169,5 175,5 F

Z
70 99,5 (3P) 169,5 (4P)

35 99,5

Note. Dimensions for front and rear connection on electrically operated devices are identical to those for manually operated devices.

192

Schneider Electric

Mounting
Front connection
On backplate On rails

Y
E47898A

4 6,5
E47899A

4 6,5

200 100

200 100

99,5 (3P) 169,5 (4P)


99,5 (3P) 169,5 (4P) 99,5

99,5

Rear connection
On backplate or rails 3P 4P

Y
E47969A

4 6,5
E47970A

6 6,5

106 44
44

106

234 44 106 117

234 44 106 117

35 70 100 200
270 70 70

35 100

Note. Mounting parameters for electrically operated devices are identical to those for manually operated devices. X and Y are the symmetry planes for a 3-pole device Z is the back plane of the device.

Schneider Electric

193

Dimensions, volumes

Compact NS630b to 1600 (fixed version) (cont.) Front-panel cutouts

Toggle control
E59368

E47901A

E59201B

(A) (B) (C)

124 mini (1) (2) 150 (2)

Door cutout A
194 mini (3P) 264 mini (4P) 194 mini

194 mini (3P) 264 mini (4P)

194 mini

201 (1)

216 (1) 266 (2)

108 (1) 133 (2)

100,5 (1) 90,5 (1)

107,5 140,5 146,5

194 (1) 244 (2)

97 (1) 122 (2)

181 (1)

E59200A

C 194 mini (3P)


264 mini (4P)

194 mini

Y
119 (1) 144 (2)

95,5 (1) 108 (2)

F : Datum. (1) Without escutcheon. (2) With escutcheon.

71 (1) 121 (2)

35,5 (1) 60,5 (2)

Electrical control
Door cutout A
E59369 E47901A

(A)

150 mini (1) (2)

194 mini (3P) 264 mini (4P)

194 mini

216 (1) 266 (2)

108 (1) 133 (2)

107,5 169,5 175,5

194 (1) 244 (2)

97 (1) 122 (2)

F : Datum. (1) Without escutcheon. (2) With escutcheon.

194

Schneider Electric

Rotary handle
Direct rotary handle
Dimensions
(A) (B) (D)
E47954

124 mini (1) (2) 180 mini (2)


E47955A

Y
60 R80

195

X
60

24

107,5 154,5 160,5 189,5 229,5

25

Z
Door cutout A
E47901A

B
E47956A E47957

D
194 mini

194 mini (3P) 264 mini (4P)

194 mini

194 mini (3P) 264 mini (4P)

194 mini

201 (1)

216 (1) 266 (2)

X
100,5 (1)

201 (1)

100,5 (1)

108 (1) 133 (2) 194 (1) 244 (2) 97 (1) 122 (2) 90,5 (1) 181 (1)

90,5 (1) 130 (1)

(1) Without escutcheon. (2) With escutcheon.

Extended rotary handle


Dimensions Door cutout

Y
E47959A E47958A

60 R100

E47960A

51

25,5

51

X
60

24

24 5

212,5 231,5 mini 605,5 maxi

Z
F

25

25 25,5 51

F : Datum

Note. X and Y are the symmetry planes for a 3-pole device Z is the back plane of the device.

Schneider Electric

195

Dimensions, volumes

Compact NS630b to 1600 (withdrawable version) Dimensions, mounting and cutouts

Dimensions
Manual control Electrical control
E47944A

E47943B

E59370B

210 mini

210 mini

127,5 (3P) 197,5 (4P) 188 94

160,5

Y
70 (*) 46 (*)

199

X
69 5 5 45,5

X
123

60 mini F

60 mini F

90 (3P) 160 (4P)

90

(*) Withdrawable position

Mounting
Bottom mounting on base plate or rails Vertical on uprights or backplate

Y
E47945

E47937A

E47175B

4 6,5

6 6,5

X
24 25 100 216 231 F
90 (3P) 160 (4P) 90 F 25 100

150

50

109 (3P) 179 (4P)

109

Cutouts
Door cutout
E47177B

Rear panel cutout


230 mini
E47178A

170 mini (3P) 240 mini (4P)

259 (1) 303 (2)

234 117

109 (1) 130,8 (2) 161 (1) 183 (2) 259 (1) 307 (2)

102,5 (3P) 172,5 (4P)

102,5

(1) Without escutcheon. (2) With escutcheon. F : Datum Note. X and Y are the symmetry planes for a 3-pole device.

196

Schneider Electric

Rotary handle
Direct rotary handle
Dimensions
210 mini
E47962A

Y
136 (*)
E47963A

60 R80

X
93 5

X
60

24

60 mini

25

(*) Withdrawable position.

Door cutout
E47964B

170 mini (3P) 240 mini (4P)

230 mini

259 (1) 303 (2)

X
109 (1) 130,8 (2)

259 (1) 307 (2)

161 (1) 183 (2)

(1) Without escutcheon. (2) With escutcheon.

Extended rotary handle


Dimensions
E47966A

Door cutout

Y
E47965A E47966A

60

R200

E47967A

51

25,5

51

X
60

X
24

24 5

207 mini 447 maxi

17 F

25

25 25,5 51

Note. X and Y are the symmetry planes for a 3-pole device.

Schneider Electric

197

Dimensions, volumes

Compact NS1600b to 3200 (fixed version) Dimensions

Dimensions
(A) (B)
E59439

132 mini
E59440

(C)

165 105 330 150 75 210

18,5 38,5 132 162,5 168,5 222,5 368 F 180 (3P) 195 (3P) 295 (4P) 310 (4P) 210 (3P) 325 (4P) 340

163 170 180 195 210

Mounting on rails
E59456A

Y
4 12

X
75

150

195 (3P) 310 (4P)

195

F : Datum

Note. X and Y are the symmetry planes for a 3-pole device

198

Schneider Electric

Door cutout
A
E59457 E59729A

216 (1) 267 (2) 108 (1) 133,5 (2)

201

100,5

173 (1) 198,5 (2) 346 (1) 397 (2)

166 332

C
E59458

119 95,9

73 146

Note. X and Y are the symmetry planes for a 3-pole device

Schneider Electric

199

Dimensions, volumes

Compact NS630b to 3200 External modules

Control-wire connections to terminal block


E47683A

S : 0,6 mm2 S : 2,5 mm2

E47684A

1
8

3,5
Only one wire per terminal.

External power-supply module (AD)


E47690A

60

2 6

L4 L3
t Inpu C 24VD ut Outp C 24VD

73

60

AD 22

0A
G1

+
G2

75

E47691A

112

L4 L3
t Inpu C 24VD ut Outp C 24VD

0A AD 22
G1

+
G2

Battery module (BAT)


60
E47692A

2 6

60
H4 H3
t Inpu C 24VD

73

24V BAT

+
H2

ut Outp C 24VD H1

112

75

E47693A

H4 H3
t Inpu C 24VD

24V BAT

+
H2

ut Outp C 24VD H1

200

Schneider Electric

MN delay unit
2 4,2

57
E47694A
1 2 3 4 5 6

81
MN UVR 30 V 100/1C AC/D

S 3 6 0.5 1

42

66

1.5 3 MN r de R UV dateu Retardelay for Time

E47695A

10 12

73
3 4 5 6

73,5

72
S 3 6 0.5 MN UVR 30 V 100/1C AC/D 1

1.5 3 MN r de R UV dateu Retardelay for Time 10 12

46

Chassis communication module


Modbus Digipact

E47685A

++
Rseau shield B B A A B B A A Breaker Network
us modb CCM Fault Com.

90 45

ss Addre . sync

Disjoncteur

58

CT

CD

54

External sensor for source ground return (SGR) protection


External sensor
E58561

CE

E47686A

"MDGF" summing module

200 130

E47687A

90 45
F MDG

45

76 150
58 106

Schneider Electric

201

Dimensions, volumes

Compact NS630b to 3200 External modules (cont.)

External sensor for neutral


400/1600 A (NS630b to 1600)
4 14
E47699

GND VN VC

H1

H2 35 76
T4 T3 T1 T2

177 208

1000/4000 A (NS1600b to 3200)


8 14
E47701

H1 VC VN GND T4 T3 T1 T2

H2

44 127

44

174 295

44

Installation 400/1600 (NS630b to NS1600)


E47697A E47696

1000/4000 A (NS1600b to NS3200)

202

Schneider Electric

Rectangular sensor for earth leakage protection (Vigi)


280 x 115 mm window

E94309

470 x 160 mm window

E94310

E90301

E90300

Busbars
Window (mm) Weight (kg)

I y 1600 A
280 x 115 14

I y 3200 A
470 x 160 18

Busbars path
280 x 115 window Busbars spaced 70 mm centre-to-centre
E94311 E90307

470 x 160 window Busbars spaced 115 mm centre-to-centre


M1 M2 M3

2 bars 50 x 10 4 bars 100 x 5

M1 M2 M3

E94312

2 bars 100 x 5 4 bars 125 x 5

E90364

Schneider Electric

203

Dimensions, volumes

Accessories NS630b to 3200

Escutcheon
NS630b to NS1600 (fixed control) A
E59891A

(A) (C)
E59885A

Y
Y
E59886A

X
X
27

275

154

27

27

27 253

131

NS630b to NS1600 (withdrawable control)


E59892A

Y
E59887A

X
X
27

313

27 317

13

27

NS1600b to NS3200 (fixed control)

Y
E94263 E94264

27

275

X
137,5

27 405

202,5

204

Schneider Electric

Compact NS

Connection

Presentation Functions and characteristics Installation recommendations Dimensions, volumes

2 11 143 165

Compact NS80H-MA, NSC100N and NSA160 Compact, Vigicompact NS100 to 630 (fixed version) Compact, Vigicompact NS100 to 630 (plug-in and withdrawable versions) Compact NS630b to 1600 (fixed version)
Bars Cables with lugs and bare cables

206 208 210 212


212 215

Compact NS630b to 1600 (plug-in and withdrawable versions)


Bars Cables with lugs

216
216 218

Compact NS1600b to 3200 (fixed version)


Electrical diagrams Additional characteristics Catalogue numbers

219
221 251 267

Schneider Electric

205

Connection

Compact NS80H-MA, NSC100N and NSA160

Compact NS80H-MA
E21878 E21877

97 48,5

Y
32 Z

29,2 29,2

Compact NSC100N
30
E43405

30
E43406

34,5

48,5 X 48,5

Y 90

45

34,5 83 Z

Compact NSA160
E21900

E21898

44 X 53 X

E62454

30

30

30

30

30

34,5

44
X

53

Y 90

45 120

45

34,5 83 Z

206

Schneider Electric

Vigicompact NSC and NSA


Bottom connection 3 poles
E62455 E43407

4 poles
30 30 30
30 30 60,8 30 30 30 30

30

60,8 30

incoming

incoming

outgoing

outgoing

Top connection 3 poles

4 poles

E62456

E43408

30

60,8 30

30

30

30

30

30

60,8 30

30

30

30

incoming

outgoing

incoming

outgoing

Schneider Electric

207

Connection

Compact, Vigicompact NS100 to 630 (fixed version)

Connection dimensions
P21 P13
E21748

E21747

G4
X

G5 G19

Y
Z

K1

K1

K1

Front connection
Terminals NS100/160/250
E21554 E21750

NS400/630
10,5

Z 14

E35578

70 X

113,5 X

Connectors NS100/160/250
E21553 E21751

NS400/630
Z 14
E21752

Z 19

Z 46,5

70 X
X

113,5
X

113,5

Rear connection
NS100/160/250
E21561 E21756

NS400/630
15

10 8,6 20 13

E21755

13

23,2 14

18 70
43 short RC 88 long RC

30

X Z
8

50 short RC 115 long RC

113,5 Z X

208

Schneider Electric

Connection with accessories


Right-angle terminal extensions (upstream only) NS100/160/250
E21563 E21556

Straight or edgewise terminal extensions NS100/160/250


4 20,5

37,5 39,5 (b)

41 Z

30

E35577

70 X
E35580

70 X

(b) Vigi module or NS250.

NS400/630
E21754

NS400/630
E21758

F 58 Z 42

View F

61 Z

8 34

8 113,5

113,5
X

Distribution connectors (interphase barriers mandatory) NS100/160/250


E21565 E21557

Spreader

K10 K8 K8 G27

E21558

K8

K9 K8

K8

X
G26
E21566

70
X

41

64,5 66,5 (b)

(b) Vigi module or NS250.

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L G4 70 113.5 G5 140 227 G19 215 327 G26 30 39 52,5 G27 41 54 67,5 K1 35 45 K8 45 52.5 70 K9 159 187.5 240 K10 114 135 170 P13 19.5 (1) 26 P21 44

(1) P13 = 21.5 mm for NS250N/H/L and Vigi MH module

Note. For dimensions of conductors, see pages 98 and 99.

Schneider Electric

209

Connection

Compact, Vigicompact NS100 to 630 (plug-in and withdrawable versions)

Plug-in base or chassis


K1
E21570 E21569

K1

K1

Front connection
Terminals
E21571

NS100/160/250 Mounting on backplate or on rails (1)


E21939

NS400/630 With spreaders


42 P21 8

(*)

P21
E21572

Z G32 G31 195,5 210,5

G32 G31

(1) For backplate mounting, the insulating screen, supplied with the plug-in base, must be installed.

Connectors NS100/160/250 Mounting on backplate or on rails (1)


(*)
E21941

NS400/630 With spreaders


94 68

Z
E21580 E21581

P28

Z G31

G32 G34
202

(*) short terminal shields are mandatory.

210

Schneider Electric

Connectors
(*)

NS100/160/250 Mounting through backplate or on rails


E21942

E21583

NS400/630
109 83

P29 P30
E21582

G32 G34

66 94

Rear connection
Mounting through backplate or on rails
E21573 E21574

(*)

P22 P23

G35 G33

P24 P25 X

Mounting on backplate Right-angle extensions (mounted down and out)


(*)

P26 P27

Long, insulated right-angle terminal extensions are mandatory.

E21576

E21577

G33 X

Right-angle extensions (mounted up and out)


E21579

(*)
E21578

P26 P27 E

G35

(*) short terminal shields are mandatory.

Dimensions (mm)
Type NS100/160/250N/H/L NS400/630N/H/L E 4 6 G31 G32 G33 108.5 100 63.5 171 156.5 104 G34 110 G35 80.5 129 K1 35 45 P21 19 26 P22 P23 P24 75.5 67 49 114.5 100.5 82.5 P25 57.5 96.5 P26 P27 75.5 67 108.5 94.5 P28 26.5 P29 54.5 P30 36.5

Schneider Electric

211

Connection

Compact NS630b to 1600 (fixed version) Bars

Horizontal rear connection


E47904A

43,5 15 123 67,5

E47905A

70

70

70

E47918A

N
E47201B

Y
44 25 9,5 12,5 60 12,5

X
67,5 123 15 31

2 11

Vertical rear connection


E47907A E47908A

43,5

70

70

70 15 View A

E47919A

97

X
97
E47205B

N
60 12,5
31

12,5 9,5 44 25

2 11

View A detail.

Front connection
E47910A

70

70

70 30

E47916A

163,5 129

E47911B

Y
View A

X
Top terminal
E47971A

Bottom terminal
2 vis M10 15

129 163,5

44 25

9,5 15

16,5

2 vis M10

15

25 44

15 9,5

View A detail.

F : Datum. Note. Recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.

212

Schneider Electric

Front connection with spreaders


E47921A E47922A

70 25

70 25

E47920A

196 181

Y
View A

15

X
E47923A

95 70 12,5

95 70 70

95

181 196

12,5

31,5

Y
View A

15

Rear connection with spreaders


E47924A E47925A E47926A

98

95 70

95 70

123 15 82,5

15

52,5

Y
123
E47927A

95 70 12,5

95 70 70

95

83

12,5

N
Spreader detail Middle left or middle right spreader for 4P
E47234A

Middle spreader for 3P


E47292A

Left or right spreader for 4P


E47293A

Left or right spreader for 3P


E47294A

77 38,5 25 = = 30 82 52 15 5 11 25 52 13,5

77 38,5 25 = = 30 13,5

77 38,5 25 = = 30 13,5

77 38,5 25 = = 30 82 52 15 5 11 25 52 13,5

82 52

15 5 11 25 52

82 52

15 5 11 25 52

View A detail

F : Datum.

Note. X and Y are the symmetry planes for a 3-pole device.

Schneider Electric

213

Connection

Compact NS630b to 1600 (fixed version) (cont.) Bars

Front connection with vertical-connection adapters


E47929A E47928A E47930A

70

70

70 15 View A

200

430

E47218A

200

25

89 = =

12,5 15

21 (1) 101

21 3 11

10 62,5
15 20

View A detail.

F : Datum. Note. (1) two mounting possibilities for vertical-connection adapters (pitch 21 mm). Recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.

214

Schneider Electric

Cables with lugs and bare cables


Front connection with vertical-connection adapters and cable-lug adapters
E47933A E47931

15
E47932A

70

70

70

View A

250 200

Y
15

E47230A

530 17 50

184 50 50

200 250

80 5 13

50 5 11

View A detail.

15 10 150

Fixed circuit breaker with 4-cable bare-cable connectors (240 mm2)


E59203A

70
E59204A

70

70

E59202A

199

206,5

N
X
398 413

Y
4 21,5

199

206,5

E59205A

26 63

26
16,5 35 61 F

54

F : Datum.

Schneider Electric

215

Connection

Compact NS630b to 1600


(plug-in and withdrawable versions)

Bars
Horizontal rear connection
E47179A E47948A E47181A

70

70

70

49 15

67,5

228 67,5 114


E47201B

N
44 25 9,5 12,5 60 12,5 2 11

267,5 F

15

Vertical rear connection


E47182A E47940A

70

70

70 15 View A

49

97

X
97
E47205B

E47184A

N
60 12,5 12,5 9,5 44 25 2 11

267,5 F

View A detail.

Front connection
E47941A E47185A E47187A

15

12,5

70

70

70

View A

171

N X
336

Y
Bottom terminal
37,9 2 11 26 83 26 25 131 52 100 9,5

Top terminal
140
9,5
E47188B

44 25

235 F

12,5

2 11 44 9,5

37,9

9,5

F : Datum. Note. Recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.

View A detail.

216

Schneider Electric

Front connection with spreaders


E47223A E47952A E47225A

95 70

95 70 View A

238 223

X
E47226A

Y
95 70 12,5 95 70 95 70 View A 12,5

207 192

250 F

Spreader detail Middle left or middle right spreader for 4P


E47234A

Middle spreader for 3P


E47292A

Left or right spreader for 4P


E47293A

Left or right spreader for 3P


E47294A

77 38,5 25 = = 30 82 52 15 5 11 25 52 13,5

77 38,5 25 = = 30 13,5

77 38,5 25 = = 30 13,5

77 38,5 25 = = 30 82 52 15 5 11 25 52 13,5

82 52

15 5 11 25 52

82 52

15 5 11 25 52

View A detail.

F : Datum.

Schneider Electric

217

Connection

Compact NS630b to 1600


(plug-in and withdrawable versions) (cont.)

Cables with lugs


Front connection with vertical-connection adapters and cable-lug adapters
15
E47953A E47227

70

70

70 15 View A

50 71 292 21 171
E47229A

15

X
140 21

583 17
E47230A

184 50 50 50

261 71 50

80 5 13

50 5 11

View A detail

193,5 F

15

F : Datum. Note. X and Y are the symmetry planes for a 3-pole device. Tightening torque: 50 Nm with contact washer. X and Y are the symmetry planes for a 3-pole device.

218

Schneider Electric

Compact NS1600b to 3200 (fixed version)

Front connection (NS1600b to 2500)


E59460

115 165 150


E59461A

115

115

E59459A

N
OFF OFF

Y
25 = =
E59462B

X
150 165

View A

13

76 = =

3 11
20 F

View A detail

15

Front connection with vertical-connection adapters (NS1600b to 2500)


E59736A E59737 E94968

115 80 80

115 80

115 80

230 142,5

X
OFF OFF

N
Z
142,5 230
E59735

Y
4 11 25 25 25 60 100 20 20 15 25 25 80

View A

25 40

20 45 60

12,5

View A detail.

Front connection (NS3200)


E59740

115
E59741A

115

115

E59739A

230 142,5

Y
4 11

View A

X
OFF OFF

Z
E59735

142,5 230

25 25 25 20 45 60 12,5 15 20 25 25 80 60 100 20

25 40

Note. Recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.

View A detail.

Schneider Electric

219

220

Schneider Electric

Compact NS

Electrical diagrams

Presentation Functions and characteristics Installation recommendations Dimensions, volumes Connection

2 11 143 165 205

Compact NSC100, Compact NS80H-MA


Indication contacts Early-make contacts

222
222 223

Compact NSA160
Indication contacts

224
224

Compact NS100 to 630


Indication contacts Motor mechanism (automatic reset) Motor mechanism (remote reset) Motor mechanism (local reset) Early-make contacts Motor protection - Trip unit STR22/43ME

226
226 228 230 232 234 236

Compact NS630b to 1600


Fixed circuit breakers Plug-in / withdrawable circuit breakers

240
240 242

Compact NS630b to 3200


Communications option 24 V DC external power supply Earth-fault and earth-leakage protection, neutral protection, zone selective interlocking Fixed circuit breakers
Additional characteristics Catalogue numbers

244
244 246 248
251 267

Schneider Electric

221

Electrical diagrams

Compact NSC100 Compact NS80H-MA Indication contacts

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position.
With OF1 and CAO1
YE VT

With OF1 and CAF1/CAF2


WH RD

D1
E43821

C1

92

94 12

14
E43822

12

14

OF1

CAO1

OF1

CAF1

CAF2

trip unit MN (1) MX SD

D4 C2

91

11
GY

11
WH RD

(1) MN or MX (MN: D1, D4; MX: C1, C2)

With MN
E43823

With MX
CN1
E43824

- CN 1 + CN2 - CN 2

CN1

- CN 1 + CN2 - CN 2

F1

F1

tripping order H1 D1 92 94

tripping order

H1 C1 92 94

trip unit MN SD

trip unit MX SD

D4

91

C2

91

Symbols Q Compact NS SD trip indication contact OF ON / OFF indication contact MN undervoltage release MX shunt release CAO early-break contact of rotary handle CAF early-make contact of rotary handle XI terminal block for CAF wiring (must be ordered) F1 breaker for the protection of MN/MX H1 lamp signalling tripped position

Colour code for auxiliary wiring RD red GN green BK black BL blue WH white

222

Schneider Electric

Early-make contacts
Following tripping due to an electrical fault, reset must be carried out locally and manually.
With MN
CN1 CN2 - CN1 + (1) - CN2 X1

tripping unit

WH

WH

WH

RD

D1

E43831

D1 C1

Q trip unit MN

WH

CAF1

CAF2

BL

D4

D4

With MN + SD
CN1 CN2 - CN1 + - CN2 X1 trippinng order

(1)

RD

BL

WH

GN

WH

WH BL

RD

D1
E43830

92
RD

94

WH

D1 C1

GN

92

94

Q trip unit MN SD

CAF1

CAF2

D4
BL BL

91

D4

91

(1) independent auxiliary source. Remark NS80H-MA and NSC100 circuit breakers are not plug-in or withdrawable devices. As a result, there is no automatic auxiliary connector. Connections are made directly to the device.
Schneider Electric

223

RD BK

Electrical diagrams

Compact NSA160 Indication contacts

E62467

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position.

With OF1
D1 C1 92 94 12 14

OF1

CAO1

trip unit MN (1) MX SD

D4 C2

91

11

(1) MN or MX (MN: D1, D4; MX: C1, C2)

Symbols Q Compact NS SD trip indication contact OF ON / OFF indication contact MN undervoltage release MX shunt release CAO early-break contact of rotary handle CAF early-make contact of rotary handle XI terminal block for CAF wiring (must be ordered) F1 breaker for the protection of MN/MX H1 lamp signalling tripped position Colour code for auxiliary wiring RD red GN green BK black BL blue WH white

224

Schneider Electric

With MN
E43823

CN1

- CN 1 + CN2 - CN 2

F1

tripping order H1 D1 92 94

trip unit MN SD

D4

91

With MX
E43824

CN1

- CN 1 + CN2 - CN 2

F1

tripping order

H1 C1 92 94

trip unit MX SD

C2

91

Schneider Electric

225

Electrical diagrams

Compact NS100 to 630 Indication contacts

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position.
E18916

Compact NS100 to 250


Manually operated circuit breaker
WH GY GY VT VT RD YE
A4 A4

314 312 352

354

D1 C1

92

94 12

14 22

24

82

84

WH

GN

GN

RD YE

CE

D1 C1

92

94 12

14 22

24 72

74 82

RD

YE

VT

VT

84

Q trip unit MN (1) MX SD

OF1

OF2

CAF1

CAF2

CAO1

(2)

SDE

Id
D4
BL

SDV C2
OR BK

91
GY

11
GY

21

71
BK

81

CD 311
YE YE

351

D4

C2

91

11

21

81
WH GY
B4

(1) MN or MX (MN: D1, D4; MX: C1, C2). (2) for the withdrawable and plug-in versions, SDV and OF2 contacts can be installed in the circuit breaker, but only one can be connected to the automatic auxiliary connectors.

Circuit breaker with motor mechanism


GY GY VT
E18917

VT

314 312 352

354

D1 C1

92

94 12

14 22

24

84

A2

WH

WH

GN

OR

RD

YE

YE

VT

VT

D1 C1

92

94 12

14 22

24 72

RD

CE

74 82

84

B2

A2

BL
B4

GN (3)

Q trip unit MN (1) MX SD

OF

OF2 MT (2) SDE

Id
D4 C2 91 11

BK (3) SDV 21 71 81 A1 L1

RD

OR

CD 311 351 D4 C2 91 11 21 A1 L1

YE

(1) MN or MX (MN: D1, D4; MX: C1, C2). (2) for the withdrawable and plug-in versions, SDV and OF2 contacts can be installed in the circuit breaker, but only one can be connected to the automatic auxiliary connectors. (3) wires supplied, must be connected to ensure correct operation. Symbols Q Compact NS100 to 250 SD trip indication contact SDE fault indication contact SDV earth-fault indication contact OF ON / OFF indication contact MN undervoltage release MX shunt release MT motor-mechanism module CAO early-break contact of rotary handle CAF early-make contact of rotary handle CE connected-position carriage switch CD disconnected-position carriage switch Colour code for auxiliary wiring RD red GN green BK black VT violet YE yellow GY grey BL blue OR orange WH white

Auxiliary wiring for plug-in / withdrawable circuit breaker Automatic auxiliary connectors Manual auxiliary connectors (wires 0.75 to 2.5 mm2) (wires 0.75 to 2.5 mm2)
E43816

YE

BL

11 91

12 92

14 94

21 81

71 A1

22 82

72 L1

24

E43817

74

B4 A4 A2

24 22 21

GN

GY

GY

BK

BK

VT

74 72 71

84 82 L1

D4 C2 D1 C1

14 12 11

94 92 91

84

81 A1

Fixed part (rear view).


D1 C1 C2 D4 A2 A4 B4

Fixed part (front view looking into base)

226

Schneider Electric

Compact NS400 to 630


Manually operated circuit breaker
E22042

GY GY

VT

VT

WH

RD YE

314 312 352 354

Z11 e+ T1 D1 C1
WH

92 94 12

14 22

24 32

34

82

84

GN

GN OR

GN

RD

BK

CE

D1 C1

92 94 12 14 22 24 32

VT

34 72 74 82

RD

YE

VT YE

YE

VT

84

Q trip unit (3) MN (1) MX SD

OF1

OF2

OF3

CAF1

CAF2

CAO1

(2)

SDE

Id
D4
BL

SDV
WH OR RD BL GY GY GY

C2

91
BK

11

21

31

71

81

CD 311
YE YE

351

Z12

e- T2 D4

C2

91

11

21

31

81
WH GY
BL

(1) MN or MX (MN: D1, D4; MX: C1, C2). (2) for the withdrawable and plug-in versions, SDV and OF3 contacts can be installed in the circuit breaker, but only one can be connected to the automatic auxiliary connectors. (3) options available with trip unit STR53UE only.

Circuit breaker with motor mechanism


E22043

GY GY

VT

VT

314 312 352 354

Z11 e+ T1 D1 C1
WH

92

94 12

14 22

24 32

34

84
WH

A2 A4 B4

GN OR

GN

YE

D1 C1

92 94 12 14 22 24 32

34 72 74 82

RD

CE

VT

84

B2 A2 A4

OR

RD

BK

YE

YE

VT

VT

GN (4)

RD

Q trip unit (3) MN (1) MX SD

OF1

OF2

OF3 MT (2) SDE

Id
D4
RD BL BL

BK (4) SDV

WH

OR

GY

GY

GY

BK

CD 311 351 Z12 e- T2 D4 C2 91 11 21 31 A1 L1

YE

(1) MN or MX (MN: D1, D4; MX: C1, C2). (2) for the withdrawable and plug-in versions, SDV and OF3 contacts can be installed in the circuit breaker, but only one can be connected to the automatic auxiliary connectors. (3) options available with trip unit STR53UE only. (4) wires supplied, must be connected to ensure correct operation.

Symbols Q Compact NS100 to 250 SD trip indication contact SDE fault indication contact SDV earth-fault indication contact OF ON / OFF indication contact MN undervoltage release MX shunt release MT motor-mechanism module CAO early-break contact of rotary handle CAF early-make contact of rotary handle CE connected-position carriage switch CD disconnected-position carriage switch Colour code for auxiliary wiring RD red GN green BK black VT violet YE yellow GY grey BL blue OR orange WH white
Schneider Electric

Auxiliary wiring for plug-in / withdrawable circuit breaker Automatic auxiliary connectors Manual auxiliary connectors (wires 0.75 to 2.5 mm2) (wires 0.75 to 2.5 mm2)
E43818

YE

11 91

12 92

14 94

21 81

22 82

24 84

31

71

32

72

34

E43817

74

T2 T1 Z12

24 22 21

_ e e+
Z11

A1

L1

Z11

e+

_ e

B4
D1 C1 C2 D4 A2 A4 B4 Z12 T1 R1 T2 R2

34 32 31

74 72 71

84 82 81 L1 A1

BK

D4 C2 D1 C1

14 12 11

GN

C2

91

11

21

31

71

81

A1

L1

VT

B4

94 92 91

A4 A2

Fixed part (front view looking into base)

Fixed part (rear view).

227

Electrical diagrams

Compact NS100 to 630 Motor mechanism (automatic reset)


Automatic reset with MN
E43825

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position. Following tripping due to an electrical fault, reset must be carried out locally and manually.

CN1

- CN1 +

CN2

- CN2

F1

F tripping order (2) D1 H1

O H2

A2

A4

B4

RD

WH

OR
A2

D1

82

84

B2

A4

BL
B4

GN (1)

Q trip unit SDE MN BK (1) MT

BL

D4

A1

GN

BK

D4

81

A1

WH

L1

L1

(1) wires supplied, must be connected to ensure correct operation. (2) the tripping order must lock out the closing order.

Automatic reset with MX


E43826

CN1

- CN1 +

CN2

- CN2

F1

F tripping order (2) C1 H1

O H2

A2

A4

B4

WH

RD

OR

C1

82

84

B2 A2

A4

BL
B4

GN (1)

Symbols Q Compact NS100 to 630 SDE fault indication contact MT motor-mechanism module F1 breaker for protection of motor-mechanism module circuits H1 lamp signalling an electrical fault H2 lamp signalling motor mechanism in manual position F closing order O opening order orders must not be simultaneous (must be > 150 ms) Colour code for auxiliary wiring RD red GN green BK black BL blue OR orange WH white

Q trip unit
SDE

WH

MT MX BK (1)

C2

A1

GN

OR

C2

81

A1

L1

BK

L1

(1) wires supplied, must be connected to ensure correct operation. (2) the tripping order must lock out the closing order.
Schneider Electric

228

Automatic reset without auxiliary


E43827

CN1

- CN1 +

CN2

- CN2

F1

H1

O H2 A2 A4 B4

RD

OR
A2

82

84

B2

A4

BL
B4

GN (1)

WH

trip unit SDE

MT

BK (1)

A1

GN

81
BK

A1

L1

L1

(1) wires supplied, must be connected to ensure correct operation.

Control via switch or relay


With MN/MX Controlled by switch
E43838 E43839

Controlled by relay

1 locked by tripping order

F locked by tripping order

B2

A2 MT

A4

B4

B2

A2 MT

A4

B4

82

81

82

81

Without auxiliary Controlled by switch


E43840 E43841

Controlled by relay

B2

A2 MT

A4

B4

B2

A2 MT

A4

B4

82

81

82

81

Schneider Electric

229

Electrical diagrams

Compact NS100 to 630 Motor mechanism (remote reset)


Remote reset with MN
E43834

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position. Following tripping due to an electrical fault, reset must be carried out locally and manually.

CN1

- CN1 + CN2 - CN2

F1

R tripping order (3) D1 RD D1 82 84 84

O H2

A2 A4 B4
WH

WH

B2 A2 A4

BL

(1)

OR

B4

Q trip unit MN MT (2) SDE

BL

D4

A1

GN

D4

81
BK

A1

L1

L1

Remote reset with MX


E43835

CN1

- CN1 + CN2 - CN2

F1

R tripping order (3) C1 84

O H2

A2

A4

B4

(1) wires supplied, must be connected to ensure correct operation. (2) connect SDE terminal 81 to auxiliary-connector terminal 84. (3) the tripping order must lock out the closing order. Symbols Q Compact NS100 to 630 SDE fault indication contact MN undervoltage release MX shunt release MT motor-mechanism module F1 breaker for protection of motor-mechanism module circuits and MN/MX H2 lamp signalling motor mechanism in manual position R reset order (must be > 150 ms) orders F closing order must not O opening order be simultaneous (must be > 150 ms, has priority over F order) Colour code for auxiliary wiring RD red GN green BK black BL blue OR orange WH white

WH

OR

C1

82

84

B2

A2

A4

BL

(1)

WH

RD

B4

Q
trip unit (2) MX SDE MT

OR

C2

A1

GN

BK

C2

81

A1

L1

L1

230

Schneider Electric

Remote reset without auxiliary


E43836

CN1

- CN1 + CN2 - CN2

(1) wires supplied, must be connected to ensure correct operation. (2) connect SDE terminal 81 to auxiliary-connector terminal 84.
F1

O H2

84

A2

A4

B4

WH

82

84

B2

A2

A4

BL
B4

(1)

Q trip unit (2) SDE MT

A1

GN
E43915

BK

81

A1

OR

RD

L1

L1

Control via switch or relay


With MN/MX Controlled by switch
E43914

Controlled by relay

2 R

O R locked by tripping order

locked by tripping order B2 A2 MT 81 A4 B4

B2

A2 MT

A4

B4

81

Without auxiliary Controlled by switch


E43916 E43917

Controlled by relay

B2

A2 MT

A4

B4

B2

A2 MT

A4

B4

81

81

Schneider Electric

231

Electrical diagrams

Compact NS100 to 630 Motor mechanism (local reset)


Local reset with MN
E43837

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position. Following tripping due to an electrical fault, reset must be carried out locally and manually.

CN1

- CN1 + CN2 - CN2

F1

F
tripping order

O H2

H1

D1

84

A2 A4 B4

WH

WH

RD

OR

D1

82

84

B2 A2 A4

BL

B4

Q
trip unit

MT MN SDE (2) (1)

BL

D4

A1

GN

BK

D4

81

A1

L1

L1

Local reset with MX


E43919

CN1

- CN1 + CN2 - CN2

F1

F
tripping order

O H2

H1

D1

84

A2 A4 B4

WH

WH

RD

OR

D1

82

84

B2 A2 A4

BL

B4

Q
trip unit

MT MX SDE (2) (1)

(1) (2) required to ensure correct indication of an electrical fault. Symbols Q Compact NS100 to 630 SDE fault indication contact MN undervoltage release MX shunt release MT motor-mechanism module F1 breaker for protection of motor-mechanism module circuits and MN/MX H1 lamp signalling an electrical fault H2 lamp signalling motor mechanism in manual position F closing order orders O opening order must not (must be > 150 ms, be simultaneous has priority over F order) Colour code for auxiliary wiring RD red GN green BK black BL blue OR orange WH white

BL

D4

A1

GN

BK

D4

81

A1

L1

L1

232

Schneider Electric

Local reset without auxiliary


E43920

CN1

- CN1 + CN2 - CN2

(1) (2) required to ensure correct indication of an electrical fault.


F1

F H1

O H2

84

A2 A4 B4

WH

RD

OR

82

84

B2 A2 A4

BL

B4

Q
trip unit

MT SDE (2) (1)

A1

GN

BK

81

A1

L1

L1

Control via switch or relay


With MN/MX
E43844 E43845

locked by tripping order

locked by tripping order B2 A2 MT 81 81 A4 B4

B2

A2 MT

A4

B4

Without auxiliary Controlled by switch


E43912 E43913

Controlled by relay

B2

A2 MT

A4

B4

B2

A2 MT

A4

B4

81

81

Schneider Electric

233

Electrical diagrams

Compact NS100 to 630 Early-make contacts

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position. Following tripping due to an electrical fault, reset must be carried out locally and manually.

With MN
E43831

CN1 CN2

- CN1 + (1) - CN2 X1

tripping order

WH

WH

WH

RD

D1

D1 C1

Q trip unit MN

WH

CAF1

CAF2

BL

D4

D4

(1) independent auxiliary source

Symbols Q Compact NS SD trip indication contact MN undervoltage release CAF early-make contact of rotary handle XI terminal block for CAF wiring (must be ordered) Colour code for auxiliary wiring RD red GN green BK black BL blue WH white

234

Schneider Electric

RD

BL

With MN + SD
E43830

CN1 CN2

- CN1 + - CN2

(1)

trippinng order X1

WH

GN

WH

WH BL

RD

D1

92

94

WH

GN

D1 C1

92

RD

94

Q trip unit MN SD

CAF1

CAF2

D4

91

BL

D4

BL

91

(1) independent auxiliary source.

RD BK

Schneider Electric

235

Electrical diagrams

Compact NS100 to 630 Motor protection Trip unit STR22/43ME

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position.
Thermal-fault indication
E28434

CN1

- CN1 + CN2 - CN2

F1

D1

BP1

WH

97 KA1

13

43

14

KA1

44

trip unit SDTAM

98

BL
D4

A1 KAI A2 H1

X1 X2

Symbols Q F1 SDTAM BP1 KA1

Compact NS100 to 630 breaker for protection of the auxiliary circuit thermal-fault early-break signal SDTAM reset button auxiliary relay - Telemecanique CA...DN31 or CA...DN22 H1 lamp signalling SDTAM fault Colour code for auxiliary wiring BL blue WH white

236

Schneider Electric

Automatic operation
E28435

overload SDTAM

I O I O

BP1 H1 Q

I O I O I O 300 ms tr IQ

tr overload (long-time) protection tripping time overload current greater than Ir (long-time tripping threshold) IQ closing order for circuit breaker Q Note. For a short-circuit or earth fault, only circuit breaker Q opens. The above automatic control sequence is not run.

Legend b O: OFF (circuit open) b I: ON (circuit closed) b : either ON or OFF

Schneider Electric

237

Electrical diagrams

Compact NS100 to 630 Motor protection Trip unit STR22/43ME

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position.
Thermal-fault indication and tripping
E43828

CN1

- CN1 + CN2 - CN2

F1

D1

WH

97

21 Q BP1 trip unit SDTAM KA1 22 KA1

42

44

(1) 98

BL
D4

E1

A1 KA1 KM1 A2 KA2 E2 KM1

A1 H1 A2

X1 X2

(1) KM1 operating conditions must be inserted between 22 and A1.

Symbols Q F1 SDTAM BP1 KA1

Compact NS100 to 630 breaker for protection of the auxiliary circuit thermal-fault early-break signal SDTAM reset button auxiliary relay - Telemecanique CA...DN31 or CA...DN22 KA2 mechanical latching unit Telemecanique LA6 DK1 RHK bistable relay - Telemecanique RHK-41 H1 lamp signalling SDTAM fault KM1 power contactor Colour code for auxiliary wiring BL blue WH white

238

Schneider Electric

Automatic operation
E28437

overload

I O I O I O I O I O I O tr

SDTAM BP1 H1 KM1 Q

tr overload (long-time) protection tripping time overload current greater than Ir (long-time tripping threshold) Note. For a short-circuit or earth fault, only circuit breaker Q opens. The above automatic control sequence is not run.

Legend b O: OFF (circuit open) b I: ON (circuit closed) b : either ON or OFF

Same automatic system using a bistable relay


E43829

CN1

- CN1 + CN2 - CN2

F1

D1

BP1 D4

E4

RHK

12 11 14

22 21 24

(1)

A1 KM1 A2 H1

X1 X2

(1) KM1 operating conditions must be inserted between 12 and A1.

Schneider Electric

239

Electrical diagrams

Compact NS630b to 1600 Fixed circuit breakers

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position.
Power
power
Z1

Control unit
upstream cb
Z2 Z3 Z4 Z5

Remote operation
downstream cb
Z1 Z2 Z3 Z4 Z5

L1

L2

L3

AT

BPO

BPF

D2

C2

A4

A2

Z1

Z2

Z3

Z4

Q I
Micrologic

Z5

MN

MX

motor-mechanism module

or

E59040

E59041

D1

C1

T1/M3

T4/F1

24 V DC

(basic) A b b b

Control unit E1-E6 communication Z1-Z5 zone selective interlocking: Z1 = ZSI OUT SOURCE Z2 = ZSI OUT; Z3 ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7)
E59039A

F2+

T2

M1

M2

T3

Remote operation MN or MX : : undervoltage release shunt release

Motor-mechanism module (*) A4 : electrical opening order A2 : electrical closing order B4, A1 : power supply for control devices and gear motor
(*) Spring-charging motor 440/480 V AC (380 V motor + additional resistor)
CN1 - 440/480 V 9 11 R A4 A2 B4

F2+, F1- external 24 V DC power supply

: basic Micrologic control unit. A: digital ammeter.


motor-mechanism module

A1 CN2 - 440/480 V

240

A1

B4

Schneider Electric

Indication contacts
E59296A E59043

Terminal-block marking (manual operation)


white yellow brown black red

open

closed

fault

fault

closed

open

E6 E5 E4 E3 E2 E1 F1 F2 M1M2 M3 Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4

blue

MN/MX D1/C1 D2/C2

OF1 OF2 OF3 SD

11 12 14 21 22 24 31 32 34 91 92 94

522

524

512

542

544

532

OF3

OF2

OF1

SDE

SD

CAF2

CAF1

534

CAO2

CAO1

521

541

531

31

11

81

91

511

21

514

32

22

12

82

84

92

34

24

14

94

CAF1 CAF2 CAO1 CAO2 531 532 534 541 542 544 511 512 514 521 522 524

81 82 84 SDE

Indication contacts
E59044

Terminal-block marking (electrical operation)


white yellow brown black red

OF3 / OF2 / OF1 : SDE :

indication contacts fault-trip indication contact (short-circuit, overload, earth fault) trip indication contact (manual operation) early-make contact (rotary handle) early-break contact (rotary handle)

E6 E5 E4 E3 E2 E1 F1 F2 M1M2 M3 Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4

blue

MN/MX D1/C1 D2/C2

SD

CAF2/CAF1

CAO2 / CAO1

SDE OF3 OF2 OF1 81 82 84 31 32 34 21 22 24 11 12 14

B4 A4 A2 A1

Schneider Electric

241

Electrical diagrams

Compact NS630b to 1600 Plug-in / withdrawable circuit breakers

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position.
Power
E59730

Control unit
upstream cb
Z1 Z2 Z3 Z4 Z5
L2 L3

Remote operation
downstream cb
Z1 Z2 Z3 Z4 Z5
E59037B

power
N L1

AT

BPO

BPF

D2

C2

A4

Z1

Z2

Z3

Z4

Q I
MN MX

Z5

motor-mechanism module

Micrologic
or

T1/M3

F2+

T2

M1

M2

T3

D1

C1

A2

T4/F1

24 V DC

Control unit
Terminal-block marking Com UC1 UC2 UC3
F2+

Remote operation
MN / MX
D2 C2

MT2
A4

MT1
A2 B4

E5 E6 Z5 M1 M2 M3 E3 E4 Z3 Z4 T3 T4 E1 E2 Z1 Z2 T1 T2

F1

D1

C1

A1

(basic) A b b b

Control unit Com: E1-E6 communication UC1 : Z1-Z5 zone selective interlocking: Z1 = ZSI OUT SOURCE Z2 = ZSI OUT; Z3 ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) UC2 : T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7)
E59039

Remote operation MN or MX : : undervoltage release shunt release

Motor-mechanism module (*) MT2 : A4 : electrical opening order MT1 : A2 : electrical closing order B4, A1 : power supply for control devices and gear motor (MCH)
(*) Spring-charging motor 440/480 V AC (380 V motor + additional resistor)

UC3 : F2+, F1- external 24 V DC power supply

CN1

- 440/480 V

9 11 R B4

: basic Micrologic control unit. A: digital ammeter.

A4

A2

motor-mechanism module

A1 CN2 - 440/480 V
Schneider Electric

242

A1

B4

Indication contacts
E59295A E47075A

Carriage switches
E46134A E47074A

open

closed

fault

fault

closed

open

disconnected

connected

Test

332

334

322

324

312

822

824

812

522

524

512

514

814

314

542

532

914 CT1

544

OF3

OF2

OF1

SDE

SD

534

CAF2

CAF1

CAO2

CAO1 CD2 CD1

CE3

CE2

CE1

331

321

821

811

311

521

541

Indication contacts
CAF2 CAF1
544 542 541 534 532 531

531

31

11

81

91

511

21

Carriage switches
SD
94 92 91

SDE
84 82 81

CAO2 CAO1
524 522 521 514 512 511

OF3
34 32 31

OF2
24 22 21

OF1
14 12 11

CD2
824 822 821

CD1
814 812 811

CE3
334 332 331

CE2
324 322 321

CE1
314 312 311

CT1
914 912 911

Indication contacts OF3 / OF2 / OF1 : SDE : indication contacts fault-trip indication contact (short-circuit, overload, earth fault) trip indication contact (manual operation) early-make contact (rotary handle) early-break contact (rotary handle)

Carriage switches CD2 : disconnected CE3 : connected CT1 : test CD1 position CE2 position position CE1

SD

CAF2/CAF1

CAO2 / CAO1

Legend Connected (only one wire per connection point).


Schneider Electric

911

912

32

22

12

82

84

92

34

24

14

94

243

Electrical diagrams

Compact NS630b to 3200 Communications option 24 V DC external power supply

Connection of the communications option


E59303

motor-mechanism module
N L1 L2 L3

manual operation OF SDE


Z1 Z2 Z3 Z4 Z5

914 opening order closing order OF SDE 911

812

314

912 812

312

SD

811

311

911

811

311

CT Q I Micrologic device communication module B' A' B A

CD

CE +

CT +

CD

CE

Modbus COM craddle BB BB

Digipact COM craddle

shield

B' A' B A (2)

CCP 303
F2+ E1 E2 E3 E4 E5 M1 M2 T1/M3 T4/F1 E6 T2 T3
5 4 3

CCP 303

H1 H2

BAT module
H3 H4 G1 G2

(1) (2)

2 1 0

Modbus junction block CJB306

brown

yellow

black

L3 L4

110/240 V AC 24/125 V DC

E1 E2 E3 E4 + A B + / / E3 / E4 E5 / E6

E5 E6 A' B' Modbus BB BB + Digipact twisted pair twisted pair

blue

red

AD module

white

24 V 0V

0V 24 VDC 1A

BB BB
Digipact junction block
24 V 24 VDC DC 150

communication power supply

None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power supply (AD module) is required for certain operating configurations as indicated in the table below. Circuit breaker
Protection function Display function Circuit-breaker status indications and control communications bus

Closed
no no (3) no

Open
no yes no

(1) Drawout device equipped with Com chassis modbus. (2) Fixed device or draw-out device without Com chassis Digipact. (3) except if current < 20 % In.

The communications bus requires its own 24 V DC power source (E1, E2). This source is not the same as the 24 V DC external power-supply module (F1-, F2+). If the 24 V DC external power supply (AD module) is used, the maximum cable length between the 24 V DC external power supply (G1, G2) and the Micrologic control unit (F1-, F2+) is ten metres. The BAT battery module, mounted in series upstream of the AD module, ensures an uninterrupted supply of power if the AD module power supply fails.

244

Schneider Electric

Examples using the COM communications option Switchboard display unit


This architecture provides remote display of the variables managed by Micrologic control units equipped with the eco COM Modbus module. b I (Micrologic A) No programming is required. For Micrologic A control unit (if current < 20 % In), it is recommended to use the 24 VDC external power supply (AD module).
E47976

CDM303 + CSD309 d < 1 km DMB300


1 2 3 4 I U P ?

5 4 3 2 1 0
24 V 0V

CCP303

switchboard display unit

Modbus junction block CJB 306

24 VDC 1A

power circuit breaker

Communicating switchboard
This configuration provides remote display and control of Compact equipped with the Modbus or Digipact COM module. The Digipact bus can be combined with the Modbus bus.
E94381

Software

PC running Micrologic utilities SMS PLC PLC

PC running Micrologic utilities SMS

TCP/IP

Communication interface
RS 232C RS 485 Bus Modbus Bus Modbus Ethernet RS 485

communication Bus

Data concentrator

DC150

Device

UA150 source change-ower

SC150 control interface

PM150 measure

Compact COM Digipact

Compact COM Modbus

PM500 measure

Sepam

Vigilohm

Altivar

Digipact Bus

Modbus Bus

Schneider Electric

245

Electrical diagrams

Compact NS630b to 3200 Earth-fault and earth-leakage protection Neutral protection Zone selective interlocking
E59305

External sensor (CT) for residual earth-fault protection


Connection of current-transformer secondary circuit for external neutral Compact equipped with a Micrologic 6 A: b shielded cable with 2 twisted pairs b T1 twisted with T2 b T3 twisted with T4 b shielding connected to GND on one end only b maximum length 10 meters b cable cross-sectional area 0.4 to 1.5 mm2 b recommended cable: Belden 9552 or equivalent. If supply is via the top, follow the shematics. If supply is via the bottom, control wiring is identical; for the power wiring, H1 is connected to the source side, H2 to the load side. For four-pole versions, for residual earth-fault protection, the current transformer for the external neutral is not necessary.
N L1 L2 L3 VN V1 V2 V3 Z1 Z2 Z3 Z4 Z5 F2+ F2+

Q I Micrologic 6 U

M1

M2

M3

T1

T2

T3 Z4 F1 /T4

H2 VC H1 VN GND T4 T3 T1 T2

External transformer for source ground return (SGR) earth-fault protection


Connection of the secondary circuit Compact equipped with a Micrologic 6 A: b unshielded cable with 1 twisted pair b maximum length 150 metres b cable cross-sectional area 0.4 to 1.5 mm2 b recommended cable: Belden 9409 or equivalent.

Z1

Z2

Z3

Q I Micrologic 6

T2

M1

M2

H1
E59306

X1 X2 PE 1 3

12 5

M3/T1

10 11 9 8

MDGF module
13 14

H2

246

T3

Z5

F1

Schneider Electric

Earth-leakage protection
Connection of the rectangular-sensor secondary circuit Compact equipped with a Micrologic 7 A: use the cable shipped with the rectangular sensor.
E59307A

L1

L2

L3

Z1

Z2

Z3

Z4

Q I Micrologic 7 U

Z5

M1 M2 M3

Neutral protection
b three pole circuit breaker: v neutral protection is impossible. b four pole circuit breaker: v Compact equipped with Micrologic A v the current transformer for external neutral is not necessary.

Zone selective interlocking


A pilot wire interconnects a number of circuit breakers equipped with Micrologic A control units, as illustrated in the diagram above. The control unit detecting a fault sends a signal upstream and checks for a signal arriving from downstream. If there is a signal from downstream, the circuit breaker remains closed for the full duration of its tripping delay. If there is no signal from downstream, the circuit breaker opens immediately, whatever the tripping-delay setting. Fault 1. Only circuit breaker A detects the fault. Because it receives no signal from downstream, it immediately opens in spite of its tripping delay set to 0.3. Fault 2. Circuit breakers A and B detect the fault. Circuit breaker A receives a signal from B and remains closed for the full duration of its tripping delay set to 0.3. Circuit breaker B does not receive a signal from downstream and opens immediately, in spite of its tripping delay set to 0.2.
E47975B

upstream circuit breaker

Z1 Z2 Z3 Z4 Z5 fault 1

F1 /T4

M3/T1

tsd = 0,3

Z1 Z2 Z3 Z4 Z5 fault 2

tsd = 0,2

Z1 Z2 Z3 Z4 Z5

downstream circuit breaker

Z1 Z2 Z3 Z4 Z5

Note. The maximum permissible distance between two devices is 3000 metres and the maximum number of devices is 100.
Schneider Electric

F2+

T2

M1

M2

T3

247

Electrical diagrams

Compact NS1600b to 3200 Fixed circuit breakers

The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in the normal position.
Power
power
Z1
N L1 L2 L3

Control unit
upstream cb
Z2 Z3 Z4 Z5

Remote operation
downstream cb
Z1 Z2 Z3 Z4 Z5

AT

D2
MN or
E59463A

Z1

Z2

Z3

Z4

Q I Micrologic

Z5

MX

E59040

D1

C2

T1/M3

T4/F1

24 V DC

(basic) A b b b

Control unit E1-E6 communication Z1-Z5 zone selective interlocking: Z1 = ZSI OUT SOURCE Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7) F2+, F1- external 24 V DC power supply

F2+

T2

M1

M2

T3

Remote operation MN or MX : : undervoltage release shunt release

: basic Micrologic control unit. A: digital ammeter.

248

C1

Schneider Electric

Indication contacts
E59464A E59465A

Terminal-block marking
E6 E5 E4 E3 E2 E1 F1 F2 M1M2 M3 Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4

MN/MX D1/C1 D2/C2

open

closed

fault

fault

OF1 OF2 OF3 SD

11 12 14 21 22 24 31 32 34 91 92 94

32

22

12

82

84

92

34

24

14

OF3

OF2

OF1

SDE

SD

31

21

11

81

91

94

81 82 84 SDE

Indication contacts OF3 / OF2 / OF1 : SDE SD : : ON / OFF indication contacts fault-trip indication contact (short-circuit, overload, earth fault) trip indication contact

Schneider Electric

249

250

Schneider Electric

Compact NS

Additional characteristics

Presentation Functions and characteristics Installation recommendations Dimensions, volumes Connection Electrical diagrams

2 11 143 165 205 221

Tripping curves
Compact NSC100 Compact NS80H-MA Compact NSA160 Compact NB100 to 600 Compact NS100 to 250 Compact NS100 to 250 protection of distribution systems Compact NS100 to 250 motor-starter protection Compact NS400 to 630 protection of distribution systems Compact NS400 to 630 motor-starter protection Compact NS630b to 3200 Reflex tripping

252
252 253 254 255 256 258 259 260 261 262 263

Current-limiting curves
Catalogue numbers

264
267

Schneider Electric

251

Additional characteristics

Tripping curves Compact NSC100

1640 A
E94504 E94503

5080 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2
16 A : Im = 37,5 x In 20 A : Im = 30 x In 25 A : Im = 24 x In 32 A : Im = 19 x In 40 A : Im = 15 x In

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1

1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1


50 A : Im = 20 x In 63 A : Im = 16 x In 70 A : Im = 14,3 x In 80 A : Im = 12,5 x In

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

100 A
E94505

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
100 A : Im = 12,5 x In

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

252

Schneider Electric

Compact NS80H-MA

MA1.5MA80
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
Im = 614 x In
E28466

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

Schneider Electric

253

Additional characteristics

Tripping curves Compact NSA160

1640 A
E94506 E94507

5080 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2
16 A : Im = 37,5 x In 25 A : Im = 24 x In 32 A : Im = 19 x In 40 A : Im = 15 x In

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1

1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1


50 A : Im = 20 x In 63 A : Im = 16 x In 80 A : Im = 12,5 x In

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

100 A
E94508

125160 A
E94509

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
100 A : Im = 12,5 x In

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
125 A : Im = 10 x In 160 A : Im = 7,8 x In

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

254

Schneider Electric

Additional characteristics

Tripping curves Compact NS100 to 250 Protection of distribution systems

TM magnetic trip units


TM16D / TM16G
E28452

TM25D / TM25G
E28453

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
TM16G : 4 x In TM16D : 12 x In

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
TM25G : 3.2 x In TM25D : 12 x In

reflex tripping : t < 10 ms

reflex tripping : t < 10 ms

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

TM32D / TM40D / TM40G


E28454

TM50D / TM63D / TM63G


10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s)
TM40D : 12 x In
E28455

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
TM40G : 2 x In TM32D : 12,5 x In

2 1 .5
TM50D : 10 x In TM63D : 8 x In

.2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1

TM63G : 2 x In

reflex tripping : t < 10 ms

reflex tripping : t < 10 ms

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

256

Schneider Electric

TM magnetic trip units (cont.)


TM80D / TM100D
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
reflex tripping: t < 10 ms NS100 Im = 8 x In NS160/250 Im = 12,5 x In
E28457 E28456

TM125D / TM160D
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
TM160D 8 x In TM125D 10 x In

reflex tripping : t < 10 ms

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

TM200D / TM250D
E28458

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
Im = 5 10 x In

reflex tripping : t < 10 ms

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

Schneider Electric

257

Additional characteristics

Tripping curves Compact NS100 to 250 Protection of distribution systems (cont.)

STR22SE and STR22GE electronic trip units


STR22SE - 40100 A
E28459

STR22SE - 160250 A
E28460

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
I = 11 x In
reflex tripping t < 10 ms Im = 210 x Ir Ir = 0.41 x In

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5


Ir = 0.41 x In

t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1


I = 11 x In
reflex tripping t < 10 ms Im = 210 x Ir

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

STR22GE - 40100 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
I = 11 x In
reflex tripping : t < 10 ms Im = 210 x Ir Ir = 0.41 x In
E28409 E28410

STR22GE - 160250 A
10 000 5 000 2 000 1 000 500
Ir = 0.41 x In

200 100 50 20 10 5 t(s) 2 1 .5


Im = 210 x Ir

.2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1


I = 11 x In
reflex tripping : t < 10 ms

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

258

Schneider Electric

Compact NS100 to 250 Motor-starter protection


MA magnetic trip units
MA2,5MA100
E30212

MA150 and MA220


10 000 5 000 2 000 1 000 500 200
thermal withstand
E28467

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
Im = 6 14 x In

thermal withstand MA220 MA150

100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05


reflex tripping : t < 10 ms

Im = 9 14 x In

.02 .01 .005 .002 .001 .5 .7 1

reflex tripping : t < 10 ms

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / In

20 30

50 70 100

200 300

STR22ME electronic trip units


STR22ME - 10220 A
E28370

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
I = 15 x In reflex tripping : t < 10 ms Im = 13 x Ir class 10 (IEC 60947-4) Ir

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

Schneider Electric

259

Additional characteristics

Tripping curves Compact NS400 to 630 Protection of distribution systems

STR23 and STR53 electronic trip units


STR23SE / STR23SV
E28461

STR53UE / STR53SV
10 000 5 000 2 000
Ir = 0.41 x In
E94513

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
I = 11 x In
reflex tripping t < 10 ms Isd = 210 x Ir Ir = 0.41 x In

1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
l 2 t OFF

tr = 0.516 s Ii = 1.511 x In

Isd = 1.510 x Ir

l 2 t OFF

0.3 0.2 0.1 0

reflex tripping : t < 10 ms

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20

5 7 10

20 30 I / In

50

Options for STR53UE


Earth-fault protection
E28371

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .05 .07 .1
I2t OFF
0.4 0.3 0.2 0.1

Ig = 0.21 x In

I2t ON

.2

.3 .4 .5 .7 1 I / In

7 10

20 30

260

Schneider Electric

Compact NS400 to 630 Motor-starter protection


MA magnetic and STR43ME electronic trip units
MA320MA500
E28468

STR43ME - 120 to 500 A - class 10 A


E28369

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
Im = 9 ... 14 x In thermal withstand

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5


Isd = 613 x Ir hot tripping curve cold tripping curve class 10 A

.2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1


Ii = 10,4 x In reflex tripping t < 10 ms

reflex tripping : t < 10 ms

3 4 5 7 10 I / In

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

STR43ME - 120 to 500 A - class 10


E38879

STR43ME - 120 to 500 A - class 20


10 000 5 000 2 000 1 000 500 200 100
class 20
E38946

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5


Isd = 613 x Ir hot tripping curve cold tripping curve class 10

50 20 10 5 t(s) 2 1 .5
Isd = 613 x Ir hot tripping curve cold tripping curve

.2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1


Ii = 10,4 x In reflex tripping t < 10 ms

.2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1


Ii = 10,4 x In reflex tripping t < 10 ms

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

Thermal-withstand capacities are given for circuit breakers operating in an ambient temperature of 65 C.
Schneider Electric

261

Additional characteristics

Tripping curves Compact NS630b to 3200

Micrologic electronic control units


Micrologic 2.0
E46350

Micrologic 5.0, 6.0, 7.0 - Micrologic 5.0A, 6.0A, 7.0A


Ir = 0,41 x In

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1

10 000 5 000 2 000 1 000 500 200

E46276

Ir = 0,41 x In

tr = 0,5...24 s

100 50 20 10 5 t(s)

tr = 0,524 s

Isd = 1,510 x Ir

2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1


0,4 0,3
0,2

Isd = 1,510 x Ir I2t ON


0,4 0,3
0,2

0,1 0

I t OFF

0,1 0

Ii = 215 x In . OFF

3 4 5 7 10 I / Ir

20 30

50 70 100

200 300

3 4 5 7 10 x Ir

20

7 10 x In

20 30

Options for Micrologic electronic control units


Earth-fault protection (Micrologic 6.0)
E46266

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .05.07 .1
I2t
0.4 0.3 0.2 0.1 0 0.4 0.3 0.2 0.1 0

Ig = AJ x In (1) 1200 A max.

I2t ON

OFF

(1)

Ig = In x
.2 .3 .4 .5 .7 1 I / In 2 3 5 7 10 200 300
Ig < 400 A 400 A y Ig y 1200 A Ig > 1200 A

A
0.3 0.2 500

B
0.3 0.3 640

C
0.4 0.4 720

D
0.5 0.5 800

E
0.6 0.6 880

F
0.7 0.7 960

0.8 0.9 1 0.8 0.9 1 1040 1120 1200

262

Schneider Electric

Reflex tripping

Compact NS100 to 630 devices incorporate the exclusive reflex-tripping system. This system breaks very high fault currents by mechanically tripping the device via a "piston" actuated directly by the pressure produced in the breaking units resulting from a short-circuit. For high short-circuits, this system provides a faster break and a trip guarantee, as well as natural total discrimination. Reflex-tripping curves are exclusively a function of the circuit-breaker rating.

E28463

TM160D...TM250D STR22SE250

20

NS630
STR22SE160

NS400 NS250
10 8 t (ms) 7 6 5 4
TM160D

TM16D...TM100D STR22SE40... 100

NS100-NS160

3 2 3 4 6 10 20 30 40 60 100 200

kA rms

Schneider Electric

263

Additional characteristics

Current-limiting curves

The limiting capacity of a circuit breaker is its aptitude to limit short-circuit currents.
E28800

Ics = 100 % Icu


The exceptional limiting capacity of the Compact NS range greatly reduces the forces created by fault currents in devices. The result is a major increase in breaking performance. In particular, the service breaking capacity Ics is equal to 100% of Icu. The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising the following operations: b break three times consecutively a fault current equal to 100 % of Icu b check that the device continues to function normally: v it conducts the rated current without abnormal temperature rise v protection functions perform within the limits specified by the standard v suitability for isolation is not impaired.

Isc prospective Isc peak prospective current prospective Isc limited Isc peak limited Isc tc actual current

Longer service life of electrical installations


Current-limiting circuit breakers greatly reduce the negative effects of short-circuits on installations. Thermal effects Less temperature rise in conductors, therefore longer service life for cables. Mechanical effects Reduced electrodynamic forces, therefore less risk of electrical contacts or bus bars being deformed or broken. Electromagnetic effects Less disturbances for measuring devices located near electrical circuits.

The exceptional limiting capacity of the Compact NS range is due to the rotating double-break technique (very rapid natural repulsion of contacts and the appearance of two arc voltages in-series with a very steep wave front).

Economy by means of cascading


Cascading is a technique directly derived from current limiting. Circuit breakers with breaking capacities less than the prospective short-circuit current may be installed downstream of a limiting circuit breaker. The breaking capacity is reinforced by the limiting capacity of the upstream device. It follows that substantial savings can be made on downstream equipment and enclosures.

Current-limiting curves
The current-limiting capacity of a circuit breaker is expressed by two curves which are a function of the prospective short-circuit current (the current which would flow if no protection devices were installed): b the actual peak current (limited current), b thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor with a resistance of 1 . Example What is the real value of a 150 kA rms prospective short-circuit (i.e. 330 kA peak) limited by an NS250L upstream ? Answer: 30 kA peak (see next page).

Maximum permissible cable stresses


The table below indicates the maximum permissible thermal stresses for cables depending on their insulation, conductor (Cu or Al) and their cross-sectional area (CSA). CSA values are given in mm2 and thermal stresses in A2s.
CSA (mm2) PVC Cu Al PRC Cu Al CSA (mm2) PVC Cu Al PRC Cu Al 1.5 2.97 x 104 4.10 x 104 16 3.4 x 106 1.39 x 106 4.69 x 106 1.93 x 106 2.5 8.26 x 104 1.39 x 105 25 8.26 x 106 3.38 x 106 1.39 x 107 4.70 x 106 4 2.12 x 105 2.92 x 105 35 1.62 x 107 6.64 x 106 2.23 x 107 9.23 x 106 6 4.76 x 105 6.56 x 105 50 3.31 x 107 1.35 x 107 4.56 x 107 1.88 x 107 10 1.32 x 106 5.41 x 105 1.82 x 106 7.52 x 105

Example Is a Cu/PVC cable with a CSA of 10 mm2 adequately protected by an NS160N? The table above indicates that the permissible stress is 1.32x106 A2s. All short-circuit currents at the point where an NS160N (Icu = 35 kA) is installed are limited with a thermal stress less than 6 x 105 A2s (see next page). Cable protection is therefore ensured up to the limit of the breaking capacity of the circuit breaker.

264

Schneider Electric

Current-limiting curves
Voltage 380/415 V AC
E58557 E90272

Voltage 660/690 V AC
300
NS1600bN NS2000N NS2500N NS3200N NS630bN NS800N NS1000N NS1250N NS1600N NS630bL NS800L NS1000L

300
NS630bH NS800H NS1000H NS1250H NS1600H NS630bL NS800L NS1000L NS630 NS400 L H N N NS250 NS160 NS100
TM32...250 TM25 TM16

200

100 80 70 60 50 kA peak40 30 20

NS630bN NS800N NS1000N NS1250N NS1600N

200 146 100 80 70 60 50 kA peak 40 30 20


N NH

NS630bH NS800H NS1000H NS1250H NS1600H

H N

NS630

NS400
TC150/250/400

NS100 NS250 NS160


TM 16 TM40100 TM 25

10 8 7 6 5 4

N NSA160

10

20

30 40

60

100

200 300

10 8 7 6 5 4

10

20

30 40

kA rms

kA rms

60 65

100

200 300

Thermal-stress curves
Voltage 380/415 V AC
E58556 E90271

Voltage 660/690 V AC
10 5
NS630bH NS800H NS1000H NS1250H NS1600H
9

10 5 3 2 10 5 3 2 10 As 5 3 2 10 5 3 2 10 5 3 2
2

NS630bN NS800N NS1000N NS1250N NS1600N

3 2 1,41 8 10 5 3 2
NS630bN NS800N NS1000N NS1250N NS1600N
7

NS1600bN NS2000N NS2500N NS3200N

NS630bH NS800H NS1000H NS1250H NS1600H

N N
6

H H

NS1000L NS630bL L NS800L NS630 L NS400 L


NS250 NS160 NS100
TM32250

10 As 5 3 2 10 5 3 2 10 5 3 2
2

H N N H N H L

NS630bL NS800L NS1000L NS630 L

L NS400
TC150/250/400

NS250 NS160

NS100
TM 40100

N E N NSA160
5

TM 25 TM 16

TM25

TM16

10

20

30 40

60

100 150 200 300

10

20

30 40

kA rms

kA rms

60 65

100 150 200 300

Schneider Electric

265

Schneider Electric

550E5100.fm/17

Compact NS

Complementary technical information

Cascading Cascading, network 220/240 V Cascading, network 380/415 V Cascading, network 440 V Motor protection cascading Cascading for installations with several transformers in parallel Protections discrimination Motor protection discrimination Cascading and enhanced discrimination Protection of motor circuits
Circuit breaker/contactor coordination Using the circuit breaker/contactor coordination tables

2 4 7 10 12 14 15 97 106 117
117, 125 122

Type coordination 2 Type coordination 1 Use of LV switches


Switch-disconnectors protection

127 148 152


156

Protection of LV/LV transformers Coordination tables between Merlin/Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Cascading and reinforced discrimination

164

167
182

Schneider Electric

Complementary technical information

Cascading

Summary
Application Distribution cascading Network 220/240 V 380/415 V 440 V Motor protection cascading 220/240 V 380/415 V 440 V Upstream device Compact NS Compact NS and Masterpact Compact NS Compact NS and Masterpact Compact NS Compact NS and Masterpact Compact NS Compact NS Compact NS Downstream device Compact and Multi 9 Compact and Multi 9 Compact and Multi 9 Compact and Multi 9 Compact and Multi 9 Compact NS Compact NS, Integral, GVM Compact NS, Integral, GVM Compact NS, Integral Tableau page 4 6 7 9 10 11 12 12 13 14

Cascading for installations with 2 or 3 transformers in parallel

What is cascading?
Cascading is the use of the current limiting capacity of circuit breakers at a given point to permit installation of lower-rated and therefore lower-cost circuit breakers downstream. The upstream Compact circuit breakers acts as a barrier against short-circuit currents. In this way, downstream circuit breakers with lower breaking capacities than the prospective short-circuit (at their point of installation) operate under their normal breaking conditions. Since the current is limited throughout the circuit controlled by the limiting circuit breaker, cascading applies to all switchgear downstream. It is not restricted to two consecutive devices.

General use of cascading


With cascading, the devices can be installed in different switchboards. Thus, in general, cascading refers to any combination of circuit breakers where a circuit breaker with a breaking capacity less than the prospective Isc at its point of installation can be used. Of course, the breaking capacity of the upstream circuit breaker must be greater than or equal to the prospective short-circuit current at its point of installation. The combination of two circuit breakers in cascading configuration is covered by the following standards: b IEC 60947-2 (construction) b NF C 15-100, 434.3.1 (installation).

Coordination between circuit breakers


The use of a protective device possessing a breaking capacity less than the prospective short-circuit current at its installation point is permitted as long as another device is installed upstream with at least the necessary breaking capacity. In this case, the characteristics of the two devices must be coordinated in such a way that the energy let through by the upstream device is not more than that which can be withstood by the downstream device and the cables protected by these devices without damage. Cascading can only be checked by laboratory tests and the possible combinations can be specified only by the circuit breaker manufacturer.

Cascading and protection discrimination


In cascading configurations, due to the Roto-active breaking technique, discrimination is maintained and , in some cases, even enhanced. Consult the enhanced discrimination tables on pages 82 to 90 for data on discrimination limits

Cascading tables
Merlin Gerin cascading tables are: b drawn up on the basis of calculations (comparison between the energy limited by the upstream device and the maximum permissible thermal stress for the downstream device) b verified experimentally in accordance with IEC standard 60947-2. For distribution systems with 220/240 V, 400/415 V and 440 V between phases, the tables of the following pages indicate cascading possibilities between upstream Compact and downstream Multi 9 and Compact circuit breakers as well as between upstream Masterpact and downstream Compact circuit breakers.

Schneider Electric

Complementary technical information

Cascading

220/240 V network downstream from a 380/415 V network


For 1P + N or 2P circuit breakers connected between the phase and neutral on a 380/415 V network, with a TT or TNS neutral system, consult the 220/240 V cascading table to determinate cascading possibilities between upstream and downstream circuit breakers.

E88004

E45057

N 1 2 3

E88005

For 1P circuit breakers connected to one phase of a 380/415 V network used together with the neutral to supply a single-phase circuit, consult the cascading tables for 380/415 V networks to determine the cascading possibilities between upstream and downstream circuit breakers.

E45030

A Isc = 80 kA NS250L 220 A B Isc = 50 kA NS100N 63 A C Isc = 24 kA C60N 25 A

Example of three level cascading


Consider three circuit breakers A, B and C connected in series. The criteria for cascading are fulfilled in the following two cases: b the upstream device A is coordinated for cascading with both devices B and C (even if the cascading criteria are not fulfilled between B and C). It is simply necessary to check that the combinations A + B and A + C have the required breaking capacity b each pair of successive devices is coordinated, i.e. A with B and B with C (even if the cascading criteria are not fulfilled between A and C). It is simply necessary to check that the combinations A + B and B + C have the required breaking capacity. The upstream breaker A is a NS250L (breaking capacity 150 kA) for a prospective lsc of 80 kA across its output terminals. A NS100N (breaking capacity 25 kA) can be used for circuit breaker B for a prospective lsc of 50 kA across its output terminals, since the "reinforced" breaking capacity provided by cascading with the upstream NS250L is 150 kA. A C60N (breaking capacity 10 kA) can be used for circuit breaker C for a prospective lsc of 24 kA across its output terminals since the "reinforced" breaking capacity provided by cascading with the upstream NS250L is 30 kA. Note that the "reinforced" breaking capacity of the C60N with the NS100N upstream is only 25 kA, but: b A + B = 150 kA b A + C = 30 kA.

Schneider Electric

Complementary technical information

Cascading, network 220/240 V Upstream: Compact NS Downstream: Compact and Multi 9


NSA160N NS100N NS100H 100 40 50 15 80 100 100 100 100 100 40 100 100 70 100 50 50 50 70 85 NS100L 150 40 50 15 80 100 100 100 100 100 40 100 100 100 150 150 70 70 70 85 100 150 150 100 150 150 NS160NE 85 40 50 30 40 50 65 65 65 40 85 65 65 85 40 40 40 60 85 85 50 85 100 100 85 NS160N 85 40 50 30 40 50 65 65 65 40 85 65 65 85 40 40 40 60 85 85 85 NS160H 100 40 50 40 60 80 80 80 80 40 100 100 70 100 50 50 50 70 85 100 100 100 100 100 NS160L 150 40 50 40 60 80 80 80 80 40 100 100 100 150 150 70 70 70 85 100 150 100 150 100 150 150 150 150 150

Upstream Breaking capacity kA rms Downstream C32 C32 DPN/DPNN C60a C60N C60H C60L y 25 A C60L y 40 A C60L y 63 A XC/SC40 PM25 u 14 A NC100H/NC125H NC100L NC100LS NC100LH/LMA C120N C120H NG125a NG125N NG125H NG125L/LMA NSA160N NS80HMA NSC100N NS100N NS100H NS160NE NS160N NS160H

NSC100N

42 50 85 Breaking capacity (kA rms) 40 40 40 42 50 50 15 15 15 30 30 30 40 40 40 42 50 50 65 42 50 65 42 50 65 40 40 85 42 50 65 65 85 42 42 40 40 40 40 40 40 40 60 85

Upstream Breaking capacity kA rms Downstream C32 C32 C60a C60N C60H C60L y 25 A C60L y 40 A C60L y 63 A XC/SC40 PM25 u 14 A NC100H/NC125H NC100L NC100LS NC100LH/LMA C120N/H NG125a NG125N NG125H NG125L/LMA NSA160N NS80HMA NSC100N NS100N NS100H NS160NE NS160N NS160H NS250N NS250H NS400N NS400H NS630N NS630H

NS250N

NS250H

NS250L

NS400N 85

NS400H 100

NS400L 150

NS630N 85

NS630H 100

NS630L 150

85 100 150 Breaking capacity (kA rm 40 40 40 42 50 50 30 40 40 40 60 60 50 65 65 65 80 80 65 80 80 50 65 65 40 40 40 65 65 85 40 40 60 85 85 85 100 70 100 50 50 70 85 100 100 100 100 100 100 100 100 150 150 70 70 85 100 150 100 150 100 150 150 150 150 150 150 150

85 85

100 100 100 100 100 100 100

100 150 100 150 150 150 150 150 150 150 150 150

85 85

100 100 100 100 100 100 100 100

100 150 100 150 150 150 150 150 150 150 150 150 150 150

Schneider Electric

Complementary technical information

Cascading, network 220/240 V Upstream: Compact NS Downstream: Compact and Multi 9


NSA160N NS100N NS100H 100 NS100L 150 NS160NE 85 50 50 20 20 30 NS160N 85 50 50 20 20 30 NS160H 100 60 60 30 30 40 NS160L 150 60 60 30 30 40

Upstream Breaking capacity kA rms Downstream NS125E NSA160E NB50N NB100F NB100N

NSC100N

42 50 85 Breaking capacity (kA rms) 50 50 20 20 20 20 20 20 30 30 30

30 30 40

30 30 40

Upstream Breaking capacity kA rms Downstream NS125E NSA160E NB50N NB100F NB100N NB225N NB400N NB600N

NS250N

NS250H

NS250L

NS400N 85 50 50

NS400H 100 60 60

NS400L 150 60 60

NS630N 85 50 50

NS630H 100 60 60

NS630L 150 60 60

85 100 150 Breaking capacity (kA rms) 50 60 60 50 60 60 20 30 30 20 30 30 30 40 40 50 60 60

50 50

60 60

60 60

50 50 50

60 60 60

60 60 60

Schneider Electric

Complementary technical information

Cascading, network 220/240 V Upstream: Compact NS, Masterpact Downstream: Compact NS, NB and Multi 9
NS800L NS1000L 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 Masterpact NT L1 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 Masterpact NW L1 150

Upstream Breaking capacity kA rms Downstream NS100N NS100H NS160NE NS160N NS160H NS250N NS250H NS400N NS400H NS630N NS630H NS630bN NS630bH NS800N NS800H NS1000N NS1000H NS1250N

NS630bL

150 150 Breaking capacity (kA rms) 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150

100 100 100 100 100 100

Upstream Breaking capacity kA rms Downstream NB225N NB400N NB600N

NS630bL

NS800L

NS1000L 150 60 60 60

Masterpact NT L1 150 60 60 60

Masterpact NW L1 150

150 150 Breaking capacity (kA rms) 60 50 60 50 60 50

Upstream Breaking capacity kA rms Downstream DPN/DPNN C60H C60a C60N NC100H/NC125H

NS125E

NSA160E

16 16 Breaking capacity (kA rms) 15 15 25 25 25 25 25 25 25 25

Schneider Electric

Complementary technical information

Cascading, network 380/415 V (1) Upstream: Compact NS Downstream: Compact and Multi 9
NSA160N NS100N NS100H 70 20 20 30 40 40 40 40 30 50 30 50 70 70 25 36 50 70 25 NS100L 150 20 20 30 40 40 40 40 30 50 30 70 100 150 25 70 100 150 25 150 50 150 150 NS160NE 25 15 15 25 25 25 25 25 25 25 NS160N 36 20 15 25 30 30 30 30 25 25 25 NS160H 70 20 20 30 40 40 40 40 30 30 30 50 70 70 25 36 50 70 25 50 50 70 70 70 NS160L 150 20 20 25 40 40 40 40 30 30 70 100 150 25 70 100 150 25 50 150 50 150 150 150 150 150

Upstream Breaking capacity kA rms Downstream C32 C60a C60N C60H C60L y 25 A C60L y 40 A C60L y 63 A XC/SC40 PM25 u 14 A NC100H/NC125H NC100L NC100LS NC100LH/LMA NG125a NG125N NG125H NG125L/LMA C120N/H NSA160N NS80HMA NSC100N NS100N NS100H NS160NE NS160N NS160H

NSC100N

18 30 25 Breaking capacity (kA rms) 15 15 15 15 15 15 18 25 25 18 30 25 30 30 25 30 25 18 25 25 18 25 25 18 25 25

25

25

25

25 36

18

25

25

25

25 36 36 36 36

25

50 70

25

Upstream

NS250N

NS250H

NS250L

NS400N

NS400H

NS400L

NS630N

NS630H

NS630L 150 20

Breaking capacity kA rms 36 70 150 45 70 150 45 70 Downstream Breaking capacity (kA rms) C32 15 20 20 20 20 15 20 20 C60a 15 20 20 C60N 25 30 30 C60H 30 30 30 C60L y 25 A 40 40 C60L y 40 A 30 40 40 C60L y 63 A 30 30 30 XC/SC40 25 30 30 NC100H/NC125H 25 30 30 NC100L 50 70 NC100LS 70 100 NC100LH/LMA 70 150 NG125a 25 25 25 NG125N 36 36 70 NG125H 50 100 NG125L/LMA 70 150 C120N/H 25 25 25 NSA160N 36 50 50 36 50 50 36 50 NS80HMA 150 150 NSC100N 36 50 50 45 50 50 45 50 NS100N 36 70 150 45 70 150 45 70 NS100H 150 150 NS160NE 36 70 150 45 70 150 45 70 NS160N 70 150 45 70 150 45 70 NS160H 150 150 NS250N 70 150 45 70 150 45 70 NS250H 150 150 NS400N 70 150 70 NS400H 150 NS630N 70 NS630H (1) With single pole, single pole + neutral and two pole circuit breakers, with TT or TNS systems, see cascading table for 220/240 V network.

50 150 50 150 150 150 150 150 150 150 150 150 150 150

Schneider Electric

Complementary technical information

Cascading, network 380/415 V (1) Upstream: Compact NS Downstream: Compact and Multi 9
NSA160N NS100N NS100H 70 NS100L 150 NS160NE 25 25 25 15 15 20 NS160N 36 25 25 15 15 20 NS160H 70 30 30 15 15 20 NS160L 150 30 30 15 15 20

Upstream Breaking capacity kA rms Downstream NS125E NSA160E NB50N NB100F NB100N

NSC100N

18 30 25 Breaking capacity (kA rms)

15 15 18

15 15 20

15 15 20

15 15 20

Upstream

NS250N

NS250H

NS250L

NS400N

NS400H

NS400L

NS630N

NS630H

NS630L 150 30 30

Breaking capacity kA rms 36 70 150 45 70 150 45 70 Downstream Breaking capacity (kA rms) NS125E 25 30 30 25 30 30 25 30 NSA160E 25 30 30 25 30 30 25 30 NB50N 15 15 15 NB100F 15 15 15 NB100N 20 20 20 NB225N 25 50 50 25 50 50 25 50 NB400N 36 50 50 36 50 NB600N 36 50 (1) With single pole, single pole + neutral and two pole circuit breakers, with TT or TNS systems, see cascading table for 220/240 V network.

50 50 50

Schneider Electric

Complementary technical information

Cascading, network 380/415 V (1) Upstream: Compact NS, Masterpact Downstream: Compact and Multi 9
NS800H 70 70 70 70 70 70 70 70 70 NS800L 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 NS1000H 70 70 70 70 70 70 70 70 70 70 NS1000L 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 NS1250H 70 70 70 70 70 70 70 70 70 70 70 NS1600H 70 70 70 70 70 70 70 70 70 70 70 Masterpact Masterpact NT L1 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 NW L1 150

Upstream kA rms Downstream NS100N NS100H NS160NE NS160N NS160H NS250N NS250H NS400N NS400H NS630N NS630H NS630bN NS630bH NS800N NS800H NS1000N NS1000H NS1250N

NS630bN

NS630bH

NS630bL

Breaking capacity to NS1600N 50 70 150 Breaking capacity (kA rms) 50 70 150 150 50 70 150 50 70 150 150 50 70 150 150 50 70 150 150 50 70 150 150

100 100 100 100 100 100

Upstream kA rms Downstream NB225N NB400N NB600N

NS630bN

NS630bH

NS630bL

NS800H 70 50 50 50

NS800L 150 50 50 50

NS1000H 70 50 50 50

NS1000L 150 50 50 50

NS1250H 70 50 50 50

NS1600N NS1600H 50/70 50 50 50

Masterpact Masterpact NT L1 150 60 60 60 NW L1 150

Breaking capacity to NS1250N 50 70 150 Breaking capacity (kA rms) 25 50 50 36 50 50 36 50 50

Upstream

NS125E

NSA160E

Breaking capacity kA rms 16 16 Downstream Breaking capacity (kA rms) C60a 15 15 C60N 16 16 C60H 16 16 XC/SC40 16 16 PM25 u 14 A 16 16 NC100H/NC125H 16 16 (1) With single pole, single pole + neutral and two pole circuit breakers, with TT or TNS systems, see cascading table for 220/240 V network.

Schneider Electric

Complementary technical information

Cascading, network 440 V Upstream: Compact NS Downstream: Compact and Multi 9


NS100H NS100L NS160NE 25 NS160N 25 NS160H 65 50 65 65 25 35 35 35 50 65 65 65 NS160L 130 70 100 130 150 50 130 130 130 130 130

Upstream Breaking capacity kA rms Downstream NC100L NC100LS NC100LH/LMA NS80HMA NSC100N NS100N NS100H NS160NE NS160N NS160H

NS100N

25 65 130 Breaking capacity (kA rms) 50 70 65 100 65 130 150 25 50 50 65 130 130

Upstream Breaking capacity kA rms Downstream NC100L NC100LS NC100LH/LMA NS80HMA NSC100N NS100N NS100H NS160NE NS160N NS160H NS250N NS250H NS400N NS400H NS630N NS630H

NS250N

NS250H

NS250L

NS400N 42

NS400H 65

NS400L 130

NS630N 42

NS630H 65

NS630L 130

35 65 130 Breaking capacity (kA rms) 50 70 65 100 65 130 150 35 50 50 35 65 130 130 35 65 130 65 130 130 65 130 130

42 42 42 42 42

50 65 65 65 65 65

150 50 130 130 130 130 130 130 130 130 130

42 42 42 42 42

50 65 65 65 65 65 65

150 50 130 130 130 130 130 130 130 130 130 130 130

10

Schneider Electric

Complementary technical information

Cascading, network 440 V Upstream: Compact NS, Masterpact Downstream: Compact NS


NS800H NS800L 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 NS1000N NS1000H NS1000L NS1250N NS1250H NS1600H Masterpact NT L1 NW L1 150 50 50 50 50 50 50 50 65 65 65 65 65 65 65 65 65 65 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 50 50 50 50 50 50 50 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 150 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Upstream Breaking capacity kA rms Downstream NS100N NS100H NS160NE NS160N NS160H NS250N NS250H NS400N NS400H NS630N NS630H NS630bN NS630bH NS800N NS800H NS1000N NS1000H NS1250N

NS630bL NS800N

130 50 65 Breaking capacity (kA rms) 130 50 65 130 130 50 65 130 50 65 130 130 50 65 130 130 50 65 130 130 50 65 130 65 65

65 65 65 65

Schneider Electric

11

Complementary technical information

Protection discrimination Upstream: Compact NS Downstream: Compact NS, Integral and GVM
NS100H NS100L NS160N 85 NS160H 100 NS160L 150 150 150 150 150 150 100 150 150 150 NS630H 100 NS630L 150 150 150 150 150 150 150 150 150 150 150 150

Network 220/240 V
Upstream Breaking capacity kA rms Downstream NS80HMA NS100N NS100H NS160N NS160H GV2M u 23 A Integral 18 u 10 A Integral 32 u 25 A Integral 63 u 32 A Upstream Breaking capacity kA rms Downstream NS80HMA NS100N NS100H NS160N NS160H NS250N NS250H NS400N NS400H NS630N NS630H Integral 18 u 10 A Integral 32 u 25 A Integral 63 u 32 A NS100N 85 100 150 Breaking capacity (kA rms) 150 100 150 150

100 100

85 85 85 85 NS250N

100 100 100 100 NS250H

100 150 150 150 NS250L

85 85 85 85 NS400H 100

100 100 100 100 NS400L 150 150 150 150 150 150 150 150 150 150

85 100 150 Breaking capacity (kA rms) 150 100 150 150 100 150 150 100 150 150

100 100 100 100

100 100 100 100 100

85 85 85

100 100 100

150 150 150

150

Network 380/415 V
Upstream Breaking capacity kA rms Downstream NS80HMA NS100N NS100H NS160N NS160H GV2M u 14 A GV2L u 18 A GV2P u 18 A GV3M Integral 18 u 10 A Integral 32 u 25 A Integral 63 u 32 A Upstream Breaking capacity kA rms Downstream NS80HMA NS100N NS100H NS160N NS160H NS250N NS250H NS400N NS400H NS630N NS630H GV3M Integral 18 u 10 A Integral 32 u 25 A Integral 63 u 32 A Upstream Breaking capacity kA rms Downstream GV2M u 14 A NSC100N NSA160N NS100N NS100H 70 NS100L 150 150 150 150 NS160N 36 NS160H 70 NS160L 150 150 150 150 150 150 18 30 25 Breaking capacity (kA rms)

70

36

70 70

18

30

25

50 70 70 70 70 70 70 NS400N 45

50 150 150 150 150 150 150 NS400H 70

70 70 70 70 NS400L 150 150 150 150 150 150 150 150 150 150

150 150 150 150 NS630N 45

150 150 150 150 NS630H 70 NS630L 150 150 150 150 150 150 150 150 150 150 150 150

NS250N

NS250H

NS250L

36 70 150 Breaking capacity (kA rms) 150 36 70 150 150 70 150 150 70 150 150

45 45 45

70 70 70 70

45 45 45

70 70 70 70 70

70 70 70 70 NS125E NSA160E

150 150 150 150

70

150

16 16 Breaking capacity (kA rms) 16 16

12

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Compact NS Downstream: Compact NS,Integral

Network 440 V
Upstream Breaking capacity kA rms Downstream NS80HMA NS100N NS100H NS160N NS160H Integral 32 u 16 A Integral 63 u 25 A NS100N NS100H NS100L NS160NE 25 NS160N 25 NS160H 65 NS160L 130 150 130 130 130 130 130 130 25 65 130 Breaking capacity (kA rms) 150 65 130 130

35

65 65

65 65

130 130

65 65

Upstream Breaking capacity kA rms Downstream NS80HMA NS100N NS100H NS160N NS160H NS250N NS250H NS400N NS400H NS630N NS630H Integral 32 u 16 A Integral 63 u 25 A

NS250N

NS250H

NS250L

NS400N 42

NS400H 65

NS400L 130 150 130 130 130 130 130 130 130 130

NS630N 42

NS630H 65

NS630L 130 150 130 130 130 130 130 130 130 130 130 130

35 65 130 Breaking capacity (kA rms) 150 35 65 130 130 65 130 130 65 130 130

42 42 42

65 65 65 65

42 42 42

65 65 65 65 65

65 65

130 130

65

130

Schneider Electric

13

Complementary technical information

Cascading for installations with several transformers in parallel


The following table indicates the types of circuit breakers to be installed on the source feeders and main feeders of an installation with 2 or 3 transformers connected in parallel (1). The following assumptions are made: b upstream network short-circuit power of 500 MVA b the transformers are all identical, 20 kV/410 V and with a normal short-circuit voltage level b the short-circuit current on the busbars does not take into account the connection impedances (the worst case) b the equipment is installed in a switchboard with an ambient temperature of 30 C b to connect several transformers in parallel, the transformers must have: v the same Usc v the same transformation ratio v the same type of connection v a maximum power ratio of 2 between any two of the transformers v Isc is given only as a general indication and may vary depending on the percent Usc values given by the transformer manufacturers; the values for breaking capacities reinforced by cascading are therefore given for higher values.

Installations with 2 transformers in parallel


E45068

D1

D2

D4

Icc

Example: Consider 2 parallel 800 kVA transformers. The source protection devices are two C125N circuit breakers equipped with STR25DE trip units set at 1250 A. The installation has two feeders rated 125 A and 630 A respectively. Isc max downstream of CB4 is 49600 A. The 630 A feeder will be protected by a NS630N circuit breaker (a breaking capacity of 50 kA with cascading). The 125 A feeder will be equipped with a NS160H circuit breaker as cascading is not possible with an NS160N.

Transformer rating (kVA) Icc maxi upstream from D4 Nominal transformer current (kVA) Circuit breaker D1 or D2 Breaking capacity (kA) Circuit breaker D4 NS100N NS160N NS250N NS400N NS630N NS800N NS1000N

250 17600 352 NS400N

315 22200 444 NS630N

400 28200 564 NS630N

500 35200 704 NS800N 50

500 35200 704 NS800H 70

630 44400 887 NS1000N 50

630 44400 887 NS1000H 70

800 37500 1126 NS1250N 50

800 37500 1126 NS1250H 70

45 45 45 Reinforced breaking capacity (kA) 45 45 45 45 45 45 45 45 45

50 50 50 50

50 70 70 70

50 50 50

50 70 70 70

50 50

70 70 70 70

E45069

Installations with 3 transformers in parallel

D1

D2

D3

D4

Isc

Transformer rating (kVA) Icc maxi downstream form D4 Nominal transformer current (kVA) Circuit breaker D1 or D2 Breaking capacity (kA) Circuit breaker D4 NS160N NS250N NS400N NS630N NS800N NS1000N

250 26400 352 NS400N

315 33300 444 NS630N

400 42300 564 NS630H

500 52800 704 NS800N 50

500 52800 704 NS800H 70

630 66600 887 NS1000N 50

630 66600 887 NS1000H 70

800 56300 1126 NS1250N 50

800 56300 1126 NS1250H 70

45 45 70 Reinforced breaking capacity (kA) 45 45 45 45 45 45 70

50 50

70 70

50 50

50 50 70

50 50

50 50 70 70

14

Schneider Electric

Complementary technical information

Protection discrimination

Contents
Using the tables Two circuit breakers offer total discrimination when the corresponding box in the discrimination table is shaded or contains the letter T. When discrimination is partial for the combination, the corresponding box indicates the maximum value of the fault current for which discrimination is provided. For fault currents above this value, the two circuit breakers trip simultaneously.
Application Discrimination: distribution circuit-breakers Upstream device C60 B curve C curve B, C curves D, K curves B curve C curve B, C, D curves D curve Downstream device Table page 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 38 44 47 50 53 56 58 60 62 64 66 68 72 76 80 84 87 90 92 95 97 98 100 102 104 105 106 107 108 110 111 112 113 114 115

Discriminination: motor protection

Discriminination reinforced by cascading distribution circuit-breakers

Discriminination reinforced by cascading motor protection

C60 C60 DPN, TC16, SC-XC40 C60 NC100, NC125 C60 C60 NC100 DPN, TC16, SC-XC40 C60 C60L C60L NC100,NC125 B, C curves NC100 NC100 D curve NC100 B, C curves C60 and C45 NSC100N, NSA160, NS125E Multi 9 NSA160 Compact NS100 to 630 Multi 9 Compact NS100 to 630 Compact NS630b to 3200 Multi 9, Compact NS100 to 250 Compact NS400 to 630 Compact NS630b to 3200 Compact C801 to C1251, CM Compact C, CM Multi 9, Compact NS100 to 250 Multi 9, Compact NS400 to 630 Compact C, CM, Masterpact Masterpact NT Multi 9, Compact NS100 to 250 Compact NS400 to 630 Compact C801 to C1251, Masterpact Masterpact NW Multi 9, Compact NS100 to 630 Compact NS630b to 3200 Compact C801 to 1001, CM Masterpact NT, NW, Masterpact Masterpact Multi 9, Compact NS100 to 630 Compact NS630b to 3200 Masterpact NT, NW Compact C, CM, Masterpact Masterpact NT, NW Compact NSC100N GV2, Integral 18, 32 Compact NS100 to 630 GV2, GV3 Integral 18, 32, 63 Multi 9, Compact NS80HMA Compact NS100 to 1600 NS100 to 630 Compact NS1600, Masterpact NT, NW NS630 to 1250 Compact NS100 to 1600 Multi 9, Integral, GV2, NS100 to 630 NSC100N, NSA160 Multi 9 Compact NS160 to 250 Multi 9 Compact NS250 to 630b NSA160N, NSC100N, NS100 to 250 Compact NS800 to 1600 NSA160N, NSC100N, NS100 to 630 Compact NS160 to 400 Integral 18 to 63 Compact NS160 GV2 M GV2 P GV2 L

Schneider Electric

15

Complementary technical information

Protection discrimination

Protection discrimination is an essential element that must be taken into account starting at the design stage of a low voltage installation to ensure the highest level of availability for users. Discrimination is important in all installations for the comfort of users, however it is fundamental in installations requiring a high level of service continuity, e.g. industrial manufacturing processes. Industrial installations without discrimination run a series of risks of varying importance including: b production deadline overruns b interruption in manufacturing, entailing: v production or finished-product losses v risk of damage to production machines in continuous processes b restarting of machines, one by one, following a general power outage b shutdown of vital safety equipment such as lubrification pumps, smoke fans, etc.

E26366

What is discrimination?
D1

D2

Discrimination, also called selectivity, is the coordination of automatic protection devices in such a manner that a fault appearing at a given point in a network is cleared by the protection device installed immediately upstream of the fault, and by that device alone. b total discrimination Discrimination is said to be total if, for all fault current values, from overloads up to the non-resistive short-circuit current, circuit breaker D2 opens and D1 remains closed. b partial discrimination Discrimination is partial if the above condition is not respected up to the full shortcircuit current, but only to a lesser value termed the selectivity limit current (Is). b no discrimination In the event of a fault, both circuit breakers D1 and D2 open.

Total discrimination as standard with the new Masterpact NT/NW circuit breakers
Thanks to their highly innovative design and the exeptional performance of their control units, the new Masterpact NT and NW circuit breakers offer total discrimination with downstream Compact NS devices up to 630 A as standard (1).

Natural discrimination with Compact NS circuit breakers


Due to the Roto-active breaking technique employed by the Compact NS, the combined use of Merlin Gerin circuit breakers provides an exceptional level of protection discrimination. This is the result of the implementation and optimisation of three different techniques: b current discrimination b time discrimination b energy discrimination.
Overload protection: current discrimination Discrimination is ensured if the ratio between setting thresholds is greater than 1.6 (for distribution circuit breakers). Low short-circuit protection: current discrimination Tripping of the upstream device is slightly delayed to ensure that the downstream device trips first. Discrimination is ensured if the ratio between the short-circuit thresholds is greater than 1.5. High short-circuit protection: time discrimination

NS100 NS250 100A 250A


E26406

10 000 5 000 2 000 1 000 500 200 100 50 20 10 5

t(s)
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1

This protection system combines the exceptional current limiting capacity of the Compact NS and the advantages of reflex tripping, sensitive to the energy dissipated in the device by the short-circuit. In the event of a high short-circuit detected by two circuit breakers, the downstream device limits it sharply. The energy dissipated in the upstream device is not sufficient to trip it, i.e. discrimination is total for all short-circuit currents. Discrimination is ensured if the ratio between the circuit breaker ratings is greater than 2.
2 3 4 5 7 10 20 30 50 70 100 200 300

I / Ir

(1) Except for the L1 performance level on Masterpact NT and subject to the discrimination rules on page 17.
Schneider Electric

16

Complementary technical information

Protection discrimination

E34281

How to use the discrimination tables


D1

D2

Discrimination between two distribution circuit breakers.


E34282

b for discrimination between 2 distribution circuit breakers Combinations providing total discrimination are indicated by coloured zones or the symbol T on a coloured background. If discrimination is partial, the table indicates the maximum fault current value for which discrimination is ensured. For fault currents above this value, the 2 circuit breakers trip simultaneously. b for discrimination between a circuit breaker and a motor control and protection assembly If discrimination is partial, the table indicates the maximum fault current value for which discrimination is ensured. For fault currents above this value, the 2 devices trip simultaneously.

D1

D2

Discrimination between circuit breakers used for motor protection.

Requisite conditions
The values indicated in the tables (for 220, 380, 415 and 440 V) are guaranteed if the following conditions are respected:

D1

Application

D2

Ratio between upstream and downstream settings Thermal protection Magnetic protection

Ir up/ Ir down Im up/ Im down TMD Distribution TMD or Multi9 u 1.6 u2 STRSE/GE u 1.6 u 1.5 Motor MA + separate therm. relay u3 u2 Thermal-magnetic motor type u3 u2 STRME u3 u 1.5 STR2.. or 3.. Distribution TMD or Multi9 u 2.5 u 1.5 fixed long time delay STRSE/GE u 1.6 u 1.5 Motor MA + separate therm. relay u3 u 1.5 Thermal-magnetic motor type u3 u 1.5 STRME u3 u 1.5 Micrologic 2/5/6/7.0 Distribution TMD or Multi9 u 1.6 u 1.5 STR5.. or 6.. STRSE/GE Micrologic 2/5/6/7.0 u 1.2 u 1.5 with adjustable long time Motor MA + separate therm. relay u3 u 1.5 delay (1) Thermal-magnetic motor type u3 u 1.5 STRME, Micrologic 2/5/6/7.0 u3 u 1.5 (1) When upstream and / or downstream control units have adjustable long time delays, adjustement must be such as upstream delay is longer than downstream delay (1 step difference).

Schneider Electric

17

Complementary technical information

Protection discrimination Upstream: C60 B curve Downstream: C60

Upstream C60a, N, H, L B curve Downstream C60a, N, H, L B curve In (A) (A) 0.5 0.75 1 2 3 4 6 10 16 20 25 32 40 (A) 0.5 0.75 1 2 3 4 6 10 16 20 (A) 0.5 0.75 1 2 3 4 6 10 16 2 8 3 12 4 16 6 24 10 40 16 64 20 80 25 100 32 128 40 160 50 200 63 252

C60a, N, H, L C curve

12

16

24

40

64

80

100

128

160

200

252

C60N, H D curve C60L K curve

12

16

24

40

64

80

100

128

160

200

252

Discrimination zone

18

Schneider Electric

Complementary technical information

Protection discrimination Upstream: C60 C curve Downstream: C60

Upstream Downstream C60a, N, H, L B curve In (A) (A) 0.5 0.75 1 2 3 4 6 10 16 20 25 32 40 50 (A) 0.5 0.75 1 2 3 4 6 10 16 20 25 32 (A) 0.5 0.75 1 1.6 2 3 4 6 10 16 20

C60a, N, H, L C curve 2 15 3 23 4 30 6 45 10 75 16 120 20 150 25 188 32 240 40 300 50 375 63 473

C60a, N, H, L C curve

15

23

30

45

75

120

150

188

240

300

375

473

C60, N, H D curve C60L K curve

15

23

30

45

75

120

150

188

240

300

375

473

Discrimination zone

Schneider Electric

19

Complementary technical information

Protection discrimination Upstream: C60 B, C curves Downstream: DPN, TC16, SC-XC40

Upstream Downstream DPN SC-XC40 B curve In (A) (A) 6 10 16 20 25 32 40 (A) 1 2 3 4 5 6 10 16 20 (A) 6 10 16 20 25 32 38 (A) 1 2 3 4 5 6 10 15 20 25 32

C60a, N, H, L B curve 2 3 4 6 10 40 16 64 20 80 25 100 32 128 40 160 50 200 63 252

DPN TC16 SC-XC40 C curve

12

16

24

40

64

80

100

128

160

200

252

DPN SC-XC40 B curve

75

120

150

188

240

300

375

473

DPN TC16 SC-XC40 C curve

15

23

30

45

75

120

150

188

240

300

375

473

Discrimination zone

20

Schneider Electric

Complementary technical information

Protection discrimination Upstream: C60 D, K curves Downstream: C60

Upstream Downstream C60a, N, H, L B curve In (A) (A) 0.5 0.75 1 2 3 4 6 10 16 20 25 32 40 50 (A) 0.5 0.75 1 2 3 4 6 10 16 20 25 32 40 50 (A) 0.5 / 0.75 1 1.6 2 3 4 6 10 16 20 25 32 40 Upstream Downstream DPN SX-XC40 B curve In (A) (A) 6 / 10 16 20 25 32 40 (A) 1 2 3 4 5 6 10 16 20 25 32

C60a, N, H D curve C60L K curve 2 24 3 36 4 48 6 72 10 120 16 192 20 240 25 300 32 384 40 480 50 600 63 756

C60a, N, H, L C curve

24

36

48

72

120

192

240

300

384

480

600

756

C60, N, H D curve C60L K curve

24

36

48

72

120

192

240

300

384

480

600

756

C60 D or K curves 2 3 4 6 10 120 16 192 20 240 25 300 32 384 40 480 50 600 63 756

DPN/DPN Vigi TC 16 SC-XC40 C curve

24

36

48

72

120

192

240

300

384

480

600

756

Discrimination zone
Schneider Electric

21

Complementary technical information

Protection discrimination Upstream: NC100, NC125 B curve Downstream: C60


NC125H B curve 16 64 20 80 25 100 32 128 40 160 50 200 63 252 80 320 100 400 125 500

Upstream Downstream C60a, N, H, L B curve In (A) (A) 1 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 1.6 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63

NC100H, L, LS, LH B curve 10 40

C60a, N, H, L C curve

40

64

80

100

128

160

200

252

320

400

500

C60, N, H D curve C60L K curve

40

64

80

100

128

160

200

252

320

400

500

C60L Z curve

40

64

80

100

128

160

200

252

320

400

500

Discrimination zone

22

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NC100, NC125 C curve Downstream: C60


NC125H C curve 16 120 20 150 25 188 32 240 40 300 50 375 63 473 80 600 100 750 125 1000

Upstream Downstream C60a, N, H, L B curve In (A) (A) 1 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 1.6 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 (A) 1.6 2.5 4 6.3 10 12.5 16 25/40

NC100H, L, LS, LH C curve 10 75

C60a, N, H, L C curve

75

120

150

188

240

300

375

473

600

750

1000

C60, N, H D curve C60L K curve

75

120

150

188

240

300

375

473

600

750

1000

C60L Z curve

75

120

150

188

240

300

375

473

600

750

1000

C60LMA

75

120

150

190

240

300

375

470

Schneider Electric

23

Complementary technical information

Protection discrimination Upstream: NC100 B, C, D curves Downstream: DPN, TC16, SC-XC40


NC100H, L, LS, LH C curve 20 80 25 100 32 128 40 160 50 200 63 252 80 320 100 400 10 16 120 20 150 25 188 32 240 40 300 50 375 63 473 80 600 100 750

Upstream NC100H, L, LS, LH B curve Downstream DPN SC40-XC40 B curve In (A) (A) 6 10 16 20 25 32 40 (A) 1 2 3 4 5 6 10 16 20 25 32 40 10 16 64

DPN TC16 SC40-XC40 C curve

40

64

80

100

128

160

200

252

320

400

75

120

150

188

240

300

375

473

600

750

4 5

4 5

Upstream NC100 D curve Downstream DPN SC-XC40 B curve In (A) (A) 5 10 16 20 25 32 38 (A) 1 2 3 4 5 10 16 20 25 32 40 10 20 16 192 20 240 25 300 32 384 40 480 50 600 63 756 80 960 100 1200

DPN TC16 SC-XC40 C curve

120

192

240

300

384

480

600

756

960

1200

Discrimination zone

24

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NC100 D curve Downstream: C60

Upstream NC100H, LS D curve Downstream C60a, N, H, L B curve In (A) (A) 1 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 1.6 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 (A) 1.6 2.5 4 6.3 10 12.5 16 25/40 10 120 16 192 20 240 25 300 32 384 40 480 50 600 63 756 80 960 100 1200

C60a, N, H, L C curve

120

192

240

300

384

480

600

756

960

1200

C60, N, H D curve C60L K curve

120

192

240

300

384

480

600

756

960

1200

C60L Z curve

120

192

240

300

384

480

600

756

960

1200

C60LMA

120

190

240

300

384

480

600

756

Schneider Electric

25

Complementary technical information

Protection discrimination Upstream: C60L Downstream: C60L

Upstream Downstream C60L Z curve In (A) (A) 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 Upstream Downstream C60L Z curve In (A) (A) 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 Upstream Downstream C60L Z curve In (A) (A) 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 Upstream Downstream C60L Z curve In (A) (A) 1 1.6 2 3 4 6 8 10 16 20 25 32 40/5

C60L B curve 2 8

3 12

4 16

6 24

10 40

16 64

20 80

25 100

32 128

40 160

50 200

63 240

C60L C curve 2 15

3 23

4 30

6 45

10 75

16 120

20 150

25 188

32 240

40 300

50 375

63 450

C60 K curve 2 24 3 36 4 48 6 72 10 120 16 192 20 240 25 300 32 384 40 480 50 600 63 720

C60L Z curve 1.6 2 4 8.6

3 9

4 12

6 18

8 24

10 30

16 48

20 60

25 75

32 96

40 120

50 150

63 189

26

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NC100, NC125 B, C curves Downstream: NC100


NC125H B curve 16 64 20 80 25 100 32 128 40 160 50 200 63 252 80 320 100 400 125 500

Upstream Downstream NC100H, L NC100LS, LH B curve In (A) (A) 10 16 20 25 32 40 50 63 80 100 (A) 10 16 20 25 32 40 50 63 80 100 (A) 10 16 20 25 32 40 50 63 80 100 Upstream Downstream NC100H, L NC100LS, LH B curve In (A) (A) 10 16 20 25 32 40 50 63 80 100 (A) 10 16 20 25 32 40 50 63 80 100 (A) 10 16 20 25 32 40/50 63 80/100

NC100H, L, LS, LH B curve 10 40

NC100H, L NC100LS, LH C curve

128

160

200

252

320

400

500

NC100H, L NC100LS, LH D curve

200

252

320

400

500

NC100H, L, LS, LH C curve 10 16 120 20 150 25 188 32 240 40 300 50 375 63 473 80 600 100 750

NC125H C curve 125 1000

NC100H, L NC100LS, LH C curve

150

188

240

300

375

473

600

750

1000

NC100H, L NC100LS, LH D curve

240

300

375

473

600

750

1000

Discrimination zone
Schneider Electric

27

Complementary technical information

Protection discrimination Upstream: NC100 D curve Downstream: NC100

Upstream Downstream NC100H, L NC100LS, LH B curve In (A) (A) 10 16 20 25 32 40 50 63 80 100 (A) 10 16 20 25 32 40 50 63 80 100 (A) 10 16 20 25 32 40 50 63 80 100

NC100H, L, LS, LH D curve 10 16 192 20 240 25 300 32 384 40 480 50 600 63 720 80 960 100 1200

NC100H, L NC100LS, LH C curve

192

240

300

384

480

600

720

960

1200

NC100H, L NC100LS, LH D curve

240

300

384

480

600

720

960

1200

Discrimination zone

28

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NC 100 B and C curves Downstream: C60 and C45
NC100H, L, LS, LH C curve 20 80 25 100 32 128 40 160 50 200 63 252 80 320 100 400 10 75 16 120 20 150 25 188 32 240 40 300 50 375 63 473 80 600 100 750

Upstream NC100H, L, LS, LH B curve Downstream C60N-C45N B curve Type 2 In (A) (A) 1 2 3 4 6 10 16 20 25 32 40 50 63 (A) 1 2 3 4 6 10 16 20 25 32 40 50 (A) 1 2 3 4 6 10 16 20 25 32 10 40 16 64

C60a, N, H, L C curve C45N-C60H Type 3

40

64

80

100

128

160

200

252

320

400

75

120

150

188

240

300

375

473

600

750

C60, N, H D curve C60L K curve C60H Type 4 C45AD

40

64

80

100

128

160

200

252

320

400

75

120

150

188

240

300

375

473

600

750

Discrimination zone

Schneider Electric

29

Complementary technical information

Protection discrimination Upstream: NSC100N, NSA160, NS125E Downstream: DPN, DPN N, XC40, C60, NC100
NSA160E/N 40 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 50 T T T T T T T T T 63 T T T T T T T T T T 3 3 3 3 3 70 T T T T T T T T T T T 3 3 3 3 3 3 3 T T T T T T T T T T 6 6 80 T T T T T T T T T T T 3 3 3 3 3 3 3 T T T T T T T T T T 6 6 100 16 T T T T T T T T T T T 3 3 3 3 3 3 3 T T T T T T T T T T 8 8 6 6 T T T T 8 8 6 6 T T T T 8 8 6 6 1.25 1.25 25 32 0.6 0.6 0.6 40 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 50 T T T T T T T T T T 3 3 3 3 3 63 T T T T T T T T T T 3 3 3 3 3 3 T T T T T T T T T 6 80 T T T T T T T T T T T 3 3 3 3 3 3 3 T T T T T T T T T T 6 6 NS125E Trip unit TM-D 100 125 160 80 100 125 T T T T T T T T T T T 3 3 3 3 3 3 3 T T T T T T T T T T 8 8 6 6 T T T T 8 8 6 6 T T T T 8 8 6 6 1.25 1.25 T T T T T T T T T T T 3 3 3 3 3 3 3 T T T T T T T T T T 8 8 6 6 T T T T 8 8 6 6 T T T T 8 8 6 6 1.25 1.25 1.25 T T T T T T T T T T T 3 3 3 3 3 3 3 T T T T T T T T T T 8 8 6 6 T T T T 8 8 6 6 T T T T 8 8 6 6 1.25 1.25 1.25 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Upstream NSC100N Downstream DPN B, C curves Rating (A) Setting Ir y 10 16 20 25 32 y 10 16 20 25 32 40 y 10 16 20 25 32 38 40 y 10 16 20 25 32 40 y 10 16 20 25 32 40 50 63 y 10 16 20 25 32 40 50 63 y 10 16 20 25 32 40 50 63 y 50 63 80 100 y 50 63 80 100 y 16 20 25 32 40 50 63 y 16 20 25 32 40 50 63 16 0.6 25 0.6 32 0.6 0.6 0.6

0.6 0.6

DPN N C, D curves

0.6

0.6

0.6 0.6 0.6

0.6 0.6

0.6 0.6 0.6

XC40 L-U curves

0.6

0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

3 3 3 3

0.6

0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

C60a C curve

0.6 0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

T T T T

T T T T T T T T T 6

0.6 0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

T T T T

C60N B, C, D curves

0.6 0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

T T T T

0.6

0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

T T T T

C60H C curve

0.6

0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

T T T T

T T T T 6

T T T T 6 6

T T T T 6 6

0.6

0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

T T T T

T T T T 6

T T T T 6 6

0.63 0.63 0.63 0.63 0.63 0.63

C60L B, C curves K curve Z curve

0.6

0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

T T T T

T T T T 6

T T T T 6 6

T T T T 6 6

0.6

0.6

0.6 0.6 0.6

0.6 0.6 0.6 0.6

15 15 15 15

15 15 15 15 6

15 15 15 15 6 6

0.63 0.63 0.63 0.63 0.63 0.63

NC100H B, C curves

0.63

NC100H D curve

1.25 1.25

1.25 1.25 1.25 0.63 0.8 1.25 1.25 1.25 0.8 1.25 1.25 0.8 0.6 0.6 0.6 0.6 0.6 0.6 0.6 T 15 15 T 15 15 15 T 15 15 15 8 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

NC100L NC100LS

0.6

0.6

0.6 0.6

0.6 0.6 0.6

T 15 15

T 15 15 15

T 15 15 15 8

T 15 15 15 8

NC100LH C curve

0.6

0.6

0.6 0.6

0.6 0.6 0.6

T 15 15

T 15 15 15

T 15 15 15 8

T 15 15 15 8

T T T T T T T T T T T T T T

0.6

0.6

0.6 0.6

0.6 0.6 0.6

T 15 15

T 15 15 15

T 15 15 15 8

30

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NSC100N, NSA160, NS125E Downstream: NSA160


NSA160E/N NS125E Trip unit TM-D 40 50 63 70 80 100 16 25 32 40 50 63 80 100 125 160 80 100 125

Upstream NSC100N Trip unit TM-D Downstream NSA160N Rating (A) 16 Setting Ir 16 25 32 40 50 63 80 100 125 160 25 32

1.25 1.25 1.25 0.63 0.8 1.25 1.25 0.8

1 1

Schneider Electric

31

Complementary technical information

Protection discrimination Upstream: NS100 to 250 - Trip unit TMD Downstream: DPN, DPN N, XC40, C60, NC100
NS160N/H/L Trip unit TM-D 32 0.4 0.4 0.4 40 0.5 0.5 0.5 50 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 63 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 80 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 100 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 80 T T T T T T T T T T T 4 4 4 4 4 4 4 T T T T T T T T T T T T T T T T T T T T T T T T 15 15 15 2.5 100 T T T T T T T T T T T 5 5 5 5 5 5 5 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2.5 2.5 125 T T T T T T T T T T T 5 5 5 5 5 5 5 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2.5 2.5 2.5 2.5 2.5 2.5 T T T T T T T T T T T T T T 160 T T T T T T T T T T T 5 5 5 5 5 5 5 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 T T T T T T T T T T T T T T NS250N/H/L Trip unit TM-D 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Downstream DPN B, C curves Rating (A) Setting Ir y 10 16 20 25 32 y 10 16 20 25 32 40 y 10 16 20 25 32 38 40 y 10 16 20 25 32 40 y 10 16 20 25 32 40 50 63 y 10 16 20 25 32 40 50 63 y 10 16 20 25 32 40 50 63 y 50 63 80 100 y 50 63 80 100 y 16 20 25 32 40 50 63 y 16 20 25 32 40 50 63

NS100N/H/L Trip unit TM-D 16 0.19 25 0.3 0.3

DPN N C, D curves

0.19

0.3 0.3

0.4 0.4 0.4

0.5 0.5 0.5

XC40 L-U curves

0.19

0.3 0.3

0.4 0.4 0.4

0.5 0.5 0.5 0.5

0.5 0.5 0.5 0.5

C60a C curve

0.19

0.3 0.3

0.4 0.4 0.4

0.5 0.5 0.5 0.5

0.5 0.5 0.5 0.5

C60N B, C. D curves

0.19

0.3 0.3

0.4 0.4 0.4

0.5 0.5 0.5 0.5

0.5 0.5 0.5 0.5

C60H C curve

0.19

0.3 0.3

0.4 0.4 0.4

0.5 0.5 0.5 0.5

0.5 0.5 0.5 0.5

0.5 0.5 0.5 0.5 0.5 0.5

C60L B, C curves K curve Z curve

0.19

0.3 0.3

0.4 0.4 0.4

0.5 0.5 0.5 0.5

0.5 0.5 0.5 0.5

0.5 0.5 0.5 0.5 0.5 0.5

NC100H B, C curves

NC100H D curve

0.63

0.8 0.8

2.5

2.5 2.5

NC100L NC100LS

0.4 0.4

0.5 0.5

0.5 0.5 0.5

0.5 0.5 0.5 0.5 0.5

0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63

NC100LH C curve

0.4 0.4

0.5 0.5

0.5 0.5 0.5

0.5 0.5 0.5 0.5

0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

T T T T T T T T T T T T

T T T T T T T T T T T T T T

32

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS100 to 250 Trip unit TMD Downstream: NC125H, NG125
NS160N/H/L Trip unit TM-D 32 40 50 63 80 100 80 100 125 160 NS250N/H/L Trip unit TM-D 160 200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Downstream NC125H NG125a C curve NG125N, Ns, H B, C curves Rating (A) Setting Ir 125 80 100 125 y 20 25, 32 40 50 63 80 100 125 y 20 25, 32 40 50 63 80 100 125 y 16 20 25, 32 40 50 63 80 y 16 20 25, 32 40 50 63 80

NS100N/H/L Trip unit TM-D 16 25

2.5 2.5 0.4 0.5 0.5 0.5 0.5 0.63 0.63 0.63 0.63 0.8 0.8 0.8 0.8 0.8 T T T 2.5 T T T 2.5 2.5 T T T 2.5 2.5 T T T 2.5 2.5 2.5 2.5 T T T 2.5 2.5 2.5 2.5 T T T T 2.5 2.5 2.5 T T T T 2.5 2.5 2.5

T T T T T T T T T T T T T T T

NG125N, Ns, H D curve

0.4

0.5

0.5

0.5 0.5

0.63 0.63 0.63

0.8 0.8 0.8 0.8

T T T 2.5

T T T 2.5 2.5

T T T 2.5 2.5

NG125L B, C curves

0.3

0.4 0.4

0.5 0.5

0.5 0.5

0.5 0.5 0.5

0.63 0.63 0.63 0.63 0.63

0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

T T T T 2.5

T T T T 2.5 2.5 T T T T 2.5 2.5

T T T T 2.5 2.5 T T T T 2.5 2.5

NG125L D curve

0.3

0.4 0.4

0.5 0.5

0.5 0.5

0.5 0.5 0.5

0.63 0.63 0.63 0.63

T T T T 2.5

T T T T T T T T T T T T T T

Schneider Electric

33

Complementary technical information

Protection discrimination Upstream: NS100 to 160 - Trip unit STR Downstream: DPN, DPN N, XC40, C60, NC100
NS160N/H/L Trip unit STR22SE 100 80 63 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 80 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 100 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 32 T 40 T T 50 T T T 63 T T T T T T T T 80 T T T T T T T T T T T T T T T 160 63 T T T T T T T T 80 T T T T T T T T T T T T T T T 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 125 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 40 1.2 1.2

Upstream Downstream DPN B, C curves Rating (A) Setting Ir y 10 16 20 25 32 y 10 16 20 25 32 40 y 10 16 20 25 32 38 40 y 10 16 20 25 32 40 y 10 16 20 25 32 40 50 63 y 10 16 20 25 32 40 50 63 y 10 16 20 25 32 40 50 63 y 50 63 80 100 y 50 63 80 100 y 16 20 25 32 40 50 63 y 16 20 25 32 40 50 63

NS100N/H/L Trip unit STR22SE 40 16 25 0.4 40 0.4 0.4

DPN N C, D curves

0.4

0.4 0.4

1.2 1.2

T T

T T T

XC40 L, U curves

0.4

0.4 0.4

1.2 1.2

1.2 1.2 1.2 1.2

T T

T T T

T T T T

T T T T

C60a C curve

0.4

0.4 0.4

1.2 1.2

1.2 1.2 1.2 1.2

T T

T T T

T T T T

T T T T T T T T T T

T T T T

T T T T T T T T T T

C60N B, C, D curves

0.4

0.4 0.4

1.2 1.2

1.2 1.2 1.2 1.2

T T

T T T

T T T T

T T T T

C60H C curve

0.4

0.4 0.4

1.2 1.2

1.2 1.2 1.2

1.2 1.2 1.2 1.2 1.2

1.2 1.2 1.2 1.2 1.2 1.2

T T

T T T

T T T T

T T T T T

T T T T

T T T T T

T T T T T T

C60L B, C curve K curve Z curve

0.4

0.4 0.4

1.2 1.2

1.2 1.2 1.2 1.2

1.2 1.2 1.2 1.2 1.2

1.2 1.2 1.2 1.2 1.2 1.2

T T

T T T

T T T T

T T T T T

T T T T

T T T T T

T T T T T T

NC100H B, C curves

NC100H D curve

T T

NC100L NC100LS

0.4

1.2

1.2 1.2 1.2

1.2 1.2 1.2 1.2

1.2 1.2 1.2 1.2 1.2

T T T

T T T T

T T T T T

T T T T T T T T T T T T

NC100LH C curve

0.4

1.2

1.2 1.2 1.2

1.2 1.2 1.2 1.2

1.2 1.2 1.2 1.2 1.2

T T T

T T T T

T T T T T

T T T T T T T T T T T T T T

34

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS250 to 630 - Trip unit STR Downstream: DPN, DPN N, XC40, C60, NC100
NS400N/H/L Trip unit STR23SE/53UE 400 200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NS630N/H/L Trip unit STR23SE/53UE 630 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Downstream DPN B, C curves Rating (A) Setting Ir y 10 16 20 25 32 y 10 16 20 25 32 40 y 10 16 20 25 32 38 40 y 10 16 20 25 32 40 y 10 16 20 25 32 40 50 63 y 10 16 20 25 32 40 50 63 y 10 16 20 25 32 40 50 63 y 50 63 80 100 y 50 63 80 100 y 16 20 25 32 40 50 63 y 16 20 25 32 40 50 63

NS250N/H/L Trip unit STR22SE 250 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 125 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

DPN N C, D curves

XC40 L, U curves

C60a C curve

C60N B, C, D curves

C60H C curve

T T T T T T

C60L B, C curves K curve Z curve

T T T T T T

NC100H B, C curves

NC100H D curve

T T

NC100L NC100LS

T T T T T

T T T T T T T T T T T T

NC100LH C curve

T T T T T

T T T T T T T T T T T T T T

Schneider Electric

35

Complementary technical information

Protection discrimination Upstream: NS100 to 160 Trip unit STR Downstream: NC125H, NG125
NS160N/H/L Trip unit STR22SE 100 80 63 80 100 32 40 50 63 80 160 63 80 100 125 160 40

Upstream Downstream NC125H NG125a C curve NG125N, Ns, H B, C curves Rating (A) Setting Ir 125 80 100 125 y 20 25, 32 40 50 63 80 100 125 y 20 25, 32 40 50 63 80 100 125 y 16 20 25, 32 40 50 63 80 y 16 20 25, 32 40 50 63 80

NS100N/H/L Trip unit STR22SE 40 16 25 40

0.63

0.8 0.8

1 1 1

T T

T T T

T T T 2

T T T 2.5 2.5

NG125N, Ns, H D curve

T T

T T T

0.63

0.8 0.8

1 1 1

T T T 2.5

T T T 2.5 2.5

NG125L B, C curves

0.63

0.8 0.8

1 1 1

T T

T T T

T T T T

T T T T 2.5

T T T T 2.5 2.5 T T T T 2.5 2.5

NG125L D curve

0.63

0.8 0.8

1 1 1

T T

T T T

T T T T

T T T T 2.5

36

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS250 to 630 Trip unit STR Downstream: NC125H, NG125
NS400N/H/L Trip unit STR23SE/53UE 400 200 T 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 160 200 T 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NS630N/H/L Trip unit STR23SE/53UE 630 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Downstream NC125H NG125a C curve NG125N, Ns, H B, C curves Rating (A) Setting Ir 125 80 100 125 y 20 25, 32 40 50 63 80 100 125 y 20 25, 32 40 50 63 80 100 125 y 16 20 25, 32 40 50 63 80 y 16 20 25, 32 40 50 63 80

NS250N/H/L Trip unit STR22SE 250 100 125 160

T T T

T T T T

T T T T T

T T T T T T

T T T T T

T T T T T T

NG125N, Ns, H D curve

T T T

T T T T

T T T T T

T T T T T T

T T T T T

T T T T T T

NG125L B, C curves

T T T T

T T T T T

T T T T T T T T T T T T

NG125L D curve

T T T T

T T T T T

T T T T T T T T T T T T T T

T T T T T T T T T T T T

T T T T T T T T T T T T T T

Schneider Electric

37

Complementary technical information

Protection discrimination Upstream: NS100 to 250 Trip unit TMD Downstream: NS100 to 250
NS160N/H/L Trip unit TM-D 32 0.4 40 0.5 0.5 50 0.5 0.5 63 0.5 0.5 0.5 80 0.63 0.63 0.63 0.63 0.63 100 0.8 0.8 0.8 0.8 0.8 0.8 80 1 1 1 1 1 100 2 2 2 2 2 2 125 2 2 2 2 2 2 1.25 2 2 2 2 2 2 1.25 2 2 2 2 2 2 1.25 1.25 1.25 160 2 2 2 2 2 2 1.25 1.25 2 2 2 2 2 2 1.25 1.25 2 2 2 2 2 2 1.25 1.25 1.25 1.25 1.25 NS250N/H/L Trip unit TM-D 160 T T T T T T T T T T 36 36 36 36 36 36 T T 36 36 36 36 36 36 2.6 2.6 2.6 200 T T T T T T T T T T 36 36 36 36 36 36 T T 36 36 36 36 36 36 4 4 4 4 4 4 4 4 4 4 4 4 2 2 250 T T T T T T T T T T 36 36 36 36 36 36 T T 36 36 36 36 36 36 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 2.5 2.5 2.5

Upstream Downstream Rating (A)

NS100N/H/L Trip unit TM-D 16 25

Setting Ir NS100N 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100H 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100L 16 Trip unit TM-D 25 32 40 50 63 80 100 NS160NE/N y 63 Trip unit TM-D 80 100 125 160 NS160H y 63 Trip unit TM-D 80 100 125 160 NS160L y 63 Trip unit TM-D 80 100 125 160 NS250N y 100 Trip unit TM-D 125 160 200 250 NS250H/L y 100 Trip unit TM-D 125 160 200 250 NS100N 40 Trip unit STR22SE100 NS100H/L 40 Trip unit STR22SE 100 NS160N 40 Trip unit STR22SE 100 160 NS160H/L 40 Trip unit STR22SE 100 160 NS250N y 100 Trip unit STR22SE 160 250 y 100 NS250H/L Trip unit STR22SE 160 250

0.5

0.5 0.5

0.5 0.5 0.5

0.63 0.63 0.63 0.63 0.63

0.8 0.8 0.8 0.8 0.8 0.8

1 1 1 1 1

2 2 2 2 2 2

0.5

0.5 0.5

0.5 0.5 0.5

0.63 0.63 0.63 0.63 0.63

0.8 0.8 0.8 0.8 0.8 0.8

1 1 1 1 1

2 2 2 2 2 2

1.25 1.25

1.25 1.25 1.25

2.6 2.6 2.6

1.25 1.25

1.25 1.25 1.25

2.6 2.6 2.6

1.6

1.6

2 2

2.5 2.5 2.5

0.63 0.63 0.63

0.8 0.8 0.8

1 1 1

1.25 1.25 1.25

1.25 1.25 1.25

1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

T T 36 36 1.6 1.6 1.6 1.6 1.6

T T 36 36 2 2 2 2 2

0.63

0.8

1.25

1.25

T T 36 36 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

1.6

38

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS100 to 250 - Trip unit TMD Downstream: NSC100N, NS125E, NSA160N, NB225N
NS160N/H/L Trip unit TM-D 32 0.4 0.4 40 0.5 0.5 50 0.5 0.5 0.5 63 0.5 0.5 0.5 0.5 80 0.63 0.63 0.63 0.63 0.63 0.63 100 0.8 0.8 0.8 0.8 0.8 0.8 0.8 80 2 2 2 2 2 100 2 2 2 2 2 2 2 125 2 2 2 2 2 2 2 2 1.25 2 2 2 2 1.25 160 2 2 2 2 2 2 2 2 1.25 1.25 2 2 2 2 1.25 1.25 2 2 2 2 2 2 1.25 1.25 NS250N/H/L Trip unit TM-D 160 T T T T T T T T T T T T T T T T T T T T T T T T 200 T T T T T T T T T T T T T T T T 4 T T T T T T T T T 250 T T T T T T T T T T T T T T T T 5 T T T T T T T T T T

Upstream Downstream NSC100N Rating (A) Setting Ir 15 20 25 32 40 50 63 70 80 100 16 25 40 63 80 100 125 16 25 32 40 50 63 80 100 125 160 100 125 150 175 200 225

NS100N/H/L Trip unit TM-D 16 25 0.3

NS125E

1 1 1

2 2 2 2

NSA160N

0.4

0.5 0.5

0.5 0.5

0.5 0.5 0.5

0.63 0.63 0.63 0.63 0.63

0.8 0.8 0.8 0.8 0.8 0.8

2 2 2 2 2

2 2 2 2 2 2

2 2 2 2 2 2 1.25

NB225N

Schneider Electric

39

Complementary technical information

Protection discrimination Upstream: NS100 to 160 Trip unit STR Downstream: NS100 to 160
NS160N/H/L Trip unit STR22SE 100 80 63 1.2 1.2 80 1.2 1.2 1.2 100 1.2 1.2 1.2 1.2 1.2 32 40 50 63 80 160 63 2 2 80 2 2 2 100 2 2 2 2 125 2 2 2 2 2 160 2 2 2 2 2 2 40

Upstream Downstream Rating (A)

NS100N/H/L Trip unit STR22SE 40 16 25 40

Setting Ir NS100N 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100H 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100L 16 Trip unit TM-D 25 32 40 50 63 80 100 NS160NE/N y 63 Trip unit TM-D 80 100 125 160 NS160H y 63 Trip unit TM-D 80 100 125 160 y 63 NS160L Trip unit TM-D 80 100 125 160 NS100N 40 Trip unit STR22SE 100 NS100H/L 40 Trip unit STR22SE 100 NS160N 40 Trip unit STR22SE 100 160 NS160H/L 40 Trip unit STR22SE 100 160

1.2 1.2

1.2 1.2 1.2

1.2 1.2 1.2 1.2 1.2

2 2

2 2 2

2 2 2

2 2 2 2 2

2 2 2 2 2 2

1.2 1.2

1.2 1.2 1.2

1.2 1.2 1.2 1.2 1.2

2 2

2 2 2

2 2 2

2 2 2 2 2

2 2 2 2 2 2

1.2 1.2 1.2

1.2 1.2 1.2

1.2 1.2 1.2

2 2 2

2 2 2

2 2 2

2 2 2

2 2 2 2 2 2 2 2

1.2

1.2

1.2

2 2

40

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS250 to 630 Trip unit STR Downstream: NS100 to 160
NS400N/H/L Trip unit STR23SE/53UE 400 200 T T T T T T T T T 36 36 36 36 36 T T 36 36 36 36 36 3 3 250 T T T T T T T T T T 36 36 36 36 36 36 T T 36 36 36 36 36 36 3 3 3 160 T T T T T T 200 T T T T T T T T T T T T T T T T T T T T T T T 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5 5 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5 5 5 NS630N/H/L Trip unit STR23SE/53UE 630 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Downstream NS100N Trip unit TM-D Rating (A) Setting Ir 16 25 32 40 50 63 80 100 16 25 32 40 50 63 80 100 16 25 32 40 50 63 80 100 y 63 80 100 125 160 y 63 80 100 125 160 y 63 80 100 125 160 y 100 125 160 200 250 y 100 125 160 200 250 40 100 40 100 40 100 160 40 100 160 y 100 160 250 y 100 160 250

NS250N/H/L Trip unit STR22SE 250 100 T T T T 125 T T T T T 160 T T T T T T

NS100H Trip unit TM-D

T T 36 36

T T 36 36 36

T T 36 36 36 36

T T T T T T

NS100L Trip unit TM-D

T T 36 36

T T 36 36 36

T T 36 36 36 36

T T T T T T

NS160NE/N Trip unit TM-D

NS160H Trip unit TM-D

3 3

3 3 3

T T

T T T

T T T

NS160L Trip unit TM-D

3 3

3 3 3

T T

T T T

T T T

NS250N Trip unit TM-D

NS250H/L Trip unit TM-D

5 5

5 5 5

T T

T T T

NS100N Trip unit STR22SE NS100H/L Trip unit STR22SE NS160N Trip unit STR22SE NS160H/L Trip unit STR22SE NS250N Trip unit STR22SE NS250H/L Trip unit STR22SE

T 36 3

T 36 3

T T 36 36 3 3 3 3 3

T T 36 36 3 3 3 3 3 3 3 3

T T 36 36 3 3 3 3 3 3 3 3 3 3

T T T T T T T T 5

T T T T T T T T T T 5

T T T T T T T T T T 5 5 5 5

T T T T T T T T T T 5 5 5 5

T T T T T T T T T T 5 5 5 5 5 5

T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T

Schneider Electric

41

Complementary technical information

Protection discrimination Upstream: NS100 to 160 - Trip unit STR Downstream: NSC100N, NS125E, NSA160N, NB225N
NS160N/H/L Trip unit STR22SE 100 80 63 0.63 0.63 0.63 80 0.8 0.8 0.8 0.8 100 1 1 1 1 1 32 40 50 63 80 160 63 2 2 2 80 2 2 2 2 100 2 2 2 2 2 125 2 2 2 2 2 2 160 2 2 2 2 2 2 2 40 0.4

Upstream Downstream NSC100N Rating (A) Setting Ir 15 20 25 32 40 50 63 70 80 100 16 25 40 63 80 100 125 16 25 32 40 50 63 80 100 125 160 100 125 150 175 200 225

NS100N/H/L Trip unit STR22SE 40 16 25 40 0.4

NS125E

NSA160N

0.4

0.4

0.63 0.63

0.8 0.8 0.8

1 1 1 1

2 2

2 2 2

2 2 2 2

2 2 2 2 2

2 2 2 2 2 2

NB225N

42

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS250 to 630 - Trip unit STR Downstream: NS400 to 630, NSC100N, NS125E, NSA160N, NB225N to 600
NS400N/H/L Trip unit STR23SE/53UE 400 200 250 160 200 250 320 400 NS630N/H/L Trip unit STR23SE/53UE 630 250 8 320 8 8 400 8 8 8 500 8 8 8 8 8 8 8 8 8 8 8 8 630 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8

Upstream Downstream NS400N Rating (A) Setting Ir 160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630

NS250N/H/L Trip unit STR22SE 250 100 125 160

NS400H

8 8

8 8 8

NS400L

8 8

8 8 8

NS630N

NS630H

NS630L

NSC100N

NS125E

NSA160N

NB225N

NB400N

NB600N

y 25 32 40 50 63 70 80 100 y 25 40 63 80 100 125 y 25 32 40 50 63 80 100 125 160 100 125 150 175 200 225 250 300 350 400 500 600

T T T

T T T T

T T T T T

T T T T T T T T T T T

T T

T T

T T T

T T T T T T T T T T T T T T T T T T T T

T T T T T

T T T T T T T T T T T

T T T T

T T T T T T T T T T T T T T T T T T T T

T T T

T T T T

T T T T T

T T T T T T

T T T T T

T T T T T T

T T T T T T T T T T T T T T T T T T T T T T 5 5

T T T T T T T T T T T T T T T T T T T T T T T 5 5 5

T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Schneider Electric

43

Complementary technical information

Protection discrimination Upstream: NS630b to 1600N/H Downstream: Multi 9, NS100 to NS250


NS630b/NS800/NS1000/NS1250/1600N/H Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 800 1000 1250 1600 630 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 250 T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1000 1250 1600 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Trip unit Rating (A) Downstream Setting Ir DPN, DPN N, XC40, C60 NC100/125, C120, NG125 NS100N 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100H/L 16 Trip unit TM-D 25 32 40 50 63 80 100 NS160N/NE y 63 Trip unit TM-D 80 100 125 160 NS160H/L y 63 Trip unit TM-D 80 100 125 160 NS250N y 100 Trip unit TM-D 125 160 200 250 NS250H/L y 100 Trip unit TM-D 125 160 200 250 NS100N 40 STR22SE 100 NS100H/L 40 STR22SE 100 NS160N 40 STR22SE 80 100 160 NS160H/L 40 STR22SE 100 160 NS250N y 100 STR22SE 160 250 NS250H/L y 100 STR22SE 160 250

NS630b/NS800/NS1000/NS1250/1600N/H Micrologic 2.0 - Isd: 10 Ir 630 250 T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T

T T T

T T

T T T

T T

T T T

T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T

T T T T T T T T T T

T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T

44

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS630b to NS1000L, NS1600b to 3200N Downstream: Multi 9, NS100 to NS250
NS1600b/NS2000/NS2500/NS3200N NS1600b/NS2000/NS2500/ NS3200N Micrologic 2.0 - Isd: 10 Ir 800 1000 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream NS630b/NS800/NS1000L Trip unit Downstream Setting Ir DPN, DPN N, XC40, C60 NC100/125, C120, NG125 NS100N 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100H/L 16 Trip unit TM-D 25 32 40 50 63 80 100 NS160N/NE y 63 Trip unit TM-D 80 100 125 160 NS160H/L y 63 Trip unit TM-D 80 100 125 160 NS250N y 100 Trip unit TM-D 125 160 200 250 NS250H/L y 100 Trip unit TM-D 125 160 200 250 NS100N 40 STR22SE 100 NS100H/L 40 STR22SE 100 NS160N 40 STR22SE 80 100 160 NS160H/L 40 STR22SE 100 160 NS250N y 100 STR22SE 160 250 NS250H/L y 100 STR22SE 160 250 Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 250 T T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Rating (A) 630

T T T

T T

T T T

T T T T T T T T T T

T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T

Schneider Electric

45

Complementary technical information

Protection discrimination Upstream: NS1600b to 3200H Downstream: Multi 9, NS100 to NS250


NS1600b/NS2000/NS2500/NS3200H Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 3200 3200 T T T T T T T T T T 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 T T T T T 40 40 40 40 40 T T 40 40 T T T T 40 40 40 T T T 40 40 40 1600 1600 T T T T T T T T T T 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 T T T T T 40 40 40 40 40 T T 40 40 T T T T 40 40 40 T T T 40 40 40 2000 2000 T T T T T T T T T T 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 T T T T T 40 40 40 40 40 T T 40 40 T T T T 40 40 40 T T T 40 40 40 2500 2500 T T T T T T T T T T 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 T T T T T 40 40 40 40 40 T T 40 40 T T T T 40 40 40 T T T 40 40 40 3200 3200 T T T T T T T T T T 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 T T T T T 40 40 40 40 40 T T 40 40 T T T T 40 40 40 T T T 40 40 40

Upstream NS1600b/NS2000/NS2500/NS3200H Trip unit Downstream Setting Ir DPN, DPN N, XC40, C60 NC100/125, C120, NG125 NS100N 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100H/L 16 Trip unit TM-D 25 32 40 50 63 80 100 NS160N/NE y 63 Trip unit TM-D 80 100 125 160 NS160H/L y 63 Trip unit TM-D 80 100 125 160 NS250N y 100 Trip unit TM-D 125 160 200 250 NS250H/L y 100 Trip unit TM-D 125 160 200 250 NS100N 40 STR22SE 100 NS100H/L 40 STR22SE 100 NS160N 40 STR22SE 80 100 160 NS160H/L 40 STR22SE 100 160 NS250N y 100 STR22SE 160 250 NS250H/L y 100 STR22SE 160 250 Micrologic 2.0 - Isd: 10 Ir 2000 2000 T T T T T T T T T T 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 T T T T T 40 40 40 40 40 T T 40 40 T T T T 40 40 40 T T T 40 40 40 2500 2500 T T T T T T T T T T 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 T T T T T 40 40 40 40 40 T T 40 40 T T T T 40 40 40 T T T 40 40 40 1600 T T T T T T T T T T 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 T T T T T 40 40 40 40 40 T T 40 40 T T T T 40 40 40 T T T 40 40 40 Rating (A) 1600

46

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS630b to 1600N/H Downstream: NS400 to 630


NS630b/NS800/NS1000/NS1250/1600N/H Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 800 1000 1250 1600 630 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 250 T 320 T T 400 T T T 500 T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T 800 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T 1000 1250 1600 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream NS630b/NS800/NS1000/NS1250/1600N/H Trip unit Downstream NS400N STR23SE STR53UE Setting Ir 160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630 Micrologic 2.0 - Isd: 10 Ir 250 T 320 T T 400 T T T 500 T T T T T T T T T T T T T T Rating (A) 630

NS400H STR23SE STR53UE

T T

T T T

T T

T T T

NS400L STR23SE STR53UE

T T

T T T

T T

T T T

NS630N STR23SE STR53UE

NS630H STR23SE STR53UE

T T

T T T

T T

T T T

NS630L STR23SE STR53UE

T T

T T T

T T

T T T

NSC100N

NS125E Trip unit TM-D

NSA160N

NS225E

NS400NB

NS600NB

y 25 32 40 50 63 70 80 100 y 25 40 63 80 100 125 y 25 32 40 50 63 80 100 125 160 100 125 150 175 200 225 250 300 350 400 500 600

T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Schneider Electric

47

Complementary technical information

Protection discrimination Upstream: NS630b to 1000L, NS1600b to 3200N Downstream: NS400 to NS630
NS1600b/NS2000/ NS2500/NS3200N Micrologic 2.0 - Isd: 10 Ir 800 1000 1000 18 18 18 18 18 18 18 18 18 18 30 30 30 30 30 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 18 18 18 18 18 18 18 18 18 18 30 30 30 30 30 12 12 12 12 12 12 12 12 12 12 12 12 NS1600b/NS2000/ NS2500/NS3200N Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream NS630b/NS800/NS1000L Trip unit Downstream NS400N STR23SE STR53UE Setting Ir 160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630 Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 250 18 320 18 18 400 18 18 18 500 18 18 18 18 18 18 18 18 30 30 30 30 12 12 630 18 18 18 18 18 18 18 18 18 18 30 30 30 30 30 12 12 12

Rating (A) 630

NS400H STR23SE STR53UE

18

18 18

18 18 18

NS400L STR23SE STR53UE

30

30 30

30 30 30

NS630N STR23SE STR53UE

12

NS630H STR23SE STR53UE

12

12 12

12 12 12

NS630L STR23SE STR53UE

12

12 12

12 12 12

NSC100N

NS125E Trip unit TM-D

NSA160N

NS225E

NS400NB

NS600NB

y 25 32 40 50 63 70 80 100 y 25 40 63 80 100 125 y 25 32 40 50 63 80 100 125 160 100 125 150 175 200 225 250 300 350 400 500 600

T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T 18 18 18 18

18 18

18 18 18

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 18 18 18 18 12 12

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 18 18 18 18 12 12

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

48

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS1600b to 3200H Downstream: NS400 to 630


NS1600b/NS2000/NS2500/NS3200H Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 3200 3200 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 1600 1600 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 2000 2000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 2500 2500 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 3200 3200 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40

Upstream NS1600b/NS2000/NS2500/NS3200H Trip unit Downstream NS400N STR23SE STR53UE Setting Ir 160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630 Micrologic 2.0 - Isd: 10 Ir 2000 2000 40 40 40 40 40 35 35 35 35 35 35 35 35 35 35 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 2500 2500 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 1600 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 Rating (A) 1600

NS400H STR23SE STR53UE

NS400L STR23SE STR53UE

NS630N STR23SE STR53UE

NS630H STR23SE STR53UE

NS630L STR23SE STR53UE

NSC100N

NS125E Trip unit TM-D

NSA160N

NS225E

NS400NB

NS600NB

y 25 32 40 50 63 70 80 100 y 25 40 63 80 100 125 y 25 32 40 50 63 80 100 125 160 100 125 150 175 200 225 250 300 350 400 500 600

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Schneider Electric

49

Complementary technical information

Protection discrimination Upstream: NS630b to 1600N/H Downstream: NS630b to 3200


NS630b/NS800/NS1000/NS1250/1600N/H Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 800 1000 1250 1600 630 1000 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1250 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 1600 250 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 320 400 25 500 25 25 630 25 25 25 800 800 25 25 25 25 70 70 70 70 25 25 25 1000 1250 1600 1000 25 25 25 25 25 70 70 70 70 70 25 25 25 25 25 25 25 25 70 70 70 70 25 25 25 1250 25 25 25 25 25 70 70 70 70 70 25 25 25 25 25 25 25 25 25 25 70 70 70 70 70 25 25 25 25 25 25 25 25 70 70 70 70 25 25 25 1600 25 25 25 25 25 70 70 70 70 70 25 25 25 25 25 25 25 25 25 25 70 70 70 70 70 25 25 25 25 25 25 25 25 25 25 70 70 70 70 70 25 25 25 25 25 25 25 25 25 25 25 630 6.3 6.3 6.3 800 8 8 8 8 8 8 8 8 8 8 8

Upstream NS630b/NS800/NS1000/NS1250/1600N/H Trip unit Downstream NS630bN/H Setting Ir 250 320 400 500 630 NS630bL 250 320 400 500 630 NS800N 320 400 500 630 800 NS800H 320 400 500 630 800 NS800L 320 400 500 630 800 NS1000N 400 500 630 800 1000 NS1000H 400 500 630 800 1000 NS1000L 400 500 630 800 1000 NS1250N 500 630 800 1000 1250 NS1250H 500 630 800 1000 1250 NS1600N 640 800 960 1250 1600 NS1600H 640 800 960 1250 1600 NS1600b/3200 1250 N/H 1600 2000 2500 3200 Micrologic 2.0 - Isd: 10 Ir 250 320 400 4 500 5 5 Rating (A) 630

5 5

6.3 6.3 6.3

70

70 70

70 70 70

6.3 6.3

25

25 25

6.3 6.3

8 8 8

25

25 25

25 25 25

6.3 6.3

8 8 8

70

70 70

70 70 70

6.3

8 8

25

25 25

6.3

8 8

10 10 10

25

25 25

25 25 25

6.3

8 8

10 10 10

70

70 70

70 70 70

10 10

25

25 25

10 10

12.5 12.5 12.5

25

25 25

25 25 25

10

12.5 12.5

25

25 25

10

12.5 12.5

16 16 16

25

25 25

25 25 25

50

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS630b to 1000L, NS1600b to 3200N Downstream: NS630b to 3200
NS1600b/NS2000/ NS2500/NS3200N Micrologic 2.0 - Isd: 10 Ir 800 1000 1000 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1600 1600 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 2000 2000 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2500 2500 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 3200 3200 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 800 10 10 10 10 10 10 10 10 10 10 10 NS1600b/NS2000/ NS2500/NS3200N Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 1600 1600 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T 60 60 60 60 T T T 2000 2000 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T 60 60 60 60 60 2500 2500 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 60 60 3200 3200 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 60 60 60

Upstream NS630b/NS800/NS1000L Trip unit Downstream NS630bN/L Setting Ir 250 320 400 500 630 250 320 400 500 630 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 640 800 960 1250 1600 640 800 960 1250 1600 1250 1600 2000 2500 3200 Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 250 320 400 10 500 10 10 630 10 10 10

Rating (A) 630

NS630bH

10

10 10

10 10 10

NS800N/L

10

10 10

NS800H

10

10 10

10 10 10

NS1000N/L

10

10 10

NS1000H

10

10 10

10 10 10

NS1250N

NS1250H

NS1600N

NS1600H

16 16 16

60 60 60

NS1600b/3200 N/H

Schneider Electric

51

Complementary technical information

Protection discrimination Upstream: NS1600b to 3200H Downstream: NS630b to 3200


S1600b/NS2000/NS2500/NS3200H Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 3200 3200 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 40 40 40 40 40 32 32 32 32 32 32 32 32 32 32 40 40 40 40 40 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 1600 1600 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 2000 2000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 2500 2500 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 3200 3200 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40

Upstream NS1600b/NS2000/NS2500/NS3200H Trip unit Downstream NS630bN/H Setting Ir 250 320 400 500 630 250 320 400 500 630 320 400 500 630 800 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 640 800 960 1250 1600 640 800 960 1250 1600 1250 1600 2000 2500 3200 Micrologic 2.0 - Isd: 10 Ir 2000 2000 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 40 40 40 40 40 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2500 2500 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 40 40 40 40 40 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 1600 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 Rating (A) 1600

NS630bL

NS800N

NS800H

NS800L

NS1000N

NS1000H

NS1000L

NS1250N

NS1250H

NS1600N

NS1600H

16 16 16

40 40 40

NS1600b/3200 N/H

52

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS630b to 1600N/H Downstream: C801 to 1251, CM


NS630b/NS800/NS1000/NS1250/1600N/H Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 800 1000 1250 1600 630 1000 10 10 10 10 1250 12.5 12.5 12.5 12.5 1600 250 16 16 16 16 16 320 400 500 25 630 25 25 800 800 25 25 25 1000 1250 1600 1000 25 25 25 25 40 40 40 40 25 25 25 1250 25 25 25 25 40 40 40 40 25 25 25 25 40 40 40 40 25 25 25 1600 25 25 25 25 25 40 40 40 40 40 25 25 25 25 25 40 40 40 40 40 25 25 25 25 630 6.3 6.3 800 8 8 8

Upstream NS630b/NS800/NS1000/NS1250/1600N/H Trip unit Downstream C801N/H STR25DE Setting Ir 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 1250 1600 2000 T00 3200 Micrologic 2.0 - Isd: 10 Ir 250 320 400 500 5 Rating (A) 630

C801L STR25DE

40

40 40

40 40 40

C1001N/H STR25DE

8 8

10 10 10

12.5 12.5 12.5 12.5

16 16 16 16 16

25

25 25

C1001L STR25DE

40

40 40

40 40 40

C1251N STR25DE

10 10

12.5 12.5 12.5

16 16 16 16

25

25 25

CM N/H ST-CM1

Schneider Electric

53

Complementary technical information

Protection discrimination Upstream: NS630b to 1000L, NS1600b to 3200N Downstream: C801 to 1251, CM
NS1600b/NS2000/ NS2500/NS3200N Micrologic 2.0 - Isd: 10 Ir 800 1000 1000 10 10 10 10 10 10 10 10 10 10 10 1600 1600 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 2000 2000 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2500 2500 25 25 25 25 25 36 36 36 36 36 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 3200 3200 32 32 32 32 32 62 62 62 62 62 32 32 32 32 32 36 36 36 36 36 32 32 32 32 32 800 10 10 10 NS1600b/NS2000/ NS2500/NS3200N Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream NS630b/NS800/NS1000L Trip unit Downstream C801N/H Setting Ir 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 1250 1600 2000 T00 3200 Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 250 320 400 500 10 630 10 10

Rating (A) 630

C801L STR25DE

10

10 10

10 10 10

C1001N/H STR25DE

10

10 10

C1001L STR25DE

10

10 10

10 10 10

C1251N STR25DE

CM N/H ST-CM1

54

Schneider Electric

Complementary technical information

Protection discrimination Upstream: NS1600b to 3200H Downstream: C801 to 1251, CM


NS1600b/NS2000/NS2500/NS3200H Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF 2500 2500 25 25 25 25 25 36 36 36 36 36 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 3200 3200 32 32 32 32 32 40 40 40 40 40 32 32 32 32 32 36 36 36 36 36 32 32 32 32 32 1600 1600 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 2000 2000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 2500 2500 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 3200 3200 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40

Upstream NS1600b/NS2000/NS2500/NS3200H Trip unit Downstream C801N/H STR25DE Micrologic 2.0 - Isd: 10 Ir Rating (A) 1600 Setting Ir 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 1250 1600 2000 T00 3200 1600 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 2000 2000 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

C801L STR25DE

C1001N/H STR25DE

C1001L STR25DE

C1251N STR25DE

CM N/H ST-CM1

Schneider Electric

55

Complementary technical information

Protection discrimination Upstream: C801 to C1251 Downstream: DPN, DPN N, XC40, C60, NC100, NC125, NG125, NS100 to 250
C801N/H 1000 1250 800 C1001N/H/C1251N/H 1000 400 T T T T T T T T T T 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T T T 45 45 45 45 45 45 45 45 45 45 T T T 500 T T T T T T T T T T 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T T T 45 45 45 45 45 45 45 45 45 45 T T T T 40 40 40 40 T T 50 50 T T T 45 45 45 T T T 40 40 40 630 T T T T T T T T T T 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T T T 45 45 45 45 45 45 45 45 45 45 T T T T T 40 40 40 40 40 T T 50 50 T T T 45 45 45 T T T 40 40 40 800 T T T T T T T T T T 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T T T 45 45 45 45 45 45 45 45 45 45 T T T T T 40 40 40 40 40 T T 50 50 T T T 45 45 45 T T T 40 40 40 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Trip unit STR35SE/GE/ME/55UE Trip unit STR35SE/GE/ME/55UE 630 T T 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 800 T T 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 8 8 8 8 8 8 8 8 8 8 10 10 10 10 10 10 10 10 10 10 8 8 8 8 8 8 1000 T T 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 15 15 15 15 15 15 15 15 15 15 18 18 18 18 18 18 18 18 18 18 15 15 15 15 15 15 1250 T T T T T T T T T T 30 30 T 30 T 30 30 30 30 30 T 30 T 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 24 24 24 24 24 24 24 24 24 24 T T 30 30 30 30 30 30 30 30 24 24 24 24 24 24 320 T T T T T T T T T T 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T T T 45 45 45 45 45 45 45 45 45 45 T

Upstream C801N/H/C1001N/H/C1251N/H Trip unit STR25DE Downstream Rating (A) 800 400 T T 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 500 T T 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 Setting Ir 320 DPN, DPN N, XC40, C60 T NC100/125, NG125 T NS100N 16 3.2 Trip unit TM-D 25 3.2 32 3.2 40 3.2 50 3.2 63 3.2 80 3.2 100 3.2 NS100H 16 3.2 Trip unit TM-D 25 3.2 32 3.2 40 3.2 50 3.2 63 3.2 80 3.2 100 3.2 NS100L 16 3.2 Trip unit TM-D 25 3.2 32 3.2 40 3.2 50 3.2 63 3.2 80 3.2 100 3.2 NS160NE/N 3.2 y 63 Trip unit TM-D 80 3.2 100 3.2 125 3.2 160 NS160H 3.2 y 63 Trip unit TM-D 80 3.2 100 3.2 125 3.2 160 NS160L 3.2 y 63 Trip unit TM-D 80 3.2 100 3.2 125 3.2 160 NS250N 3.2 y 100 Trip unit TM-D 125 160 200 250 NS250H/L 3.2 y 100 Trip unit TM-D 125 160 200 250 NS100N 40 3.2 Trip unit STR22SE 100 3.2 NS100H/L 40 3.2 Trip unit STR22SE 100 3.2 NS160N 40 3.2 Trip unit STR22SE 100 3.2 160 3.2 NS160H/L 40 3.2 Trip unit STR22SE 100 3.2 160 3.2 NS250N 3.2 y 100 Trip unit STR22SE 160 3.2 250 NS250H/L 3.2 y 100 Trip unit STR22SE 160 3.2 250

4 4

5 5 5

40

40 40 40

T T T

4 4 4 4 4 4 4 4 4 4 4 4 4 4

5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5

T T 50 50 T T T 45 45 45 T T 40 40

T T 50 50 T T T 45 45 45 T T 40 40

T T T T T T T T T T T T T T

56

Schneider Electric

Complementary technical information

Protection discrimination Upstream: C801 to C1251, CM Downstream: DPN, DPN N, XC40, C60, NC100, NC125, NG125, NS100 to 250
C1001N/H/C1251N/H Trip unit STR45AE C801L Trip unit STR35SE/GE/ME/55UE 1000 1250 800 C1001L Trip unit STR35SE/GE/ME/55UE 1000 400 T T 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 500 T T 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 630 T T 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 800 T T 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 400 T T 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 3.2 3.2 3.2 3.2 3.2 3.2 500 T T 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 4 4 4 4 4 4 630 T T 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 5 5 5 5 5 5 800 T T 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 6.3 6.3 6.3 6.3 6.3 6.3 all 1000 T T T T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T 8 T CM N/H (1)

Upstream C801N/H Trip unit STR45AE Downstream Rating (A) 800 Setting Ir DPN, DPN N, XC40, C60 NC100/125, NG125 NS100N 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100H 16 Trip unit TM-D 25 32 40 50 63 80 100 NS100L 16 Trip unit TM-D 25 32 40 50 63 80 100 NS160NE/N y 63 Trip unit TM-D 80 100 125 160 NS160H y 63 Trip unit TM-D 80 100 125 160 NS160L y 63 Trip unit TM-D 80 100 125 160 NS250N y 100 Trip unit TM-D 125 160 200 250 NS250H/L y 100 Trip unit TM-D 125 160 200 250 NS100N 40 Trip unit STR22SE 100 NS100H/L 40 Trip unit STR22SE 100 NS160N 40 Trip unit STR22SE 100 160 NS160H/L 40 Trip unit STR22SE 100 160 NS250N y 100 Trip unit STR22SE 160 250 NS250H/L y 100 Trip unit STR22SE 160 250 320 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T

T T T

T T

T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T

400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

1000 1250 320 T T T T T T T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T T T T T 6.4 T T 6.4 T T 6.4 T T T T T T 6.4 T T 6.4 T T 6.4 T T T T T T 6.4 T T T T T T T T T T 6.4 T T T T T T T T T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T 6.4 T T T T 6.4 T T 6.4 T T T T 6.4 T T 6.4 T T

6.4 6.4

6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4

(1) With trip unit STCM2-STCM3.


Schneider Electric

57

Complementary technical information

Protection discrimination Upstream: C801 to C1251 Downstream: DPN, DPN N, XC40, C60, NC100, NC125, NG125, NS400 to 630
C801N/H Trip unit STR35SE/GE/ME/55UE 1000 1250 1250 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 800 320 12 12 400 12 12 12 500 12 12 12 12 12 12 12 12 12 12 12 12 12 12 630 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 800 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 630 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 800 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 1000 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 C1001N/H/C1251N/H Trip unit STR35SE/GE/ME/55UE 1000 400 T T 500 T T T 630 T T T T 45 45 45 45 45 45 45 45 40 40 40 800 T T T T T 45 45 45 45 45 45 45 45 45 45 40 40 40 40 40 40 40 40 40 40 40 40 1000 T T T T T 45 45 45 45 45 45 45 45 45 45 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 1250 1250 T T T T T 45 45 45 45 45 45 45 45 45 45 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40

Upstream Downstream Rating (A) NS400N Setting Ir 160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630

C801N/H/C1001N/H/C1251N/H Trip unit STR25DE 800 320 3.2 3.2 400 4 4 4 500 5 5 5 5 5 5 5 5 5 5 5 5 5 5

NS400H

3.2 3.2

4 4 4

12 12

12 12 12

45 45

45 45 45

NS400L

3.2 3.2

4 4 4

12 12

12 12 12

45 45

45 45 45

NS630N

12

40

40 40

NS630H

5 5

6.3 6.3 6.3

12

12 12

12 12 12

40

40 40

40 40 40

NS630L

5 5

6.3 6.3 6.3

12

12 12

12 12 12

40

40 40

40 40 40

NSC100N

NS125E

NSA160N

NB225N

NB400N

NB600N

y 25 32 40 50 63 70 80 100 y 25 40 63 80 100 125 y 25 32 40 50 63 80 100 125 160 100 125 150 175 200 225 250 300 350 400 500 600

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

10 10 10 10 10 10 10 10 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10 5 5 5 5

15 15 15 15 15 15 15 15 6.3 6.3 6.3 6.3 6.3 6.3 15 15 15 15 15 15 15 15 15 6.3 6.3 6.3 6.3 6.3

T T T T T T T T 10 10 10 10 10 10 T T T T T T T T T 8 8 8 8 8 8

T T T T T T T T 18 18 18 18 18 18 T T T T T T T T T 15 15 15 15 15 15

T T T T T T T T 30 30 30 30 30 30 T T T T T T T T T 24 24 24 24 24 24

T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

58

Schneider Electric

Complementary technical information

Protection discrimination Upstream: C801 to C1251, CM Downstream: DPN, DPN N, XC40, C60, NC100, NC125, NG125, NS400 to 630
C1001N/H/C1251N/H Trip unit STR45AE C801L Trip unit STR35SE/GE/ME/55UE 1000 1250 800 630 35 35 35 35 35 35 35 35 35 35 35 35 28 28 28 28 28 28 28 28 28 28 28 800 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 28 28 28 28 28 28 28 28 28 28 28 28 28 28 400 T T T T T T T T 70 70 70 70 T 500 T T T T T T T T 70 70 70 70 T T 630 T T T T T T T T T T 70 70 70 70 70 T T 800 T T T T T T T T T T 70 70 70 70 70 T T T T T T T 65 65 65 65 1000 T T T T T T T T T T 70 70 70 70 70 T T T T T T T T T 65 65 65 65 65 1250 T T T T T T T T T T 70 70 70 70 70 T T T T T T T T T 65 65 65 65 65 320 400 500 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 630 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 800 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 C1001L Trip unit STR35SE/GE/ME/55UE 1000 400 8 8 8 8 8 8 8 8 8 8 8 8 8 500 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 630 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 800 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 1000 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 all T T T T T T T T T T T T T T T T T T T T T T T T T T T T T CM N/H (1)

Upstream

C801N/H Trip unit STR45AE

Downstream Rating (A) NS400N Setting Ir 160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 630 250 320 400 500 630 250 320 400 500 630

800 320 400 500 35 35 35 35 35 35

NS400H

35

35 35

35 35 35

NS400L

35

35 35

35 35 35

6.4 6.4

6.4 6.4 6.4

NS630N

28

28 28

28 28

6.4

NS630H

28

28 28

28 28 28

T T

T T T

6.4

6.4 6.4

6.4 6.4 6.4

8 8

8 8 8

NS630L

28

28 28

28 28 28

65

65 65

65 65 65

6.4

6.4 6.4

6.4 6.4 6.4

8 8

8 8 8

NSC100N

NS125E

NSA160N

NB225N

NB400N

NB600N

y 25 32 40 50 63 70 80 100 y 25 40 63 80 100 125 y 25 32 40 50 63 80 100 125 160 100 125 150 175 200 225 250 300 350 400 500 600

T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 35 35 35 35 28 28

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T

T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T 6.4 6.4 6.4 6.4 6.4 6.4 T T T T T T T T T 6.4

T T T T T T T T 6.4 6.4 6.4 6.4 6.4 6.4 T T T T T T T T T 6.4 6.4

T T T T T T T T 6.4 6.4 6.4 6.4 6.4 6.4 T T T T T T T T T 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4

T T T T T T T T 6.4 6.4 6.4 6.4 6.4 6.4 T T T T T T T T T 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4

6.4 6.4 6.4 6.4 6.4 6.4

6.4 6.4 6.4 6.4 6.4 6.4

T T T T T T T T 6.4 6.4 6.4 6.4 6.4 6.4 T T T T T T T T T 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4

T T T T T T T T 8 8 8 8 8 8 T T T T T T T T T 8 8 8 8 8 8 8 8 8 8 8 8

T T T T T T T T 8 8 8 8 8 8 T T T T T T T T T 8 8 8 8 8 8 8 8 8 8 8 8

T T T T T T T T 8 8 8 8 8 8 T T T T T T T T T 8 8 8 8 8 8 8 8 8 8 8 8

T T T T T T T T 8 8 8 8 8 8 T T T T T T T T T 8 8 8 8 8 8 8 8 8 8 8 8

T T T T T T T T 8 8 8 8 8 8 T T T T T T T T T 8 8 8 8 8 8 8 8 8 8 8 8

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

(1) With trip unit STCM2-STCM3.

Schneider Electric

59

Complementary technical information

Protection discrimination Upstream: C801 to C1251 Downstream: C801 to C1251, CM, Masterpact
C801N/H 1000 1250 800 C1001N/H/C1251N/H 1000 400 500 630 12 800 12 12 12 400 500 630 15 800 15 15 15 1000 15 15 15 15 15 15 15 15 1250 1250 15 15 15 15 15 15 15 15 Trip unit STR35SE/GE/ME/55UE Trip unit STR35SE/GE/ME/55UE 630 6.3 800 8 8 8 1000 10 10 10 10 10 10 10 10 1250 320 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

Upstream Downstream C801N Trip unit STR25DE Rating (A) Setting Ir 320 400 500 630 800 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 1250 1600 2000 2500 3200 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25

C801N/H/C1001N/H/C1251N/H Trip unit STR25DE 800 320 400 500

C801H Trip unit STR25DE

6.3

8 8 8

12

12 12 12

15

15 15 15

C801L

C1001N Trip unit STR25DE

8 8

10 10 10

12.5 12.5 12.5

12 12

15 15

15 15 15

15 15 15

C1001H Trip unit STR25DE

8 8

10 10 10

12.5 12.5 12.5

12 12

15 15

15 15 15

15 15

C1001L

C1251N Trip unit STR25DE

10 10

12.5 12.5

12

15

15 15

15 15

C1251H Trip unit STR25DE

10 10

12.5 12.5

12

15

15 15

15 15

CM

Masterpact N1/H1/H2 STR28D

Masterpact L STR28D

Nota : b C801N/H with trip unit STR45AE : no distrimination with the dowstream devices give, in this table b upstream values CM N/H are to be read with distrimination: v CM (trip unit STCM1) v Masterpact L (trip unit STR38S - 68U).

60

Schneider Electric

Complementary technical information

Protection discrimination Upstream: C801 to C1251, CM Downstream: C801 to C1251, CM, Masterpact
C801L Trip unit STR35SE/GE/ME/55UE 1000 1250 800 1000 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 C1001L Trip unit STR35SE/GE/ME/55UE 1000 1250 1600 2000 2500 3200 1600 45 45 45 45 45 45 45 45 45 45 80 80 80 80 80 45 45 45 45 45 45 45 45 80 80 80 80 45 45 45 2000 45 45 45 45 45 45 45 45 45 45 80 80 80 80 80 45 45 45 45 45 45 45 45 45 45 80 80 80 80 80 45 45 45 45 45 45 45 45 35 2500 45 45 45 45 45 45 45 45 45 45 80 80 80 80 80 45 45 45 45 45 45 45 45 45 45 80 80 80 80 80 45 45 45 45 45 45 45 45 45 45 35 35 3200 45 45 45 45 45 45 45 45 45 45 80 80 80 80 80 45 45 45 45 45 45 45 45 45 45 80 80 80 80 80 45 45 45 45 45 45 45 45 45 45 35 35 35 CM N/H Trip unit STCM2-STCM3

Upstream

C1001N/H/C1251N/H Trip unit STR45AE

Downstream C801N Trip unit STR25DE

Rating (A) Setting Ir 320 400 500 630 800 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 1250 1600 2000 2500 3200 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25

800 400 500 630 800 15 15 15 15 15 15

C801H Trip unit STR25DE

15

15 15

15 15 15

C801L

15

15 15

15 15 15

C1001N Trip unit STR25DE

15

15 15

1250 320 400 500 630 800 400 500 630 800 1000 1250 15 45 15 45 15 45 15 45 15 15 45 15 45 15 45 15 45 15 15 80 15 80 15 80 15 80 15 15 45 15 45 15 45 15 15 15 15 15 15 15 15 15 15 15 15 45 45 45

C1001H Trip unit STR25DE

15

15 15

15 15 15

C1001L

15

15 15

15 15 15

80 80 80

C1251N Trip unit STR25DE

15

15 15

45 45

C1251H Trip unit STR25DE

15

15 15

15 15 15

45 45

45 45 45

CM

Masterpact N1/H1/H2 STR28D

35

35 35

35 35 35

Masterpact L STR28D

40

40 40

40 40 40

35 35 35 35

35 35 35 35 35

Schneider Electric

61

Complementary technical information

Protection discrimination Upstream: Masterpact NT Downstream: Multi 9, NS100 to 250


Masterpact NT H1 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NT06 NT08 NT10 630 800 1000 630 800 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Masterpact NT H1 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NT06 NT08 NT10 630 800 1000 630 800 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Masterpact NT H1 Trip unit Micrologic 2.0 Isd: 10 Ir NT06 NT08 NT10 Downstream Rating (A) 630 800 1000 Setting Ir 630 800 1000 DPN, DPN N, XC40, C60 T T T NC100H, C120, NC125H, NG125 T T T NS100N 16 T T T TM-D 25 T T T 32 T T T 40 T T T 50 T T T 63 T T T 80 T T T 100 T T T NS100H 16 T T T TM-D 25 T T T 32 T T T 40 T T T 50 T T T 63 T T T 80 T T T 100 T T T NS100L 16 T T T TM-D 25 T T T 32 T T T 40 T T T 50 T T T 63 T T T 80 T T T 100 T T T NS160N/NE T T T y 63 TM-D 80 T T T 100 T T T 125 T T T 160 T T T NS160H T T T y 63 TM-D 80 T T T 100 T T T 125 T T T 160 T T T NS160L T T T y 63 TM-D 80 T T T 100 T T T 125 T T T 160 T T T NS250N T T T y 100 TM-D 125 T T T 160 T T T 200 T T T 250 T T T NS250H/L T T T y 100 TM-D 125 T T T 160 T T T 200 T T T 250 T T T NS100N 40 T T T STR22SE 100 T T T NS100H/L 40 T T T STR22SE 100 T T T NS160N 40 T T T STR22SE 100 T T T 160 T T T NS160H/L 40 T T T STR22SE 80 T T T 100 T T T 160 T T T NS250N T T T y 100 STR22SE 160 T T T 250 T T T NS250H/L T T T y 100 STR22SE 160 T T T 250 T T T

NT12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NT16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NT12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NT16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NT12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NT16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

62

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NT Downstream: Multi 9, NS100 to 250


Masterpact NT L1 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NT06 NT08 NT10 630 800 1000 630 800 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Masterpact NT L1 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NT06 NT08 NT10 630 800 1000 630 800 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Masterpact NT L1 Trip unit Micrologic 2.0 Isd: 10 Ir NT06 NT08 NT10 Downstream Rating (A) 630 800 1000 Setting Ir 630 800 1000 DPN, DPN N, XC40, C60 T T T NC100H, NC125H, C120, NG125 T T T NS100N 16 T T T TM-D 25 14 T T 32 11 17 T 40 11 17 T 50 11 17 T 63 11 17 T 80 11 17 T 100 11 17 T NS100H 16 T 17 28 TM-D 25 11 17 28 32 11 17 28 40 11 17 28 50 11 17 28 63 11 17 28 80 11 17 28 100 11 17 28 NS100L 16 T 17 28 TM-D 25 14 17 28 32 11 17 28 40 11 17 28 50 11 17 28 63 11 17 28 80 11 17 28 100 11 17 28 NS160N/NE 9 13 22 y 63 TM-D 80 9 13 22 100 9 13 22 125 9 13 22 160 9 13 22 NS160H 9 13 22 y 63 TM-D 80 9 13 22 100 9 13 22 125 9 13 22 160 9 13 22 NS160L 9 13 22 y 63 TM-D 80 9 13 22 100 9 13 22 125 9 13 22 160 9 13 22 NS250N 8 11 19 y 100 TM-D 125 8 11 19 160 8 11 19 200 8 11 19 250 8 11 19 NS250H/L 8 11 19 y 100 TM-D 125 8 11 19 160 8 11 19 200 8 11 19 250 8 11 19 NS100N 40 11 17 T STR22SE 100 11 17 T NS100H/L 40 11 17 28 STR22SE 100 11 17 28 NS160N 40 9 13 22 STR22SE 100 9 13 22 160 9 13 22 NS160H/L 40 9 13 22 STR22SE 80 9 13 22 100 9 13 22 160 9 13 22 NS250N 8 11 19 y 100 STR22SE 160 8 11 19 250 8 11 19 NS250H/L 8 11 19 y 100 STR22SE 160 8 11 19 250 8 11 19 Schneider Electric

63

Complementary technical information

Protection discrimination Upstream: Masterpact NT Downstream: NS400 to 630, NSC100N, NS125E, NSA160, NB225 to 600
NT12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NT16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Masterpact NT H1 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NT06 NT08 NT10 630 800 1000 630 800 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NT12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NT16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Masterpact NT H1 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NT06 NT08 NT10 630 800 1000 630 800 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NT12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NT16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Trip unit

Downstream Rating (A) Setting Ir NS400N 160 STR23SE 200 STR53UE 250 320 400 NS400H 160 STR23SE 200 STR53UE 250 320 400 NS400L 160 STR23SE 200 STR53UE 250 320 400 NS630N 250 STR23SE 320 STR53UE 400 500 630 NS630H 250 STR23SE 320 STR53UE 400 500 630 NS630L 250 STR23SE 320 STR53UE 400 500 630

Masterpact NT H1 Micrologic 2.0 Isd: 10 Ir NT06 NT08 NT10 630 800 1000 630 800 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NSC100N

y 25 32 40 50 63 70 80 100 y 25 NS125E Trip unit TM-D 40 63 80 100 125 NSA160N y 25 32 40 50 63 80 100 125 160 NB225N 100 125 150 175 200 225 NS400NB 250 300 350 400 NB600N 500 600

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

64

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NT Downstream: NS400 to 630, NSC100N, NS125E, NSA160, NB225 to 600
Masterpact NT L1 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NT06 NT08 NT10 630 800 1000 630 800 1000 8.5 15 18 8.5 15 18 8.5 15 18 8.5 15 18 8.5 15 18 8.5 15 18 8.5 15 18 8.5 15 18 8.5 15 18 8.5 15 18 8.5 15 23 8.5 15 23 8.5 15 23 8.5 15 23 8.5 15 23 9.4 12 12 9.4 12 12 9.4 12 12 12 12 12 9.4 12 12 9.4 12 12 9.4 12 12 12 12 12 9.4 12 12 9.4 12 12 9.4 12 12 12 12 12 Masterpact NT L1 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NT06 NT08 NT10 630 800 1000 630 800 1000 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12

Upstream Trip unit

Downstream Rating (A) Setting Ir NS400N 160 STR23SE 200 STR53UE 250 320 400 NS400H 160 STR23SE 200 STR53UE 250 320 400 NS400L 160 STR23SE 200 STR53UE 250 320 400 NS630N 250 STR23SE 320 STR53UE 400 500 630 NS630H 250 STR23SE 320 STR53UE 400 500 630 NS630L 250 STR23SE 320 STR53UE 400 500 630

Masterpact NT L1 Micrologic 2.0 Isd: 10 Ir NT06 NT08 NT10 630 800 1000 630 800 1000 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 6.3 8 10 8 10 10 6.3 8 10 6.3 8 10 6.3 8 10 8 10 10 6.3 8 10 6.3 8 10 6.3 8 10 8 10 10

NSC100N

y 25 32 40 50 63 70 80 100 y 25 NS125E Trip unit TM-D 40 63 80 100 125 NSA160N y 25 32 40 50 63 80 100 125 160 NB225N 100 125 150 175 200 225 NS400NB 250 300 350 400 NB600N 500 600

12 12 12 12 12 12 12 12 9 9 9 9 9 9 11 11 11 11 11 11 11 11 11 8 8 8 8 8 8 6.3 6.3 6.3 6.3

T T T T T T T T 13 13 13 13 13 13 T T T T T T T T T 11 11 11 11 11 11 8 8 8 8 8 8

T T T T T T T T T T T T T T T T T T T T T T T 19 19 19 19 19 19 10 10 10 10 10 10

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 8.5 8.5 8.5 8.5

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 15 15 15 15 12 12

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 18 18 18 18 12 12

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 18 18 18 18

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 18 18 18 18 12 12

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 18 18 18 18 12 12

Schneider Electric

65

Complementary technical information

Protection discrimination Upstream: Masterpact NT Downstream: NS630b to NS1600, C801 to C1251, CM, Masterpact NT
Masterpact NT H1 Micrologic 5.0 - 6.0 -7.0 Inst: 15 In NT10 1000 1000 10 10 10 10 10 10 10 10 10 10 10 10 NT12 1250 1250 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 NT16 1600 1600 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 NT06 630 630 9.4 9.4 9.4 NT08 800 800 12 12 12 12 12 12 12 NT10 1000 1000 15 15 15 15 15 15 15 15 15 15 15 15 NT12 1250 1250 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 NT16 1600 1600 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 Masterpact NT H1 Micrologic 5.0 - 6.0 -7.0 Inst: OFF NT06 630 630 T T T NT08 800 800 T T T T T T T NT10 1000 1000 T T T T T T T T T T T T NT12 1250 1250 T T T T T T T T T T T T T T T T T NT16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T

Upstream Trip unit

Masterpact NT H1 Micrologic 2.0 Isd: 10 Ir NT06 NT08 800 800 8 8 8 8 8 8 8

Downstream NS630bN/H/L

Rating (A)

630 630 6.3 6.3 6.3

Setting Ir 250 320 400 500 630 NS800N/H/L 320 400 500 630 800 NS1000N/H/L 400 500 630 800 1000 NS1250N/H 500 630 800 1000 1250 NS1600N/H 640 800 960 1280 1600 C801N/H/L 320 400 500 630 800 C1001N/H/L 400 500 630 800 1000 C1251N/H 500 630 800 1000 1250 CM 1250 N/H 1600 2000 2500 3200 Masterpact NT NT06 H1 NT08 NT10 NT12 NT16 Masterpact NT NT06 L1 NT08 NT10

8 8 8

10 10 10 10 10 10 10

12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

16 16 16 16 16 16 16 16 16 16 16 16 16 16

12 12 12

15 15 15 15 15 15 15

18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7

24 24 24 24 24 24 24 24 24 24 24 24 24 24

T T T

T T T T T T T

T T T T T T T T T T T T

T T T T T T T T T T T T T T

10

12.5 12.5

16 16 16

15

18.7 18.7

24 24 24

T T

T T T

10

12.5 12.5

16 16 16

15

18.7 18.7

24 24 24

T T

T T T

66

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NT Downstream: NS630b to NS1600, C801 to C1251, CM, Masterpact NT
Masterpact NT L1 Inst: 15 In NT10 1000 1000 10 10 10 10 10 10 10 10 10 10 10 10 NT06 630 630 9.4 9.4 9.4 NT08 800 800 10 10 10 10 10 10 10 NT10 1000 1000 10 10 10 10 10 10 10 10 10 10 10 10 Masterpact NT L1 Inst: OFF NT06 630 630 10 10 10 NT08 800 800 10 10 10 10 10 10 10 NT10 1000 1000 10 10 10 10 10 10 10 10 10 10 10 10 Micrologic 5.0 - 6.0 - 7.0 Micrologic 5.0 - 6.0 - 7.0

Upstream Trip unit

Masterpact NT L1 Micrologic 2.0 Isd: 10 Ir NT06 NT08 800 800 8 8 8 8 8 8 8

Downstream NS630bN/H/L

Rating (A)

630 630 6.3 6.3 6.3

Setting Ir 250 320 400 500 630 NS800N/H/L 320 400 500 630 800 NS1000N/H/L 400 500 630 800 1000 NS1250N/H 500 630 800 1000 1250 NS1600N/H 640 800 960 1280 1600 C801N/H/L 320 400 500 630 800 C1001N/H/L 400 500 630 800 1000 C1251N/H 500 630 800 1000 1250 CM 1250 N/H 1600 2000 2500 3200 Masterpact NT NT06 H1 NT08 NT10 NT12 NT16 Masterpact NT NT06 L1 NT08 NT10

8 8 8

10 10 10 10 10 10 10

10 10 10

10 10 10 10 10 10 10

10 10 10

10 10 10 10 10 10 10

10

10

10

10

10

10

Schneider Electric

67

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: Multi 9, NS100 to 630, NSC100N, NSA160, NB225 to 600
Masterpact NW N1 - H1 - H2 Micrologic 5.0 - 6.0 - 7.0 - Inst: 15 In 1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Trip unit Downstream DPN, DPN N C60 XC40 NC100H NC125H NC125N/H/L C120N/H NS100N NS100H NS100L NS160N/NE NS160H NS160L NS250N NS250H/L NS400N STR23SE STR53UE Rating (A) Setting Ir

Masterpact NW N1 - H1 - H2 Micrologic 2.0 - Isd: 10 Ir 800 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NS400H STR23SE STR53UE

NS400L STR23SE STR53UE

NS630N STR23SE STR53UE

NS630H STR23SE STR53UE

NS630L STR23SE STR53UE

160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630

NSC100N NS125E NSA160N NB225N NB400N NB600N

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

68

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: Multi 9, NS100 to 630, NSC100N, NSA160, NB225 to 600

Upstream Trip unit Downstream DPN, DPN N C60 XC40 NC100H NC125H NG125N/H/L C120H/L NS100N NS100H NS100L NS160N/NE NS160H NS160L NS250N NS250H/L NS400N STR23SE STR53UE Rating (A) Setting Ir

Masterpact NW N1 - H1 - H2 Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF


NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

800 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NS400H STR23SE STR53UE

NS400L STR23SE STR53UE

NS630N STR23SE STR53UE

NS630H STR23SE STR53UE

NS630L STR23SE STR53UE

160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630

NSC100N NS125E NSA160N NB225N NB400N NB600N

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

Schneider Electric

69

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: Multi 9, NS100 to 630, NSC100, NSA160, NB225 to 600
Masterpact NW H3 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NW32 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW40 4000 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW20 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW25 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW32 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW40 4000 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Masterpact NW H3 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NW20 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW25 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW32 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW40 4000 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Masterpact NW H3 Trip unit Micrologic 2.0 Isd: 10 Ir NW20 Downstream DPN, DPN N C60 XC40 NC100H NC125H NG125N/H/L C1200N/H NS100N NS100H NS100L NS160N/NE NS160H NS160L NS250N NS250H/L NS400N STR23SE STR53UE Rating (A) Setting Ir 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW25 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NS400H STR23SE STR53UE

NS400L STR23SE STR53UE

NS630N STR23SE STR53UE

NS630H STR23SE STR53UE

NS630L STR23SE STR53UE

160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630

NSC100N NS125E NSA160N NB225N NB400N NB600N

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

70

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: Multi 9, NS100 to 630, NSC100, NSA160, NB225 to 600
Masterpact NW L1 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NW12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW20 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW08 800 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW10 1000 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW20 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Masterpact NW L1 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NW08 800 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW10 1000 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW12 1250 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW16 1600 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW20 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Masterpact NW L1 Trip unit Micrologic 2.0 Isd: 10 Ir NW08 Downstream DPN, DPN N C60 XC40 NC100H NC125H NG125N/H/L C120N/H NS100N NS100H NS100L NS160N/NE NS160H NS160L NS250N NS250H/L NS400N STR23SE STR53UE Rating (A) Setting Ir 800 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW10 1000 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NS400H STR23SE STR53UE

NS400L STR23SE STR53UE

NS630N STR23SE STR53UE

NS630H STR23SE STR53UE

NS630L STR23SE STR53UE

160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630

NSC100N NS125E NSA160N NB225N NB400N NB600N

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

Schneider Electric

71

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: NS630b to NS3200


Masterpact NW N1 - H1 - H2 Micrologic 5.0-6.0-7.0 - Inst: 15 In

Upstream Trip unit Rating (A) Downstream NS630bN Setting Ir 250 320 400 500 630 NS630bH 250 320 400 500 630 NS630bL 250 320 400 500 630 NS800N 320 400 500 630 800 NS800H 320 400 500 630 800 NS800L 320 400 500 630 800 NS1000N 400 500 630 800 1000 NS1000H 400 500 630 800 1000 NS1000L 400 500 630 800 1000 NS1250N 500 630 800 1000 1250 NS1250H 500 630 800 1000 1250 NS1600N 640 800 960 1280 1600 NS1600H 640 800 960 1280 1600 NS1600b/3200 1250 N/H 1600 2000 2500 3200

Masterpact NW N1 - H1 - H2 Micrologic 2.0 - Isd: 10 Ir

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 1000 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1250 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 1600 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 2000 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2500 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 3200 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 4000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 5000 T T T T T 50 50 50 50 50 50 50 50 50 50 T T T T T 50 50 50 50 50 50 50 50 50 50 T T T T T 50 50 50 50 50 50 50 50 50 50 T T T T T 50 50 50 50 50 T T T T T 50 50 50 50 50 50 50 50 50 50 6300 T T T T T 63 63 63 63 63 63 63 63 63 63 T T T T T 63 63 63 63 63 63 63 63 63 63 T T T T T 63 63 63 63 63 63 63 63 63 63 T T T T T 63 63 63 63 63 T T T T T 63 63 63 63 63 63 63 63 63 63 800 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 1000 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 1250 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 1600 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 2000 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 2500 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 40 40 40 40 40 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 40 40 40 40 40 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 40 40 40 40 40 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 3200 48 48 48 48 48 48 48 48 48 48 T T T T T 48 48 48 48 48 48 48 48 48 48 T T T T T 48 48 48 48 48 48 48 48 48 48 T T T T T 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 4000 T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 60 60 60 60 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 75 75 75 75 75 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 94.5 94.5 94.5 94.5 94.5

8 8 8

12 12 12

8 8 8

12 12 12

8 8

12 12

8 8

10 10 10

12 12

15 15 15

8 8

10 10 10

12 12

15 15 15

10 10

12

15 15

10 10

12.5 16 12.5 16 12.5 16 16 12.5 16 12.5 16 16

12

15 15

18.7 24 18.7 24 18.7 24 24 18.7 24 18.7 24 24

10

15

10

12.5 16 12.5 16 16

15

18.7 24 18.7 24 24

72

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: NS630b to NS3200

Upstream Trip unit

Masterpact NW N1 - H1 - H2 Micrologic 5.0-6.0-7.0 - Inst: OFF

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 Rating (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 Downstream NS630bN Setting Ir 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630 320 400 500 630 800 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 640 800 960 1280 1600 640 800 960 1280 1600 1250 1600 2000 2500 3200 800 T T T T T T T T T T T T T T T 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

NS630bH

NS630bL

NS800N

NS800H

T T T

NS800L

T T T

NS1000N

T T

NS1000H

T T

T T T

NS1000L

T T

T T T

NS1250N

T T

NS1250H

T T

T T T

NS1600N

T T

NS1600H

T T

T T T

NS1600b/3200 N/H

Schneider Electric

73

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: NS630b to NS3200


Masterpact NW H3 Micrologic 5.0 - 6.0 - 7.0 - Inst: 15 In NW40 4000 4000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 NW20 2000 2000 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 NW25 2500 2500 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 40 40 40 40 40 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 40 40 40 40 40 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 40 40 40 40 40 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 NW32 3200 3200 48 48 48 48 48 48 48 48 48 48 T T T T T 48 48 48 48 48 48 48 48 48 48 T T T T T 48 48 48 48 48 48 48 48 48 48 T T T T T 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 NW40 4000 4000 T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 T T T T T 60 60 60 60 60 60 60 60 60 NW32 3200 3200 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 Masterpact NW H3 Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF NW20 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 NW25 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 NW32 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 NW40 4000 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 65

Upstream Trip unit

Masterpact NW H3 Micrologic 2.0 - Isd: 10 Ir NW25 2500 2500 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

NW20 Rating (A) 2000 Downstream Setting Ir NS630bN 250 320 400 500 630 NS630bH 250 320 400 500 630 NS630bL 250 320 400 500 630 NS800N 320 400 500 630 800 NS800H 320 400 500 630 800 NS800L 320 400 500 630 800 NS1000N 400 500 630 800 1000 NS1000H 400 500 630 800 1000 NS1000L 400 500 630 800 1000 NS1250N 500 630 800 1000 1250 NS1250H 500 630 800 1000 1250 NS1600N 640 800 960 1280 1600 NS1600H 640 800 960 1280 1600 NS1600b/3200 1250 N/H 1600 2000 2500 3200 2000 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

74

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: NS630b to NS3200


Masterpact NW L1 Micrologic 5.0 - 6.0 - 7.0 - Inst: 15 In NW20 2000 2000 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 NW08 800 800 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 NW10 1000 1000 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 NW12 1250 1250 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 NW16 1600 1600 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 NW20 2000 2000 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 NW16 1600 1600 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 Masterpact NW L1 Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF NW08 800 800 37 37 37 37 37 37 37 37 T T T T 37 37 37 NW10 1000 1000 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 T T T T 37 37 37 NW12 1250 1250 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 T T T T 37 37 37 NW16 1600 1600 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 37 37 37 NW20 2000 2000 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 37 37 T T T T T 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37

Upstream Trip unit Rating (A) Downstream Setting Ir NS630bN 250 320 400 500 630 NS630bH 250 320 400 500 630 NS630bL 250 320 400 500 630 NS800N 320 400 500 630 800 NS800H 320 400 500 630 800 NS800L 320 400 500 630 800 NS1000N 400 500 630 800 1000 NS1000H 400 500 630 800 1000 NS1000L 400 500 630 800 1000 NS1250N 500 630 800 1000 1250 NS1250H 500 630 800 1000 1250 NS1600N 640 800 960 1280 1600 NS1600H 640 800 960 1280 1600 NS1600b/3200 1250 N/H 1600 2000 2500 3200 Schneider Electric

Masterpact NW L1 Micrologic 2.0 - Isd: 10 Ir NW08 800 800 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 NW10 1000 1000 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 NW12 1250 1250 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

8 8 8

12 12 12

37 37 37

8 8 8

12 12 12

T T T

8 8

12 12

37 37

8 8

10 10 10

12 12

15 15 15

37 37

37 37 37

8 8

10 10 10

12 12

15 15 15

T T

T T T

10 10

12

15 15

37

37 37

10 10

12.5 12.5 12.5

12

15 15

18.7 18.7 18.7

37

37 37

37 37 37

10

12.5 12.5

15

18.7 18.7

37

37 37

10

12.5 12.5

16 16 16

15

18.7 18.7

24 24 24

37

37 37

37 37 37

75

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: C801 to C1251, CM


Masterpact NW N1 - H1 - H2 Micrologic 5.0 - 6.0 - 7.0 - Inst: 15 In 1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 15 15 15 15 1250 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 1600 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 2000 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 2500 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 3200 48 48 48 48 48 48 48 48 48 48 60 60 60 60 60 48 48 48 48 48 48 48 48 48 48 60 60 60 60 60 48 48 48 48 48 48 48 48 48 48 4000 T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Trip unit Downstream C801N Rating (A) Setting Ir 320 400 500 630 800 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 1250 1600 2000 2500 3200

Masterpact NW N1 - H1 - H2 Micrologic 2.0 - Isd: 10 Ir 800 800 8 8 8

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1250 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 1600 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 2000 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2500 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 3200 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 4000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 5000 T T T T T 50 50 50 50 50 70 70 70 70 70 T T T T T 50 50 50 50 50 70 70 70 70 70 T T T T T 50 50 50 50 50 6300 T T T T T 63 63 63 63 63 T T T T T T T T T T 63 63 63 63 63 T T T T T T T T T T 63 63 63 63 63 800 12.5 12.5 12.5

C801H

8 8 8

12.5 15 12.5 15 12.5 15 15 12.5 15 12.5 15 12.5 15 15 15 15 15

C801L

8 8 8

C1001N

C1001H

10 10 10

15 15 15

C1001L

10 10 10

15 15 15

C1251N

C1251H

12.5 16 12.5 16 12.5 16 16

18.7 24 18.7 24 18.7 24 24

CM N/H

76

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: C801 to C1251, CM

Upstream Trip unit Downstream C801N Rating (A) Setting Ir 320 400 500 630 800 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 1250 1600 2000 2500 3200

Masterpact NW N1 - H1 - H2 Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF


NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

800 800 T T T

1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

C801H

T T T

C801L

T T T

C1001N

C1001H

T T T

C1001L

T T T

C1251N

C1251H

T T T

CM N/H

Schneider Electric

77

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: C801 to C1251, CM


Masterpact NW H3 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NW32 3200 3200 32 32 32 32 32 32 32 32 32 32 NW40 4000 4000 40 40 40 40 40 40 40 40 40 40 NW20 2000 2000 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 NW25 2500 2500 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 NW32 3200 3200 48 48 48 48 48 48 48 48 48 48 60 60 60 60 60 48 48 48 48 48 48 48 48 48 48 60 60 60 60 60 48 48 48 48 48 NW40 4000 4000 T T T T T 60 60 60 60 60 T T T T T T T T T T 60 60 60 60 60 T T T T T T T T T T Masterpact NW H3 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NW20 2000 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW25 2500 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW32 3200 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NW40 4000 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Trip unit

Masterpact NW H3 Micrologic 2.0 Isd: 10 Ir NW20 NW25 2500 2500 25 25 25 25 25 25 25 25 25 25

Downstream C801N

Rating (A) Setting Ir 320 400 500 630 800 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 1250 1600 2000 2500 3200

2000 2000 20 20 20 20 20 20 20 20 20 20

C801H

C801L

C1001N

20 20 20 20 20

25 25 25 25 25

32 32 32 32 32

40 40 40 40 40

C1001H

C1001L

C1251N

20 20 20 20 20

25 25 25 25 25

32 32 32 32 32

40 40 40 40 40

C1251H

CM N/H

78

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: C801 to C1251, CM


Masterpact NW L1 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NW12 1250 1250 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 NW16 1600 1600 16 16 16 16 16 16 16 16 16 16 NW20 2000 2000 20 20 20 20 20 20 20 20 20 20 NW08 800 800 12 12 12 NW10 1000 1000 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 NW12 1250 1250 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 18.7 NW16 1600 1600 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 NW20 2000 2000 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 Masterpact NW L1 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NW08 800 800 T T T NW10 1000 1000 T T T T 50 50 50 50 90 90 90 90 T T T NW12 1250 1250 T T T T T 50 50 50 50 50 90 90 90 90 90 T T T T 50 50 50 50 90 90 90 90 50 50 50 NW16 1600 1600 T T T T T 50 50 50 50 50 90 90 90 90 90 T T T T T 50 50 50 50 50 90 90 90 90 90 50 50 50 50 NW20 2000 2000 T T T T T 50 50 50 50 50 90 90 90 90 90 T T T T T 50 50 50 50 50 90 90 90 90 90 50 50 50 50 50

Upstream Trip unit

Masterpact NW L1 Micrologic 2.0 Isd: 10 Ir NW08 NW10 1000 1000 10 10 10 10 10 10 10 10

Downstream C801N

Rating (A) Setting Ir 320 400 500 630 800 320 400 500 630 800 320 400 500 630 800 400 500 630 800 1000 400 500 630 800 1000 400 500 630 800 1000 500 630 800 1000 1250 500 630 800 1000 1250 1250 1600 2000 2500 3200

800 800 8 8 8

C801H

8 8 8

12 12 12

50 50 50

C801L

12 12 12

90 90 90

C1001N

10 10 10

12.5 12.5 12.5 12.5

16 16 16 16 16

20 20 20 20 20

C1001H

15 15 15

50 50 50

C1001L

15 15 15

90 90 90

C1251N

12.5 12.5 12.5

16 16 16 16

20 20 20 20 20

C1251H

CM N/H

Schneider Electric

79

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: Masterpact NT, NW, Masterpact M


Masterpact NW N1 - H1 - H2 Micrologic 5.0-6.0-7.0 - Inst: 15 In 1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 1250 1600 15 18.7 24 18.7 24 24 2000 30 30 30 30 35 35 35 30 30 30 2500 37.5 37.5 37.5 37.5 37.5 65 65 65 37.5 37.5 37.5 37.5 3200 T T T T T T T T 48 48 48 48 48 4000 T T T T T T T T 60 60 60 60 60 60 5000 T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T

Upstream Trip unit Downstream Masterpact NT H1 Rating (A) Setting Ir NT06 NT08 NT10 NT12 NT16 NT06 NT08 NT10 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25

Masterpact NW N1 - H1 - H2 Micrologic 2.0 - Isd: 10 Ir 800 800

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 10 12 16 12 16 16 2000 20 20 20 20 20 20 20 20 20 20 2500 25 25 25 25 25 26 26 26 25 25 25 25 3200 32 32 32 32 32 45 45 45 32 32 32 32 32 4000 40 40 40 40 40 T T T 40 40 40 40 40 40 5000 T T T T T T T T 50 50 50 50 50 50 50 6300 800 T T T T T T T T 63 63 63 63 63 63 63 63

Masterpact NT L1 Masterpact NW N1/H1

10

12 12 12

16 16 16 16 16

15

18.7 24 18.7 24 24 18.7 24 24

Masterpact NW H2/H3

12

16 16

20 20 20

25 25 25 25

32 32 32 32 32

40 40 40 40 40 40

50 50 50 50 50 50 50

63 63 63 63 63 63 63 63

18.7 24 24

30 30 30

37.5 37.5 37.5 37.5

48 48 48 48 48

60 60 60 60 60 60

75 75 75 75 75 75 75

82 82 82 82 82 82 82 82

Masterpact NW L1

12

16 16

20 20 20

25 25 25 25 25 25 25 25

Masterpact N1/H1

12

16 16

20 20 20

32 32 32 32 32 32 32 32 32 32

40 40 40 40 40 40 40 40 40 40 40

50 50 50 50 50 50 50 50 50 50 50 50

63 63 63 63 63 63 63 63 63 63 63 63 63

18.7 24 24

30 30 30

37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5

18.7 24 24

30 30 30

48 48 48 48 48 48 48 48 48 48

60 60 60 60 60 60 60 60 60 60 60

75 75 75 75 75 T T T T T T T

94.5 94.5 94.5 94.5 94.5 T T T T T T T T

Masterpact H2

12

16 16

20 20 20

25 25 25 25

32 32 32 32 32

40 40 40 40 40 40

50 50 50 50 50 50 50

63 63 63 63 63 63 63 63

18.7 24 24

30 30 30

37.5 37.5 37.5 37.5

48 48 48 48 48

60 60 60 60 60 60

75 75 75 75 75 75 75

85 85 85 85 85 85 85 85

Masterpact L1

80

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: Masterpact NT, NW, Masterpact M

Upstream Trip unit Downstream Masterpact NT H1 Rating (A) Setting Ir NT06 NT08 NT10 NT12 NT16 NT06 NT08 NT10 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 M08 M10 M12 M16 M20 M25 M32 M40 M50 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25

Masterpact NW N1 - H1 - H2 Micrologic 5.0-6.0-7.0 - Inst: OFF


NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

800 800

1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 1250 1600 T T T T T T 2000 T T T T T T T T T T 2500 T T T T T T T T T T T T 3200 T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T

Masterpact NT L1 Masterpact NW N1/H1

T T T

T T T T T

Masterpact NW H2/H3

85

85 85

85 85 85

85 85 85 85

85 85 85 85 85

85 85 85 85 85 85

T T T T 100 100 100

T T T T 100 100 100 100

Masterpact NW L1

T T

T T T

T T T T T T T T

Masterpact N1/H1

T T

T T T

T T T T T T T T T T

T T T T T T T T T T T

T T T T T T T T T T T T

T T T T T T T T T T T T T 85 85 85 85 85 85 85 85

Masterpact H2

85

85 85

85 85 85

85 85 85 85

85 85 85 85 85

85 85 85 85 85 85

85 85 85 85 85 85 85

Masterpact L1

Schneider Electric

81

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: Masterpact NT, NW, Masterpact M


Masterpact NW H3 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NW32 3200 3200 32 32 32 32 32 32 32 32 32 32 32 32 32 NW40 4000 4000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 NW20 2000 2000 30 30 30 30 35 35 35 30 30 30 NW25 2500 2500 37.5 37.5 37.5 37.5 37.5 65 65 65 37.5 37.5 37.5 37.5 NW32 3200 3200 T T T T T 110 110 110 48 48 48 48 48 NW40 4000 4000 T T T T T T T T 60 60 60 60 60 60 Masterpact NW H3 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NW20 2000 2000 T T T T T T T T T T NW25 2500 2500 T T T T T T T T T T T T NW32 3200 3200 T T T T T T T T T T T T T NW40 4000 4000 T T T T T T T T T T T T T T

Upstream Trip unit

Masterpact NW H3 Micrologic 2.0 Isd: 10 Ir NW20 NW25 2500 2500 25 25 25 25 25 25 25 25 25 25 25 25

Downstream

Rating (A)

2000 2000 20 20 20 20 20 20 20 20 20 20

Setting Ir Masterpact NT NT06 H1 NT08 NT10 NT12 NT16 Masterpact NT NT06 L1 NT08 NT10 Masterpact NW NW08 N1/H1 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 Masterpact NW NW08 H2/H3 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 Masterpact NW NW08 L1 NW10 NW12 NW16 NW20 Masterpact M08 N1/H1 M10 M12 M16 M20 M25 M32 M40 M50 M63 Masterpact M08 H2 M10 M12 M16 M20 M25 M32 M40 M50 M63 Masterpact M08 L1 M10 M12 M16 M20 M25

20 20 20

25 25 25 25

32 32 32 32 32

40 40 40 40 40 40

30 30 30

37.5 37.5 37.5 37.5

48 48 48 48 48

60 60 60 60 60 60

65 65 65

65 65 65 65

65 65 65 65 65

65 65 65 65 65 65

20 20 20

25 25 25 25 25 25 25 25

32 32 32 32 32 32 32 32 32 32

45 45 45 45 45 40 40 40 40 40 40

30 30 30

37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5

48 48 48 48 48 48 48 48 48 48

60 60 60 60 60 60 60 60 60 60 60

100 100 100

100 100 100 100 T T T T

100 100 100 100 100 T T T T T

100 100 100 100 100 T T T T T T

25 25 25 25

32 32 32 32 32

40 40 40 40 40 40

37.5 37.5 37.5 37.5

48 48 48 48 48

60 60 60 60 60 60

65 65 65 65

65 65 65 65 65

65 65 65 65 65 65

82

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact NW Downstream: Masterpact NT, NW, Masterpact M


Masterpact NW L1 Micrologic 5.0 - 6.0 - 7.0 Inst: 15 In NW12 1250 1250 12.5 12.5 NW16 1600 1600 16 16 16 NW20 2000 2000 20 20 20 20 20 20 20 20 20 20 NW08 800 800 NW10 1000 1000 15 NW12 1250 1250 18.7 18.7 NW16 1600 1600 24 24 24 Masterpact NW L1 Micrologic 5.0 - 6.0 - 7.0 Inst: OFF NW20 2000 2000 30 30 30 30 30 30 30 30 30 30 NW08 800 800 NW10 1000 1000 37 NW12 1250 1250 37 37 NW16 1600 1600 37 37 37 NW20 2000 2000 37 37 37 37 T T T 37 37 37

Upstream Trip unit

Masterpact NW L1 Micrologic 2.0 Isd: 10 Ir NW08 NW10 1000 1000 10

Downstream

Rating (A)

800 800

Setting Ir Masterpact NT NT06 H1 NT08 NT10 NT12 NT16 Masterpact NT NT06 L1 NT08 NT10 Masterpact NW NW08 N1/H1 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 Masterpact NW NW08 H2/H3 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 Masterpact NW NW08 L1 NW10 NW12 NW16 NW20 Masterpact M08 N1/H1 M10 M12 M16 M20 M25 M32 M40 M50 M63 Masterpact M08 H2 M10 M12 M16 M20 M25 M32 M40 M50 M63 Masterpact M08 L1 M10 M12 M16 M20 M25

10

12.5 12.5 12.5

16 16 16 16 16

15

18.7 18.7 18.7

24 24 24 24 24

T T 37

T T T 37 37

12.5

16 16

20 20 20

18.7

24 24

30 30 30

37

37 37

37 37 37

12.5

16 16

20 20 20

18.7

24 24

30 30 30

37

37 37

37 37 37

12.5

16 16

20 20 20

18.7

24 24

30 30 30

37

37 37

37 37 37

12.5

16 16

20 20 20

18.7

24 24

30 30 30

37

37 37

37 37 37

12.5

16 16

20 20 20

18.7

24 24

30 30 30

37

37 37

37 37 37

Schneider Electric

83

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: Multi 9, NS100 to 630, NSC100N, NSA160, NB225 to 600
Masterpact N1 - H1 - H2 Trip unit STR38S - 58U - Inst: ON - position maxi 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 1000 T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 T T T T T 45 45 45 45 45 45 45 45 45 45 1250 T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 T T T T T 45 45 45 45 45 45 45 45 45 45 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Downstream DPN, DPN N XC40 C60 NC100 NC125 NG125N/H/L C120N/H NS100N/H/L NS160N/H/L NS250N/H/L NS400N Rating (A) Setting Ir

Masterpact N1 - H1 - H2 Trip unit STR28D 800 T T T T T T T T T T 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 1000 T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 T T T T T 45 45 45 45 45 45 45 45 45 45 1250 T T T T T T T T T T T T T T T T T T T T 70 70 70 70 70 T T T T T 45 45 45 45 45 45 45 45 45 45

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M60 M63

NS400H

NS400L

NS630N

NS630H

NS630L

160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630

NSC100N NS125E NSA160N NB225N NB400N NB600N

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

84

Schneider Electric

Protection discrimination Upstream: Masterpact M Downstream: Multi 9, NS100 to 630, NSC100N, NSA160, NB225 to 600
Upstream Downstream DPN, DPN N XC40 C60 NC100 NC125 NG125 C120 NS100N/H/L NS160N/H/L NS250N/H/L NS400N Rating (A) Setting Ir Masterpact N1 - H1 - H2 Trip unit STR68U - Inst: ON - position maxi 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Masterpact N1 - H1 Trip unit STR38S - 58U - Inst: OFF 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M60 M63

NS400H

NS400L

NS630N

NS630H

NS630L

160 200 250 320 400 160 200 250 320 400 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 250 320 400 500 630

NSC100N NS125E NSA160N NB225N NB400N NB600N

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

Schneider Electric

85

Complementary technical information

Masterpact N1 - H1 Trip unit STR68U - Inst: OFF Downstream Rating (A) M08 M10 M12 M16 M20 M25 Setting Ir 800 1000 1250 1600 2000 2500 DPN, DPN N T T T T T T XC40 T T T T T T C60 T T T T T T NC100/125 T T T T T T NG125 T T T T T T C120 T T T T T T NS100N T T T T T T y 32 Trip unit TM-D 40 T T T T T T 50 T T T T T T 63 T T T T T T 80 T T T T T T 100 T T T T T T NS100H/L T T T T T T y 32 Trip unit TM-D 40 T T T T T T 50 T T T T T T 63 T T T T T T 80 T T T T T T 100 T T T T T T NS160N T T T T T T y 63 Trip unit TM-D 80 T T T T T T 100 T T T T T T 125 T T T T T T 160 T T T T T T NS160H/L T T T T T T y 63 Trip unit TM-D 80 T T T T T T 100 T T T T T T 125 T T T T T T 160 T T T T T T NS250N T T T T T T y 100 Trip unit TM-D 125 T T T T T T 160 T T T T T T 200 T T T T T T 250 T T T T T T NS250H/L T T T T T T y 100 Trip unit TM-D 125 T T T T T T 160 T T T T T T 200 T T T T T T 250 T T T T T T NS100N 40 T T T T T T Trip unit STR22SE 100 T T T T T T NS100H/L 40 T T T T T T Trip unit STR22SE 100 T T T T T T NS160N 40 T T T T T T Trip unit STR22SE 100 T T T T T T 160 T T T T T T NS160H/L 40 T T T T T T Trip unit STR22SE 100 T T T T T T 160 T T T T T T NS250N T T T T T T y 100 Trip unit STR22SE 160 T T T T T T 250 T T T T T T NS250H/L T T T T T T y 100 Trip unit STR22SE 160 T T T T T T 250 T T T T T T NS400N/H/L 160 T T T T T T 200 T T T T T T 250 T T T T T T 320 T T T T T T 400 T T T T T T NS630N/H/L 250 T T T T T T 320 T T T T T T 400 T T T T T T 500 T T T T T T 630 T T T T T T

Upstream

Masterpact L Trip unit STR38S - 58U M32 M40 M50 M63 M08 M10 M12 M16 M20 3200 4000 5000 6300 800 1000 1250 1600 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 7 9 9 T T T T T T 7 9 9 T T T T T T 7 9 9 T T T T T T 7 9 9 T T T T T T 7 9 9 T T T T T T 7 9 9 T T T T T T 7 9 9 35 35 T T T T 7 9 9 35 35 T T T T 7 9 9 35 35 T T T T 7 9 9 35 35 T T T T 7 9 9 35 35 T T T T 7 9 9 35 35 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 30 30 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 7 9 9 25 25 T T T T 8 10 10 T T T T T T 8 10 10 T T T T T T 8 10 10 35 35 T T T T 8 10 10 35 35 T T T T 8 10 10 30 30 T T T T 8 10 10 30 30 T T T T 8 10 10 30 30 T T T T 8 10 10 30 30 T T T T 8 10 10 30 30 T T T T 8 10 10 30 30 T T T T 8 10 10 25 25 T T T T 8 10 10 25 25 T T T T 8 10 10 25 25 T T T T 8 10 10 25 25 T T T T 8 10 10 25 25 T T T T 8 10 10 25 25 T T T T 8 10 10 12 12 T T T T 8 10 10 12 12 T T T T 8 10 10 12 12 T T T T 8 10 10 12 12 T T T T 8 10 10 12 12 T T T T 10 10 10 10 T T T T 10 10 10 10 T T T T 10 10 10 10 T T T T 10 10 10 10 T T T T 10 10 10 10

Masterpact L Trip unit STR68U M25 M08 M10 M12 M16 2500 800 1000 1250 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 25 25 25 T T 25 25 25 T T 25 25 25 T T 25 25 25 T T 25 25 25 T T 25 25 25 T 60 25 25 25 50 60 25 25 25 50 60 25 25 25 50 60 25 25 25 50 60 25 25 25 50 60 25 25 25 50 T 18 18 18 T T 18 18 18 T T 18 18 18 T T 18 18 18 T T 18 18 18 T 50 18 18 18 40 50 18 18 18 40 50 18 18 18 40 50 18 18 18 40 50 18 18 18 40 T 16 16 16 T T 16 16 16 T T 16 16 16 T T 16 16 16 T T 16 16 16 T 36 16 16 16 36 36 16 16 16 36 36 16 16 16 36 36 16 16 16 36 36 16 16 16 36 T 25 25 25 T T 25 25 25 T 60 25 25 25 50 60 25 25 25 50 T 18 18 18 T T 18 18 18 T T 18 18 18 T 50 18 18 18 40 50 18 18 18 40 50 18 18 18 40 T 16 16 16 T T 16 16 16 T T 16 16 16 T 36 16 16 16 36 36 16 16 16 36 36 16 16 16 36 18 8 10 10 12 18 8 10 10 12 18 8 10 10 12 18 8 10 10 12 18 8 10 10 12 12 8 10 10 12 12 8 10 10 12 12 8 10 10 12 12 8 10 10 12 12 8 10 10 12

M20 2000 T T T T T T T T T T T T 50 50 50 50 50 50 T T T T T 40 40 40 40 40 T T T T T 36 36 36 36 36 T T 50 50 T T T 40 40 40 T T T 36 36 36 12 12 12 12 12 12 12 12 12 12

M25 2500 T T T T T T T T T T T T 50 50 50 50 50 50 T T T T T 40 40 40 40 40 T T T T T 36 36 36 36 36 T T 50 50 T T T 40 40 40 T T T 36 36 36 12 12 12 12 12 12 12 12 12 12

NSC100N NS125E NSA160N NB225N NB400N NB600N

y 50 u 50

T T T T T T T

T T T T T T T

T T T T T T T

T T T T T T T

T T T T T T T

T T T T T T T

T T T T T T T

T T T T T T T

T T T T T T T

T T T T T T T

T 7 T 10 7 8

T 9 T 15 9 10 10

T 9 T 15 9 10 10

T T T T 25 12 10

T T T T 25 12 10

T T T T T 18 12

T T T T 16 8

T T T T 16 10 10

T T T T 16 10 10

T T T T T 12 12

T T T T T 12 12

T T T T T 12 12

86

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: NS630b to NS3200


Masterpact N1 - H1 - H2 STR38S/58U - Inst: ON - position maxi

Upstream Trip unit Downstream NS630bN Rating (A) 250 320 400 500 630 NS630bH 250 320 400 500 630 NS630bL 250 320 400 500 630 NS800N 320 400 500 630 800 NS800H 320 400 500 630 800 NS800L 320 400 500 630 800 NS1000N 400 500 630 800 1000 NS1000H 400 500 630 800 1000 NS1000L 400 500 630 800 1000 NS1250N 500 630 800 1000 1250 NS1250H 500 630 800 1000 1250 NS1600N 640 800 960 1280 1600 NS1600H 640 800 960 1280 1600 NS1600b/3200 1250 N/H 1600 2000 2500 3200

Masterpact N1 - H1 - H2 STR28D 800 8 8 8 8 8 8 8 8 8 8 8 8 1000 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1250 12 12 12 12 12 12 12 12 12 12 16 16 16 16 16 12 12 12 12 12 12 12 12 12 12 16 16 16 16 16 12 12 12 12 12 12 12 12 12 12 12 12 1600 16 16 16 16 16 16 16 16 16 16 30 30 30 30 30 16 16 16 16 16 16 16 16 16 16 30 30 30 30 30 16 16 16 16 16 16 16 16 16 16 18 18 18 18 18 16 16 16 16 16 16 16 16 2000 20 20 20 20 20 20 20 20 20 20 45 45 45 45 45 20 20 20 20 20 20 20 20 20 20 45 45 45 45 45 20 20 20 20 20 20 20 20 20 20 31 31 31 31 31 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2500 25 25 25 25 25 25 25 25 25 25 90 90 90 90 90 25 25 25 25 25 25 25 25 25 25 90 90 90 90 90 25 25 25 25 25 25 25 25 25 25 54 54 54 54 54 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 3200 32 32 32 32 32 32 32 32 32 32 T T T T T 32 32 32 32 32 32 32 32 32 32 T T T T T 32 32 32 32 32 32 32 32 32 32 T T T T T 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 4000 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 5000 T T T T T 50 50 50 50 50 T T T T T T T T T T 50 50 50 50 50 T T T T T T T T T T 50 50 50 50 50 T T T T T T T T T T 50 50 50 50 50 T T T T T 50 50 50 50 50

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 6300 800 T T T T T 63 63 63 63 63 T T T T T T T T T T 63 63 63 63 63 T T T T T T T T T T 63 63 63 63 63 T T T T T T T T T T 63 63 63 63 63 T T T T T 63 63 63 63 63 1000 28 28 28 28 28 28 28 28 28 28 70 70 70 70 70 28 28 28 28 28 28 28 28 70 70 70 70 1250 28 28 28 28 28 28 28 28 28 28 70 70 70 70 70 28 28 28 28 28 28 28 28 28 28 70 70 70 70 70 28 28 28 28 28 28 28 28 70 70 70 70 1600 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 2000 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 2500 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 3200 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 4000 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 5000 T T T T T 50 50 50 50 50 T T T T T T T T T T 50 50 50 50 50 T T T T T T T T T T 50 50 50 50 50 T T T T T T T T T T 50 50 50 50 50 T T T T T 50 50 50 50 50 50 50 50 50 50 6300 T T T T T 63 63 63 63 63 T T T T T T T T T T 63 63 63 63 63 T T T T T T T T T T 63 63 63 63 63 T T T T T T T T T T 63 63 63 63 63 T T T T T 63 63 63 63 63 63 63 63 63 63

Schneider Electric

87

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: NS630b to NS3200


Masterpact N1 - H1 STR38S/58U - Inst: OFF

Upstream Trip unit Rating (A) Downstream NS630bN Setting Ir 250 320 400 500 630 NS630bH 250 320 400 500 630 NS630bL 250 320 400 500 630 NS800N 320 400 500 630 800 NS800H 320 400 500 630 800 NS800L 320 400 500 630 800 NS1000N 400 500 630 800 1000 NS1000H 400 500 630 800 1000 NS1000L 400 500 630 800 1000 NS1250N 500 630 800 1000 1250 NS1250H 500 630 800 1000 1250 NS1600N 640 800 960 1280 1600 NS1600H 640 800 960 1280 1600 NS1600b/3200 1250 N/H 1600 2000 2500 3200

Masterpact N1 - H1 - H2 STR68U - Inst: ON - position maxi

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 T T T T 1250 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 T T T T 1600 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 40 40 T T T T T 40 40 40 40 40 40 40 40 2000 T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T 65 65 65 65 40 2500 T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T 65 65 65 65 65 40 40 3200 T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T 65 65 65 65 65 40 40 40 4000 T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T 65 65 65 65 65 40 40 40 40 5000 T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T 65 65 65 65 65 50 50 50 50 50 6300 T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T T T T T T 65 65 65 65 65 T T T T T 65 65 65 65 65 63 63 63 63 63 800 T T T T T T T T T T T T T T T 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T

T T T

T T T

T T T

T T T

T T T

88

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: NS630b to NS3200


Masterpact L STR38S/58U Masterpact L STR68U

Upstream Trip unit

Masterpact N1 - H1 STR68U - Inst: OFF

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M08 M10 M12 M16 M20 M25 Rating (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500 Downstream NS630bN Setting Ir 250 320 400 500 630 NS630bH 250 320 400 500 630 NS630bL 250 320 400 500 630 NS800N 320 400 500 630 800 NS800H 320 400 500 630 800 NS800L 320 400 500 630 800 NS1000N 400 500 630 800 1000 NS1000H 400 500 630 800 1000 NS1000L 400 500 630 800 1000 NS1250N 500 630 800 1000 1250 NS1250H 500 630 800 1000 1250 NS1600N 640 800 960 1280 1600 NS1600H 640 800 960 1280 1600 NS1600b/3200 1250 N/H 1600 2000 2500 3200 800 T T T T T T T T T T T T T T T 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 800 1000 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T 10 T T 10 T 10 T 10 T 10 T T 10 T 10 T 10 T 10 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1250 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1600 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 12 2000 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 15 2500 800 1000 15 10 15 10 15 10 15 10 15 10 15 10 15 10 15 10 15 10 15 10 25 10 25 10 25 10 25 10 25 10 15 10 15 10 15 10 15 10 15 15 10 15 10 15 10 15 10 15 25 10 25 10 25 10 25 10 25 15 15 15 15 15 15 15 15 15 15 25 25 25 25 25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 1250 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1600 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 12 2000 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 15 2500 15 15 15 15 15 15 15 15 15 15 25 25 25 25 25 15 15 15 15 15 15 15 15 15 15 25 25 25 25 25 15 15 15 15 15 15 15 15 15 15 25 25 25 25 25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

T T T

T T T

T T T

T T T

T T T

T T T

12 12 12

12 12 12

Schneider Electric

89

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: Masterpact NT, NW


Masterpact N1 - H1 - H2 STR38S/58U - Inst: ON - position maxi 1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 1250 1600 28 28 40 28 40 40 2000 40 40 40 40 120 120 120 40 40 40 2500 40 40 40 40 40 120 120 120 40 40 40 40 3200 40 40 40 40 40 120 120 120 40 40 40 40 40 4000 40 40 40 40 40 120 120 120 40 40 40 40 40 40 5000 T T T T T T T T 50 50 50 50 50 50 50 6300 T T T T T T T T 63 63 63 63 63 63 63 63

Upstream Masterpact N1 - H1 - H2 Trip unit STR28D

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 Rating (A) 800 Downstream Masterpact NT N1/H1 Setting Ir NT06 NT08 NT10 NT12 NT16 NT06 NT08 NT10 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 10 12 16 12 16 16 2000 20 20 20 20 20 20 20 20 20 20 2500 25 25 25 25 25 25 25 25 25 25 25 25 3200 32 32 32 32 32 32 32 32 32 32 32 32 32 4000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 5000 T T T T T T T T 50 50 50 50 50 50 50 6300 800 T T T T T T T T 63 63 63 63 63 63 63 63

Masterpact NT L1 Masterpact NW N1/H1/H2/H3

10

12 12

16 16 16 12.5 16 16

70

70 70 28

120 120 120 40 40

Masterpact NW L1

12.5 16 16

20 20 20

25 25 25 25

32 32 32 32 32

40 40 40 40 40

50 50 50 50 50

63 63 63 63 63

30

70 70

70 70 70

70 70 70 70

70 70 70 70 70

70 70 70 70 70

T T T T T

T T T T T

Upstream Masterpact N1 - H1 - H2 Trip unit STR68U - Inst: ON - position maxi

Masterpact N1 - H1 STR38S/58 - Inst: OFF 1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 1250 1600 T T T T T T 2000 T T T T T T T T T T 2500 T T T T T T T T T T T T 3200 T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 Rating (A) 800 Downstream Masterpact NT N1/H1 Setting Ir 800 NT06 NT08 NT10 NT12 NT16 NT06 NT08 NT10 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 40 40 40 40 40 40 2000 T T T T T T T 65 65 65 2500 T T T T T T T T 65 65 65 65 3200 T T T T T T T T 65 65 65 65 65 4000 T T T T T T T T 65 65 65 65 65 65 5000 T T T T T T T T 65 65 65 65 65 65 65 6300 800 T T T T T T T T 65 65 65 65 65 65 65 65

Masterpact NT L1 Masterpact NW N1/H1/H2/H3

T T 40

T T T 40 40

T T T

T T T T T

Masterpact NW L1

40

40 40

95 95 95

95 95 95 95

95 95 95 95 95

95 95 95 95 95

95 95 95 95 95

95 95 95 95 95

T T

T T T

T T T T

T T T T T

T T T T T

T T T T T

T T T T T

90

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: Masterpact NT, NW


Masterpact L STR38S/58U Masterpact L STR68U

Upstream Masterpact N1 - H1 Trip unit STR68U - Inst: OFF

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M08 M10 M12 M16 M20 M25 Rating (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500 Downstream Setting Ir Masterpact NT NT06 N1/H1 NT08 NT10 NT12 NT16 Masterpact NT NT06 L1 NT08 NT10 Masterpact NW NW08 N1/H1/H2/H3 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 Masterpact NW NW08 L1 NW10 NW12 NW16 NW20 800 1000 1250 1600 T T T T T T 2000 T T T T T T T T T T 2500 T T T T T T T T T T T T 3200 T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T 6300 800 1000 T 10 T T T T T 10 T T T T T T T T T T 1250 1600 2000 10 12 12 10 12 12 12 12 12 10 10 15 15 15 15 15 15 2500 800 1000 15 10 15 15 15 15 25 10 25 25 1250 1600 2000 10 12 12 10 12 12 12 12 12 10 10 15 15 15 15 15 15 2500 15 15 15 15 15 25 25 25

T T T

T T T T T

T T

T T T

T T T T

T T T T T

T T T T T

T T T T T

T T T T T

Schneider Electric

91

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: C801 to C1251, CM, Masterpact


Masterpact N1 - H1 - H2 Trip unit STR38S - 58U - Inst: ON - position maxi 2500 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 20 20 3200 32 32 32 32 32 32 32 32 32 32 35 35 35 35 35 32 32 32 32 32 32 32 32 32 32 35 35 35 35 35 32 32 32 32 32 32 32 32 32 32 25 25 25 4000 40 40 40 40 40 40 40 40 40 40 50 50 50 50 50 40 40 40 40 40 40 40 40 40 40 50 50 50 50 50 40 40 40 40 40 40 40 40 40 40 32 32 32 32 40 40 40 40 40 40 5000 45 45 45 45 45 45 45 45 45 45 90 90 90 90 90 45 45 45 45 45 45 45 45 45 45 90 90 90 90 90 45 45 45 45 45 45 45 45 45 45 40 40 40 40 40 50 50 50 50 50 50 50 6300 800 T T T T T 65 65 65 65 65 100 100 100 100 100 T T T T T 65 65 65 65 65 100 100 100 100 100 T T T T T 65 65 65 65 65 50 50 50 50 50 63 63 63 63 63 63 63 63 1000 30 30 30 30 30 30 30 30 40 40 40 40 1250 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 70 70 70 70 1600 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 2000 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 45 45 35 2500 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 45 45 35 35 3200 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 45 45 70 70 70 70 70 45 45 45 45 45 45 45 45 45 45 40 40 40 4000 T T T T T 50 50 50 50 50 80 80 80 80 80 T T T T T 50 50 50 50 50 80 80 80 80 80 T T T T T 50 50 50 50 50 40 40 40 40 40 40 40 40 40 40 5000 T T T T T 60 60 60 60 60 110 110 110 110 110 T T T T T 60 60 60 60 60 110 110 110 110 110 T T T T T 60 60 60 60 60 50 50 50 50 50 50 50 50 50 50 50 50 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 63 63 63 63 63 63 63 63 63 63 63 63 63

Upstream Downstream C801N Trip unit STR25DE, 35SE/GE, 55UE Rating (A)

Masterpact N1 - H1 - H2 Trip unit STR28D (1)

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M60 M63

Setting Ir 800 1000 1250 1600 2000 320 10 12 16 20 400 10 12 16 20 500 10 12 16 20 630 10 12 16 20 800 12 16 20 C801H 320 10 12 16 20 Trip unit 400 10 12 16 20 STR25DE, 500 10 12 16 20 35SE/GE, 55UE 630 10 12 16 20 800 12 16 20 C801L 320 10 12 16 20 Trip unit 400 10 12 16 20 STR25DE, 500 10 12 16 20 35SE/GE, 55UE 630 10 12 16 20 800 12 16 20 C1001N 400 12 16 20 Trip unit 500 12 16 20 STR25DE, 630 12 16 20 35SE/GE, 55UE 800 12 16 20 1000 16 20 C1001H 400 12 16 20 Trip unit 500 12 16 20 STR25DE, 630 12 16 20 35SE/GE, 55UE 800 12 16 20 1000 16 20 C1001L 400 12 16 20 Trip unit 500 12 16 20 STR25DE, 630 12 16 20 35SE/GE, 55UE 800 12 16 20 1000 16 20 C1251N 500 16 20 Trip unit 630 16 20 STR25DE, 800 16 20 35SE/GE, 55UE 1000 16 20 1250 20 C1251H 500 16 20 Trip unit 630 16 20 STR25DE, 800 16 20 35SE/GE, 55UE 1000 16 20 1250 20 CM 1250 15 Trip unit ST 1600 CM1,2,3 2000 2500 3200 Masterpact M08 12 16 20 N1, H1, H2 M10 16 20 Trip unit M12 20 STR28D M16 M20 M25 M32 M40 M50 M63 Masterpact L M08 Trip unit M10 STR38S, M12 58U, 68U M16 M20 M25 (1) Discrimination with Compact C trip unit STR25DE only.

25 25 25 25

32 32 32 32 32

30

35 35

35 35 35

35 35 35 35

40 40 40 40 40

50

50 50

50 50 50

50 50 50 50

50 50 50 50 50

55 55 55 55 55 55

60 63 63 63 63 60

80 80 80 80 80 80

92

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: C801 to C1251, CM, Masterpact


Masterpact N1 - H1 Trip unit STR38S - 58U - Inst: OFF 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 65 65 T T T T T T T 6300 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 65 65 T T T T T T T T 1000 T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Upstream Downstream C801N Trip unit STR25DE, 35SE/GE, 55UE

Masterpact N1 - H1 - H2 Trip unit STR68U - Inst: ON - position maxi

Rating (A) M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M60 M63 800 1000 T T T T 50 50 50 50 T T T T 1250 T T T T T 50 50 50 50 50 T T T T T T T T T 50 50 50 50 T T T T 1600 T T T T T 50 50 50 50 50 T T T T T T T T T T 50 50 50 50 50 T T T T T T T T T 50 50 50 50 2000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 65 T T T T T T

Setting Ir 320 400 500 630 800 C801H 320 Trip unit 400 STR25DE, 500 35SE/GE, 55UE 630 800 C801L 320 Trip unit 400 STR25DE, 500 35SE/GE, 55UE 630 800 C1001N 400 Trip unit 500 STR25DE, 630 35SE/GE, 55UE 800 1000 C1001H 400 Trip unit 500 STR25DE, 630 35SE/GE, 55UE 800 1000 C1001L 400 Trip unit 500 STR25DE, 630 35SE/GE, 55UE 800 1000 C1251N 500 Trip unit 630 STR25DE, 800 35SE/GE, 55UE 1000 1250 C1251H 500 Trip unit 630 STR25DE, 800 35SE/GE, 55UE 1000 1250 CM 1250 Trip unit ST 1600 CM1,2,3 2000 2500 3200 Masterpact M08 N1, H1, H2 M10 Trip unit M12 STR28D M16 M20 M25 M32 M40 M50 M63 Masterpact L M08 Trip unit STR38S, M10 58U, 68U M12 M16 M20 M25

T T

T T T

T T T T

T T T T T

T T

T T T

T T T T

T T T T T

T T

T T T

T T T T

T T T T T

T T T T T T

T T T T T T

T T T T T T

T T

T T T

T T T T

T T T T T

T T T T T T

T T T T T T

T T T T T T

Schneider Electric

93

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: C801 to C1251, CM, Masterpact


Masterpact L (1) Trip unit STR38S - 58U 3200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 4000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 65 T T T T T T 5000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 65 65 T T T T T T T 6300 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65 65 65 65 T T T T T T T T 1000 8 8 8 8 8 8 8 8 8 8 8 8 1250 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1600 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 2000 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 Masterpact L (1) Trip unit STR68U 2500 800 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 1000 8 8 8 8 8 8 8 8 8 8 8 8 1250 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1600 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 2000 12 12 12 12 12 12 2 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 2500 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

Upstream Masterpact N1 - H1 Trip unit STR68U - Inst: OFF Downstream C801N Trip unit STR25DE, 35SE/GE, 55UE Setting Ir 800 1000 1250 1600 2000 320 T T T T 400 T T T T 500 T T T T 630 T T T T 800 T T T C801H 320 T T T T Trip unit 400 T T T T STR25DE, 500 T T T T 35SE/GE, 55UE 630 T T T T 800 T T T C801L 320 T T T T Trip unit 400 T T T T STR25DE, 500 T T T T 35SE/GE, 55UE 630 T T T T 800 T T T C1001N 400 T T T Trip unit 500 T T T STR25DE, 630 T T T 35SE/GE, 55UE 800 T T T 1000 T T C1001H 400 T T T Trip unit 500 T T T STR25DE, 630 T T T 35SE/GE, 55UE 800 T T T 1000 T T C1001L 400 T T T Trip unit 500 T T T STR25DE, 630 T T T 35SE/GE, 55UE 800 T T T 1000 T T C1251N 500 T T Trip unit 630 T T STR25DE, 800 T T 35SE/GE, 55UE 1000 T T 1250 T C1251H 500 T T Trip unit 630 T T STR25DE, 800 T T 35SE/GE, 55UE 1000 T T 1250 T CM 1250 65 Trip unit ST 1600 CM1,2,3 2000 2500 3200 Masterpact M08 T T T N1, H1, H2 M10 T T Trip unit STR28D M12 T M16 M20 M25 M32 M40 M50 M63 Masterpact L M08 T T T Trip unit STR38S, M10 T T 58U, 68U M12 T M16 M20 M25 (1) Discrimination with Compact C trip unit STR25DE only. 2500 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 65 65

Rating (A) M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M08 M10 M12 M16 M20 M25

T T T T

T T T T T

10

12 12

12 12 12

15 15 15 15

10

12 12

12 12 12

15 15 15 15

T T T T

T T T T T

T T T T T T

T T T T T T

T T T T T T

94

Schneider Electric

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: Masterpact NT, NW


Masterpact N1 - H1 - H2 STR38S/58U - Inst: ON - position maxi 1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 1250 1600 30 30 40 30 40 40 2000 40 40 40 40 T T T 40 40 40 2500 40 40 40 40 40 T T T 40 40 40 40 3200 40 40 40 40 40 T T T 40 40 40 40 40 4000 40 40 40 40 40 T T T 40 40 40 40 40 40 5000 T T T T T T T T 50 50 50 50 50 50 50 6300 T T T T T T T T 63 63 63 63 63 63 63 63

Upstream Trip unit Downstream Masterpact NT H1 Rating (A) Setting Ir NT06 NT08 NT10 NT12 NT16 NT06 NT08 NT10 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20

Masterpact N1 - H1 - H2 STR28D 800 800

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 10 12 16 12 16 16 2000 20 20 20 20 20 20 20 20 20 20 2500 25 25 25 25 25 25 25 25 25 25 25 25 3200 32 32 32 32 32 32 32 32 32 32 32 32 32 4000 40 40 40 40 40 40 40 40 40 40 40 40 40 40 5000 T T T T T T T T 50 50 50 50 50 50 50 6300 800 T T T T T T T T 63 63 63 63 63 63 63 63

Masterpact NT L1 Masterpact NW N1/H1/H2/H3

10

12 12 12

16 16 16 16 16

70

100 100 28

T T T 40 40

Masterpact NW L1

12

16 16

20 20 20

25 25 25 25

32 32 32 32 32

40 40 40 40 40

50 50 50 50 50

63 63 63 63 63

30

40 40

40 40 40

40 40 40 40

40 40 40 40 40

40 40 40 40 40

60 60 60 60 60

T T T T T

Upstream Trip unit Downstream Masterpact NT H1 Rating (A) rglage Ir NT06 NT08 NT10 NT12 NT16 NT06 NT08 NT10 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20

Masterpact N1 - H1 - H2 STR68U - Inst: ON - position maxi 800 800

Masterpact N1 - H1 STR38S/58U - Inst: OFF 1000 1250 1600 2000 2500 3200 4000 5000 6300 1000 1250 1600 T T T T T T 2000 T T T T T T T T T T 2500 T T T T T T T T T T T T 3200 T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T 6300 T T T T T T T T T T T T T T T T

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 T T T T T T 2000 T T T T T T T 65 65 65 2500 T T T T T T T T 65 65 65 65 3200 T T T T T T T T 65 65 65 65 65 4000 T T T T T T T T 65 65 65 65 65 65 5000 T T T T T T T T 65 65 65 65 65 65 65 6300 800 T T T T T T T T 65 65 65 65 65 65 65 65

Masterpact NT L1 Masterpact NW N1/H1/H2/H3

T T 65

T T T 65 65

T T T

T T T T T

Masterpact NW L1

95

95 95

T T T

T T T T

T T T T T

T T T T T

T T T T T

T T T T T

T T

T T T

T T T T

T T T T T

T T T T T

T T T T T

T T T T T

Schneider Electric

95

Complementary technical information

Protection discrimination Upstream: Masterpact M Downstream: Masterpact NT, NW


Masterpact L STR38S/58U Masterpact L STR68U

Upstream Trip unit Downstream

Masterpact N1 - H1 STR68U - Inst: OFF

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M08 M10 M12 M16 M20 M25 Rating (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500 800 1000 1250 1600 T T T T T T 2000 T T T T T T T T T T 2500 T T T T T T T T T T T T 3200 T T T T T T T T T T T T T 4000 T T T T T T T T T T T T T T 5000 T T T T T T T T T T T T T T T 6300 800 1000 T 10 T T T T T 10 T T T T T T T T T T 1250 1600 2000 10 12 12 10 12 12 12 12 12 10 10 15 15 15 15 15 15 2500 800 1000 15 10 15 15 15 15 25 10 25 25 1250 1600 2000 10 12 12 10 12 12 12 12 12 10 10 15 15 15 15 15 15 2500 15 15 15 15 15 25 25 25 rglage Ir Masterpact NT NT06 H1 NT08 NT10 NT12 NT16 Masterpact NT NT06 L1 NT08 NT10 Masterpact NW NW08 N1/H1/H2/H3 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 Masterpact NW NW08 L1 NW10 NW12 NW16 NW20

T T T

T T T T T

T T

T T T

T T T T

T T T T T

T T T T T

T T T T T

T T T T T

96

Schneider Electric

Complementary technical information

Motor protection discrimination Upstream: Compact NSC100N Downstream: GV2, Integral 18, 32
NSC100N 18 kA Trip unit TM-D

Upstream

Downstream

Trip unit

Rating (A)

16

20

25

32 T T T T T T T T 0.6 0.6

40 T T T T T T T T 0.6 0.6

50 T T T T T T T T 1 1 1

63 T T T T T T T T 1 1 1 1

70 T T T T T T T T 1 1 1 1 1

80 T T T T T T T T 1 1 1 1 1 1 T T T T T T T T 1 1 1 1 1 1 T T T T T T 1 1 1 1 1 T T T T T T T T 1 1 1 1 T T T T T T 1 1 1 1

100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

or Th. relay Setting Ir GV2 M01 integrated 0.1 to 0.16 T T T GV2 M02 integrated 0.16 to 0.25 T T T GV2 M03 integrated 0.25 to 0.40 T T T GV2 M04 integrated 0.40 to 0.63 T T T GV2 M05 integrated 0.63 to 1 T T T GV2 M06 integrated 1 to 1.6 T T T GV2 M07 integrated 1.6 to 2.5 T T T GV2 M08 integrated 2.5 to 4 T T T GV2 M10 integrated 4 to 6.3 0.6 0.6 GV2 M14 integrated 6 to 10 GV2 M16 integrated 9 to 14 GV2 M20 integrated 13 to 18 GV2 M21 integrated 17 to 23 GV2 M22 integrated 20 to 25 GV2 M32 integrated 24 to 32 GV2 P01 integrated 0.1 to 0.16 T T T GV2 P02 integrated 0.16 to 0.25 T T T GV2 P03 integrated 0.25 to 0.40 T T T GV2 P04 integrated 0.40 to 0.63 T T T GV2 P05 integrated 0.63 to 1 T T T GV2 P06 integrated 1 to 1.6 T T T GV2 P07 integrated 1.6 to 2.5 T T T GV2 P08 integrated 2.5 to 4 T T T GV2 P10 integrated 4 to 6.3 0.6 0.6 GV2 P14 integrated 6 to 10 GV2 P16 integrated 9 to 14 GV2 P20 integrated 13 to 18 GV2 P21 integrated 17 to 23 GV2 P22 integrated 20 to 25 GV2 L03 LR2 D13 03 0.25 to 0.40 T T T GV2 L04 LR2 D13 04 0.40 to 0.63 T T T GV2 L05 LR2 D13 05 0.63 to 1 T T T GV2 L06 LR2 D13 06 1 to 1.6 T T T GV2 L07 LR2 D13 07 1.6 to 2.5 T T T GV2 L08 LR2 D13 08 2.5 to 4 T T T GV2 L10 LR2 D13 10 4 to 6.3 0.6 0.6 GV2 L14 LR2 D13 14 7 to 10 GV2 L16 LR2 D13 16 9 to 13 GV2 L20 LR2 D13 21 12 to 18 GV2 L22 LR2 D13 22 17 to 25 Integral 18 LB1-LB03P01 0.1 to 0.16 T T T LD1-LB030 LB1-LB03P02 0.16 to 0.25 T T T LB1-LB03P03 0.25 to 0.40 T T T LB1-LB03P04 0.40 to 0.63 T T T LB1-LB03P05 0.63 to 1 T T T LB1-LB03P06 1 to 1.6 T T T LB1-LB03P07 1.6 to 2.5 T T T LB1-LB03P08 2.5 to 4 T T T LB1-LB03P10 4 to 6 0.6 0.6 LB1-LB03P13 6 to 10 LB1-LB03P17 10 to 16 LB1-LB03P21 12 to 18 Integral 32 LB1-LC03M03 0.25 to 0.40 T T T LD1-LC030 LB1-LC03M04 0.40 to 0.63 T T T LD4-LC130 LB1-LC03M05 0.63 to 1 T T T LD4-LC030 LB1-LC03M06 1 to 1.6 T T T LB1-LC03M07 1.6 to 2.5 T T T LB1-LC03M08 2.5 to 4 T T T LB1-LC03M10 4 to 6 0.6 0.6 LB1-LC03M13 6 to 10 LB1-LC03M17 10 to 16 LB1-LC03M22 16 to 25 LB1-LC03M53 23 to 32 Note. respect the basic overload and short-circuit discrimination rules, see page 16.

T T T T T T T T 0.6 0.6

T T T T T T T T 0.6 0.6

T T T T T T T T 1 1 1

T T T T T T T T 1 1 1 1

T T T T T T T T 1 1 1 1 1 T T T T T T 1 1 1 1 T T T T T T T T 1 1 1 1 T T T T T T 1 1 1

T T T T T T 0.6 0.6

T T T T T T 0.6 0.6

T T T T T T 1 1 1

T T T T T T 1 1 1 1 T T T T T T T T 1 1 1 1 T T T T T T 1 1 1

T T T T T T T T 0.6 0.6

T T T T T T T T 0.6 0.6

T T T T T T T T 1 1 1 T T T T T T 1 1 1

T T T T T T 0.6 0.6

T T T T T T 0.6 0.6

Schneider Electric

97

Complementary technical information

Motor protection discrimination Upstream: NS100 to 630 Downstream: GV2, GV3


NS100N/H/L Trip unit TM-D 16 25 40 63 80 T T T T T T T 4 1 0.7 0.7 0.7 0.7 0.7 T T T T T T T 4 1 0.7 0.7 0.7 0.7 0.7 T T T T T 4 0.7 0.7 0.7 0.7 0.7 T 0.7 0.7 0.7 0.7 0.7 0.7 100 T T T T T T T 10 2 0.8 0.8 0.8 0.8 0.8 T T T T T T T 10 2 0.8 0.8 0.8 0.8 0.8 T T T T T 10 2 0.8 0.8 0.8 0.8 T T 0.8 0.8 0.8 0.8 0.8 NS160N/H/L Trip unit TM-D 40 T T T T T T T 4 1 0.5 63 T T T T T T T 4 1 0.5 0.5 0.5 80 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2 1.5 1 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3 2 2 125 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3 2 2 1.25 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 3 2 2 1.25

Upstream Downstream Trip unit Rating (A)

or Th. relay Setting Ir GV2 M01 integrated 0.1 to 0.16 A T T T T GV2 M02 integrated 0.16 to 0.25 A T T T T GV2 M03 integrated 0.25 to 0.40 A T T T T GV2 M04 integrated 0.40 to 0.63 A T T T T GV2 M05 integrated 0.63 to 1 A T T T T GV2 M06 integrated 1 to 1.6 A 2 T T T GV2 M07 integrated 1.6 to 2.5 A 0.6 2 T T GV2 M08 integrated 2.5 to 4 A 0.2 0.8 4 4 GV2 M10 integrated 4 to 6.3 A 0.3 1 1 GV2 M14 integrated 6 to 10 A 0.5 0.5 GV2 M16 integrated 9 to 14 A 0.5 GV2 M20 integrated 13 to 18 A 0.5 GV2 M21 integrated 17 to 23 A GV2 M22 integrated 20 to 25 A GV2 P01 integrated 0.1 to 0.16 A T T T T GV2 P02 integrated 0.16 to 0.25 A T T T T GV2 P03 integrated 0.25 to 0.40 A T T T T GV2 P04 integrated 0.40 to 0.63 A T T T T GV2 P05 integrated 0.63 to 1 A T T T T GV2 P06 integrated 1 to 1.6 A 2 T T T GV2 P07 integrated 1.6 to 2.5 A 0.6 2 T T GV2 P08 integrated 2.5 to 4 A 0.2 0.8 4 4 GV2 P10 integrated 4 to 6.3 A 0.3 1 1 GV2 P14 integrated 6 to 10 A 0.5 0.5 GV2 P16 integrated 9 to 14 A 0.5 GV2 P20 integrated 13 to 18 A 0.5 GV2 P21 integrated 17 to 23 A GV2 P22 integrated 20 to 25 A GV2 L03 LR2 D13 03 0.25/0.4 T T T T GV2 L04 LR2 D13 04 0.4/0.63 T T T T GV2 L05 LR2 D13 05 0.63/1 T T T T GV2 L06 LR2 D13 06 1/1.6 2 T T T GV2 L07 LR2 D13 07 1.6/2.5 0.6 2 T T GV2 L08 LR2 D13 08 2.5/4 0.2 0.8 4 4 GV2 L10 LR2 D13 10 4/6 0.3 1 1 GV2 L14 LR2 D13 14 7/10 0.5 0.5 GV2 L16 LR2 D13 16 9/13 0.5 GV2 L20 LR2 D13 21 12/18 0.5 GV2 L22 LR2 D33 22 17/25 GV3 M06 integrated 1 to 1.6 A 0.2 0.3 T T GV3 M07 integrated 1.6 to 2.5 A 0.2 0.3 1 1 GV3 M08 integrated 2.5 to 4 A 0.2 0.3 0.5 0.5 GV3 M10 integrated 4 to 6 A 0.2 0.3 0.5 0.5 GV3 M14 integrated 6 to 10 A 0.5 0.5 GV3 M20 integrated 10 to 16 A 0.5 GV3 M25 integrated 16 to 25 A GV3 M40 integrated 25 to 40 A GV3 M63 integrated 40 to 63 A GV3 M80 integrated 63 to 80 A Note. respect the basic overload and short-circuit discrimination rules, see page 16.

T T T T T T T 4 1 0.5

T T T T T T T 4 1 0.5 0.5 0.5

T T T T T 4 1 0.5

T T T T T 4 1 0.5 0.5 0.5 T 1 0.5 0.5 0.5 0.5

T 1 0.5 0.5 0.5

98

Schneider Electric

Complementary technical information

Motor protection discrimination Upstream: NS100 to 630 Downstream: GV2, GV3


NS250N/H/L Trip unit TM-D NS100N/H/L STR22SE (1) 100 125 160 200 250 40 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1 1 0.8 0.5 0.5 100 T T T T T T 4 3 2 1.2 1.2 1.2 1.2 1.2 T T T T T T 4 3 2 1.2 1.2 1.2 1.2 1.2 T T T T 4 3 2 1.2 1.2 1.2 1.2 T T 5 2 1.2 1.2 1.2 NS160N/H/L STR22SE (1) 80 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 0.9 0.9 0.9 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NS250N/H/L STR22SE (1) 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NS400N/H/L STR23SE /53UE (1) NS630N/H/L STR23SE /53UE (1)

Upstream

Downstream Trip unit

Rating (A)

40

63

80

160 to 400 250 to 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

or Th. relay Setting Ir GV2 M01 integrated 0.1 to 0.16 A T T T T T T T GV2 M02 integrated 0.16 to 0.25 A T T T T T T T GV2 M03 integrated 0.25 to 0.40 A T T T T T T T GV2 M04 integrated 0.40 to 0.63 A T T T T T T T GV2 M05 integrated 0.63 to 1 A T T T T T T T GV2 M06 integrated 1 to 1.6 A T T T T T T T GV2 M07 integrated 1.6 to 2.5 A T T T T T T T GV2 M08 integrated 2.5 to 4 A 4 4 T T T T T GV2 M10 integrated 4 to 6.3 A 1 1 T T T T T GV2 M14 integrated 6 to 10 A 0.5 0.5 T T T T T GV2 M16 integrated 9 to 14 A 0.5 T T T T T GV2 M20 integrated 13 to 18 A 0.5 T T T T T GV2 M21 integrated 17 to 23 A T T T T T GV2 M22 integrated 20 to 25 A T T T T T GV2 P01 integrated 0.1 to 0.16 A T T T T T T T GV2 P02 integrated 0.16 to 0.25 A T T T T T T T GV2 P03 integrated 0.25 to 0.40 A T T T T T T T GV2 P04 integrated 0.40 to 0.63 A T T T T T T T GV2 P05 integrated 0.63 to 1 A T T T T T T T GV2 P06 integrated 1 to 1.6 A T T T T T T T GV2 P07 integrated 1.6 to 2.5 A T T T T T T T GV2 P08 integrated 2.5 to 4 A 4 4 T T T T T GV2 P10 integrated 4 to 6.3 A 1 1 T T T T T GV2 P14 integrated 6 to 10 A 0.5 0.5 T T T T T GV2 P16 integrated 9 to 14 A 0.5 T T T T T GV2 P20 integrated 13 to 18 A 0.5 T T T T T GV2 P21 integrated 17 to 23 A T T T T T GV2 P22 integrated 20 to 25 A T T T T T GV2 L03 LR2 D13 03 0.25/0.4 T T T T T T T GV2 L04 LR2 D13 04 0.4/0.63 T T T T T T T GV2 L05 LR2 D13 05 0.63/1 T T T T T T T GV2 L06 LR2 D13 06 1/1.6 T T T T T T T GV2 L07 LR2 D13 07 1.6/2.5 T T T T T T T GV2 L08 LR2 D13 08 2.5/4 4 4 T T T T T GV2 L10 LR2 D13 10 4/6 1 1 T T T T T GV2 L14 LR2 D13 14 7/10 0.5 0.5 T T T T T GV2 L16 LR2 D13 16 9/13 0.5 T T T T T GV2 L20 LR2 D13 21 12/18 0.5 T T T T T GV2 L22 LR2 D33 22 17/25 T T T T T GV3 M06 integrated 1 to 1.6 A T T T T T T T GV3 M07 integrated 1.6 to 2.5 A 1 1 T T T T T GV3 M08 integrated 2.5 to 4 A 0.5 0.5 T T T T T GV3 M10 integrated 4 to 6 A 0.5 0.5 T T T T T GV3 M14 integrated 6 to 10 A 0.5 0.5 2 3 3 T T GV3 M20 integrated 10 to 16 A 0.5 1.5 2 2 T T GV3 M25 integrated 16 to 25 A 1 2 2 T T GV3 M40 integrated 25 to 40 A 1.25 T T GV3 M63 integrated 40 to 63 A T GV3 M80 integrated 63 to 80 A (1) Note. respect the basic overload and short-circuit discrimination rules, see page 16.

T T T T T 1 1 0.8 0.5 0.5

T T T 1 1 0.8 0.5 0.5

T 1 0.5 0.5 0.5

Schneider Electric

99

Complementary technical information

Motor protection discrimination Upstream: NS100 to 630 Downstream: Integral 18, 32, 63
NS100N/H/L Trip unit TM-D 16 25 40 63 80 T T T T T T 4 0.7 0.7 0.7 0.7 0.7 T T T T 1 0.7 0.7 0.7 0.7 0.7 0.65 0.65 0.65 100 T T T T T T T 2 1 0.8 0.8 0.8 T T T T T 1 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 NS160N/H/L Trip unit TM-D 40 T T T T T T 1.5 0.5 0.5 0.5 63 T T T T T T 1.5 0.5 0.5 0.5 0.5 0.5 T T T T 1.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 80 T T T T T T T T T T 4 3 T T T T T T T T 4 3 1 1 1 100 T T T T T T T T T T T T T T T T T T T T T T T 1.25 1.25 1.25 1.25 125 T T T T T T T T T T T T T T T T T T T T T T T 1.25 1.25 1.25 1.25 1.25 160 T T T T T T T T T T T T T T T T T T T T T T T 1.25 1.25 1.25 1.25 1.25 1.25

Upstream Downstream Trip unit Rating (A)

or Th. relay Setting Ir Integral 18 LB1-LB03P01 0.1 to 0.16 A T T T T LD1-LB030 LB1-LB03P02 0.16 to 0.25 A T T T T LB1-LB03P03 0.25 to 0.40 A T T T T LB1-LB03P04 0.40 to 0.63 A T T T T LB1-LB03P05 0.63 to 1 A T T T T LB1-LB03P06 1 to 1.6 A 0.2 T T T LB1-LB03P07 1.6 to 2.5 A 0.2 0.3 1.5 1.5 LB1-LB03P08 2.5 to 4 A 0.2 0.3 0.5 0.5 LB1-LB03P10 4 to 6 A 0.3 0.5 0.5 LB1-LB03P13 6 to 10 A 0.5 0.5 LB1-LB03P17 10 to 16 A 0.5 LB1-LB03P21 12 to 18 A 0.5 Integral 32 LB1-LC03M03 0.25 to 0.40 A T T T T LD1-LC030 LB1-LC03M04 0.40 to 0.63 A T T T T LD4-LC130 LB1-LC03M05 0.63 to 1 A T T T T LD4-LC030 LB1-LC03M06 1 to 1.6 A 0.2 T T T LB1-LC03M07 1.6 to 2.5 A 0.2 0.3 1.5 1.5 LB1-LC03M08 2.5 to 4 A 0.2 0.3 0.5 0.5 LB1-LC03M10 4 to 6 A 0.3 0.5 0.5 LB1-LC03M13 6 to 10 A 0.5 0.5 LB1-LC03M17 10 to 16 A 0.5 LB1-LC03M22 16 to 25 A 0.5 LB1-LC03M53 23 to 32 A Integral 63 LB1-LD03M16 10 13 A 0.5 0.5 LD1-LD030 LB1-LD03M21 13 18 A 0.5 LD4-LD130 LB1-LD03M22 18 to 25 A LD4-LD030 LB1-LD03M53 23 to 32 A LB1-LD03M55 28 to 40 A LB1-LD03M57 35 to 50 A LB1-LD03M61 45 to 63 A Note. respect the basic overload and short-circuit discrimination rules, see page 16.

T T T T 1.5 0.5 0.5 0.5

0.5

100

Schneider Electric

Complementary technical information

Motor protection discrimination Upstream: NS100 to 630 Downstream: Integral 18, 32, 63
NS250N/H/L Trip unit TM-D NS100N/H/L STR22SE (1) 100 125 160 200 250 40 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2 0.5 0.5 0.5 100 T T T T T T T 3 1.2 1.2 1.2 1.2 T T T T T 3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 NS160N/H/L STR22SE (1) 80 T T T T T T T T T T T T T T T T T T T T T T T T 0.9 0.9 0.9 160 T T T T T T T T T T T T T T T T T T T T T T T T 35 35 35 35 NS250N/H/L STR22SE (1) 160 T T T T T T T T T T T T T T T T T T T T T T T T 35 35 35 35 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NS400N/H/L STR23SE/ 53UE (1) NS630N/H/L STR23SE/ 53UE (1)

Upstream

Downstream Trip unit

Rating (A)

40

63

80

160 to 400 250 to 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

or Th. relay Setting Ir Integral 18 LB1-LB03P01 0.1 to 0.16 A T T T T T T T LD1-LB030 LB1-LB03P02 0.16 to 0.25 A T T T T T T T LB1-LB03P03 0.25 to 0.40 A T T T T T T T LB1-LB03P04 0.40 to 0.63 A T T T T T T T LB1-LB03P05 0.63 to 1 A T T T T T T T LB1-LB03P06 1 to 1.6 A T T T T T T T LB1-LB03P07 1.6 to 2.5 A 1.5 1.5 T T T T T LB1-LB03P08 2.5 to 4 A 0.5 0.5 T T T T T LB1-LB03P10 4 to 6 A 0.5 0.5 T T T T T LB1-LB03P13 6 to 10 A 0.5 0.5 T T T T T LB1-LB03P17 10 to 16 A 0.5 4 T T T T LB1-LB03P21 12 to 18 A 0.5 3 T T T T Integral 32 LB1-LC03M03 0.25 to 0.40 A T T T T T T T LD1-LC030 LB1-LC03M04 0.40 to 0.63 A T T T T T T T LD4-LC130 LB1-LC03M05 0.63 to 1 A T T T T T T T LD4-LC030 LB1-LC03M06 1 to 1.6 A T T T T T T T LB1-LC03M07 1.6 to 2.5 A 1.5 1.5 T T T T T LB1-LC03M08 2.5 to 4 A 0.5 0.5 T T T T T LB1-LC03M10 4 to 6 A 0.5 0.5 T T T T T LB1-LC03M13 6 to 10 A 0.5 0.5 T T T T T LB1-LC03M17 10 to 16 A 0.5 1 T T T T LB1-LC03M22 16 to 25 A 0.5 0.8 T T T T LB1-LC03M53 23 to 32 A T T T T Integral 63 LB1-LD03M16 13 to 13 A 0.5 0.5 1 1.25 1.25 T T LD1-LD030 LB1-LD03M21 13 to 18 A 0.5 1 1.25 1.25 T T LD4-LD130 LB1-LD03M22 18 to 25 A 1 1.25 1.25 T T LD4-LD030 LB1-LD03M53 23 to 32 A 1.25 1.25 T T LB1-LD03M55 28 to 40 A 1.25 T T LB1-LD03M57 35 to 50 A T T LB1-LD03M61 45 to 63 A T (1) Note: respect the basic overload and short-circuit discrimination rules, see page 16.

T T T T 0.5 0.5 0.5 0.5

0.5

Schneider Electric

101

Complementary technical information

Motor protection discrimination Upstream: NS100 to 630 Downstream: C60LMA, NC100LMA, NS80HMA
NS100N/H/L Trip unit TM-D 16 0.2 0.2 0.2 25 T 0.3 0.3 0.3 0.3 40 T T 0.5 0.5 0.5 0.5 0.5 63 T T 0.5 0.5 0.5 0.5 0.5 0.5 80 T T 3 0.7 0.7 0.7 0.7 0.7 0.7 100 T T T 5 2 0.8 0.8 0.8 0.8 0.8 T T T 10 2 0.8 0.8 0.8 0.8 0.8 NS160N/H/L Trip unit TM-D 40 T T 0.5 0.5 0.5 0.5 0.5 63 T T 0.5 0.5 0.5 0.5 0.5 0.5 80 T T T T T T T T T 100 T T T T T T T T T T T T T T T T T T T T 125 T T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T T

Upstream Downstream C60LMA 1.6 C60LMA 2.5 C60LMA 4 C60LMA 6.3 C60LMA 10 C60LMA 10 C60LMA 12.5 C60LMA 16 C60LMA 25 C60LMA 40 C60LMA 40 NC100LMA 1.6 NC100LMA 2.5 NC100LMA 4 NC100LMA 6.3 NC100LMA 10 NC100LMA 10 NC100LMA 12.5 NC100LMA 16 NC100LMA 25 NC100LMA 40 NC100LMA 40 NC100LMA 63 NC100LMA 63 NS80HMA 2.5 NS80HMA 2.5 NS80HMA 6.3 NS80HMA 6.3 NS80HMA 12.5 NS80HMA 12.5 NS80HMA 12.5 NS80HMA 25 NS80HMA 25 NS80HMA 50 NS80HMA 50 NS80HMA 50 NS80HMA 80 Trip unit or Th. relay LR2 D13 06 LR2 D13 07 LR2 D13 08 LR2 D13 10 LR2 D13 12 LR2 D13 14 LR2 D13 16 LR2 D13 21 LR2 D13 22 LR2 D33 53 LR2 D33 55 LR2 D13 06 LR2 D13 07 LR2 D13 08 LR2 D13 10 LR2 D13 12 LR2 D13 14 LR2 D13 16 LR2 D13 21 LR2 D13 22 LR2 D33 53 LR2 D33 55 LR2 D33 57 LR2 D33 59 LR2 D13 06 LR2 D13 07 LR2 D13 08 LR2 D13 10 LR2 D13 12 LR2 D13 14 LR2 D13 16 LR2 D13 21 LR2 D33 22 LR2 D33 53 LR2 D33 55 LR2 D33 57 LR2 D33 59 Rating (A) Setting Ir 1/1.6 1.6/2.5 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 23/32 30/40 1/1.6 1.6/2.5 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 23/32 30/40 37/50 48/65 1/1.6 1.6/2.5 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 23/32 30/40 37/50 48/65

0.2 0.2 0.2

T 0.3 0.3 0.3 0.3

T T 0.5 0.5 0.5 0.5 0.5

T T 0.5 0.5 0.5 0.5 0.5 0.5

T T 10 0.7 0.7 0.7 0.7 0.7 0.7

T T 0.5 0.5 0.5 0.5 0.5

T T 0.5 0.5 0.5 0.5 0.5 0.5

T T T T T T T T T

T T 0.2

T T 0.3 0.3 0.3

T T 0.5 0.5 0.5 0.5 0.5

T T 0.5 0.5 0.5 0.5 0.5 0.5

T T 0.7 0.7 0.7 0.7 0.7 0.7 0.7

T T 10 2 0.8 0.8 0.8 0.8 0.8 0.8

T T 0.5 0.5 0.5 0.5 0.5

T T 0.5 0.5 0.5 0.5 0.5 0.5

T T T T T T T 1 1

T T T T T T T T 1.2 1.2

T T T T T T T T 1.2 1.2 1.2

T T T T T T T T 1.2 1.2 1.2 1.2

102

Schneider Electric

Complementary technical information

Motor protection discrimination Upstream: NS100 to 630 Downstream: C60LMA, NC100LMA, NS80HMA
NS250N/H/L Trip unit TM-D NS100N/H/L NS160N/H/L NS250N/H/L NS400N/H/L NS630N/H/L STR22SE 80 100 125 160 200 250 40 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1 0.5 0.5 0.5 0.5 0.5 STR22SE (1) STR22SE (1) STR23SE/ 53UE STR23SE/ 53UE

Upstream

Downstream

Trip unit

Rating (A)

40

63

100 80 T T T 5 2 1.2 1.2 1.2 1.2 1.2 T T 15 2 1.2 1.2 1.2 1.2 1.2 1.2 T T T T T T T T T T T T T T T T T T T T

160 160 250 160 to 400 250 to 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

or Th. relay Setting Ir C60LMA 1.6 LR2 D13 06 1/1.6 T T T T T T C60LMA 2.5 LR2 D13 07 1.6/2.5 T T T T T T C60LMA 4 LR2 D13 08 2.5/4 0.5 0.5 T T T T C60LMA 6.3 LR2 D13 10 4/6 0.5 0.5 T T T T C60LMA 10 LR2 D13 12 5.5/8 0.5 0.5 T T T T C60LMA 10 LR2 D13 14 7/10 0.5 0.5 T T T T C60LMA 12.5 LR2 D13 16 9/13 0.5 0.5 T T T T C60LMA 16 LR2 D13 21 12/18 0.5 T T T T C60LMA 25 LR2 D13 22 17/25 T T T T C60LMA 40 LR2 D33 53 23/32 T T T C60LMA 40 LR2 D33 55 30/40 T T NC100LMA 1.6 LR2 D13 06 1/1.6 T T T T T T NC100LMA 2.5 LR2 D13 07 1.6/2.5 T T T T T T NC100LMA 4 LR2 D13 08 2.5/4 0.5 0.5 T T T T NC100LMA 6.3 LR2 D13 10 4/6 0.5 0.5 T T T T NC100LMA 10 LR2 D13 12 5.5/8 0.5 0.5 T T T T NC100LMA 10 LR2 D13 14 7/10 0.5 0.5 T T T T NC100LMA 12.5 LR2 D13 16 9/13 0.5 0.5 T T T T NC100LMA 16 LR2 D13 21 12/18 0.5 T T T T NC100LMA 25 LR2 D13 22 17/25 T T T T NC100LMA 40 LR2 D33 53 23/32 T T T NC100LMA 40 LR2 D33 55 30/40 T T NC100LMA 63 LR2 D33 57 37/50 T NC100LMA 63 LR2 D33 59 48/65 NS80HMA 2.5 LR2 D13 06 1/1.6 T T T T T T NS80HMA 2.5 LR2 D13 07 1.6/2.5 T T T T T T NS80HMA 6.3 LR2 D13 08 2.5/4 0.5 0.5 T T T T NS80HMA 6.3 LR2 D13 10 4/6 0.5 0.5 T T T T NS80HMA 12.5 LR2 D13 12 5.5/8 0.5 0.5 T T T T NS80HMA 12.5 LR2 D13 14 7/10 0.5 0.5 T T T T NS80HMA 12.5 LR2 D13 16 9/13 0.5 0.5 T T T T NS80HMA 25 LR2 D13 21 12/18 0.5 1 T T T NS80HMA 25 LR2 D33 22 17/25 1 1.2 1.2 T NS80HMA 50 LR2 D33 53 23/32 1.2 1.2 T NS80HMA 50 LR2 D33 55 30/40 1.2 T NS80HMA 50 LR2 D33 57 37/50 T NS80HMA 80 LR2 D33 59 48/65 (1) Note. respect the basic overload and short-circuit discrimination rules, see page 16.

T 1 0.5 0.5 0.5 0.5 0.5

T 1 0.5 0.5 0.5 0.5 0.5

T T T 5 2 1.2 1.2 1.2 1.2 1.2

T T T T T T T T T

Schneider Electric

103

Complementary technical information

Motor protection discrimination Upstream: NS100 to 630, NS630b to NS1600 Downstream: NS100 to 630
NS100N/H/L Trip unit TM-D 16 0.19 0.19 0.19 25 3 3 3 3 3 32 T 4 4 4 4 4 40 T 5 5 5 5 5 5 50 T 5 5 5 5 5 5 63 T 5 5 5 5 5 5 5 80 T T 6.4 6.4 6.4 6.4 6.4 6.4 6.4 100 T T 8 8 8 8 8 8 8 8 NS160N/H/L Trip unit TM-D 80 T T T T 10 10 10 10 10 100 T T T T 12.5 12.5 12.5 12.5 12.5 12.5 125 T T T T 12.5 12.5 12.5 12.5 12.5 12.5 12.5 160 T T T T 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 NS250N/H/L Trip unit TM-D 200 T T T T 20 20 20 20 20 20 20 20 20 250 T T T T 25 25 25 25 25 25 25 25 25 25

Upstream Downstream NS100N/H/LMA 2.5 NS100N/H/LMA 2.5 NS100N/H/LMA 6.3 NS100N/H/LMA 6.3 NS100N/H/LMA 12.5 NS100N/H/LMA 12.5 NS100N/H/LMA 12.5 NS100N/H/LMA 25 NS100N/H/LMA 25 NS100N/H/LMA 50 NS100N/H/LMA 50 NS100N/H/LMA 50 NS100N/H/LMA 100 NS100N/H/LMA 100 NS100N/H/LMA 100 NS160N/H/LMA 150 NS250N/H/LMA 220 NS400N/H/LMA 320 NS630N/H/LMA 500 NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS160N/H/L NS250N/H/L NS400N/H/L Trip unit or Th. relay LR2 D13 06 LR2 D13 07 LR2 D13 08 LR2 D13 10 LR2 D13 12 LR2 D13 14 LR2 D13 16 LR2 D13 21 LR2 D33 22 LR2 D33 53 LR2 D33 55 LR2 D33 57 LR2 D33 59 LR2 D33 63 Rating (A) Setting Ir 1/1.6 1.6/2.5 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 23/32 30/40 37/50 48/65 63/80

STR22ME40 STR22ME50 STR22ME80 STR22ME100 STR22ME150 STR22ME220 STR43ME320

24/40 30/50 48/80 60/100 90/150 131/220 190/320

12.5

12.5 12.5

36 36

36 36 36

Upstream NS100N/H/L NS160N/H/L NS250N/H/L STR22SE (1) STR22SE (1) Downstream Trip unit Rating (A) 40 100 80 160 250

NS400N/H/L NS630N/H/L STR23SE (1) STR53SE 400 630 T T T T T T T T T T T T T T T T T

NS630bN/H NS800N/H Micrologic 2.0 - 5.0 630 T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T

NS630bL NS800bL Micrologic 2.0 - 5.0 630 T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T

NS1000N/H NS1250/1600N/H Micrologic 2.0 - 5.0 1000 T T T T T T T T T T T T T T T T T T T T T T T T T 1250 T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T

NS1000L Micrologic 2.0 - 5.0 1000 T T T T T T T T T T T T T T T T T 18 T T T T T T 18

or Thermal th. Setting Ir NS100N/H/LMA 2,5 LR2 D13 06 1/1,6 0,45 T T T T T NS100N/H/LMA 2,5 LR2 D13 07 1,6/2,5 0,45 T T T T T NS100N/H/LMA 6,3 LR2 D13 08 2,5/4 0,45 1,1 T T T T NS100N/H/LMA 6,3 LR2 D13 10 4/6 0,45 1,1 T T T T NS100N/H/LMA 12,5 LR2 D13 12 5,5/8 0,45 1,1 0,9 T T T NS100N/H/LMA 12,5 LR2 D13 14 07/10 0,45 1,1 0,9 T T T NS100N/H/LMA 12,5 LR2 D13 16 9/13 0,45 1,1 0,9 T T T NS100N/H/LMA 25 LR2 D13 21 12/18 1,1 0,9 1,75 36 T NS100N/H/LMA 25 LR2 D33 22 17/25 1,1 0,9 1,75 36 T NS100N/H/LMA 50 LR2 D33 53 23/32 1,1 1,75 36 T NS100N/H/LMA 50 LR2 D33 55 30/40 1,75 36 T NS100N/H/LMA 50 LR2 D33 57 37/50 1,75 36 T NS100N/H/LMA 100 LR2 D33 59 48/65 36 T NS100N/H/LMA 100 LR2 D33 63 63/80 36 T NS100N/H/LMA 100 T NS160N/H/LMA 150 NS250N/H/LMA 220 NS400N/H/LMA 320 NS630N/H/LMA 500 NS100N/H/L STR22ME40 24/40 1,75 3,6 T NS100N/H/L STR22ME50 30/50 1,75 3,6 T NS100N/H/L STR22ME80 48/80 3,6 T NS100N/H/L STR22ME100 60/100 T NS160N/H/L STR22ME150 90/150 NS250N/H/L STR22ME220 131/220 NS400N/H/L STR43ME320 190/320 (1) Note. respect the basic overload and short-circuit discrimination rules, see page 16.

T T T T

T T T T T T

T T T T T T

T T T T T T

T T T T T T

104

Schneider Electric

Complementary technical information

Motor protection discrimination Upstream: NS1600, Masterpact NT, NW Downstream: NS630, NS630b, NS800, NS1000, NS1250
NS1600N/H Micrologic 2.0 - 5.0 T NT16H1 Micrologic 2.0 - 5.0 T NW16N1/H1 Micrologic 2.0 - 5.0 T NW20H1/H2/H3 NW25H1/H2/H3 NW32H1/H2/H3 NW40H1/H2/H3 Micrologic 2.0 - 5.0 T T Micrologic 2.0 - 5.0 T T T Micrologic 2.0 - 5.0 T T T T Micrologic 2.0 - 5.0 T T T T

Upstream Downstream NS630N/H/L NS630bN/H/L NS800N/H/L NS1000N/H/L NS1250N/H/L STR43ME Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 200...500 250...630 320...800 400...1000 500...1250

Schneider Electric

105

Complementary technical information

Cascading and enhanced discrimination Upstream: Compact NS100 to NS1600 Downstream: circuit breaker Multi 9 / Integral /GV2 / Compact NS100 to 630
With traditional circuit breakers, cascading between two devices generally results in the look of discrimination. With Compact NS circuit breakers, the discrimination characteristics in the tables remain applicable and are in some cases even enhanced. Protection discrimination is ensured for short-circuit currents greater than the rated breaking capacity of the circuit breaker and even, in some cases, for its enhanced breaking capacity. In the later case, protection discrimination is total, i.e. only the downstream device trips for any and all possible faults at its point in the installation. Example Consider a combination between: b a Compact NS250N with trip unit TM250D b a Compact NS100N with trip unit TM100D. The discrimination tables indicate total discrimination. Protection discrimination is therefore ensured up to the breaking capacity of the NS100N, i.e. 25 kA. The cascading tables indicate an enhanced breaking capacity of 36 kA. The enhanced discrimination tables indicate that in a cascading configuration, discrimination is ensured up to 36 kA, i.e. for any and all possible faults at that point in the installation.

Enhanced discrimination tables - 380/415 V


For each combination of two circuit breakers, the tables indicate the: downstream device breaking capacity enhanced by cascading (in kA) selectivity limit enhanced by cascading (in kA) In a table, a box containing two equal values indicates that discrimination is provided up to the reinforced breaking capacity of the downstream device. These tables apply only to cases with combined discrimination and cascading between two devices. For all other cases, refer to the normal cascading and discrimination tables.

15/25

Technical principle
Enhanced discrimination is the result of the exclusive Compact NS Roto-active breaking technique which operates as follows: b due to the short-circuit current (electrodynamic forces), the contacts in both devices simultaneously separate. The result is major limitation of the short-circuit current b the dissipated energy provokes the reflex tripping of the downstream device, but is insufficient to trip the upstream device.

E43820

NS160N TM160D discrimination limit in kA

NS400H STR23SE

30 / 30

70 / 70

C60N 63 A

NS160N TM160D

cascading limit in kA

106

Schneider Electric

Complementary technical information

Cascading and enhanced discrimination Upstream: NSC100N, NSA160 Downstream: Multi 9

Upstream: Compact NSC100 TM-D Downstream: Multi 9


Upstream Breaking capacity Trip unit Downstream C60a 5 kA Rating y 16 20 25 32 40 y 16 20 25 32 40 50 63 NSC100N 18 kA TM-D 63 18/18 18/18 18/18 6/18 18/18 18/18 18/18 6/18 70 18/18 18/18 18/18 6/18 6/18 18/18 18/18 18/18 6/18 6/18 80 18/18 18/18 18/18 6/18 6/18 18/18 18/18 18/18 6/18 6/18 6/18 100 18/18 18/18 18/18 8/18 8/18 18/18 18/18 18/18 8/18 8/18 6/18 6/18

C60N

10 kA

Upstream: Compact NSA160 TM-D Downstream: Multi 9


Upstream Breaking capacity Trip unit Downstream C60a 5 kA NSA160E 16 kA TM-D 160 15/15 15/15 15/15 8/15 8/15 15/15 15/15 15/15 8/15 8/15 6/15 6/15 NSA160N 30 kA TM-D 63 15/15 15/15 15/15 6/15 6/15 15/25 15/25 15/25 6/25 80 15/15 15/15 15/15 6/15 6/15 15/25 15/25 15/25 6/25 6/25 6/25 15/30 15/30 15/30 6/30 6/30 6/30 15/30 15/30 15/30 6/30 6/30 6/30 30/30 15/30 8/30 100 15/15 15/15 15/15 8/15 8/15 15/25 15/25 15/25 8/25 8/25 6/25 6/25 30/30 30/30 30/30 8/30 8/30 6/30 6/30 30/30 30/30 30/30 8/30 8/30 6/30 6/30 30/30 30/30 30/30 30/30 125 15/15 15/15 15/15 8/15 8/15 15/25 15/25 15/25 8/25 8/25 6/25 6/25 30/30 30/30 30/30 8/30 8/30 6/30 6/30 30/30 30/30 30/30 8/30 8/30 6/30 6/30 30/30 30/30 30/30 30/30 160 15/15 15/15 15/15 8/15 8/15 15/25 15/25 15/25 8/25 8/25 6/25 6/25 30/30 30/30 30/30 8/30 8/30 6/30 6/30 30/30 30/30 30/30 8/30 8/30 6/30 6/30 30/30 30/30 30/30 30/30

Rating 63 80 100 125 15/15 15/15 15/15 15/15 y 16 20 15/15 15/15 15/15 15/15 25 15/15 15/15 15/15 15/15 32 6/15 6/15 8/15 8/15 40 6/15 6/15 8/15 8/15 C60N 10 kA 15/15 15/15 15/15 15/15 y 16 20 15/15 15/15 15/15 15/15 25 15/15 15/15 15/15 15/15 32 6/15 6/15 8/15 8/15 40 6/15 8/15 8/15 50 6/15 6/15 6/15 63 6/15 6/15 C60H 15 kA y 16 20 25 32 40 50 63 C60L 25 kA y 16 20 25 20 kA 32 40 15 kA 50 63 NC100L 22 kA y 16 20 - 25 32 - 40 50 - 63 Note. respect the basic overload and short-circuit discrimination rules, see page 16.

15/30 15/30 15/30 6/30

15/30 15/30 15/30 6/30

30/30 15/30

Schneider Electric

107

Complementary technical information

Cascading and enhanced discrimination Upstream: NS160 to NS250 Trip unit TM-D Downstream: Multi 9
NS160H 70 kA TM-D NS160L 150 kA TM-D 80 20/20 20/20 20/20 20/20 20/20 30/30 30/30 30/30 15/30 15/30 15/30 40/40 40/40 40/40 15/40 15/40 15/40 40/40 40/40 40/40 15/40 15/40 15/40 100/125/160 20/20 20/20 20/20 20/20 20/20 30/30 30/30 30/30 30/30 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 NS250N 36 kA TM-D 160/200/250 15/15 15/15 15/15 15/15 15/15 25/25 25/25 25/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 NS250H 70 kA TM-D 160/200/250 20/20 20/20 20/20 20/20 20/20 30/30 30/30 30/30 30/30 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 30/30 30/30 40/40 40/40 40/40 40/40 40/40 30/30 30/30 30/30 30/30 30/30 30/30 30/30 50/50 50/50 50/50 50/50 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36 36/36 50/50 50/50 50/50 50/50 50/50 70/70 70/70 70/70 70/70 70/70 NS250L 150 kA TM-D 160/200/250 20/20 20/20 20/20 20/20 20/20 30/30 30/30 30/30 30/30 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 30/30 30/30 40/40 40/40 40/40 40/40 40/40 30/30 30/30 30/30 30/30 30/30 30/30 30/30 70/70 70/70 70/70 70/70 100/100 100/100 100/100 100/100 150/150 150/150 150/150 150/150 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 70/70 70/70 70/70 70/70 70/70 70/70 70/70 100/100 100/100 100/100 100/100 100/100 150/150 150/150 150/150 150/150 150/150

Upstream Breaking capacity Trip unit Downstream C60a 5 kA

NS160N 36 kA TM-D

Rating 80 100/125/160 80 100/125/160 y 16 15/15 15/15 20/20 20/20 20 15/15 15/15 20/20 20/20 25 15/15 15/15 20/20 20/20 32 15/15 15/15 20/20 20/20 40 15/15 15/15 20/20 20/20 y 16 C60N 10 kA 25/25 25/25 30/30 30/30 20 25/25 25/25 30/30 30/30 25 25/25 25/25 30/30 30/30 32 15/25 25/25 15/30 30/30 40 15/25 25/25 15/30 30/30 50 15/25 25/25 15/30 30/30 63 25/25 30/30 C60H 15 kA 30/30 30/30 40/40 40/40 y 16 20 30/30 30/30 40/40 40/40 25 30/30 30/30 40/40 40/40 32 15/30 30/30 15/40 40/40 40 15/30 30/30 15/40 40/40 50 15/30 30/30 15/40 40/40 63 30/30 40/40 C60L 25 kA 30/30 30/30 40/40 40/40 y 16 20 30/30 30/30 40/40 40/40 25 30/30 30/30 40/40 40/40 20 kA 32 15/30 30/30 15/40 40/40 40 15/30 30/30 15/40 40/40 15 kA 50 15/30 30/30 15/40 40/40 63 30/30 40/40 NC100H 10 kA 50 63 80 100 NC125H 10 kA 125 NC100L 22 kA 36/36 36/36 50/50 50/50 y 16 20 - 25 36/36 36/36 50/50 50/50 32 - 40 36/36 36/36 50/50 50/50 50 - 63 36/36 50/50 50/50 y 16 NC100LS 36 kA 70/70 70/70 20 - 25 70/70 70/70 32 - 40 70/70 70/70 50 - 63 70/70 70/70 NC100LH 50 kA 70/70 70/70 y 16 20 - 25 70/70 70/70 32 - 40 70/70 70/70 50 - 63 70/70 70/70 C120N/H 10/15 kA y 16 25/25 25/25 25/25 25/25 20 - 25 25/25 25/25 25/25 25/25 32 - 40 25/25 25/25 25/25 25/25 50 - 63 80 100 125 y 16 NG125a 16 kA 25/25 25/25 25/25 25/25 20 - 25 25/25 25/25 25/25 25/25 32 - 40 25/25 25/25 25/25 25/25 50 - 63 80 100 125 NG125N 25 kA 36/36 36/36 36/36 36/36 y 16 20 - 25 36/36 36/36 36/36 36/36 32 - 40 36/36 36/36 36/36 36/36 50 - 63 80 100 125 NG125H 36 kA 50/50 50/50 y 16 20 - 25 50/50 50/50 32 - 40 50/50 50/50 50 - 63 80 NG125L 50 kA 70/70 70/70 y 16 NG125LMA 20 - 25 70/70 70/70 32 - 40 70/70 70/70 50 - 63 80 Note. respect the basic overload and short-circuit discrimination rules, see page 16.

70/70 70/70 70/70 70/70 100/100 100/100 100/100 100/100 150/150 150/150 150/150 150/150 25/25 25/25 25/25

70/70 70/70 70/70 70/70 100/100 100/100 100/100 100/100 150/150 150/150 150/150 150/150 25/25 25/25 25/25

25/25 25/25 25/25

25/25 25/25 25/25

70/70 70/70 70/70

70/70 70/70 70/70

25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36 36/36

100/100 100/100 100/100

100/100 100/100 100/100

150/150 150/150 150/150

150/150 150/150 150/150

108

Schneider Electric

Complementary technical information

Cascading and enhanced discrimination Upstream: NS160 to NS250 Trip unit STR Downstream: Multi 9
NS160H 70 kA STR22SE NS160L 150 kA STR22SE 80 20/20 20/20 20/20 160 20/20 20/20 20/20 20/20 20/20 30/30 30/30 30/30 30/30 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/40 NS250N 36 kA STR22SE 250 15/15 15/15 15/15 15/15 15/15 25/25 25/25 25/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 NS250H 70 kA STR22SE 250 20/20 20/20 20/20 20/20 20/20 30/30 30/30 30/30 30/30 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 30/30 30/30 40/40 40/40 40/40 40/40 40/40 30/30 30/30 30/30 30/30 30/30 30/30 30/30 50/50 50/50 50/50 50/50 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36 50/50 50/50 50/50 50/50 50/50 70/70 70/70 70/70 70/70 70/70 NS250L 150 kA STR22SE 250 20/20 20/20 20/20 20/20 20/20 30/30 30/30 30/30 30/30 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 30/30 30/30 40/40 40/40 40/40 40/40 40/40 30/30 30/30 30/30 30/30 30/30 30/30 30/30 70/70 70/70 70/70 70/70 100/100 100/100 100/100 100/100 150/150 150/150 150/150 150/150 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 70/70 70/70 70/70 70/70 70/70 70/70 100/100 100/100 100/100 100/100 100/100 150/150 150/150 150/150 150/150 150/150

Upstream Breaking capacity Trip unit Downstream C60a 5 kA

NS160N 36 kA STR22SE

Rating 80 160 80 160 y 16 15/15 15/15 20/20 20/20 20 15/15 15/15 20/20 20/20 25 15/15 15/15 20/20 20/20 32 15/15 20/20 40 15/15 20/20 y 16 C60N 10 kA 25/25 25/25 30/30 30/30 20 25/25 25/25 30/30 30/30 25 25/25 25/25 30/30 30/30 32 25/25 30/30 40 25/25 30/30 50 25/25 30/30 63 25/25 30/30 C60H 15 kA 30/30 30/30 40/40 40/40 y 16 20 30/30 30/30 40/40 40/40 25 30/30 30/30 40/40 40/40 32 30/30 40/40 40 30/30 40/40 50 30/30 40/40 63 30/30 40/40 C60L 25 kA 30/30 30/30 40/40 40/40 y 16 20 30/30 30/30 40/40 40/40 25 30/30 30/30 40/40 40/40 20 kA 32 30/30 40/40 40 30/30 40/40 15 kA 50 30/30 40/40 63 30/30 40/40 NC100H 10 kA 50 63 80 100 NC125H 10 kA 125 NC100L 22 kA 36/36 36/36 50/50 50/50 y 16 20 - 25 36/36 36/36 50/50 50/50 32 - 40 36/36 50/50 50 - 63 36/36 50/50 y 16 NC100LS 36 kA 70/70 70/70 20 - 25 70/70 70/70 32 - 40 70/70 50 - 63 70/70 NC100LH 50 kA 70/70 70/70 y 16 20 - 25 70/70 70/70 32 - 40 70/70 50 - 63 70/70 C120N/H 10/15 kA y 16 25/25 25/25 25/25 25/25 20 - 25 25/25 25/25 25/25 25/25 32 - 40 25/25 25/25 50 - 63 80 100 125 y 16 NG125a 16 kA 25/25 25/25 25/25 25/25 20 - 25 25/25 25/25 25/25 25/25 32 - 40 25/25 25/25 50 - 63 80 100 125 NG125N 25 kA 36/36 36/36 36/36 36/36 y 16 20 - 25 36/36 36/36 36/36 36/36 32 - 40 36/36 36/36 50 - 63 80 100 125 NG125H 36 kA 50/50 50/50 y 16 20 - 25 50/50 50/50 32 - 40 50/50 50 - 63 80 NG125L 50 kA 70/70 70/70 y 16 NG125LMA 20 - 25 70/70 70/70 32 - 40 70/70 50 - 63 80 Note. respect the basic overload and short-circuit discrimination rules, see page 16. Schneider Electric

30/30 30/30 30/30

40/40 40/40 40/40

40/40 40/40 40/40

70/70 70/70

100/100 100/100

150/150 150/150

25/25 25/25

70/70 70/70 70/70 70/70 100/100 100/100 100/100 100/100 150/150 150/150 150/150 150/150 25/25 25/25 25/25

25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36

25/25 25/25

25/25 25/25 25/25

70/70 70/70

70/70 70/70 70/70

100/100 100/100

100/100 100/100 100/100

150/150 150/150

150/150 150/150 150/150

109

Complementary technical information

Cascading and enhanced discrimination Upstream: NS250 to NS630b Downstream: NSA160N, NSC100N, NS100 to NS250
NS250H 70 kA TM-D 200 50/50 50/50 70/70 36/70 250 50/50 50/50 70/70 36/70 NS250L 150 kA TM-D 160 50/50 50/50 150/150 36/150 150/150 36/150 36/150 36/150 36/150 36/150 200 50/50 50/50 150/150 36/150 150/150 36/150 36/150 36/150 36/150 36/150 250 50/50 50/50 150/150 36/150 150/150 36/150 36/150 36/150 36/150 36/150 NS250N NS250H NS250L 36 kA STR22SE 250 36/36 36/36 36/36 36/36 250 50/50 50/50 70/70 36/70 250 50/50 50/50 150/150 36/150 150/150 36/150 36/150 36/150 36/150 36/150 70 kA 150 kA

Upstream: Compact NS250 Downstream: Compact NS100 to NSA160


Upstream Breaking capacity Trip unit Downstream NSA160N 30 kA NSC100N 18 kA NS100N 25 kA Trip unit TM-D NS100H 70 kA Trip unit TM-D NS100N 25 kA NS250N 36 kA TM-D

Rating 160 200 250 160 63 - 160 36/36 36/36 36/36 50/50 16 - 100 36/36 36/36 36/36 50/50 36/36 36/36 36/36 70/70 y 25 40 - 100 36/36 36/36 36/36 36/70 y 25 40 - 100 Trip unit STR22SE 36/36 36/36 36/36 36/70 Trip unit STR22ME 36/36 36/36 36/36 36/70 NS100H 70 kA Trip unit STR22SE Trip unit STR22ME Note. respect the basic overload and short-circuit discrimination, see page 16.

36/70 36/70

36/70 36/70

36/36 36/36

36/70 36/70

Upstream: Compact NS400 to NS630b Downstream: Compact NS100 to NS250


Upstream Breaking capacity Trip unit Downstream NSA160N 30 kA NSC100N 18 kA NS100N 25 kA NS100H 70 kA NS160N 35 kA NS160H 70 kA NS250N 35 kA NS250H 70 kA NS100N 25 kA NS100H NS160N NS160H NS250N NS250H 70 kA 35 kA 70 kA 35 kA 70 kA 63 - 160 16 - 100 all TM-D-G-MA all TM-D-MA all TM-D-MA all TM-D-MA all TM-D-MA all TM-D-MA Trip unit STR22SE Trip unit STR22ME Trip unit STR22/SE Trip unit STR22ME Trip unit STR22SE Trip unit STR22ME Trip unit STR22SE Trip unit STR22ME Trip unit STR22SE Trip unit STR22ME Trip unit STR22SE Trip unit STR22ME NS400N NS400 H NS400L NS630N NS630H NS630L NS630bN 45 kA Rating 36/36 36/36 45/45 45/45 70 kA 400 50/50 50/50 70/70 70/70 150 kA 400 50/50 50/50 150/150 150/150 150/150 150/150 45 kA 400 36/36 36/36 45/45 45/45 45/45 45/45 45/45 70/70 70/70 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 45/45 45/45 70 kA 630 50/50 50/50 70/70 70/70 70/70 70/70 70/70 150 kA 630 50/50 50/50 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 50 kA Micrologic 5.0 630 36/36 36/36 50/50 50/50 50/50 50/50 50/50 STR23SE or STR53UE STR23SE or STR53UE NS630bH 70 kA Micrologic 5.0 630 50/50 50/50 70/70 70/70 70/70 70/70 70/70 NS630bL 150 kA Micrologic 5.0 630 50/50 50/50 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 630

45/45 45/45

70/70 70/70

45/45 45/45

70/70 70/70

50/50 50/50

70/70 70/70

45/45 45/45

70/70 70/70

50/50 50/50

70/70 70/70

110

Schneider Electric

Complementary technical information

Cascading and enhanced discrimination Upstream: NS800 to NS1600 Downstream: NSA160N, NSC100N, NS100 to NS630
NS800 H 70 kA NS800L 150 kA NS1000N NS1000H NS1000L 50 kA 70 kA 1000 150 kA 1000 Micrologic 2.0 NS1250N NS1250H NS1600N NS1600H 50 kA 1250 70 kA 1250 50 kA 1600 70 kA 1600 Micrologic 2.0 Micrologic 2.0

Upstream Breaking capacity Trip unit Downstream NSA160N 30 kA NSC100N 18 kA NS100N 25 kA NS100H 70 kA NS160N 35 kA NS160H 70 kA NS250N 35 kA NS250H 70 kA NS100N 25 kA

NS800N 50 kA

Micrologic 2.0

Rating 800 800 800 1000 63 - 160 16 - 100 all TM-D-G-MA 50/50 70/70 150/150 50/50 all TM-D-MA 150/150 all TM-D-MA 50/50 70/70 150/150 50/50 all TM-D-MA 150/150 all TM-D-MA 50/50 70/70 150/150 50/50 all TM-D-MA 150/150 Trip unit STR22SE 50/50 70/70 150/150 50/50 Trip unit STR22ME 50/50 70/70 150/150 50/50 NS100H 70 kA Trip unit STR22SE 150/150 Trip unit STR22ME 150/150 NS160N 35 kA Trip unit STR22SE 50/50 70/70 150/150 50/50 Trip unit STR22ME 50/50 70/70 150/150 50/50 NS160H 70 kA Trip unit STR22SE 150/150 Trip unit STR22ME 150/150 NS250N 35 kA Trip unit STR22SE 50/50 70/70 150/150 50/50 Trip unit STR22ME 50/50 70/70 150/150 50/50 NS250H 70 kA Trip unit STR22SE 150/150 Trip unit STR22ME 150/150 NS400N 45 kA Trip unit STR23SE 50/50 70/70 50/50 Trip unit STR53UE 50/50 70/70 50/50 Trip unit STR43ME 50/50 70/70 50/50 NS630N 45 kA Trip unit STR23SE 50/50 70/70 50/50 Trip unit STR53UE 50/50 70/70 50/50 Trip unit STR43ME 50/50 70/70 50/50 Note. respect the basic overload and short-circuit discrimination rules, see page 16.

70/70 70/70 70/70 70/70 70/70

70/70 70/70

70/70 70/70

150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150

50/50 50/50 50/50 50/50 50/50

70/70 70/70 70/70 70/70 70/70

50/50 50/50 50/50 50/50 50/50

70/70 70/70 70/70 70/70 70/70

50/50 50/50

70/70 70/70

50/50 50/50

70/70 70/70

50/50 50/50

70/70 70/70

50/50 50/50

70/70 70/70

70/70 70/70 70/70 70/70 70/70 70/70

50/50 50/50 50/50 50/50 50/50 50/50

70/70 70/70 70/70 70/70 70/70 70/70

50/50 50/50 50/50 50/50 50/50 50/50

70/70 70/70 70/70 70/70 70/70 70/70

Schneider Electric

111

Complementary technical information

Cascading and enhanced discrimination Upstream: Compact NS160 to NS400 Downstream: Integral 18 to Integral 63
NS160H 70 kA TM-D NS160L 150 kA TM-D 100/125/160 80 NS250H 70 kA TM-D 100/125/160 160 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 200/250 NS250L 150 kA TM-D 160 200/250

Upstream Breaking capacity Trip unit Downstream Thermal Rating (A)

80

relay Integral 18 LB1-LB03P01 0.1 to 0.16 70/70 70/70 150/150 LD1-LB030 LB1-LB03P02 0.16 to 0.25 70/70 70/70 150/150 LB1-LB03P03 0.25 to 0.40 70/70 70/70 150/150 LB1-LB03P04 0.40 to 0.63 70/70 70/70 150/150 LB1-LB03P05 0.63 to 1 70/70 70/70 150/150 LB1-LB03P06 1 to 1.6 70/70 70/70 150/150 LB1-LB03P07 1.6 to 2.5 70/70 70/70 150/150 LB1-LB03P08 2.5 to 4 70/70 70/70 150/150 LB1-LB03P10 4 to 6 70/70 70/70 150/150 LB1-LB03P13 6 to 10 70/70 70/70 150/150 LB1-LB03P17 10 to 16 70/70 LB1-LB03P21 12 to 18 70/70 Integral 32 LB1-LC03M03 0.25 to 0.40 70/70 70/70 150/150 LD1-LC030 LB1-LC03M04 0.40 to 0.63 70/70 70/70 150/150 LD4-LC130 LB1-LC03M05 0.63 to 1 70/70 70/70 150/150 LD4-LC030 LB1-LC03M06 1 to 1.6 70/70 70/70 150/150 LB1-LC03M07 1.6 to 2.5 70/70 70/70 150/150 LB1-LC03M08 2.5 to 4 70/70 70/70 150/150 LB1-LC03M10 4 to 6 70/70 70/70 150/150 LB1-LC03M13 6 to 10 70/70 150/150 LB1-LC03M17 10 to 16 70/70 150/150 LB1-LC03M22 16 to 25 70/70 150/150 LB1-LC03M53 23 to 32 70/70 8/150 Integral 63 LB1-LD03M16 10 to 13 LD1-LD030 LB1-LD03M21 11 to 18 LD4-LD130 LB1-LD03M22 18 to 25 LD4-LD030 LB1-LD03M53 23 to 32 LB1-LD03M55 28 to 40 LB1-LD03M57 35 to 50 LB1-LD03M61 45 to 63 Note: respect the basic overload and short-circuit discrimination rules, see page 16. Upstream Breaking capacity Trip unit Downstream Thermal Rating (A) NS160H 70 kA STR22SE 80 160 NS160L 150 kA STR22SE 80

70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70

70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70

150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150

150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150

NS250H 70 kA 160 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 250 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70

NS250L 150 kA 250 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150

NS400H 70 kA 400

NS400L 150 kA 400

STR22SE or STR53UE

STR22SE or STR53UE

relay Integral 18 LB1-LB03P01 0.1 to 0.16 70/70 70/70 150/150 LD1-LB030 LB1-LB03P02 0.16 to 0.25 70/70 70/70 150/150 LB1-LB03P03 0.25 to 0.40 70/70 70/70 150/150 LB1-LB03P04 0.40 to 0.63 70/70 70/70 150/150 LB1-LB03P05 0.63 to 1 70/70 70/70 150/150 LB1-LB03P06 1 to 1.6 70/70 70/70 150/150 LB1-LB03P07 1.6 to 2.5 70/70 70/70 150/150 LB1-LB03P08 2.5 to 4 70/70 70/70 150/150 LB1-LB03P10 4 to 6 70/70 70/70 150/150 LB1-LB03P13 6 to 10 70/70 70/70 150/150 LB1-LB03P17 10 to 16 70/70 70/70 150/150 LB1-LB03P21 12 to 18 70/70 70/70 150/150 Integral 32 LB1-LC03M03 0.25 to 0.40 70/70 70/70 150/150 LD1-LC030 LB1-LC03M04 0.40 to 0.63 70/70 70/70 150/150 LD4-LC130 LB1-LC03M05 0.63 to 1 70/70 70/70 150/150 LD4-LC030 LB1-LC03M06 1 to 1.6 70/70 70/70 150/150 LB1-LC03M07 1.6 to 2.5 70/70 70/70 150/150 LB1-LC03M08 2.5 to 4 70/70 70/70 150/150 LB1-LC03M10 4 to 6 70/70 70/70 150/150 LB1-LC03M13 6 to 10 70/70 70/70 150/150 LB1-LC03M17 10 to 16 70/70 70/70 150/150 LB1-LC03M22 16 to 25 70/70 70/70 150/150 LB1-LC03M53 23 to 32 70/70 Integral 63 LB1-LD03M16 10 to 13 70/70 LD1-LD030 LB1-LD03M21 11 to 18 LD4-LD130 LB1-LD03M22 18 to 25 LD4-LD030 LB1-LD03M53 23 to 32 LB1-LD03M55 28 to 40 LB1-LD03M57 35 to 50 LB1-LD03M61 45 to 63 Note. respect the basic overload and short-circuit discrimination rules, see page 16.

70/70 70/70 70/70 70/70 70/70 70/70 70/70

150/150 150/150 150/150 150/150 150/150 150/150 150/150

112

Schneider Electric

Complementary technical information

Cascading and enhanced discrimination Upstream: Compact NS160 Downstream: GV2 M


NS160H/L 70/150 kA TM-D

Upstream Breaking capacity Trip unit Downstream Thermal GV2 M01 GV2 M02 GV2 M03 GV2 M04 GV2 M05 GV2 M06 GV2 M07 GV2 M08 GV2 M10 GV2 M14 GV2 M16 GV2 M20 GV2 M21 GV2 M22 GV2 M32 relay integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated Rating (A) 0.1 to 0.16 0.16 to 0.25 0.25 to 0.40 0.40 to 0.63 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6.3 6 to 10 9 to 14 13 to 18 17 to 23 20 to 25 24 to 32

NS160N 36 kA TM-D 16 36/36 36/36 36/36 36/36 36/36 25 36/36 36/36 36/36 36/36 36/36 36/36 40 36/36 36/36 36/36 36/36 36/36 36/36 36/36 63 36/36 36/36 36/36 36/36 36/36 36/36 36/36 80 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 100 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 125 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 160 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36

16 50/50 50/50 50/50 50/50 50/50

25 50/50 50/50 50/50 50/50 50/50 50/50

40 50/50 50/50 50/50 50/50 50/50 50/50 50/50

63 50/50 50/50 50/50 50/50 50/50 50/50 50/50

80 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50

100 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50

125 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50

160 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50

Upstream Breaking capacity Trip unit Downstream Thermal GV2 M01 GV2 M02 GV2 M03 GV2 M04 GV2 M05 GV2 M06 GV2 M07 GV2 M08 GV2 M10 GV2 M14 GV2 M16 GV2 M20 GV2 M21 GV2 M22 GV2 M32 relay integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated Rating (A) 0.1 to 0.16 0.16 to 0.25 0.25 to 0.40 0.40 to 0.63 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6.3 6 to 10 9 to 14 13 to 18 17 to 23 20 to 25 24 to 32

NS160N 36 kA STR22SE80 32 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 40 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 50 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 63 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 80 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 STR22SE160 100 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 125 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 160 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36

NS160H/L 70/150 kA STR22SE80 32 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 40 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 63 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 80 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 STR22SE160 100 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 125 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 160 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50

Schneider Electric

113

Complementary technical information

Cascading and enhanced discrimination Upstream: Compact NS160 Downstream: GV2 P


NS160H 700 kA TM-D NS160L 150 kA TM-D 100 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 125 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 160 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 80 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 100 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 125 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 160 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150

Upstream Breaking capacity Trip unit Downstream Thermal GV2 P01 GV2 P02 GV2 P03 GV2 P04 GV2 P05 GV2 P06 GV2 P07 GV2 P08 GV2 P10 GV2 P14 GV2 P16 GV2 P20 GV2 P21 GV2 P22 relay integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated Rating (A) 0.1 to 0.16 0.16 to 0.25 0.25 to 0.40 0.40 to 0.63 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6.3 6 to 10 9 to 14 13 to 18 17 to 23 20 to 25

80 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70

Upstream Breaking capacity Trip unit Downstream Thermal GV2 P01 GV2 P02 GV2 P03 GV2 P04 GV2 P05 GV2 P06 GV2 P07 GV2 P08 GV2 P10 GV2 P14 GV2 P16 GV2 P20 GV2 P21 GV2 P22 relay integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated Rating (A) 0.1 to 0.16 0.16 to 0.25 0.25 to 0.40 0.40 to 0.63 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6.3 6 to 10 9 to 14 13 to 18 17 to 23 20 to 25

NS160H 70 kA STR22SE80 32 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 40 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 50 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 63 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 80 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 STR22SE160 100 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 125 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 160 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70

Upstream Breaking capacity Trip unit Downstream Thermal GV2 P01 GV2 P02 GV2 P03 GV2 P04 GV2 P05 GV2 P06 GV2 P07 GV2 P08 GV2 P10 GV2 P14 GV2 P16 GV2 P20 GV2 P21 GV2 P22 Relay integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated integrated Rating (A) 0.1 to 0.16 0.16 to 0.25 0.25 to 0.40 0.40 to 0.63 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6.3 6 to 10 9 to 14 13 to 18 17 to 23 20 to 25

NS160L 150 kA STR22SE80 32 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 40 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 50 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 63 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 80 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 STR22SE160 100 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 125 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 160 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150

114

Schneider Electric

Complementary technical information

Cascading and enhanced discrimination Upstream: Compact NS160 Downstream: GV2 L


NS160H 700 kA TM-D NS160L 150 kA TM-D 100 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 125 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 160 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 80 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 100 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 125 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 160 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150

Upstream Breaking capacity Trip unit Downstream Thermal GV2 L03 GV2 L04 GV2 L05 GV2 L06 GV2 L07 GV2 L08 GV2 L10 GV2 L14 GV2 L16 GV2 L20 GV2 L22 relay LR2 D13 03 LR2 D13 04 LR2 D13 05 LR2 D13 06 LR2 D13 07 LR2 D13 08 LR2 D13 10 LR2 D13 14 LR2 D13 16 LR2 D13 21 LR2 D13 22 Rating (A) 0.25 to 0.40 0.40 to 0.63 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6.3 7 to 10 9 to 13 12 to 18 17 to 25

80 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70

Upstream Breaking capacity Trip unit Downstream Thermal GV2 L03 GV2 L04 GV2 L05 GV2 L06 GV2 L07 GV2 L08 GV2 L10 GV2 L14 GV2 L16 GV2 L20 GV2 L22 relay LR2 D13 03 LR2 D13 04 LR2 D13 05 LR2 D13 06 LR2 D13 07 LR2 D13 08 LR2 D13 10 LR2 D13 14 LR2 D13 16 LR2 D13 21 LR2 D13 22 Rating (A) 0.25 to 0.40 0.40 to 0.63 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6.3 7 to 10 9 to 13 12 to 18 17 to 25

NS160H 70 kA STR22SE80 32 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 40 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 50 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 63 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 80 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 STR22SE160 100 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 125 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 160 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70 70/70

Upstream Breaking capacity Trip unit Downstream Thermal GV2 L03 GV2 L04 GV2 L05 GV2 L06 GV2 L07 GV2 L08 GV2 L10 GV2 L14 GV2 L16 GV2 L20 GV2 L22 relay LR2 D13 03 LR2 D13 04 LR2 D13 05 LR2 D13 06 LR2 D13 07 LR2 D13 08 LR2 D13 10 LR2 D13 14 LR2 D13 16 LR2 D13 21 LR2 D13 22 Rating (A) 0.25 to 0.40 0.40 to 0.63 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6.3 7 to 10 9 to 13 12 to 18 17 to 25

NS160L 150 kA STR22SE80 32 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 40 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 50 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 63 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 80 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 STR22SE160 100 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 125 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 160 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150

Schneider Electric

115

Complementary technical information

116

Schneider Electric

Complementary technical information

Protection of motor circuits Circuit breaker/contactor coordination


A circuit supplying a motor may include one, two, three or four switchgear or controlgear devices fulfilling one or more functions. When a number of devices are used, they must be coordinated to ensure optimum operation of the motor. Protection of a motor circuit involves a number of parameters that depend on: b the application (type of machine driven, operating safety, starting frequency, etc.) b the level of service continuity imposed by the load or the application b the applicable standards to ensure protection of life and property. The necessary electrical functions are of very different natures: b protection (motor-dedicated for overloads) b control (generally with high endurance levels) b isolation

E34300

Protection functions
Disconnection functions: Isolate a motor circuit prior to maintenance operations. Short-circuit protection: Protect the starter and the cables against major overcurrents (> 10 In). Control: Start and stop the motor, and, if applicable: b gradual acceleration b speed control. Overload protection: Protect the starter and the cables against minor overcurrents (< 10 In). Additional specific protection: b limitative fault protection (while the motor is running) b preventive fault protection (monitoring of motor insulation with motor off). Overloads (I < 10 In) An overload may be caused by: b an electrical problem, for instance on the mains (loss of a phase, voltage outside tolerances, etc.) b a mechanical problem, for instance excessive torque due to abnormally high demands by the process or motor damage (bearing vibrations, etc.). A further consequence of these two origins is excessively long starting. Impedant short-circuit (10 < I < 50 In) Deterioration of motor-winding insulation is the primary cause. Short-circuit (I > 50 In) This type of fault is relatively rare. A possible cause may be a connection error during maintenance. Overload protection Thermal relays provide protection against this type of fault. They may be: b integrated in the short-circuit protective device b separate. Short-circuit protection This type of protection is provided by a circuit breaker. Protection against insulation faults This type of protection may be provided by: b a residual current device (RCD) b an insulation monitoring device (IMD).

disconnection and short-circuit protection

control

overload or thermal protection

specific or internal motor protection

Schneider Electric

117

Complementary technical information

Protection of motor circuits Circuit breaker/contactor coordination


Applicable standards
A circuit supplying a motor must comply with the general rules set out in IEC standard 60947-4-1 and in particular with those concerning contactors, motor starters and their protection as stipulated in IEC 60947-4-1, notably: b coordination of the components of the motor circuit b trip class for thermal relays b contactor utilisation categories b coordination of insulation.

Coordination of the components of the motor circuit


Two types of coordination The standard defines tests at different current levels. The purpose of these tests is to place the switchgear and controlgear in extreme conditions. Depending on the state of the components following the tests, the standard defines two types of coordination. b type 1 Deterioration of the contactor and the relay is acceptable under two conditions: v no danger to operating personnel v no danger to any components other than the contactor and the relay; b type 2 Only minor welding of the contactor or starter contacts is permissible and the contacts must be easily separated. v following type-2 coordination tests, the switchgear and controlgear functions must be fully operational. Which type of coordination is needed? Selection of a type of coordination depends on the operating conditions encountered. The goal is to achieve the best balance between the users needs and the cost of the installation. b type 1 v qualified maintenance service v low cost of switchgear and controlgear v continuity of service is not imperative or may be ensured by simply replacing the faulty motor drawer; b type 2 v continuity of service is imperative v limited maintenance service v specifications stipulating type 2.

118

Schneider Electric

Complementary technical information

Protection of motor circuits Circuit breaker/contactor coordination


The different test currents
Ic, r and Iq test currents To qualify for type-2 coordination, the standard requires three fault-current tests to check that the switchgear and controlgear operates correctly under overload and short-circuit conditions. Ic current (overload I < 10 In) The thermal relay provides protection against this type of fault, up to the Ic value (a function of Im or Isd) defined by the manufacturer. IEC standard 60947-4-1 stipulates two tests that must be carried out to guarantee coordination between the thermal relay and the short-circuit protective device: b at 0.75 Ic, only the thermal relay reacts b at 1.25 Ic, the short-circuit protective device reacts. Following the tests at 0.75 and 1.25 Ic, the trip characteristics of the thermal relay must be unchanged. Type-2 coordination thus enhances continuity of service. The contactor may be closed automatically following clearing of the fault. r current (Impedant short-circuit 10 < I < 50 In) The primary cause of this type of fault is the deterioration of insulation. IEC standard 60947-4-1 defines an intermediate short-circuit current r. This test current is used to check that the protective device provides protection against impedant short-circuits. There must be no modification in the original characteristics of the contactor and the thermal relay following the test. The circuit breaker must trip in i 10 ms for a fault current u 15 In.
Operational current Ie (AC3) of the motor (in A) Ie y 16 16 < Ie y 63 63 < Ie y 125 125 < Ie y 315 315 < Ie < 630 r current (in kA) 1 3 5 10 18

Iq current (short-circuit I > 50 In) This type of fault is relatively rare. A possible cause may be a connection error during maintenance. Short-circuit protection is provided by devices that open quickly. IEC standard 60947-4-1 defines the Iq current as generally u 50 kA. The Iq current is used to check the coordination of the switchgear and controlgear installed on a motor supply circuit. Following this test under extreme conditions, all the coordinated switchgear and controlgear must remain operational.

time
E34301

t er i charac

circuit-breaker thermal withstand limit (MA)


ft

service continuity >

s ti

o cs

he

rm

al r e

lay

thermal-relay withstand limit

<imperative tripping of the circuit-breaker


ma

gneti

c release (MA)

1 In

10 0,75lc overload zone Ic 1,25lc inpedant short-circuit zone r short-circuit zone

50 ~ k ln Iq

Schneider Electric

119

Complementary technical information

Protection of motor circuits Circuit breaker/contactor coordination


Trip class of a thermal relay

E34302

ts

class 30 30s class 20 20s class 10 10s

The four trip class of a thermal relay are 10 A, 10, 20 and 30 (maximum tripping times at 7.2 Ir). Classes 10 and 10 A are the most commonly used. Classes 20 and 30 are reserved for motors with difficult starting conditions. The diagram and the table opposite can be used to select a thermal relay suited to the motor starting time.
Class 10 A 10 20 30 1.05 Ir t>2h t>2h t>2h t>2h 1.2 Ir t<2h t<2h t<2h t<2h 1.5 Ir t < 2 min. t < 4 min. t < 8 min. t < 12 min. 7.2 Ir 2 y t y 10 s 4 y t y 10 s 6 y t y 20 s 9 y t y 30 s

1.05 1.20

1.5

7.2

l/lr

Trip class of a thermal relay.

120

Schneider Electric

Protection of motor circuits Circuit breaker/contactor coordination


The four utilisation categories of contactors (AC1 to AC4)
The four utilisation categories of contactors (AC1 to AC4)The utilisation category determines the operating frequency and endurance of a contactor. The category depends on the type of load. If the load is a motor; the category also depends on the service classification. Main characteristics of the controlled electrical circuits and applications

Category AC1 AC2

Type of load no-inductive (cos 0,8) slip-ring motors (cos 0,65)

AC3

AC4

squirrel-cage motors (cos 0,45 for le y 100A) (cos 0,35 for le > 100A) squirrel-cage motors (cos 0,45 for le y 100A) (cos 0,35 for le > 100A)

Contactor usage energisation starting switching off during running regenerative braking inching starting switching off during running starting switching off during running regenerative braking plugging inching

typical applications heating, distribution wire drawing machines

compressors, lifts, mixing pumps, escalators, fans, conveyers, air-conditioning printing machines, wire drawing machines

E94969

current Ic interruption of power supply

AC3 utilisation category


This category covers asynchronous squirrel-cage motors that are switched off during running. This is the most common situation (85% of all cases). The control device establishes the starting current and interrupts the rated current at a voltage equal to approximately one-sixth of the rated value. Current interruption is carried out with no difficulty.

Id

starting period

time

AC3 utilisation category. The contactor interrupts the rated current of the motor.

E34304

current Ic interruption of power current

AC4 utilisation category


This category covers asynchronous squirrel-cage or slip-ring motors capable of operating under regenerative-braking or inching (jogging) conditions. The control device establishes the starting current and is capable of interrupting the starting current at a voltage that may be equal to that of the mains. Such difficult conditions require oversizing of the control and protective devices with respect to category AC3.

Id

starting period

time

AC4 utilisation category. The contactor must be capable of interrupting the starting current id.

Schneider Electric

121

Complementary technical information

Protection of motor circuits Using the circuit breaker / contactor coordination tables
Subtransient phenomena related to direct on-line starting of asynchronous motors
Subtransient phenomena occurring when starting squirrel-cage motors: A squirrel-cage motor draws a high inrush current during starting. This current is related to the combined influence of two parameters: b the high inductance of the copper stator winding b the magnetisation of the iron core of the stator. In motor: current drawn by the motor at full rated load (in A rms) Id: current drawn by the motor during starting (in A ms) Id: subtransient current generated by the motor when it is energised. This very short subtransient phenomenon is expressed as k x Id x r (in A peak). td: motor starting time, from 0.5 to 30 seconds depending on the application. td: duration of the subtransient current, from 0.010 to 0.015 seconds when the motor is energised. Irm: magnetic setting of the circuit breakers.

t(s)
E41251

thermal relay

td (0.5 to 30s)

td (0.010 to 0.015s)

short-circuit protection (magnetic circuit breaker)

In motor

Irm Id" (2 to 2.5 Id in A peak) Id (5.8 to 8.6 In in A rms)

I(A)

Typical upper and lower limits for these subtransient currents: These values, not covered by standards, also depend on the type of motor technology used: b ordinary motors Id=2 Id to 2.1 Id (in A peak), b high-efficiency motors Id=2.2 Id to 2.5 Id (in A peak). b variation of Id as a function of Id:
Type of motor Ordinary motor Id (in A rms) 5,8 8,6 In motor Id (in A peak) Id = 2 Id = 11,5 In (A peak) to Id = 2,1 Id = 18 In (A peak) High-efficiency motor 5,8 8,6 In motor Id = 2,2 Id = 12,5 In (A peak) to Id = 2,5 Id = 21,5 In (A peak) Example: Upon energisation, a high-efficiency motor with an Id of 7.5 In produces a subtransient current with a value between (depending on its characteritics): v minimum = 16.5 In (in A peak), v maximum = 18.8 In (in A peak).

122

Schneider Electric

Complementary technical information

Protection of motor circuits Using the circuit breaker / contactor coordination tables
Subtransient currents and protection settings: b as illustrated in the above table, subtransient currents can be very high. If they approach their upper limits, they can trip short-cicuit protection devices (nuisance tripping) b Merlin Gerin and Telemecanique circuit breakers are rated to provide optimum short-circuit protection for motor starters (type 2 coordination with thermal relay and contactor) b combinations made up of Merlin Gerin circuit breakers and Telemecanique contactors and thermal relays are designed to allow starting of motors generating high subtransient currents (up to 19 In motor peak) b the tripping of short-circuit protective devices when starting with a combination listed in the coordination tables means: v the limits of certain devices may be reached. v the use of the starter under type 2 coordination conditions on the given motor may lead to premature wear of one of the components of the combination. In event of such a problem, the ratings of the starter and the associated protective devices must be redesigned.

Using the coordination tables for Merlin Gerin circuit breaker and Telemecanique contactors:
b ordinary motor: The starter components can be selected directly from the coordination tables, whatever the values of the starting current (Id from 5.8 to 8.6 In) and the subtransient current. b high-efficiency motors with Id y 7.5 In: The starter components can be selected directly from the coordination tables, whatever the values of the starting current and the subtransient current. b high-efficiency motors with Id > 7.5 In When Merlin Gerin circuit breakers are used for motor currents in the neighbourhood of their rated current, they are set to provide minimum shortcircuit protection at 19 In motor (A peak). There are two possibilities: b the subtransient starting current is known (indicated by the motor manufacturer) and is less than 19 In motor (A peak). In this case, the starter components can be selected directly from the coordination tables, whatever the value of the starting current (for Id > 7.5 In). Example: For a 110 kW 380/415 V 3-phase motor, the selected components are: NS250-MA220 / LC1-F225 / LR9-F5371. b the subtransient starting current is unknown or greater than 19 In motor (A peak). In this case, the value used for the motor power in the coordination tables should be increased by 20 % to satisfy optimum starting and coordination conditions. Example: For a 110 kW 380/415 V 3-phase motor, the selected components are those for a motor power of 110 + 20 % = 132 kW: NS400-MA320 / LC1-F265 / LR9-F5371.

Reversing starters and coordination:


The starter components can be selected using the tables for direct-on-line starting. Replace contactors LC1 by LC2.

Start-delta starting and coordination:


b the components should be sized according to the current flowing in the motor windings. b the mounting locations and connections of the various components of star-delta starters should be selected according to the type of coordination required and the protective devices implemented.

Schneider Electric

123

Complementary technical information

Protection of motor circuits Using the circuit breaker / contactor coordination tables
Start-delta starting and type 1 coordination
Contactors KM2 and KM3 are sized for the line current divided by e KM1 can be sized for the line current divided by 3, however, for the sake of homogeneity, it is often identical to contactors KM2 and KM3. The starter components are selected from the special star-delta type 1 coordination tables. Example: Consider the following case: b 45 kW motor supplied at 380 V b star-delta starting b separate thermal relay b short-circuit current of 20 kA at the starter b type 1 coordination. The starter components are selected using the table on page 149: b circuit breaker: NS100N-MA 100 b contactor: LC3-D50 b thermal relay: LR2-D3357

E34305

KM2

KM3

KM1

M
Solution with thermal-magnetic motor circuit breaker

E34306

KM2

KM3

KM1

Solution with magnetic motor circuit breaker

E34305

Start-delta starting and type 2 coordination


Contactors KM1, KM2 and KM3 are sized for the line current. The starter components are selected from the direct-on-line type 2 coordination tables. Example: Consider the following case: b 55 kW motor supplied at 415 V b star-delta starting b thermal protection built into the circuit breaker providing short-circuit protection b short-circuit current of 45 kA at the starter b type 2 coordination. The starter components are selected using the table on page 130: b circuit breaker: NS160H with STR22ME b starter: LC1-F115A to be replaced by LC3-F115.

KM2

KM3

KM

M
Solution with thermal-magnetic motor circuit breaker

E34307

KM2

KM3

KM1

M
Solution with magnetic motor circuit breaker

124

Schneider Electric

Complementary technical information

Protection of motor circuits Circuit breaker/contactor coordination


Starting class and thermal relays
The data in the tables on pages 133 to 158 corresponds to normal motor starting times. The associated thermal relays are either class 10 or 10 A (tripping time < 10 s). b for motors with long starting times, the class 10 or 10 A thermal relays must be replaced with class 20 thermal relays as indicated in the correspondence table opposite (for type 1 and type 2 coordination) b long starting times requiring a class 30 relay: v apply a derating coefficient (K = 0.8) to the circuit breaker and the contactor. Example: E.g.NS100H MA 100 for 80 A maximum.LC1F115 for 92 A maximum; b these tables may also be used for standard thermal protection using current transformers. The required thermal relays are: v LR2-D1305 (0.63 to 1 A) for class 10 v LR2-D1505 (0.63 to 1 A) for class 20 with terminal block LA7-D1064. The current transformer ratings must be 5 VA per phase. The other characteristics are identical to those described below. b coordination tables with the multifunction protective relay LT6-P v three types of multifunction relays (see the corresponding catalogue for detailed characteristics) are available. They may be connected: - directly to the motor power supply line; - to the secondary winding of the current transformer.
Relay Rating Connecting Direct LT6-P0M005 FM LT6-P0M025 FM 0,2 to 1 A 1 to 5 A 5 to 25 A b b b Using current transformers b b

v the characteristics of the current transformers are the following (as defined by IEC 44-1 / 44-3):

10

Accuracy class (5 %) CT intended for motor protection Multiple of the saturation current

Schneider Electric

125

Complementary technical information

Protection of motor circuits Circuit breaker/contactor coordination


Correspondence table for class 10/10 A and class 20 relays
Thermal relay Class 10/10 A LR2-D1305 LR2-D1306 LR2-D1307 LR2-D1308 LR2-D1310 LR2-D1312 LR2-D1314 LR2-D1316 LR2-D1321 LR2-D1322 LR2-D2353 LR2-D2355 LR2-D3322 LR2-D3353 LR2-D3355 LR2-D3357 LR2-D3359 LR2-D3361 LR2-D3363 LR2-D3365 LR9-D5357 LR9-D5363 LR9-D5367 LR9-D5369 LR9-F5357 LR9-F5363 LR9-F5367 LR9-F5369 LR9-F5371 LR9-F7375 LR9-F7379 LR9-F7381 LR2-F7379 LR2-F7381 LR2-F8383 LR2-F8385 Class 20 Setting range 0.63 to 1 1 to 1.6 1.6 to 2.5 2.5 to 4 4 to 6 5.5 to 8 7 to 10 9 to 13 12 to 18 17 to 25 23 to 32 28 to 36 17 to 25 23 to 32 30 to 40 37 to 50 48 to 65 55 to 70 63 to 80 80 to 93 30 to 50 48 to 80 60 to 100 90 to 150 30 to 50 48 to 80 60 to 100 90 to 150 132 to 220 200 to 300 300 to 500 380 to 630 315 to 500 400 to 630 500 to 800 630 to 1000

LR2-D1508 LR2-D1510 LR2-D1512 LR2-D1514 LR2-D1516 LR2-D1521 LR2-D1522 LR2-D2553 LR2-D3522 LR2-D3553 LR2-D3555 LR2-D3557 LR2-D3559 LR2-D3561 LR2-D3563 LR9-D5557 LR9-D5563 LR9-D5567 LR9-D5569 LR9-F5557 LR9-F5563 LR9-F5567 LR9-F5569 LR9-F5571 LR9-F7575 LR9-F7579 LR9-F7581 LR2-F7579 LR2-F7581 LR2-F7583 LR2-F7585

Type 1 coordination tables


Circuit breaker Direct on-line starting reverser page 147 Star-delta starting page 150 page 151

With short circuit protection With short circuit page 148 and overload protection

Type 2 coordination tables


Circuit breaker Direct on-line starting, star-delta or reverser 220/240 V 380/415 V 440 V 500/525 V p. 128 p. 131 p. 136 p. 141 p. 133 p. 138 690 V p. 144

Magnetic MA Magnetic MA + multifonctional or thermal relay on CT Electronic p. 127

p. 130

p. 135

p. 140

p. 143

b the coordination data for 440 V is valid for 480 V NEMA.

126

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 220/240 V

electronic circuit-breaker

Merlin Gerin circuit breakers,Telemecanique contactors


Performance: U = 220/240 V
Circuit breakers NS100-STR22ME NS160-STR22ME NS250-STR22ME NS400-STR43ME NS630-STR43ME N 85 kA 85 kA 85 kA 85 kA 85 kA H 100 kA 100 kA 100 kA 100 kA 100 kA L 130 kA 130 kA 130 kA 130 kA 130 kA

E62559

contactor

Starting: Normal Long Motors P (kW) 1.5 2.2 3 4 5.5 6.3 7.5 10 11 15 18.5 22 I (A) 220 V 6.5 9 12 15 21 24 28 36 39 52 63 75 I (A) 240 V 6 8 11 14 19 22 25 33 36 48 59 70 Ie max (A) 10 10 12.5 20 25 25 40 40 40 80 80 100 Circuit-breakers Type NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS400 NS100 NS400 NS160 NS400 NS160 NS400 NS250 NS400 NS400 NS400 NS630 NS630 NS630 Trip unit STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR43ME STR43ME STR43ME STR43ME STR43ME Irth (A) 6/10 6/10 7.5/12.5 7.5/20 7.5/25 7.5/25 24/40 24/40 24/40 48/80 48/80 60/100 60/120 60/100 60/120 90/150 100/200 90/150 100/200 131/220 100/200 160/320 160/320 250/500 250/500 250/500

STR22ME class 10 -

STR43ME class 10 class 20 Contactors

Irm (A) 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth 13 Irth

30

100

95

100

37

125

115

150

45

150

140

150

55 75 90 110 132 150

180 250 300 360 430 460

170 235 280 330 400 450

185 265 320 400 500 500

Type LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 or LC1-F115 LC1-F185 LC1-D115 or LC1-F115 LC1-F185 LC1-D150 or LC1-F150 LC1-F185 LC1-D150 or LC1-F150 LC1-F185 LC1-F185 LC1-F185 LC1-F265 LC1-F330 LC1-F400 LC1-F500 LC1-F500

Schneider Electric

127

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 220/240 V

E34309

magnetic circuit breaker (MA)

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 220/240 V
Circuit breaker NS80-MA N H 100 kA L -

contactor thermal relay

Starting (1): normal

LRD2 class 10 A, LR9 class 10

Motors P (kW) 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 6.3 7.5 10 11 15 18.5 22 I (A) 220 V 0.7 0.9 1.2 1.5 2 2.8 3.5 5 6.5 9 12 15 21 24 28 36 39 52 63 75 I (A) 240 V 0.6 0.8 1.1 1.4 1.8 2.6 3.2 4.5 6 8 11 14 19 22 25 33 36 48 59 70 Ie max (A) 1 1 1.6 2.5 2.5 4 4 6 8 10 12.5 18 25 25 32 50 40 50 50 63 80 63 80 80

Circuit breakers Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal. (A) 1.5 1.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 50 80 80 80 Irm (A) 13.5 13.5 22.5 32.5 32.5 57 57 82 113 138 163 250 325 325 450 550 650 880 880 1040

Contactors (2) Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D50 LC1-D80 LC1-D50 LC1-D80 LC1-D65 LC1-D80 LC1-D65 LC1-D80 LC1-D80 LC1-D80

Thermal relays Type LR2-D13 05 LR2-D13 05 LR2-D13 06 LR2-D13 07 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D13 21 LR2-D33 22 LR2-D33 22 LR2-D33 53 LR9-D53 57 LR2-D33 55 LR9-D53 57 LR2-D33 57 LR9-D53 57 LR2-D33 59 LR9-D53 63 LR2-D33 59 LR9-D53 63 LR2-D33 63 LR9-D53 63 Irth (1) (A) 0.63/1 0.63/1 1/1.6 1.6/2.5 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 17/25 23/32 30/50 30/40 30/50 37/50 30/50 48/65 48/80 48/65 48/80 63/80 48/80

(1) For long starting (class 20), see the correspondence table for thermal relays, page 126. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

128

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 220/240 V

E34309

magnetic circuit breaker (MA)

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 220/240 V
Circuit breakers NS100-MA NS160/250-MA NS400/630-MA N 85 kA 85 kA H 100 kA 100 kA 100 kA L 130 kA 130 kA 130 kA

contactor thermal relay

Starting (1): normal


Motors P (kW) 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 6.3 7.5 10 11 15 18.5 22 30 37 45 55 I (A) 220 V 1.2 1.5 2 2.8 3.5 5 6.5 9 12 15 21 24 28 36 39 52 63 75 100 125 150 180 I (A) 240 V 1.1 1.4 1.8 2.6 3.2 4.5 6 8 11 14 19 22 25 33 36 48 59 70 95 115 140 170 Ie max (A) 1.6 2.5 2.5 4 4 6 8 10 12.5 18 25 25 32 50 40 50 40 50 63 80 63 80 80 100 150 150 Circuit breakers Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA Cal. (A) 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 50 100 100 100 100 150 150 Irm (A) 22.5 32.5 32.5 57 57 82 113 138 163 250 325 325 450 650 550 650 550 650 700 1100 900 1100 1100 1300 1950 1950 2420 2880 3500 4160 5700 6500 6500

LR2 class 10 A, LR9 class 10


Contactors (2) Type LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-F115 LC1-D150 LC1-F150 LC1-D150 LC1-F150 LC1-F185 LC1-F265 LC1-F265 LC1-F330 LC1-F400 LC1-F500 LC1-F500 Thermal relays Type LR2-D13 06 LR2-D13 07 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D13 21 LR2-D33 22 LR2-D33 22 LR2-D33 53 LR9-D53 57 LR2-D33 55 LR9-D53 57 LR2-D33 55 LR9-D53 57 LR2-D33 59 LR9-D53 63 LR2-D33 59 LR9-D53 63 LR2-D33 63 LR9-D53 63 LR9-D53 67 LR9-F53 67 LR9-D53 69 LR9-F53 69 LR9-D53 69 LR9-F53 69 LR9-F53 71 LR9-F73 75 LR9-F73 75 LR9-F73 79 LR9-F73 79 LR9-F73 79 Irth (1) (A) 1/1.6 1.6/2.5 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 17/25 23/32 30/50 30/40 30/50 30/40 30/50 48/65 48/80 48/65 48/80 63/80 48/80 60/100 90/150 90/150 132/220 200/330 200/330 300/500 300/500 300/500

185 NS250-MA 220 220 NS400-MA 320 75 250 235 265 NS400-MA 320 90 300 270 320 NS400-MA 320 110 360 330 400 NS630-MA 500 132 430 400 500 NS630-MA 500 150 460 450 500 NS630-MA 500 (1) For long starting (class 20), see the correspondence table for thermal relays, page 358. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

129

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 380/415 V

electronic circuit-breaker

Merlin Gerin circuit breakers,Telemecanique contactors


Performance: U = 380/415 V
Circuit breakers NS100-STR22ME NS160-STR22ME NS250-STR22ME NS400-STR43ME NS630-STR43ME NS630b/1000-Micrologic 5.0 N 25 kA 35 kA 35 kA 45 kA 45 kA STR22ME class 10 H 70 kA 70 kA 70 kA 70 kA 70 kA STR43ME class 10 class 20 L 130 kA 130 kA 130 kA 130 kA 130 kA 130 kA Micrologic 5.0 class 10 class 20 Contactors (1) Irth(A) 12/20 15/25 15/25 24/40 24/40 30/50 48/80 48/80 60/100 60/120 90/150 60/120 90/150 100/200 131/220 100/200 131/220 160/200 160/320 160/320 250/500 250/500 250/500 250/630 320/800 320/800 320/800 320/800 400/1000 Irm(A) 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth Isd = 9Irth (tsd > 0.1) Ii = 10In Isd = 9Irth (tsd > 0.1) Ii = 10In Isd = 9Irth (tsd > 0.1) Ii = 11In Isd = 9Irth (tsd > 0.1) Ii = 11In Isd = 9Irth (tsd > 0.1) Ii = 12In Isd = 9Irth (tsd > 0.1) Ii = 10In Type LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 or LC1-F115 LC1-F185 LC1-D115 or LC1-F115 LC1-F185 LC1-D150 or LC1-F150 LC1-F185 LC1-F185 LC1-F185 LC1-F225 LC1-F225 LC1-F265 LC1-F330 LC1-F400 LC1-F500 LC1-F500 LC1-F630 LC1-F630 LC1-F630 LC1-F800 LC1-F800 LC1-F800

E62559

contactor

Starting: standard IEC 60947-4-1 , type 2


Normal Long Motors P(kW) 7.5 10 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 I(A) 380V 16 21 23 30 37 44 60 72 85 105 138 170 205 250 300 370 408 460 I(A) 415V 14 19 21 28 35 40 55 66 80 100 135 165 200 240 280 340 385 425 Ie max 20 25 25 40 40 50 80 80 100 115 150 185 220 265 320 400 500 500 630 630 630 800 800 800 Circuit breakers Type NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS400 NS160 NS400 NS160 NS400 NS250 NS400 NS250 NS400 NS400 NS400 NS630 NS630 NS630 NS630bL NS800L NS800L NS800L NS800L NS1000L Trip unit/t.u. STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR43ME STR43ME STR43ME STR43ME STR43ME Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Micrologic 5.0

300 335 375 400 450

565 620 670 710 800

500 560 620 660 750

(1) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

130

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 380/415 V

E34309

magnetic circuit breaker (MA)

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 380/415 V
Circuit breaker NS80-MA N H 70 kA L -

contactor thermal relay

Starting (1): normal

LR2 class 10 A, LR9 class 10

Motors P (kW) 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 I (A) 380 V 0.7 0.9 1.2 1.6 2 2.8 3.7 5.3 7 9 12 16 21 23 30 37 43 59 72 I (A) 415 V 0.6 0.8 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 19 21 28 34 40 55 66 Ie max (A) 1 1 1.6 2.5 2.5 4 4 6 8 10 12.5 18 25 25 32 40 50 63 80

Circuit breakers Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal. (A) 1.5 1.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 50 80 80 Irm (A) 13.5 13.5 22.5 32.5 32.5 57 57 82 113 138 163 250 325 325 450 550 650 880 1040

Contactors (2) Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D50 LC1-D80 LC1-D50 LC1-D80 LC1-D65 LC1-D80 LC1-D80 LC1-D80

Thermal relays Type LR2-D13 05 LR2-D13 05 LR2-D13 06 LR2-D13 07 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D13 21 LR2-D33 22 LR2-D33 22 LR2-D33 53 LR9-D53 57 LR2-D33 55 LR9-D53 57 LR2-D33 57 LR9-D53 57 LR2-D33 59 LR9-D53 63 LR2-D33 63 LR9-D53 63 Irth (1) (A) 0.63/1 0.63/1 1/1.6 1.6/2.5 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 17/25 23/32 30/50 30/40 30/50 37/50 30/50 48/65 48/80 63/80 48/80

(1) For long starting (class 20), see the correspondence table for thermal relays, page 358. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

131

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 380/415 V

with short circuit protection

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 380/415 V
Circuit breakers NS100-MA NS160/250-MA NS400/630-MA NS630b/1000-Micrologic 5.0 (LR OFF) N 25 kA 35 kA H 70 kA 70 kA 70 kA L 130 kA 130 kA 130 kA 130 kA

E62560

contactor thermal relay

Starting (1): normal

LRD2 class 10 A, autres class 10

Motors P(kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 I(A) 380V 1.2 1.6 2 2.8 3.7 5.3 7 9 12 16 21 23 30 37 43 59 72 85 I(A) 415V 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 19 21 28 34 40 55 66 80 Ie max 1.6 2.5 2.5 4 4 6 8 10 12.5 18 25 25 32 50 40 50 50 63 80 80 100

Circuit breakers Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA Cal. (A) 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 50 100 100 100 Irm(A) 22.5 32.5 32.5 57 57 82 113 138 163 250 325 325 450 650 550 650 650 650 900 1100 1100 1300

Contactors (2) Type LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80

Thermal relays Type LR2D13 06 LR2-D13 07 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D13 21 LR2-D33 22 LR2-D33 22 LR2-D33 53 LR9-F53 57 LR2-D33 55 LR9-F53 57 LR2-D33 57 LR9-F53 57 LR2-D33 59 LR9-F53 63 LR2-D33 63 LR9-F53 63 LR9-D53 67 LR9-F53 67 LR9-D53 69 LR9-F53 69 LR9-D53 69 LR9-F53 69 LR9-F53 71 LR9-F53 71 LR9-F73 75 LR9-F73 75 LR9-F73 79 LR9-F73 79 LR9-F73 79 LR9-F7379 LR9-F7381 LR9-F7381 LR2-F8385 LR2-F8385 LR2-F8385 Irth (1) 1/1.6 1.6/2.5 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7 /10 9/13 12/18 17/25 17/25 23/32 30/50 30/40 30/50 37/50 30/50 48/65 48/80 63/80 48/80 60/100 90/150 90/150 132/220 132/220 200/330 200/330 300/500 300/500 300/500 300/500 380/630 380/630 630/1000 630/1000 630/1000

LC1-D115 LC1-F115 55 105 100 115 NS160-MA 150 1500 LC1-D115 LC1-F115 75 140 135 150 NS160-MA 150 1950 LC1-D150 LC1-F150 90 170 160 185 NS250-MA 220 2420 LC1-F185 110 210 200 220 NS250-MA 220 2860 LC1-F225 NS400-MA 320 2880 LC1-F265 132 250 230 265 NS400-MA 320 3500 LC1-F265 160 300 270 320 NS400-MA 320 4160 LC1-F330 200 380 361 400 NS630-MA 500 5700 LC1-F400 220 420 380 500 NS630-MA 500 6500 LC1-F500 250 460 430 500 NS630-MA 500 6500 LC1-F500 500 NS630bL-Micrologic 5.0 630 Isd = 9Irth (tsd > 0.1) LC1-F630 Ii = 10In 300 565 500 630 NS800L-Micrologic 5.0 800 Isd = 9Irth (tsd > 0.1) LC1-F630 Ii = 10In 335 620 560 630 NS800L-Micrologic 5.0 800 Isd = 9Irth (tsd > 0.1) LC1-F630 Ii = 11In 375 670 620 800 NS800L-Micrologic 5.0 800 Isd = 9Irth (tsd > 0.1) LC1-F800 Ii = 11In 400 710 660 800 NS800L-Micrologic 5.0 800 Isd = 9Irth (tsd > 0.1) LC1-F800 Ii = 12In 450 800 750 800 NS1000L-Micrologic 5.0 1000 Isd = 9Irth (tsd > 0.1) LC1-F800 Ii = 10In (1) For long starting (class 20), see the correspondence table for thermal relays, page 358. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

132

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 380/415 V

E34310

magnetic circuit breaker (MA) contactor thermal relay on TC

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 380/415 V
Circuit breakers NS80-MA N H 70 kA L -

Starting (1): adjustable class 10 A to 30

Motors

Circuit breakers

Contactors (2)

Thermal relays Irth (1) (A) 0.2/1 0.2/1 1/5 1/5 1/5 1/5 1/5 5/25 5/25 5/25 5/25 5/25 5/25 5/25 on TC on TC on TC on TC on TC

P (kW) I (A) 380 V I (A) 415 V Ie max (A) Type Rating (A) Irm (A) Type Type 0.18 0.7 0.6 1 NS80H-MA 1.5 13.5 LC1-D40 LT6-POM 0.25 0.9 0.8 1 NS80H-MA 1.5 13.5 LC1-D40 LT6-POM 0.37 1.2 1.1 2.5 NS80H-MA 2.5 32.5 LC1-D40 LT6-POM 0.55 1.6 1.5 2.5 NS80H-MA 2.5 32.5 LC1-D40 LT6-POM 0.75 2 1.8 2.5 NS80H-MA 2.5 32.5 LC1-D40 LT6-POM 1.1 2.8 2.6 5 NS80H-MA 6.3 70 LC1-D40 LT6-POM 1.5 3.7 3.4 5 NS80H-MA 6.3 70 LC1-D40 LT6-POM 2.2 5.3 4.8 6.3 NS80.H-MA 6.3 82 LC1-D40 LT6-POM 3 7 6.5 12.5 NS80H-MA 12.5 163 LC1-D40 LT6-POM 4 9 8.2 12.5 NS80H-MA 12.5 163 LC1-D40 LT6-POM 5.5 12 11 12.5 NS80H-MA 12.5 163 LC1-D40 LT6-POM 7.5 16 14 25 NS80H-MA 25 325 LC1-D40 LT6-POM 10 21 19 25 NS80H-MA 25 325 LC1-D40 LT6-POM 11 23 21 25 NS80H-MA 25 325 LC1-D40 LT6-POM 15 30 28 50 NS80H-MA 50 650 LC1-D80 LT6-POM 18.5 37 34 50 NS80H-MA 50 650 LC1-D80 LT6-POM 22 43 40 50 NS80H-MA 50 650 LC1-D80 LT6-POM 30 59 55 80 NS80H-MA 80 1040 LC1-D80 LT6-POM 37 72 66 80 NS80H-MA 80 1040 LC1-D80 LT6-POM (1) Observe the recommendations on page 126 for installations with a class 30 relay and mounting of the thermal relay on the current transformer. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

133

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 380/415 V

E62565

with short circuit breaker protection contactor thermal relay on TC

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 380/415 V
Circuit breakers NS100-MA NS160/250-MA NS400/630-MA NS630b/1000-Micrologic 5.0 (LT OFF) N 25 kA 35 kA H 70 kA 70 kA 70 kA L 130 kA 130 kA 130 kA 130 kA

Starting (1): adjustable class 10 A to 30

Motors P(kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 I(A) 380V 1.2 1.6 2 2.8 3.7 5.3 7 9 12 16 21 23 30 37 43 59 72 85 I(A) 415V 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 19 21 28 34 40 55 66 80 Ie max 2.5 2.5 2.5 5 5 6.3 12.5 12.5 12.5 25 25 25 50 50 50 80 80 100

Circuit breakers Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA Rating (A) 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 50 100 100 100 Irm(A) 32.5 32.5 32.5 70 70 82 163 163 163 325 325 325 650 650 650 1100 1100 1300

Contactors (2)

Thermal relays

Type Type Irth (1) LC1-D40 LT6-P0M 1/5 LC1-D40 LT6-P0M 1/5 LC1-D40 LT6-P0M 1/5 LC1-D40 LT6-P0M 1/5 LC1-D40 LT6-P0M 1/5 LC1-D40 LT6-P0M 5/25 LC1-D80 LT6-P0M 5/25 LC1-D80 LT6-P0M 5/25 LC1-D80 LT6-P0M 5/25 LC1-D80 LT6-P0M 5/25 LC1-D80 LT6-P0M 5/25 LC1-D80 LT6-P0M 5/25 LC1-D80 LT6-P0M on TI LC1-D80 LT6-P0M on TI LC1-D80 LT6-P0M on TI LC1-D80 LT6-P0M on TI LC1-D80 LT6-P0M on TI LC1-D115 LT6-P0M on TI LC1-F115 55 105 100 115 NS160-MA 150 1500 LC1-D115 LT6-P0M on TI LC1-F115 75 140 135 150 NS160-MA 150 1950 LC1-D150 LT6-P0M on TI LC1-F150 90 170 160 185 NS250-MA 220 2420 LC1-F185 LT6-P0M on TI 110 210 200 220 NS250-MA 220 2860 LC1-F225 LT6-P0M on TI 265 NS400-MA 320 3500 LC1-F265 132 250 230 265 NS400-MA 320 3500 LC1-F265 LT6-P0M on TI 160 300 270 320 NS400-MA 320 4000 LC1-F330 LT6-P0M on TI 200 380 361 400 NS630-MA 500 5700 LC1-F400 LT6-P0M on TI 220 420 380 500 NS630-MA 500 6300 LC1-F500 LT6-P0M on TI 250 460 430 500 NS630-MA 500 6300 LC1-F500 LT6-P0M on TI 630 NS630bL-Micrologic 5.0 630 Isd = 9 Irth (tsd > 0.1) LC1-F630 LT6-P0M on TI Ii = 10 In 300 565 500 630 NS800L-Micrologic 5.0 800 Isd = 9 Irth (tsd > 0.1) LC1-F630 LT6-P0M on TI Ii = 10 In 335 620 560 630 NS800L-Micrologic 5.0 800 Isd = 9Irth (tsd > 0.1) LC1-F630 LT6-P0M on TI Ii = 11 In 375 670 620 800 NS800L-Micrologic 5.0 800 Isd = 9Irth (tsd > 0.1) LC1-F800 LT6-P0M on TI Ii = 11 In 400 710 660 800 NS800L-Micrologic 5.0 800 Isd = 9Irth (tsd > 0.1) LC1-F800 LT6-P0M on TI Ii = 12 In 450 800 750 800 NS1000L-Micrologic 5.0 1000 Isd = 9 Irth (tsd > 0.1) LC1-F800 LT6-P0M on TI Ii = 10 In (1) Observe the recommendations on page 126 for installations with a class 30 relay and mounting of the thermal relay on the current transformer. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

134

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 440 V

with short circuit and overload protection

Merlin Gerin circuit breakers,Telemecanique contactors


Performance (1): U = 440V
Circuit breakers NS100-STR22ME NS160-STR22ME NS250-STR22ME NS400-STR43ME NS630-STR43ME NS630b-Micrologic 5.0 N 25 kA 35 kA 35 kA 42 kA 42 kA STR22ME class10 H 65 kA 65 kA 65 kA 65 kA 65 kA STR43ME class10 class 20 L 130 kA 130 kA 130 kA 130 kA 130 kA 130 kA Micrologic 5.0 class 10 class 20

E62562

contactor

Starting: standard IEC 60947-4-1, type 2


Normal Long Motors P(kW) 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 300 I(A) 440V 5.8 8 10.5 13.7 19 20 26.5 33 39 51 64 76 90 125 146 178 215 256 320 353 400 460 Ie max 10 10 12.5 20 25 25 40 40 40 80 80 80 100 150 150 185 220 265 320 400 400 500 630 630 630 800 800 Circuit breakers Type NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS400 NS160 NS400 NS160 NS400 NS250 NS400 NS250 NS400 NS400 NS400 NS630 NS630 NS630 NS630bL NS630bL NS630bL NS800L NS800L Trip unit t.u. STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR43ME STR43ME STR43ME STR43ME STR43ME Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Irth(A) 6/10 6/10 7.5/12.5 12/20 15/25 15/25 24/40 24/40 24/40 48/80 48/80 48/80 60/100 60/120 90/150 100/200 90/150 100/200 131/220 100/200 131/220 160/3200 160/320 160/320 250/500 250/500 250/500 250/630 250/630 250/630 320/800 320/800 Irm(A) 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth Isd = 9 Irth (tsd > 0.1) Ii = 10 In Isd = 9 Irth (tsd > 0.1) Ii = 11In Isd = 9 Irth (tsd > 0.1) Ii = 12In Isd = 9 Irth (tsd > 0.1) Ii = 10In Isd = 9 Irth (tsd > 0.1) Ii = 12In

Contactors (2) Type LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 or LC1-F115 LC1-F185 LC1-D150 or LC1-F150 LC1-F185 LC1-D150 or LC1-F150 LC1-F185 LC1-F185 LC1-F185 LC1-F225 LC1-F225 LC1-F265 LC1-F330 LC1-F400 LC1-F400 LC1-F500 LC1-F630 LC1-F630 LC1-F630 LC1-F800 LC1-F800

335 375 400 450

518 575 611 720

(2) Valid for 480 V NEMA. (3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

135

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 440 V

E34309

magnetic circuit breaker (MA)

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance (2): U = 440 V
Circuit breakers NS80-MA N H 65 kA L -

contactor thermal relay

Starting (1): normal

LR2 class 10 A, LR9 class 10

Motors P (kW) 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 I (A) 440 V 0.7 1 1.4 1.7 2.4 3.1 4.5 5.8 8 10.5 13.7 19 20 26.5 33 39 52 63 76 Ie max (A) 1 1.6 1.6 2.5 2.5 4 6 6 8 12.5 18 25 25 32 40 50 40 50 63 80 63 80 80

Circuit breakers Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Rating (A) 1.5 2.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 25 25 25 50 50 50 80 80 80 Irm (A) 13.5 22.5 22.5 32.5 32.5 57 82 82 113 163 250 325 325 450 550 650 550 650 880 1040 880 1040 1040

Contactors (3) Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D40 LC1-D50 LC1-D80 LC1-D50 LC1-D80 LC1-D65 LC1-D80 LC1-D65 LC1-D80 LC1-D80

Thermal relays Type LR2-D13 05 LR2-D13 06 LR2-D13 06 LR2-D13 07 LR2-D13 07 LR2-D13 08 LR2-D13 10 LR2-D13 10 LR2-D13 12 LR2-D13 16 LR2-D13 21 LR2-D33 22 LR2-D33 22 LR2-D33 53 LR2-D33 55 LR9-D53 57 LR2-D33 55 LR9-D53 57 LR2-D33 59 LR9-D53 63 LR2-D33 59 LR9-D53 63 LR2-D33 63 LR9-D53 63 Irth (1) (A) 0.63/1 1/1.6 1/1.6 1.6/2.5 1.6/2.5 2.5/4 4/6 4/6 5.5/8 9/13 12/18 17/25 17/25 23/32 30/40 30/50 30/40 30/50 48/65 48/80 48/65 48/80 63/80 48/80

(1) For long starting (class 20), see the correspondence table for thermal relays on page 126. (2) Valid for 480 V NEMA. (3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

136

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 440 V

with short circuit protection

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance (2): U = 440V
Circuit breakers NS100-MA NS160/250-MA NS400/630-MA NS630b/800-Micrologic 5.0 (LT OFF) N 25 kA 35 kA H 65 kA 65 kA 65 kA L 130 kA 130 kA 130 kA 130 kA

E62560

contactor thermal relay

Starting (1): normal

LRD2 class 10 A, LR9 class 10

Motors P(kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 300 I(A) 440V 1 1.4 1.7 2.4 3.1 4.5 5.8 8 10.5 13.7 19 20 26.5 33 39 52 63 76 90 125 140 178 210 256 310 353 400 460 Ie max 1.6 1.6 2.5 2.5 4 6 6 8 12.5 18 25 25 32 40 50 40 50 63 80 63 80 80 100 150 150 185 220 265 265 320 400 500 500 630

Circuit breakers Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA NS250-MA NS250-MA NS400-MA NS400-MA NS400-MA NS630-MA NS630-MA NS630-MA NS630bL-Micrologic 5.0 Rating (A) 2.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 25 25 25 50 50 50 100 100 100 100 150 150 220 220 320 320 320 500 500 500 630 Irm(A) 22.5 22.5 32.5 32.5 57 82 82 113 163 250 325 325 450 550 650 550 650 900 1100 900 1100 1100 1300 1950 1950 2420 2860 3500 3500 4160 5500 6500 6500

Contactors (3) Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-F115 LC1-D150 LC1-F150 LC1-D150 LC1-F150 LC1-F185 LC1-F225 LC1-F265 LC1-F265 LC1-F330 LC1-F400 LC1-F500 LC1-F500 LC1-F630 LC1-F630 LC1-F630 LC1-F800 LC1-F800

Thermal relays Type LR2-D13 06 LR2-D13 06 LR2-D13 07 LR2-D13 07 LR2-D13 08 LR2-D13 10 LR2-D13 10 LR2-D13 12 LR2-D13 16 LR2-D13 21 LR2-D33 22 LR2-D33 22 LR2-D33 53 LR2-D33 55 LR9-F53 57 LR2-D33 55 LR9-D53 57 LR2-D33 59 LR9-D53 63 LR2-D33 59 LR9-D53 63 LR2-D33 63 LR9-D53 63 LR9-D53 67 LR9-F53 67 LR9-D53 69 LR9-F53 69 LR9-D53 69 LR9-F53 69 LR9-F53 71 LR9-F53 71 LR9-F73 75 LR9-F73 75 LR9-F73 79 LR9-F73 79 LR9-F73 79 LR2-F73 79 LR9-F75 80 LR9-F75 80 LR9-F75 80 LR9-F75 80 LR2-F75 83 Irth (1) 1/1.6 1/1.6 1.6/2.5 1.6/2.5 2.5/4 4/6 4/6 5.5/8 9/13 12/18 17/25 17/25 23/32 30/40 30/50 30/40 30/50 48/65 48/80 48/65 48/80 63/80 48/80 60/100 90/150 90/150 132/220 132/220 200/330 200/330 300/500 300/500 300/500 315/500 380/630 380/630 380/630 380/630 500/800

Isd = 9 Irth (tsd > 0.1) Ii = 10 In 335 518 630 NS630bL-Micrologic 5.0 630 Isd = 9 Irth (tsd > 0.1) Ii = 11 In 375 575 630 NS630bL-Micrologic 5.0 630 Isd = 9 Irth (tsd > 0.1) Ii = 12 In 400 611 630 NS800L-Micrologic 5.0 800 Isd = 9 Irth (tsd > 0.1) Ii = 10 In 450 720 800 NS800L-Micrologic 5.0 800 Isd = 9 Irth (tsd > 0.1) Ii = 12 In (1) For long starting (class 20), see the correspondence table for thermal relays on page 126. (2) Valid for 480 V NEMA. (3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

137

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 440 V

E34310

magnetic circuit breaker (MA) contactor thermal relay on TC

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance (2): U = 440 V
Circuit breakers NS80 MA N H 65 kA L -

Starting (1): adjustable class 10 A to 30

Motors

Circuit breakers

Contactors (3)

Thermal relays

P (kW) I (A) 440 V Ie max (A) Type Rating (A) Irm (A) Type Type Irth (1) (A) 0,25 0,7 1 NS80H-MA 1,5 13,5 LC1-D40 LT6-POM 0,2/1 0,37 1 2,5 NS80H-MA 2,5 32,5 LC1-D40 LT6-POM 1/5 0,55 1,4 2,5 NS80H-MA 2,5 32,5 LC1-D40 LT6-POM 1/5 0,75 1,7 2,5 NS80H-MA 2,5 32,5 LC1-D40 LT6-POM 1/5 1,1 2,4 2,5 NS80H-MA 2,5 32,5 LC1-D40 LT6-POM 1/5 1,5 3,1 4 NS80H-MA 6,3 82 LC1-D40 LT6-POM 1/5 2,2 4,5 5 NS80H-MA 6,3 82 LC1-D40 LT6-POM 1/5 3 5,8 6,3 NS80H-MA 6,3 82 LC1-D40 LT6-POM 5/25 4 8 12,5 NS80H-MA 12,5 163 LC1-D40 LT6-POM 5/25 5,5 10,5 12,5 NS80H-MA 12,5 163 LC1-D40 LT6-POM 5/25 7,5 13,7 25 NS80H-MA 25 325 LC1-D40 LT6-POM 5/25 10 19 25 NS80H-MA 25 325 LC1-D40 LT6-POM 5/25 11 20 25 NS80H-MA 25 325 LC1-D40 LT6-POM 5/25 15 26,5 50 NS80H-MA 50 550 LC1-D80 LT6-POM on TC 18,5 33 50 NS80H-MA 50 550 LC1-D80 LT6-POM on TC 22 39 50 NS80H-MA 50 550 LC1-D80 LT6-POM on TC 30 52 80 NS80H-MA 80 1040 LC1-D80 LT6-POM on TC 37 63 80 NS80H-MA 80 1040 LC1-D80 LT6-POM on TC 45 76 80 NS80H-MA 80 1040 LC1-D80 LT6-POM on TC (1) Observe the recommendations on page 126 for installations with a class 30 relay and mounting of the thermal relay on the current transformer. (2) Valid for 480 V NEMA. (3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

138

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 440 V

with short circuit breaker protection contactor thermal relay on TC

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance (2): U = 440V
Circuit breakers NS100-MA NS160/250-MA NS400/630-MA NS630b/1000-Micrologic 5.0 (LR OFF) N 25 kA 35 kA H 65 kA 65 kA 65 kA L 130 kA 130 kA 130 kA 130 kA

E62565

Starting (1): adjustable class 10 A to 30

Motors P(kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 55 75 90 110 132 I(A) 440V 1 1.4 1.7 2.4 3.1 4.5 5.8 8 10.5 13.7 19 20 26.5 33 39 52 63 76 90 125 140 178 210 Ie max 2.5 2.5 2.5 2.5 5 5 6.3 12.5 12.5 25 25 25 50 50 50 80 80 80 100 150 150 185 220 265 265 320 400 500 500 630

Circuit breakers Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA NS250-MA NS250-MA NS400-MA NS400-MA NS400-MA NS630-MA NS630-MA NS630-MA NS630bL-Micrologic 5.0 Rating (A) 2.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 25 25 25 50 50 50 100 100 100 100 150 150 220 220 320 320 320 500 500 500 630 Irm(A) 32.5 32.5 32.5 32.5 82 82 82 163 163 325 325 325 550 550 550 1100 1100 1100 1300 1950 1950

Contactors (3) Type LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-F115 LC1-D150 LC1-F150 LC1-D150 LC1-F150 LC1-F185 LC1-F225 LC1-F265 LC1-F265 LC1-F330 LC1-F400 LC1-F500 LC1-F500 LC1-F630

Thermal relays Type LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M LT6-P0M Irth (1) 1/5 1/5 1/5 1/5 1/5 1/5 5/25 5/25 5/25 5/25 5/25 5/25 on TI on TI on TI on TI on TI on TI on TI on TI on TI

2420 LT6-P0M on TI 2860 LT6-P0M on TI 3500 160 256 3500 LT6-P0M on TI 200 310 4000 LT6-P0M on TI 220 353 5500 LT6-P0M on TI 250 400 6500 LT6-P0M on TI 300 460 6500 LT6-P0M on TI Isd = 9 Irth (tsd > 0.1) LT6-P0M on TI Ii = 10 In 335 518 630 NS630bL-Micrologic 5.0 630 Isd = 9 Irth (tsd > 0.1) LC1-F630 LT6-P0M on TI Ii = 11 In 375 575 630 NS630bL-Micrologic 5.0 630 Isd = 9Irth (tsd > 0.1) LC1-F630 LT6-P0M on TI Ii = 12 In 400 611 800 NS800L-Micrologic 5.0 800 Isd = 9 Irth (tsd > 0.1) LC1-F800 LT6-P0M on TI Ii = 10 In 450 720 800 NS800L-Micrologic 5.0 800 Isd = 9 Irth (tsd > 0.1) LC1-F800 LT6-P0M on TI Ii = 12 In (1) Observe the recommendations on page 126 for installations with a class 30 relay and mounting of the thermal relay on the current transformer. (2) Valid for 480 V NEMA. (3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

139

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 500/525 V

with short circuit and overload protection

Merlin Gerin circuit breakers,Telemecanique contactors


Performance: U = 500/525 V
Circuit breakers NS100-STR22ME NS160-STR22ME NS250-STR22ME NS400-STR43ME NS630-STR43ME NS630b/800-Micrologic 5.0 H 50/35 kA 50/35 kA 50/35 kA 50/35 kA 50/35 kA STR22ME class 10 L 70/50 kA 70/50 kA 70/50 kA 70/50 kA 70/50 kA 100/100kA STR43ME class 10 class 20 Micrologic 5.0 class 10 class 20

E62562

contactor

Starting: standard IEC 60947-4-1 , type 2


Normal Long

Motors P(kW) 4 5.5 7.5 10 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 315 335 375 400 450 I(A) 500V 6.5 9 12 15 18.4 23 28.5 33 45 55 65 75 105 130 155 185 220 280 310 360 445 472 527 540 608 I(A) 525V 6.5 9 12 15 18.4 23 28.5 33 45 55 65 75 105 130 155 185 220 280 310 360 445 472 527 540 608 Ie max 10 12.5 12.5 20 20 25 40 40 50 80 80 100 115 150 185 220 265 320 320 500 500 500 630 630 800

Circuit breakers Type NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS100 NS400 NS160 NS400 NS160 NS400 NS250 NS400 NS250 NS400 NS400 NS400 NS630 NS630 NS630 NS630bL NS630bL NS630bL NS800L Trip unit t.u. STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR22ME STR43ME STR43ME STR43ME STR43ME STR43ME STR43ME Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Micrologic 5.0 Irth(A) 6/10 7.5/12.5 7.5/12.5 12/20 12/20 15/25 24/40 24/40 30/50 48/80 48/80 60/100 60/120 90/150 60/120 90/150 100/200 131/220 100/200 131/220 160/320 160/320 160/320 250/500 250/500 250/500 250/630 250/630 250/630 320/800 Irm(A) 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth Isd = 9 Irth (tsd > 0.1) Ii = 10 In Isd = 9 Irth (tsd > 0.1) Ii = 11 In Isd = 9 Irth (tsd > 0.1) Ii = 12 In Isd = 9 Irth (tsd > 0.1) Ii = 10 In

Contactors (1) Type LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 or LC1-F115 LC1-F185 LC1-D115 or LC1-F115 LC1-F185 LC1-D150 or LC1-F150 LC1-F185 LC1-F185 LC1-F185 LC1-F265 LC1-F265 LC1-F265 LC1-F400 LC1-F500 LC1-F500 LC1-F500 LC1-F500 LC1-F630 LC1-F630 LC1-F800

(1) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

140

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 500/525 V

E34309

magnetic circuit breaker (MA)

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 500/525 V
Circuit breakers NS80-MA H 35 kA L -

contactor thermal relay

Starting (1): normal

LR2 class 10 A, LR9 class 10

Motors P (kW) 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 I (A) 500 V 0.6 0.9 1.2 1.5 2 2.8 3.8 5 6.5 9 12 15 18.4 23 28.5 33 I (A) 525 V 0.6 0.9 1.2 1.5 2 2.8 3.8 5 6.5 9 12 15 18.4 23 28.5 33 Ie max (A) 1 1 1.6 1.6 2.5 4 4 6 8 10 12.5 16 25 25 32 40 50 50

Circuit breakers Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Rating (A) 1.5 1.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 Irm (A) 13.5 13.5 22.5 22.5 32.5 57 57 82 113 138 163 250 325 325 450 550 650 650

Contactors (2) Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D40 LC1-D50 LC1-D115 LC1-F115 LC1-D50 LC1-D115 LC1-F115 LC1-D65 LC1-D115 LC1-F115 LC1-D115 LC1-F115 LC1-D115 LC1-F115

Thermal relays (1) Type LR2-D13 05 LR2-D13 05 LR2-D13 06 LR2-D13 06 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D33 21 LR2-D33 22 LR2-D33 22 LR2-D33 53 LR2-D33 55 LR9-D53 57 LR9-F53 57 LR2-D33 57 LR9-D53 57 LR9-F53 57 LR2-D33 59 LR9-D53 63 LR9-F53 63 LR2-D33 63 LR9-D53 63 LR9-F53 63 LR9-D53 63 Irth (A) 0.63/1 0.63/1 1/1.6 1/1.6 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 17/25 23/32 30/40 30/50 30/50 37/50 30/50 30/50 48/65 48/80 48/80 63/80 48/80 48/80 48/80

30

45

45

NS80H-MA

50

37

55

55

63 80 80 80

NS80H-MA

80

880 1040 1040 1040

45 55

65 75

65 75

NS80H-MA NS80H-MA

80 80

(1) For long starting (class 20), see the correspondence table for thermal relays on page 126. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

141

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 500/525 V

with short circuit protection

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 500/525 V
Circuit breakers NS100-MA NS160/250-MA NS400/630-MA NS630b/800-Micrologic 5.0 (LT OFF) H 50/35 kA 50/35 kA 50/35 kA L 70/50 kA 70/50 kA 70/50 kA 100/100 kA

E62560

contactor thermal relay

Starting (1): normal

LRD2 class 10 A, autres class 10

Motors P(KW) 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 I(A) 500V 1.2 1.5 2 2.8 3.8 5 6.5 9 12 15 18.4 23 28.5 33 I(A) 525V 1.2 1.5 2 2.8 3.8 5 6.5 9 12 15 18.4 23 28.5 33 Ie max 1.6 1.6 2.5 4 4 6 8 10 12.5 16 25 25 32 40 50

Circuit breakers Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA Rating (A) 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 Irm(A) 22.5 22.5 32.5 57 57 82 113 138 163 250 325 325 450 550 650

Contactors (2)

Thermal relays (1) Type LR2-D13 06 LR2-D13 06 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D13 21 LR2-D33 22 LR2-D33 22 LR2-D33 55 LR2-D33 55 LR9-D53 57 LR9-F53 57 LR2-D33 57 LR9-D53 57 LR9-F53 57 LR2-D33 59 LR9-D53 63 LR9-F53 63 LR9-D53 63 LR9-F53 63 LR9-D53 67 LR9-F53 67 LR9-D53 69 LR9-F53 69 LR9-D53 69 LR9-F53 69 LR9-F53 71 LR9-F53 71 LR9-F73 75 LR9-F73 75 LR9-F73 75 LR9-F73 79 LR9-F73 79 LR9-F73 79 LR9-F75 81 LR9-F75 81 LR9-F75 81 Irth 1/1.6 1/1.6 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 17/25 23/32 23/32 30/50 30/50 30/40 30/50 30/50 48/65 48/80 48/80 48/80 60/100 90/150 90/150 132/220 132/220 200/330 200/330 200/330 300/500 300/500 300/500 380/630 380/630 380/630

Type LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-F115 30 45 45 50 NS100-MA 50 650 LC1-D80 LC1-D115 LC1-F115 37 55 55 63 NS100-MA 100 900 LC1-D80 80 1100 LC1-D115 LC1-F115 45 65 65 80 NS100-MA 100 1100 LC1-D115 LC1-F115 55 75 75 100 NS100-MA 100 1300 LC1-D115 LC1-F115 75 105 105 115 NS160-MA 150 1500 LC1-D115 LC1-F115 90 130 130 150 NS160-MA 150 1950 LC1-D150 LC1-F150 110 156 156 185 NS250-MA 220 2420 LC1-F185 132 187 187 220 NS250-MA 220 2860 LC1-F265 160 230 220 320 NS400-MA 320 4160 LC1-F400 200 280 280 320 NS400-MA 320 4160 LC1-F400 220 310 310 330 NS630-MA 500 4500 LC1-F500 250 360 360 500 NS630-MA 500 6500 LC1-F500 315 445 445 500 NS630-MA 500 6500 LC1-F500 335 472 472 500 NS630bL-Micrologic 5.0 630 Isd = 9 Irth (tsd > 0.1) LC1-F500 Ii = 10 In 375 527 527 630 NS630bL-Micrologic 5.0 630 Isd = 9 Irth (tsd > 0.1) LC1-F630 Ii = 11 In 400 540 540 630 NS630bL-Micrologic 5.0 630 Isd = 9 Irth (tsd > 0.1) LC1-F630 Ii = 12 In 450 608 608 630 NS800L-Micrologic 5.0 800 Isd = 9 Irth (tsd > 0.1) LC1-F800 Ii = 10 In (1) For long starting (class 20), see the correspondence table for thermal relays on page 126. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

142

Schneider Electric

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 690 V

thermal-magnetic motor circuit-breaker

Merlin Gerin circuit breakers,Telemecanique contactors


Performance: U = 690 V
Circuit breakers NS100L-STR22ME NS400L-STR43ME L 75 kA 75 kA STR22ME class10 STR43ME class10 class 20

E34308

contactor

Starting: standard IEC 60947-4-1, type 2


Normal Long

Motors P(kW) 5.5 7.5 10 15 18.5 22 30 37 45 55 75 I(A) 690V 6.6 8.9 11.5 17 20.2 24.2 33 40 47 58 76

Circuit breakers Irth(A) 6/10 6/10 7.5/12.5 12/20 12/20 24/40 30/50 30/50 30/50 48/80 60/100 60/120 60/120 100/200 100/200 100/200 160/320 160/320 160/320 Irm(A) 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth 13Irth

Contactors (2) Type LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1F-115 LC1F-115 LC1F-265 LC1F-265 LC1F-265 LC1F-265 LC1F-265 LC1F-330 LC1F-330 LC1F-400

Ie max Type Trip unit t.u. 10 NS100L STR22ME 10 NS100L STR22ME 13 NS100L STR22ME 18 NS100L STR22ME 25 NS100L STR22ME 40 NS100L STR22ME 50 NS100L STR22ME 50 NS100L STR22ME 50 NS100L STR22ME 63 NS100L STR22ME 80 NS100L STR22ME 165 NS400L STR43ME 90 94 165 NS400L STR43ME 110 113 165 NS400L STR43ME 132 135 165 NS400L STR43ME 160 165 165 NS400L STR43ME 200 203 230 NS400L STR43ME 220 224 230 NS400L STR43ME 250 253 280 NS400L STR43ME (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

143

Complementary technical information

Type 2 coordination (IEC 60947-4-1) 690 V

E34309

magnetic circuit breaker (MA)

Merlin Gerin circuit breakers,Telemecanique contactors and thermal relays


Performance: U = 690 V
Circuit breakers NS100L-MA NS400L-MA L 75 kA 75 kA

contactor thermal relay

Starting (1): normal

LRD2 class 10 A autres class 10

Motors

Circuit breakers

Contactors (2) Type LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1F-115 LC1F-115 LC1F-265 LC1F-265 LC1F-265 LC1F-265 LC1F-330 LC1F-330 LC1F-400

Thermal relays Type LR2-D13 06 LR2-D13 06 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D13 21 LR2-D13 22 LR2-D13 22 LR9-D53 57 LR9-D53 57 LR9-D53 57 LR9-F53 63 LR9-F53 63 LR9-F53 67 LR9-F53 69 LR9-F53 69 LR9-F53 71 LR9-F73 75 LR9-F73 75 LR9-F73 75 Irth (1) 1/1.6 1.25/2 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 9/13 12/18 17/25 17/25 30/50 30/50 30/50 48/80 48/80 60/100 90/150 90/150 132/220 200/330 200/330 200/330

P(kW) I(A) 690V Ie max Type Rating (A) Irm(A) 0.75 1.2 1.6 NS100L MA 2.5 22.5 1 1.5 2 NS100L MA 2.5 27.5 1.5 2 2.5 NS100L MA 2.5 32.5 2.2 2.8 4 NS100L MA 6.3 57 3 3.8 4 NS100L MA 6.3 57 4 4.9 6 NS100L MA 6.3 82 5.5 6.6 8 NS100L MA 12.5 113 7.5 8.9 10 NS100L MA 12.5 138 10 11.5 13 NS100L MA 25 175 15 17 18 NS100L MA 25 250 18.5 20.2 25 NS100L MA 25 325 22 24.2 25 NS100L MA 25 325 30 33 50 NS100L MA 50 650 37 40 50 NS100L MA 50 650 45 47 50 NS100L MA 50 650 55 58 80 NS100L MA 100 1100 75 76 80 NS100L MA 100 1100 90 94 100 NS400L MA 320 2880 110 113 150 NS400L MA 320 2880 132 135 150 NS400L MA 320 2880 160 165 165 NS400L MA 320 2880 200 203 230 NS400L MA 320 2880 220 224 230 NS400L MA 320 2880 250 253 280 NS400L MA 320 3520 (1) For long starting (class 20), see the correspondence table for thermal relays on page 126. (2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

144

Schneider Electric

Complementary technical information

Type 1 coordination (IEC 60947-4-1)

E34309

magnetic circuit breaker (MA)

Merlin Gerin NS80 circuit breakers, Telemecanique contactors and thermal relays
Direct-on-line starting Reserver
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone. Starting (1): normal LR2 class 10 A, LR9 class 10

contactor thermal relay

Motors 220/230 V P I (kW) (A) 380 V P (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 I (A) 1.2 1.6 2 2.8 3.7 5 6.6 8.5 11.5 15.5 415 V P (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 I (A) 1.1 1.5 1.8 2.5 3.5 4.8 6.5 8.2 11 14 17 21 440 V (2) P (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 I (A) 1 1.4 1.7 2.4 3.1 4.5 5.8 7.9 10.4 13.7 16.9 20.1 500/525 V P (kW) 0.55 0.75 1.1 1.5 3 4 5.5 7.5 9 10 11 I (A) 1.2 1.5 2 2.6 5 6.5 9 12 14 15 10 5.5 20 11 22 18.4 15 18.5 7.5 11 15 18.5 28 39 52 64 30 59 30 37 45 55 66 80 15 18.5 22 30 37 44 15 22 25 28 40 47 15 22 30 37 26.5 39 30 51.5 37 64 37 55 45 22 75 37 72 45 76 55 80 49 42 45 33 39 18.5 22 28.5 33 30 17 21.3 34.6 11.5 660/690 V P (kW) 0.75 1 1.5 2.2 3 4 5.5 7.5 3 4 11.5 14.5 I (A) 1.2 1.5 2 2.8 3.8 4.9 6.6 8.9

Circuit breakers Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA

Contactors (3)

Thermal relays (1) Type LR2-D13 06 LR2-D13 06 LR2-D13 07 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 14 LR2-D13 16 LR2-D13 21 LR2-D13 21 LR2-D13 16 LR2-D13 22 LR2-D13 21 LR2-D13 22 LR2-D33 53 LR2-D33 55 LR2-D33 57 LR2-D33 57 LR2-D33 59 LR2-D33 57 LR2-D33 59 LR2-D33 61 LR2-D33 57 LR2-D33 63 LR9-D53 63 LR9-F53 63 Irth (A) 1/1.6 1/1.6 1.6/2.5 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 7/10 9/13 12/18 12/18 9/13 17/25 12/18 17/25 23/32 30/40 37/50 37/50 48/65 37/50 48/65 55/70 37/50 63/80 48/80

Rating Type (A) 2.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 12.5 25 25 25 25 25 50 50 50 50 50 50 50 80 80 80 80 80 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D12 LC1-D18 LC1-D18 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D50 LC1-D50 LC1-D65 LC1-D65 LC1-D65 LC1-D80 LC1-D80 LC1-D115 LC1-F115

0.37 0.55 1.1 1.5 2.2

1.8 2.8 4.4 6.1 8.7

55 60 75 80 (1) For long starting (class 20), see the correspondence table for thermal relays on page 126. (2) Valid for 480 V NEMA. (3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

145

Complementary technical information

Type 1 coordination (IEC 60947-4-1)

magnetic circuit breaker (MA)

Merlin Gerin NS100 circuit breakers, Telemecanique contactors and thermal relays
Direct-on-line starting Reserver
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone Starting (1): normal LR2 class 10 A, LR9 class 10

E34309

contactor thermal relay

Motors 220/230 V 380 V P I P (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 I (A) 1.2 1.6 2 2.8 3.7 5 6.6 8.5 (kW) (A) 415 V P (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 I (A) 1.1 1.5 1.8 2.5 3.5 4.8 6.5 8.2 11 14 17 21 440 V (2) P (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 I (A) 1 1.4 1.7 2.4 3.1 4.5 5.8 7.9 10.4 13.7 16.9 20.1 500/525 V P I (kW) (A) 0.55 1.2 0.75 1.5 660/690 V P I

Circuit breakers Type Rating (A) 2.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 12.5 12.5 25 25 25 25 25 50 50 50 50 50 50 100 100 100 100 100 100

Contactors (3) Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D12 LC1-D18 LC1-D18 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D50 LC1-D65 LC1-D65 LC1-D80 LC1-D80 LC1-D95 LC1-D115 LC1-F115 LC1-D115 LC1-F115

Thermal relays (1) Type LR2-D13 06 LR2-D13 06 LR2-D13 07 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 14 LR2-D13 16 LR2-D13 21 LR2-D13 21 LR2-D13 16 LR2-D13 22 LR2-D13 21 LR2-D13 22 LR2-D33 53 LR2-D33 55 LR9-D53 57 LR2-D33 57 LR9-D53 57 LR2-D33 57 LR9-D53 57 LR2-D33 57 LR9-D53 57 LR2-D33 59 LR9-D53 63 LR2-D33 57 LR9-D53 63 LR2-D33 63 LR9-D53 63 LR2-D33 65 LR9-D53 67 LR9-D53 63 LR9-F53 63 LR9-D53 67 LR9-F53 67 Irth (A) 1/1.6 1/1.6 1.6/2.5 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 7/10 9/13 12/18 12/18 9/13 17/25 12/18 17/25 23/32 30/40 30/50 37/50 30/50 37/50 30/50 37/50 30/50 48/65 48/80 37/50 48/80 63/80 48/80 80/93 60/100 48/80 60/100

0.37 1.8 0.55 2.8 1.1 1.5 2.2 3 4 4.4 6.1 8.7

11.5 5.5 14.5 7.5

11.5 5.5 15.5 7.5 9 22 11

5.5

20

11

7.5

28

15

30

15

28

15

26.5

NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA 1.1 2 1.5 2 NS100N/H/L-MA 1.5 2.6 2.2 2.8 NS100N/H/L-MA 3 3.8 NS100N/H/L-MA 3 5 4 4.9 NS100N/H/L-MA 4 6.5 5.5 6.6 NS100N/H/L-MA 5.5 9 NS100N/H/L-MA 7.5 8.9 NS100N/H/L-MA 7.5 12 NS100N/H/L-MA 9 14 NS100N/H/L-MA 10 15 NS100N/H/L-MA 10 11.5 NS100N/H/L-MA 11 18.4 NS100N/H/L-MA 15 17 NS100N/H/L-MA 18.5 21.3 NS100N/H/L-MA 18.5 28.5 NS100N/H/L-MA 22 33 30 34.6 NS100N/H/L-MA NS100N/H/L-MA

(kW) (A) 0.75 1.2 1 1.5

11

39

18.5 37 22 44

22 25

40 47

22

39 30 45 33 37 39 42

NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA

15 52 18.5 64

30

59

30

55

30 37

51.5 64 37

55 45 49 NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA 55 60 80 NS100N/H/L-MA NS100N/H/L-MA

22 25

75 85

37 45

72 85

37 45

72 80

45

76

55

80

30

100

55

100

55

96

75

(1) For long starting (class 20), see the correspondence table for thermal relays on page 126. (2) Valid for 480 V NEMA. (3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

146

Schneider Electric

Complementary technical information

Type 1 coordination (IEC 60947-4-1)

with short circuit protection

contactor thermal relay

Merlin Gerin NS160 to NS1250 and C1251 circuit breakers,Telemecanique contactors and thermal relays
Direct-on-line starting Reserver
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone. Starting (1): normal class 10

E62560

Motors 220/230 V P (kW) 37 45 55 I (A) 125 150 180 380 V P (kW) 55 75 90 110 I (A) 105 140 170 210 415 V P (kW) 75 90 110 I (A) 135 160 200 440 V (2) P (kW) 75 90 110 132 I (A) 124 156 180 215 500/525 V P (kW) 75 90 110 I (A) 110 130 156 660/690 V P (kW) 90 110 I

Circuit breakers Type

Contactors Thermal relay


(3) (1)

Rating Type (A) 150 220 220 220 320 320 500 500 500 500 630 500 630 630 800 1000 630 800 1000 800 800 1000 800 800 1000 630 800 1000 800 1000 1000 1000 1000 1250 1250 LC1D-150 LC1F-150 LC1F-185 LC1F-225 LC1F-265 LC1F-265 LC1F-330 LC1F-400 LC1F-400 LC1F-500 LC1F-500 LC1-F630 LC1-F630

Type

Irth

(A) 100 NS160N/H/L MA 120 NS 250N/H/L MA NS 250N/H/L MA

(A) LR9-D53 69 90/150 LR9-F53 69 100/160 LR9-F53 71 132/220 LR9-F53 71 LR9-F53 71 LR9-F73 75 LR9-F73 75 LR9-F73 79 LR9-F73 75 LR9-F73 79 LR9-F73 79 LR9-F73 81 LR9-F73 81 132/220 132/220 200/330 200/330 300/500 200/330 300/500 300/500 380/630 380/630

132 75 90 110 250 312 360 132 160 200 250 300 380 132 160 220 230 270 380 220 360 160 256 160 200 220

190 228 281 310

132 160

140 NS 250N/H/L MA 175 NS400N/H/L MA 220 NS400N/H/L MA 240 NS630N/H/L MA 270 NS630N/H/L MA 335 NS630N/H/L MA

200 220

250 220 150 480 250 420 480 250 430 250 401 315 335 445 460 335

NS630N/H/L MA NS630bN/H/L Micrologic 5.0 300 480 375 400 NS630N/H/L MA 450 480 NS630bN/H/L Micrologic 5.0 160 520 300 570 300 510 335 540 355 500 NS630bN/H/L Micrologic 5.0 375 530 C801N/H STR35ME 400 570 C1001L STR35ME 200 630 335 630 335 580 375 590 450 630 NS630bN/H/L Micrologic 5.0 C801N/H STR35ME C1001L STR35ME 220 700 375 700 375 650 400 650 NS800N/H/L Micrologic 5.0 C801N/H STR35ME C1001L STR35ME 400 750 400 690 450 720 NS800N/H/L Micrologic 5.0 C801N/H STR35ME C1001L STR35ME 500 530 NS630bN/H/L Micrologic 5.0 560 580 C801N/H STR35ME C1001L STR35ME 250 800 450 800 450 750 500 700 NS800N/H/L Micrologic 5.0 560 760 NS1000N/H/L Micrologic 5.0 C1001N/H STR35ME 500 900 500 830 500 800 600 830 NS1000N/H/L Micrologic 5.0 560 900 C1001N/H STR35ME 300 970 560 1000 560 920 600 960 670 920 NS1250N/H Micrologic 5.0 600 1100 600 1000 670 1080 750 1020 C1251N/H STR35ME (1) For long starting (class 20), see the correspondence table for thermal relays on page 126. (2) Valid for 480 V NEMA. (3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

LC1-F630

LR9-F73 81

380/630

LC1-F800

LR2-F83 83

500/800

LC1-F800 LC1-BL33 LC1-BL33

LR2-F83 83

500/800

LR2-F83 83

500/800

LC1-BM33 LR2-F83 83

500/800

LC1-BM33 LR2-F83 85 LC1-BP33 LR2-F83 85

630/1000 630/1000

Schneider Electric

147

Complementary technical information

Type 1 coordination (IEC 60947-4-1)

with short circuit and overload protection

Merlin Gerin NS160 to NS1250 and C1251 circuit breakers,Telemecanique contactors


Direct-on-line starting Reserver
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone. Starting:
Normal Long STR22ME class 10 STR43ME class 10 class 20 STR55UE class 10 class 20 Micrologic 5.0 class 10 class 20

E62562

contactor

Motors 220/230 V P I (kW) (A) 7.5 28 11 39 15 18.5 22 25 30 37 45 55 52 64 75 85 100 125 150 180 380 V P (kW) 15 18.5 22 30 37 45 I (A) 30 37 44 59 72 85 415 V P (kW) 15 22 25 30 37 I (A) 28 40 47 55 72 440 V (1) P (kW) 15 22 30 37 45 I (A) 26.5 39 51.5 64 76 500/525 V P (kW) 18.5 22 30 37 55 I (A) 28.5 33 45 55 80 660/690 V P (kW) 30 33 37 45 55 75 90 110 I (A) 34.6 39 42 49 60 80 100 120

Circuit breakers Type NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS160N/H/L NS 250N/H/L NS 250N/H/L NS 250N/H/L NS400N/H/L NS400N/H/L NS630N/H/L NS630N/H/L NS630N/H/L NS630N/H/L NS630bN/H/L NS630bN/H/L NS800N/H/L C801N/H C1001L NS630bN/H/L NS800N/H/L C801N/H C1001L NS800N/H/L C801N/H C1001L NS800N/H/L C801N/H C1001L NS630bN/H/L C801N/H C1001L NS1000N/H/L C1001N/H NS1000N/H/L C1001N/H NS1250N/H/L C1251N/H Trip unit STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR43ME STR43ME STR43ME STR43ME STR43ME STR43ME Micrologic 5.0 Micrologic 5.0 STR55UE Micrologic 5.0 STR55UE Micrologic 5.0 STR55UE Micrologic 5.0 STR55UE Micrologic 5.0 STR55UE Micrologic 5.0 STR55UE Micrologic 5.0 STR55UE Micrologic 5.0 STR55UE Irth (A) 24/40 24/40 30/50 48/80 48/80 48/80 60/100 60/100 60/100 90/150 131/220 131/220 131/220 190/320 190/320 300/500 300/500 300/500 300/500 250/630 250/630 320/800 320/800 400/1000 250/630 320/800 320/800 400/1000 320/800 320/800 400/1000 320/800 320/800 400/1000 250/630 320/800 400/1000 400/1000 400/1000 400/1000 400/1000 630/1250 630/1250

Contactors (2) Type LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D65 LC1-D80 LC1-D95 LC1D-115 or LC1F-115 LC1D-115 or LC1F-115 LC1D-150 or LC1F-150 LC1F-185 LC1F-225 LC1F-265 LC1F-265 LC1F-330 LC1F-400 LC1F-500 LC1F-500 LC1-F630 LC1-F630

55 75 90 110

105 140 170 210

55 75 90 110

100 135 160 200

55 75 90 110 132

96 124 156 180 215

75 90 110

110 130 156

132 75 90 110 150 250 312 360 480 132 160 200 220 250 250 300 380 420 480 132 160 220 250 230 270 380 430 300 160 520 300 570 300 510 335 480 540 160 256 160 200 220 315 335 355 375 400

190 228 281 310 445 460 500 530 570

132 160 200 220 250 335 375 450

140 175 220 240 270 335 400 480

220 250

360 401

200

630

335

630

335

580

375

590

450

630

LC1-F630

220

700

375

700

375

650

400

650

LC1-800

400

750

400

690

450

720

LC1-800 LC1-BL33 LC1-BL33

500 560 250 800 450 500 300 970 800 900 450 500 750 830 500 560 600 670 800 900 960 1080 500 560 600 670 750 700 760 830 920 1020

530 580

LC1-BM33 LC1-BM33 LC1-BP33

560 1000 560 920 600 1100 600 1000 (1) Valid for 480V NEMA (2) Reversers: replace LC1 with LC2.

148

Schneider Electric

Complementary technical information

Type 1 coordination (IEC 60947-4-1)

E34311

magnetic circuit breaker (MA)

Merlin Gerin NS80 and NS100 circuit breakers,Telemecanique contactors and thermal relays
Star-delta starting
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker. Starting: normal

star-delta starter

thermal relay

Motors 220/230 V P (kW) 0.55 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 0.55 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 I (A) 2.8 4.4 6.1 8.7 11.5 14.5 20 28 39 52 64 75 2.8 4.4 6.1 8.7 11.5 14.5 20 28 39 52 64 30 37 59 72 30 37 45 55 55 66 80 100 30 37 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 59 72 3.7 5 6.6 8.5 11.5 15.5 22 30 37 44 30 37 45 1.5 2.2 3 4 5.5 7.5 9 11 15 22 25 55 66 80 3.5 4.8 6.5 8.2 11 14 17 21 28 40 47 380 V P (kW) 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 I (A) 3.7 5 6.6 8.5 11.5 15.5 22 30 37 44 415 V P (kW) 1.5 2.2 3 4 5.5 7.5 9 11 15 22 25 I (A) 3.5 4.8 6.5 8.2 11 14 17 21 28 40 47 440 V (1) P (kW) 1.5 2.2 3 4 5.5 7.5 9 11 15 22 30 37 45 1.5 2.2 3 4 5.5 7.5 9 11 15 22 30 37 45 55 I (A) 3.1 4.5 5.8 7.9 10.4 13.7 16.9 20.1 26.5 39 51.5 64 76 3.1 4.5 5.8 7.9 10.4 13.7 16.9 20.1 26.5 39 51.5 64 76 96

Circuit breakers Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA Rating (A) 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 50 80 80 80 80 80 6.3 6.3 12.5 12.5 12.5 25 25 25 50 50 100 100 100 100 100 100 100 100

Contactors Type LC3-D09 LC3-D09 LC3-D09 LC3-D09 LC3-D09 LC3-D09 LC3-D12 LC3-D12 LC3-D18 LC3-D18 LC3-D32 LC3-D32 LC3-D32 LC3-D40 LC3-D40 LC3-D50 LC3-D09 LC3-D09 LC3-D09 LC3-D09 LC3-D09 LC3-D09 LC3-D12 LC3-D12 LC3-D18 LC3-D18 LC3-D32 LC3-D32 LC3-D32 LC3-D40 LC3-D40 LC3-D50 LC3-D50 LC3-D50

Thermal relays Type LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D13 16 LR2-D13 21 LR2-D13 22 LR2-D33 53 LR2-D33 53 LR2-D33 55 LR2-D33 55 LR2-D33 57 LR2-D33 57 LR2-D13 07 LR2-D13 08 LR2-D13 08 LR2-D13 10 LR2-D13 12 LR2-D13 14 LR2-D13 16 LR2-D13 16 LR2-D13 21 LR2-D13 22 LR2-D33 53 LR2-D33 53 LR2-D33 55 LR2-D33 55 LR2-D33 57 LR2-D33 57 LR2-D33 57 LR2-D33 59 Irth (A) 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 9/13 9/13 12/18 17/25 23/32 23/32 30/40 30/40 37/50 37/50 1.6/2.5 2.5/4 2.5/4 4/6 5.5/8 7/10 9/13 9/13 12/18 17/25 23/32 23/32 30/40 30/40 37/50 37/50 37/50 48/65

22 75 25 85 45 85 30 100 (1) Valid for 480 V NEMA.

Schneider Electric

149

Complementary technical information

Type 1 coordination (IEC 60947-4-1)

circuit breaker with short circuit protection

Merlin Gerin NS160 to NS1000 and C1001 circuit breakers,Telemecanique contactors and thermal relays
Star-delta starting
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone. Starting: normal

E62563

star-delta starter

thermal relay

Motors 220/230 V P (kW) 37 45 I (A) 125 150 380 V P (kW) 55 75 75 90 55 180 110 210 110 200 132 75 90 110 150 250 312 360 480 132 160 200 220 250 250 300 380 420 480 132 160 220 250 230 270 380 430 300 160 520 300 570 300 510 335 480 540 160 220 250 256 360 401 215 I (A) 105 140 140 170 415 V P (kW) 75 I (A) 135 440 V (1) P (kW) 75 I (A) 124

Circuit breakers Type NS160N/H/L MA NS160N/H/L MA NS160N/H/L MA NS 250N/H/L MA NS 250N/H/L MA NS 250N/H/L MA NS 250N/H/L MA NS400N/H/L MA NS400N/H/L MA NS630N/H/L MA NS630N/H/L MA NS630N/H/L MA NS630N/H/L MA NS630bN/H/L Micrologic 5.0 NS630bN/H/L Micrologic 5.0 NS800N/H/L Micrologic 5.0 C801N/H STR35ME C1001L STR35ME NS630bN/H/L Micrologic 5.0 NS800N/H/L Micrologic 5.0 C801N/H STR35ME C1001L STR35ME NS630bN/H/L Micrologic 5.0 NS800N/H/L Micrologic 5.0 NS800N/H/L Micrologic 5.0 NS1000N/H/L Micrologic 5.0 Rating (A) 150 150 150 220 220 220 220 320 320 500 500 500 500 630 630 800 800 1000 630 800 800 1000 630 800 800 1000

Contactors Type LC3-D80 LC3-D80 LC3-D115 LC3-F115 LC3-D115 LC3-F115 LC3-D115 LC3-F115 LC3-D115 LC3-F115 LC3-D150 LC3-F150 LC3-D150 LC3-F150 LC3F-185 LC3-F265 LC3-F265 LC3-F330 LC3-F330 LC3-F400

Thermal relays Type LR2-D33 59 LR2-D33 63 LR9-D53 67 LR9-F53 67 LR9-D53 67 LR9-F53 67 LR9-D53 69 LR9-F53 67 LR9-D53 69 LR9-F53 69 LR9-D53 69 LR9-F53 69 LR9-D53 69 LR9-F53 69 LR9-F53 71 LR9-F73 75 LR9-F73 75 LR9-F73 75 LR9-F73 75 LR9-F73 75 Irth (A) 48/65 63/80 60/100 60/100 90/150 90/150 90/150 90/150 132/220 200/330 200/330 200/330 200/330 200/330

90

160

90 110

156 180

335

580

375

590

LC3-F400

LR9-F73 79

300/500

375 400

620 665

400 450

627 706

LC3-F400 LC3-F500

LR9-F73 79 LR9-F73 79

300/500 300/500

(1) Valid for 480V NEMA.

150

Schneider Electric

Complementary technical information

Type 1 coordination (IEC 60947-4-1)

circuit breaker with short circuit and overlaod protection

Merlin Gerin NS100 to NS1000 and C1001 circuit breakers, Contactors Telemecanique
Star-delta starting

E 62564

star-delta starter

"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone. Starting: normal

Motors 220/230 V P (kW) 7.5 11 15 18.5 22 25 30 37 45 55 75 90 110 150 160 I (A) 28 39 52 64 75 85 100 125 150 180 250 312 360 480 520 30 37 45 55 75 75 90 110 132 160 200 220 250 300 59 72 85 55 105 140 140 170 210 250 300 380 420 480 570 75 90 110 132 160 220 250 300 100 135 160 200 230 270 380 430 510 300 335 480 540 55 75 90 110 132 160 220 250 96 124 156 180 215 256 360 401 30 37 45 55 66 80 380 V P (kW) 15 18.5 22 I (A) 30 37 44 415 V P (kW) 15 22 25 I (A) 28 40 47 440 V (1) P (kW) 15 22 30 37 45 I (A) 26.5 39 51.5 64 76

Circuit breakers Type NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS100N/H/L NS160N/H/L NS160N/H/L NS160N/H/L NS 250N/H/L NS 250N/H/L NS 250N/H/L NS400N/H/L NS400N/H/L NS630N/H/L NS630N/H/L NS630N/H/L NS630N/H/L NS630bN/H/L NS800N/H/L C801N/H C1001L NS630bN/H/L NS800N/H/L C801N/H C1001L NS630bN/H/L NS800N/H/L NS800N/H/L NS1000N/H/L Trip unit STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR22ME STR43ME STR43ME STR43ME STR43ME STR43ME STR43ME Micrologic 5.0 STR55UE Micrologic 5.0 STR55UE Micrologic 5.0 Micrologic 5.0 Irth (A) 24/40 30/50 30/50 48/80 48/80 48/80 48/80 60/100 60/100 60/100 90/150 90/150 90/150 131/220 131/220 131/220 190/320 190/320 300/500 300/500 300/500 300/500 250/630 320/800 320/800 400/1000 250/630 320/800 320/800 400/1000 250/630 320/800 320/800 Type

Contactors

LC3-D18 LC3-D18 LC3-D32 LC3-D32 LC3-D32 LC3-D40 LC3-D40 LC3-D50 LC3-D50 LC3-D50 LC3-D80 LC3-D80 LC3-D115 or LC3-F115 LC3-D115 or LC3-F115 LC3-D115 or LC3-F115 LC3-D150 or LC3-F150 LC3-D150 or LC3-F150 LC3F-185 LC3-F265 LC3-F265 LC3-F330 LC3-F330 LC3-F400

335

580

375

590

LC3-F400

375 400

620 665

400 450

627 706

LC3-F400 LC3-F500

(1) Valid for 480V NEMA.

Schneider Electric

151

Complementary technical information

Use of LV switches

E94516

Functions performed by switch

source coupling switch-disconnector

main power distribution board-tertiary

main power distribution board-industrial

y 1000 A

15 -40 kA

y 1600 A

20 -80 kA

sub-distribution board-modular products

industrial distribution switchboard y 160 A : 15 - 25 kA y 400 A : 20 - 80 kA

control and command switchboard

y 160 A

15 - 25 kA

y 400 A

enclosure for local isolation y 10 kA

final distribution board y 63 A y 10 kA

enclosure for local isolation y 25 kA

control and command enclosure y 40 A y 5 kA

y 63 A

y 630 A

heating, lighting, etc.

M
NB. Adjacent to or built into the machine

building utilities

final distribution -building

continuous processes

manufacturing processes individual machines

152

Schneider Electric

Complementary technical information

Use of LV switches

Functions and positions of LV switches


The switch is therefore essentially a control device, (generally manual, possibly electrical on opening - termed a free tripping switch) capable of breaking and closing a normal service circuit. It does not use any electricity to remain open or closed (2 stable positions). For safety reasons, in the majority of cases is suitable for isolation. It must always be used in association with a device which protects against overloads and short-circuits. 6 applications have thus been identified: b coupling and insolating switch in a power switchboard b insolating switch in an industrial switchboard and automation cabinets b insolating switch in a modular switchboard b insolating switch in proximity units b insolating switch in small commercial distribution units b automation unit switch.

Suitable for isolation


E36281

Switch-disconnector
MERLIN GERIN
interpact INS160 Ui 750V Uimp 8kV Lth 100A 60C Ue(V) DC23A 250 AC22A 690 AC23A 500 AC23A 690 DC23A 250

Ie

100A 100A
100A 63A 100A

IEC 947.3 BS CEI UNE UTE VDE


UTE VDE BS CEI UNE

IEC 947.3

Isolation permits a circuit or a device to be disconnected from the rest of the electrical installation, in order to guarantee the safety of those who have to achieve repairs or maintenance. Normally, all circuits in an electrical installation must be capable of being isolated. In practice, to ensure optimal continuity of service, an isolating device is installed at the start of every circuit distribution. Certain switches allow this function to be achieved in addition to their circuit control function. Therefore a switch-disconnector must display the symbol (illustrated opposite), visibly on the front face of the installed device.

Isolating function
Installation standards stipulate the requirements which must be respected in order for a device to carry out its isolating function. It must: b be with equipped with omnipolar isolation, that is to say that the live conductors, including the neutral (with the exception of the PEN conductor which must never be isolated) must be isolated simultaneously b be lockable in the open position so as to prevent any risk of unvolontary reclosing ; this is imperative for industrial devices b conform to a standard which guarantees its suitability for isolation b It must also meet overvoltage withstand requirements. However, if the isolation is explicitly recognized by a manufacturing standard, for example IEC 60947-1/3 for industrial switch-disconnectors, a device which complies with this isolation standard is judged to comply fully with the conditions required by installation standards. The manufacturing standard guarantees its use for isolation suitability for the user.

Schneider Electric

153

Complementary technical information

Use of LV switches (cont.)

Switch standards and characteristics


Switch standards
Standards define: b the frequency of operation cycles (with a maximum of 120 per hour) b mechanical and electrical endurance b operating breaking and making capacity v normal v occasional (closing on short-circuit for example) b utilization categories. The IEC standards 60947-3 (1) and 60669-1 (2) thus define the principal values which are given below.

Utilization category
Depending on the rated operating current and the A or B mechanical endurance, standards define the utilization categories shown in the table below. Example: A switch with a rating of 125 A, from the AC23 category must be able to: b make a 10 In (1250 A) current with a cos of 0.35 b break a 8 In (1000 A) current with a cos of 0.35. Its other characteristics are: b to withstand a 12 In - 1 s short-circuit current, which defines the Icw = 1500 A r.m.s. thermal withstand during 1 s b Icm (peak A) short-circuit making capacity which corresponds to the electrodynamic loads.

Utilization category
Frequent operations
AC-21A

Characteristic applications

Non frequent operations


AC-21B

Resistive loads including moderate overloads (cos = 0,95) AC-22A AC-22B Mixed resistive and inductive loads including moderate overloads (cos = 0,65) AC-23A AC-23B Motors with cage winding or orther loads which are very inductive (cos = 0,45 or 0,35) (1) The industrial type of switch is defined by the IEC standard 60947-3. (2) The domestic type of switch is defined by the IEC standard 60669-1.

Choice of switch criteria


Network characteristics
Nominal voltage, nominal frequency and nominal current are determined in the same way as they are for a circuit breaker: b nominal voltage = network nominal voltage b frequency = network frequency b nominal current = rated current with a value which is just above the downstream load current. It is to be noted that the rated current is defined for a given ambient temperature and that a derating may possibly have to be taken into account.

Localization and application


This determines the type and characteristics or major functions that the switch should include. There are 3 levels of functions (see the table opposite): b basic functions practically common to all types of switch: isolation, control, notice. b functions with complementary characteristics. They are the direct translation of the users needs and the environment in which the switch is located.

154

Schneider Electric

Complementary technical information

Use of LV switches (cont.)

These are: v industrial type performances v Isc level v type of locking v type of control v utilization category v mounting system. b specific functions They are linked to the operation and installation restrictions, which are: v earth leakage protection v electrical controls v remote opening v withdrawable capacity.

Circuit-breaker or fuse / switch coordination


Coordination
As a switch only has a limited breaking capacity and short-circuit withstand, it must be protected by a short-circuit protection device (SCPD) placed upstream. Tables show the SCPD (circuit-breaker or fuse) ensuring proper coordination with the switches in the event of a downstream short-circuit. Warning: switches must be also protected against overloads. It's generally admitted that the protection against the overloads and short-circuit, is ensured by each downstream circuit-breakers as these circuit-breakers and these switches are located in the same switchboard, designed according to the electrical standards.
E36280

two-pole NC100H

Modular switch
Isc 20 kA C60H 30 A C60H 30 A C60H 30 A

Example 1: An enclosure feeder, with an Isc on the busbar of 20 kA, supplies loads with operational currents of 30 A, 20 A and 10 A respectiveldy in single-phase. The installation earthing system is the TT one. The feeder supplying this enclosure is placed in the usptream switchboard and protected by a two-pole NC100H circuitbreaker. Which residual current switch should you choose for the enclosure incomer? As the feeders are placed in the same enclosure as the switch, cordination can be achieved with each enclosure feeder. Choice will thus be made of an ID residual current switch or rating 63 A and of C60H type circuit-breakes for the feeders: the table above shows that the C60H withstands 20 kA in this case. Note that C60N type circuit-breakers would have been sufficient without the switch: in actual fact, the breaking capacity of the C60N downstream form a NC100H is increased to 100 kA.

Schneider Electric

155

Complementary technical information

Use of LV switches (cont.) Switch-disconnectors protection

E31431

Compact NA switch-disconnectors
Upstream protection
push to trip

NSA125NA

NSA160NA

STR
90 %Ir 105

22 DE
z test

50/60H

Im Ir .9 .85 .8 .98 .7 .63 xIn 1 .95 2 1.5 xIr 10 3 8 4 5 6

alarm
Ir Im

push to trip

By Compact NS Type / maximum rating (A) Isc max. (380/415 V) Making capacity (380/415 V) Type / calibre max. (A) Isc max. (380/415 V) Making capacity (380/415 V) Type / maximum rating (A) Isc max. (380/415 V) Making capacity (380/415 V) Type / maximum rating (A) Isc max. (380/415 V) Making capacity (380/415 V) Type / maximum rating (A) Isc max. (380/415 V) Making capacity (380/415 V) By fuse Type aM (1) maximum rating (A) Isc max. (500 V) Making capacity (500 V) Type gl (2) maximum rating (A) Isc max. (500 V) Making capacity (500 V) Type gl (1) maximum rating (A) Isc max. (500 V) Making capacity (500 V) Type BS (2) maximum rating (A) Isc max. (500 V) Making capacity (500 V) Type BS (1) maximum rating (A) Isc max. (500 V) Making capacity (500 V)

kA ms kA peak kA ms kA peak kA ms kA peak kA ms kA peak kA eff. kA peak

NS160N / 125 36 75 NS160H / 125 70 154 NS160L / 125 150 330 NSA160N / 125 30 63

NS160N / 160 36 75 NS160H / 160 70 154 NS160L / 160 150 330 NSA160N / 160 30 63

kA ms kA peak kA ms kA peak kA ms kA peak kA ms kA peak kA ms kA peak

125 55 121 100 100 220 160 100 220 100 & 63M100 80 176 160 & 100M160 80 176

160 33 69 125 100 220 160 100 220 125 & 100M125 80 176 160 & 100M160 80 176

(1) Protection by external thermal relay obligatory (2) Without external thermal relay

156

Schneider Electric

Complementary technical information

Use of LV switches (cont.) Switch-disconnectors protection (cont.)


Compact NA switch-disconnectors
Upstream protection
Compact NS By 380/415 V circuit breaker type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type aM (2) / maximum rating (A) Isc max. making capacity type gG (3) / maximum rating (A) Isc max. making capacity type gG (2) / maximum rating (A) Isc max. making capacity type BS (3) / maximum rating (A) Isc max. making capacity type BS (2) / maximum rating (A) Isc max. making capacity

kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak 100 kA rms kA peak 80 kA rms kA peak 100 kA rms kA peak 80 et 63M80 kA rms kA peak 160 et 100M160 kA rms kA peak

By 440/480 V circuit breaker (1)

By 500 V circuit breaker

By 525 V circuit breaker

By 690 V circuit breaker

By fuse By 500 V fuse

(1) Suitable for NEMA 480 V voltage. (2) Protection by external thermal relay obligatory. (3) Without external thermal relay.

158

Schneider Electric

Complementary technical information

Use of LV switches (cont.) Switch-disconnectors protection (cont.)


NS250NA NS400NA NS630NA

NS100NA

NS160NA

NS100N/100 25 53 NS100H/100 70 154 NS100L/100 150 330 NS100N/100 25 53 NS100H/100 65 143 NS100L/100 130 286 NS100N/100 18 36 NS100H/100 50 105 NS100L/100 100 220 NS100N/100 18 36 NS100H/100 35 74 NS100L/100 100 220 NS100N/100 8 14 NS100H/100 10 17 NS100L/100 75 165 160 100 220 125 100 220 160 100 220 125 et 100M125 80 176 160 et 100M160 80 176

NS160N/160 35 74 NS160H/160 70 154 NS160L/160 150 330 NS160N/160 35 74 NS160H/160 65 143 NS160L/160 130 286 NS160N/160 30 63 NS160H/160 50 105 NS160L/160 70 154 NS160N/160 22 46 NS160H/160 35 74 NS160L/160 50 105 NS160N/160 8 14 NS160H/160 10 17 NS160L/160 20 40 250 100 220 200 100 220 250 100 220 160 et 100M160 80 176 250 et 200M250 80 176

NS250N/250 35 74 NS250H/250 70 154 NS250L/250 150 330 NS250N/250 35 74 NS250H/250 65 143 NS250L/250 130 286 NS250N/250 30 63 NS250H/250 50 105 NS250L/250 70 154 NS250N/250 22 46 NS250H/250 35 74 NS250L/250 50 105 NS250N/250 8 14 NS250H/250 10 17 NS250L/250 20 40 400 100 220 315 100 220 400 100 220 315 et 200M315 80 176 355 et 315M355 80 176

NS400N/400 45 95 NS400H/400 70 154 NS400L/400 150 330 NS400N/400 42 88 NS400H/400 65 143 NS400L/400 130 286 NS400N/400 30 63 NS400H/400 50 105 NS400L/400 100 220 NS400N/400 22 46 NS400H/400 35 74 NS400L/400 100 220 NS400N/400 10 17 NS400H/400 20 40 NS400L/400 75 165 630 100 220 500 100 220 630 100 220 500 80 176 450 et 400M450 80 176

NS630N/630 45 95 NS630H/630 70 154 NS630L/630 150 330 NS630N/630 42 88 NS630H/630 65 143 NS630L/630 130 286 NS630N/630 30 63 NS630H/630 50 105 NS630L/630 70 154 NS630N/630 22 46 NS630H/630 35 74 NS630L/630 50 105 NS630N/630 10 17 NS630H/630 20 40 NS630L/630 35 74

100 220 100 220 100 220 80 176 80 176

Schneider Electric

159

Complementary technical information

Use of LV switches (cont.) Switch-disconnectors protection (cont.)


Compact NA switch-disconnectors
Upstream protection
Compact NS By 380/415 V circuit breaker type / maximum rating (A) Isc max. making capacity type / cal maxi (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A)) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity

kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

By 440/480 V circuit breaker (1)

By 500/525 V circuit breaker

By 690 V circuit breaker

Masterpact NT H1 By 220/690 V circuit breaker

kA rms DIN off / DIN on (2) kA peak DIN off / DIN on (2)

Masterpact NT L1 By 220/525 V circuit breaker

kA rms kA peak kA rms kA peak

By 690 V circuit breaker

Masterpact NW N1-H1-H2-H3 By 220/440-480 V type / maximum rating (A) circuit breaker (1) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity By 500/525 V circuit breaker type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity By 690 V circuit breaker type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity

kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3)

(1) Suitable for NEMA 480 V voltage. (2) Maximum setting position 15. (3) DIN on: b maximum setting position 15 (In y 2000). b maximum setting position 12 (In = 2500). b maximum setting position 8 (In = 3200).

Masterpact NW L1 By 220/690 V circuit breaker

type / maximum rating (A) Isc max. making capacity

kA rms kA peak

160

Schneider Electric

Complementary technical information

Use of LV switches (cont.) Switch-disconnectors protection (cont.)


NS1000NA NS1250NA NS1600NA

NS630bNA

NS800NA

NS630bN/630 50 105 NS630bH/630 70 154 NS630bL/630 150 330 NS630bN/630 50 105 NS1600H-bH/1600 65 143 NS630bL/630 130 286 NS630bN/630 40 84 NS630bH/630 50 105 NS630bL/630 100 220 NS630bN/630 30 63 NS630bH/630 42 88 NS630bL/630 25 53 NT06H1/630 25 / 42 53 / 88 NT06L1/630 100 220 NT06L1/630 25 53 NW08N1/630 25 / 42 53 / 88 NW08H1/630 25 / 50 53 / 105 NW08H2/630 25 / 50 53 / 105 NW08N1/630 25 / 40 53 / 84 NW08H1/630 25 / 40 53 / 84 NW08H2/630 25 / 40 53 / 84 NW08N1/630 25 / 30 53 / 63 NW08H1/630 25 / 30 53 / 63 NW08H2/630 25 / 30 53 / 63 NW08L1/630 25 53

NS800N/800 50 105 NS800H/800 70 154 NS800L/800 150 330 NS800N/800 50 105 NS1600H-bH/1600 65 143 NS800L/800 130 286 NS800N/800 40 84 NS800H/800 50 105 NS800L/800 100 220 NS800N/800 30 63 NS800H/800 42 88 NS800L/800 25 53 NT08H1/800 25 / 42 53 / 88 NT08L1/800 100 220 NT08L1/800 25 53 NW08N1/800 25 / 42 53 / 88 NW08H1/800 25 / 50 53 / 105 NW08H2/800 25 / 50 53 / 105 NW08N1/800 25 / 40 53 / 84 NW08H1/800 25 / 40 53 / 84 NW08H2/800 25 / 40 53 / 84 NW08N1/800 25 / 30 53 / 63 NW08H1/800 25 / 30 53 / 63 NW08H2/800 25 / 30 53 / 63 NW08L1/800 25 53

NS1000N/1000 50 105 NS1000H/1000 70 154 NS1000L/1000 150 330 NS1000N/1000 50 105 NS2000H/2000 65 143 NS1000L/1000 130 286 NS1000N/1000 40 84 NS1000H/1000 50 105 NS1000L/1000 100 220 NS1000N/1000 30 63 NS1000H/1000 42 88 NS1000L/1000 25 53 NT10H1/1000 25 / 42 53 / 88 NT10L1/1000 100 220 NT10L1/1000 25 53 NW10N1/1000 25 / 42 53 / 88 NW10H1/1000 25 / 50 53 / 105 NW10H2/1000 25 / 50 53 / 105 NW10N1/1000 25 / 40 53 / 84 NW10H1/1000 25 / 40 53 / 84 NW10H2/1000 25 / 40 53 / 84 NW10N1/1000 25 / 30 53 / 63 NW10H1/1000 25 / 30 53 / 63 NW10H2/1000 25 / 30 53 / 63 NW10L1/1000 25 53

NS1250N/1250 50 105 NS1250H/1250 70 154

NS1600N-bN/1600 50 105 NS1600H-bH/1600 70 154

NS1250N/1250 50 105 NS2500H/2500 65 143

NS1600N-bN/1600 50 105 NS3200H/3200 65 143

NS1250N/1250 40 84 NS1250H/1250 50 105

NS1600N-bN/1600 40 84 NS1600H-bH/1600 50 105

NS1250N/1250 30 63 NS1250H/1250 42 88

NS1600N-bN/1600 30 63 NS1600H-bH/1600 42 88

NT12H1/1000 25 / 42 53 / 88 NT12L1/1250 100 220 NT12L1/1250 25 53 NW12N1/1250 25 / 42 53 / 88 NW12H1/1250 25 / 50 53 / 105 NW12H2/1250 25 / 50 53 / 105 NW12N1/1250 25 / 40 53 / 84 NW12H1/1250 25 / 40 53 / 84 NW12H2/1250 25 / 40 53 / 84 NW12N1/1250 25 / 30 53 / 63 NW12H1/1250 25 / 30 53 / 63 NW12H2/1250 25 / 30 53 / 63 NW12L1/1250 25 53

NT16H1/160 25 / 42 53 / 88 NT16L1/160 100 220 NT16L1/160 25 53 NW16N1/160 25 / 4 53 / 88 NW16H1/1600 25 / 50 53 / 105 NW16H2/1600 25 / 50 53 / 105 NW16N1/160 25 / 40 53 / 84 NW16H1/1600 25 / 40 53 / 8 NW16H2/160 25 / 40 53 / 84 NW16N1/160 25 / 3 53 / 6 NW16H1/160 25 / 30 53 / 6 NW16H2/160 25 / 30 53 / 6 NW16L1/160 25 53

Schneider Electric

161

Complementary technical information

Use of LV switches (cont.) Switch-disconnectors protection (cont.)


Compact NA switch-disconnectors
Upstream protection
Compact NS By 380/415 V circuit breaker type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity

kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

By 440/480 V circuit breaker (1)

By 500/525 V circuit breaker

By 690 V circuit breaker

Masterpact NT H1 By 220/690 V circuit breaker

kA rms DIN off / DIN on (2) kA peak DIN off / DIN on (2)

Masterpact NT L1 By 220/525 V circuit breaker

kA rms kA peak kA rms kA peak

By 690 V circuit breaker

Masterpact NW N1-H1-H2-H3 By 220/440-480 V type / maximum rating (A) circuit breaker (1) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity By 500/525V circuit breaker type / maximum rating (A) Icc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity By 690V circuit breaker type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity type / maximum rating (A) Isc max. making capacity

kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3) kA rms DIN off / DIN on (3) kA peak DIN off / DIN on (3)

(1) Suitable for NEMA 480 V voltage. (2) Maximum setting position 15. (3) DIN on: b maximum setting position 15 (In y 2000) b maximum setting position 12 (In = 2500) b maximum setting position 8 (In = 3200).

Masterpact NW L1 By 220/690V circuit breaker

type / maximum rating (A) Isc max. making capacity

kA rms kA peak

162

Schneider Electric

Complementary technical information

Use of LV switches (cont.) Switch-disconnectors protection (cont.)


NS2500NA NS3200NA

NS1600bNA

NS2000NA

NS1600N/bN/1600 50 / 70 105 / 154 NS1600H/bH/1600 70 / 85 154 / 187 NS1600N/bN/1600 50 / 65 105 / 143 NS1600H/bH/1600 65 / 85 143 / 187 NS1600N/bN/1600 40 / 65 84 / 143 NS1600H/BH/1600 50 / 65 105 / 143 NS1600N/bN/1600 30 / 65 63 / 143 NS1600H/bH/1600 42 / 65 88 / 143 NT16H1/1600 30 / 42 63 / 88 NT16L1/1600 100 220 NT16L1/1600 25 50 NW16N1/1600 50 / 88 50 / 88 NW16H1/1600 65 143 NW16H2/1600 70 154

NS2000N/2000 70 154 NS2000H/2000 85 187 NS2000N/2000 65 143 NS2000H/2000 85 187 NS2000N/2000 65 143 NS2000H/2000 65 143 NS2000N/2000 65 143 NS2000H/2000 65 143

NS2500N/2500 70 154 NS2500H/2500 85 187 NS2500N/2500 65 143 NS2500H/2500 85 187 NS2500N/2500 65 143 NS2500H/2500 65 143 NS2500N/2500 65 143 NS2500H/2500 65 143

NS3200N/3200 70 154 NS3200H/320 85 187 NS3200N/3200 65 143 NS3200H/3200 85 187 NS3200N/3200 65 143 NS3200H/3200 65 143 NS3200N/3200 65 143 NS3200H/3200 65 143

NW20H1/2000 65 143 NW20H2/2000 70 154 NW20H3/2000 70 154

NW25H1/2500 65 143 NW25H2/2500 70 154 NW25H3/2500 70 154

NW32H1/3200 65 143 NW32H2/3200 70 154 NW32H3/3200 70 154

NW16N1/1600 50 / 88 50 / 88 NW16H1/1600 65 143 NW16H2/1600 70 154

NW20H1/2000 65 143 NW20H2/2000 65 143 NW20H3/2000 65 143

NW25H1/2500 65 143 NW25H2/2500 65 143 NW25H3/2500 65 143

NW32H1/3200 65 143 NW32H2/3200 65 143 NW32H3/3200 65 143

NW16N1/1600 42 88 NW16H1/1600 65 143 NW16H2/1600 65 143

NW20H1/2000 65 143 NW20H2/2000 65 143 NW20H3/2000 65 143 NW20L1/2000 100 220

NW25H1/2500 65 143 NW25H2/2500 65 143 NW25H3/2500 65 143

NW32H1/3200 65 143 NW32H2/3200 65 143 NW32H3/3200 65 143

NW16L1/1600 100 220

Schneider Electric

163

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
When chosing a circuit breaker to protect a busbar trunking system, it is necessary to take into account: b the usual rules concerning the circuit breaker current settings: Ib y Ir y Inc where Ib = maximum load current Ir = circuit breaker current setting Inc = current rating of the busbar trunking b the electrodynamic withstand of the busbar trunking: the peak current limited by the circuit breaker must be less than the electrodynamic withstand capacity (or rated peak current) of the busbar trunking. Coordination tables The tables for coordinating Merlin Gerin

Traditional circuit breaker selection method


The circuit breaker used to protect a distribution circuit is chosen according to two fundamental criteria: b the maximum load current Ib flowing in the supply circuit b the prospective short-circuit current Isc at a point where the circuit breaker is to be installed. The circuit breaker is choosen such that: v In circuit breaker u Ib v breaking capacity of the circuit breaker u Isc.

Installation example
E40700

CB1 Ib = 360 A Icc = 65 kA

CB2 Ib = 140 A Icc = 65 kA

Application for Compact NS range


E40701

CB1 = NS400H (P of C = 70 kA)

CB2 = NS160H (P of C = 70 kA)

Schneider Electric

167

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Example Consider two 630 kVA/400 V transformer (Usc 4 %) supplying a main LV switchboard for which the prospective short-circuit current on the busbars is 44 kA. From the switchboard, a 30-metre long Canalis KVA63 transmission electrical busbar trunking system (630A) supplies a Canalis KSA63 trunking system (630A) for distribution with high-density tap-offs. A tap-off on the KSA63 trunking supplies a Canalis KSA16 trunking system. The short-circuit level are respectively: b 44 kA downstream of circuit-breaker CB1 and at the upstream connection of the KVA63 trunking b 33 kA at the junction between the KVA63 transmission trunking and the KSA63 trunking for high-density tap-offs. What circuit breakers should be chosen for CB1 and CB2 to protect the installation against short-circuits?
Prospective Isc Circuit breakers Isc protection level for KVA63 trunking Isc protection level for KVA63 trunking Isc protection level for KSA16 trunking
E59246

CB1 44 kA NS630N (45 kA breaking capacity) 45 kA 45 kA

CB2 33 kA NS160N (35 kA breaking capacity)

35 kA

630 kVA 400 V

630 kVA 400 V

prospective Isc 44 kA LV main swichboard

D1 disconnector ? prospective Isc 44 kA prospective Isc 33 kA canalis KSA 63

a 30-meter KVA63 transmission EBT system D2 disconnector ?

canalis KSA 16

168

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
The different types of Telemecanique busbar trunking

Type of busbar trunking Busbar trunking for transmission and distribution with low-density tap-offs Busbar trunking for distribution with high-density tap-offs Busbar trunking for lighting distribution and management

Low power

KN 40 at 100 A (tension 380/415 V) KLE, KBA, KBB K System (tension 380/415 V)

Medium power KVA 200 to 800 A KVC 200 to 800 A (380/415 V - 660/690 V) KSA 100 to 800 A (380/415 V - 660/690 V)

High power KTA 1000 to 4000 A KTC 1000 to 4000 A (380/415 V - 660/690 V) KHF 1000 to 4500 A (380/415 V - 660/690 V)

Coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis electrical busbar trunking Voltage: 380 V / 415 V
Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Multi 9 Icc max. in kA ms. KLE-16/20 16/20 10 15 25 KBA-25 KBB-25 25 25 KBA-40 40 KBB-40 40 KN-04 40 KN-06 63 KN-10 100 C60N16/20 C60H16/20 C60L16/20 C60N25 C60H25 C60L25 NC100LH25 C60N40 C60H40 C60L40 NC100LH40 C60N63 C60H63 C60L63 NC100LH63 NS100N (1) NS100H (1) NS100L (1) (1) TM-D trip unit, rating 40 or 63 or 100 A and STR22SE rating 40 or 100 A.

10 15 25 50

10 15 25 50 10 15 25 50 10 15 25 50 10 15 25 50 10 15 15 50 25 25 25

25 25 25

25 25 25

Schneider Electric

169

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 380 V / 415 V
KSA-10 NS100N NS100H NS100L NS160N NS160H NS160L NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L NS630bN NS630bH NS630bL NS800N NS800H NS800L NS1000N NS1000H NS1000L NS1250N NS1250H NT06H1 NT08H1 NT10H1 NT12H1 NT06L1 NT08L1 NT10L1 NW08N1 NW10N1 NW12N1 NW08H1 NW10H1 NW12H1 NW08H2 NW10H2 NW12H2 NW08L1 NW10L1 NW12L1 100 25 25 25 20 20 20 17 17 17 KSA-16 160 25 70 90 36 70 70 36 55 55 30 30 30 KSA-25 250 KSA-40 400 KSA-50 500 KSA-63 630 KSA-80 800

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

36 70 150 36 70 150 45 45 45 30 30 30 14 14

45 70 150 45 70 150

45 70 150 26 26 70

45 70 150 32 32 120 32 32 120

Masterpact

14

24 24 24 24 55 55 55 24 24 24 24 24 24 24 24 24 24 24 24

26 26 26 26 70 70 70 26 26 26 26 26 26 26 26 26 26 26 26

32 32 32 32 120 120 120 32 32 32 32 32 32 32 32 32 32 32 32

45 70 150 38 38 150 38 38 150 38 38 150 38 38 38 38 38 38 150 150 150 38 38 38 38 38 38 38 38 38 38 38 38

170

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 380 V / 415 V
KVA-20 NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L NS630bN NS630bH NS630bL NS800N NS800H NS800L NS1000N NS1000H NS1000L NT06H1 NT08H1 NT10H1 NT06L1 NT08L1 NT10L1 NW08N1 NW10N1 NW08H1 NW10H1 NW08H2 NW10H2 NW08L1 NW10L1 200 36 70 100 35 35 35 KVA-31 315 36 70 100 45 70 150 45 70 150 KVA-40 400 KVA-50 500 KVA-63 630 KVA-80 800

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

45 70 150 45 70 150

45 70 150 45 70 150 26 26 120

45 70 150 45 70 150 29 29 150 29 29 150

35 35 150 35 35 150 35 35 150 150 150 35 35 35 35 35 35 35 35

Masterpact

18

19 19 28 28

26 26 65 65

29 29 29 85 85 85 29 29 29 29 29 29 29 29

Voltage: 380 V / 415 V


Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms. NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L NS630bN NS630bH NS630bL NS800N NS800H NS800L NS1000N NS1000H NS1000L NT06H1 NT08H1 NT10H1 NT06L1 NT08L1 NT10L1 NW08N1 NW10N1 NW08H1 NW10H1 NW08H2 NW10H2 NW08L1 NW10L1 KVC-20 200 36 70 100 35 35 35 KVC-31 315 36 70 100 45 70 150 KVC-40 400 KVC-63 630 KVC-80 800

45 70 150 45 70 150 19 19 40

45 70 150 45 70 150 29 29 150 29 29 150

35 35 150 35 35 150 35 35 150 35 35 150 150 35 35 35 35 35 35 35 35

Masterpact

18

19

55

60

29 29 29 85 85 85 29 29 29 29 29 29 29 29

Schneider Electric

171

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 380 V / 415 V
KTA-10 NS1000N NS1000H NS1000L NS1250N NS1250H NS1600N NS1600H NT10H1 NT12H1 NT16H1 NT10L1 NW10N1 NW12N1 NW16N1 NW20N1 NW10H1 NW12H1 NW16H1 NW20H1 NW25H1 NW32H1 NW40H1 NW40bH1 NW50H1 NW10H2 NW12H2 NW16H2 NW20H2 NW25H2 NW32H2 NW40H2 NW40bH2 NW50H2 NW25H3 NW32H3 NW40H3 NW10L1 NW12L1 NW16L1 NW20L1 1000 40 40 150 40 40 40 40 40 40 40 150 40 40 40 40 40 40 KTA-12 1200 KTA-16 1600 KTA-20 2000 KTA-25 2500 KTA-30 3000 KTA-40 4000

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

Masterpact

50 50 50 50 42 42 42 150 42 42 42 50 50 50

60 60 60 60 42 42 42 150 42 42 42 42 60 60 60 60 60

42 42 42 150 42 42 42 42 65 65 65 65 65

42

42

65 65 65 65 65 80

65 65 65 65 65 86

65 65 90 90

40 40 40

50 50 50

60 60 60 60 60

72 72 72 72 72

80 80 80 80 80 80 80 80 80

86 86 86 86 86 86 86 86 86

90 90 90 90 90 90

60

72

40 40

55 55

80 80 80 80

140 140

150 150

150

172

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 380 V / 415 V
KTC-10 NS1000N NS1000H NS1000L NS1250N NS1250H NS1600N NS1600H NT10H1 NT12H1 NT16H1 NT10L1 NW10N1 NW12N1 NW16N1 NW20N1 NW10H1 NW12H1 NW16H1 NW20H1 NW25H1 NW32H1 NW40H1 NW40bH1 NW50H1 NW63H1 NW10H2 NW12H2 NW16H2 NW20H2 NW25H2 NW32H2 NW40H2 NW40bH2 NW50H2 NW63H2 NW25H3 NW32H3 NW40H3 NW10L1 NW12L1 NW16L1 NW20L1 1000 40 40 150 40 40 40 40 40 40 40 150 40 40 40 40 40 40 KTC-13 1350 50 50 150 50 50 50 50 KTC-16 1600 KTC-20 2000 KTC-25 2500 KTC-30 3000 KTC-40 4000 KTC-50 5000

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

60 60 60 60

Masterpact

150 42 42 42 50 50 50

150 42 42 42 42 60 60 60 60 60

150 42 42 42 42 65 65 65 65 65

42

42

65 65 65 65 82

65 65 65 65 82

65 65 90 90 90

95 95

40 40 40

50 50 50

60 60 60 60 60

73 73 73 73 73

82 82 82 82 82

82 82 82 82 82

90 90 90 90 90 90 90

95 95

60

73

82 82 82

82 82 82

40 40

55 55 55 55

80 80 80 80

140 140

150 150

150 150

Schneider Electric

173

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 380 V / 415 V
KHF NS800N NS800H NS800L NS1000N NS1000H NS1000L NS1250N NS1250H NS1600N NS1600H NS1600bN NS1600bH NS2000N NS2000H NS2500N NS2500H NS3200N NS3200H NT08H1 NT10H1 NT12H1 NT16H1 NT08L1 NT10L1 NW08N1 NW10N1 NW12N1 NW16N1 NW20N1 NW08H1 NW10H1 NW12H1 NW16H1 NW20H1 NW25H1 NW32H1 NW40H1 NW40bH1 NW50H1 NW63H1 NW08H2 NW10H2 NW12H2 NW16H2 NW20H2 NW25H2 NW32H2 NW40H2 NW40bH2 NW50H2 NW63H2 NW25H3 NW32H3 NW40H3 NW08L1 NW10L1 NW12L1 NW16L1 NW20L1 1000 28 28 70 28 28 70 28 28 KHF 1200 KHF 1450 KHF KHF KHF 2200/2500 3000/3400 4000/4500

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

38 38 150 38 38 38 38 38 38

48 48 150 48 48 48 48 48 48

70 85 70 85 70 85 70 85

70 85 70 85 70 85 70 85

Masterpact

28 28 28 28 80 80 28 28 28 28 28 28 28 28 28 28 28

38 38 38 38 150 150 38 38 38 38 38 38 38 38 38 38 38

38 38 38 38 150 150 38 38 38 38 38 38 38 38 38 38 38

42

42 42

42

65 65 65 65 65 92 92 92

65 65 65 65 100 100 100

65 65 100 100 100

28 28 28 28 28 28

38 38 38 38 38 38

38 38 38 38 38 38

28

38

38

92 92 92 92 92 92 92 92 92 92 92

100 100 100 100 117 117 117 117 117 117

100 100 147 147 147 147 147

28 28 28 28 28

38 38 38 38 38

38 38 38 38 38

150 150

150

174

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 660 V / 690 V
KSA-10 NS100N NS100H NS100L NS160N NS160H NS160L NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L NS630bN NS630bH NS630bL NS800N NS800H NS800L NS1000N NS1000H NS1000L NT06H1 NT08H1 NT10H1 NT12H1 NT06L1 NT08L1 NT10L1 NW08N1 NW10N1 NW12N1 NW08H1 NW10H1 NW12H1 NW08H2 NW10H2 NW12H2 NW08L1 NW10L1 NW12L1 100 8 10 20 8 10 20 8 10 15 KSA-16 160 8 10 75 8 10 75 8 10 20 10 17 14 KSA-25 250 KSA-40 400 KSA-50 500 KSA-63 630 KSA-80 800

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

8 10 75 8 10 20 10 20 28

14

10 20 35 10 20 35 24 24 75

10 20 35 26 26 75 26 26 75

10 20 35 30 32 75 30 32 75

Masterpact

14

24 24 24 24 25 25 25 24 24 24 24 24 24 24 24 24 24 24 24

26 26 26 26 25 25 25 26 26 26 26 26 26 26 26 26 26 26 26

32 32 32 32 25 25 25 32 32 32 32 32 32 32 32 32 32 32 32

20 20 35 30 38 75 30 38 75 30 38 35 38 38 38 38 25 25 25 38 38 38 38 38 38 38 38 38 38 38 38

Schneider Electric

175

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 660 V / 690 V
KVA-20 NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L NS630bN NS630bH NS630bL NS800N NS800H NS800L NS1000N NS1000H NS1000L NT06H1 NT08H1 NT10H1 NT06L1 NT08L1 NT10L1 NW08N1 NW10N1 NW08H1 NW10H1 NW08H2 NW10H2 NW08L1 NW10L1 200 8 10 20 10 20 20 KVA-31 315 KVA-40 400 KVA-50 500 KVA-63 630 KVA-80 800

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

10 20 75 10 20 35

10 20 75 10 20 35 24 24

10 20 75 10 20 35 26 26

Masterpact

23 23 23

24 24 24

26 26 26

10 20 75 10 20 35 30 30 65 30 30 75 30 30 35 36 36 36 25 25 25 36 36 36 36 36 36 36 36

65 30 35 75 30 35 35 40 40 25 25 25 40 40 40 40 40 40 40 40

176

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 660 V / 690 V
KVC-20 NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L NS630bN NS630bH NS630bL NS800N NS800H NS800L NS1000N NS1000H NS1000L NT06H1 NT08H1 NT10H1 NT06L1 NT08L1 NT10L1 NW08N1 NW10N1 NW08H1 NW10H1 NW08H2 NW10H2 NW08L1 NW10L1 200 8 10 20 10 20 20 KVC-31 315 KVC-40 400 KVC-63 630 KVC-80 800

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

10 20 75 10 20 35

10 20 75 10 20 35 19 19 27

10 20 75 10 20 35 30 30 75 30 36 75

Masterpact

25

27

25

25

36 36 36 25 25 25 36 36 36 36 36 36 36 36

30 35 75 30 35 35 40 40 40 25 25 25 40 40 40 40 40 40 40 40

Schneider Electric

177

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 660 V / 690 V
KTA-10 NS1000N NS1000H NS1000L NS1250N NS1250H NS1600N NS1600H NT10H1 NT12H1 NT16H1 NT10L1 NW10N1 NW12N1 NW16N1 NW20N1 NW10H1 NW12H1 NW16H1 NW20H1 NW25H1 NW32H1 NW40H1 NW40bH1 NW50H1 NW10H2 NW12H2 NW16H2 NW20H2 NW25H2 NW32H2 NW40H2 NW40bH2 NW50H2 NW25H3 NW32H3 NW40H3 NW10L1 NW12L1 NW16L1 NW20L1 1000 30 40 35 30 40 30 40 40 40 40 25 40 40 40 40 40 40 40 KTA-12 1200 30 42 35 30 42 30 42 42 42 42 25 42 42 42 42 50 50 50 KTA-16 1600 KTA-20 2000 KTA-25 2500 KTA-30 3000 KTA-40 4000

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

Masterpact

42 42 42 25 42 42 42 42 60 60 60 60

42 42 42 25 42 42 42 42 65 65 65 65

42

65 65 65 65 65 80

65 65 65 65 65 86

65 65 90 90

40 40 40

50 50 50

60 60 60 60 60

72 72 72 72 72

80 80 80 80 80 80 80 80 80

86 86 86 86 86 86 86 86 86

85 85 90 90 90 90

60

72

40 40

50 50

65 65 65 65

100 100

100 100

178

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 660 V / 690 V
KTC-10 NS1000N NS1000H NS1000L NS1250N NS1250H NS1600N NS1600H NT10H1 NT12H1 NT16H1 NT10L1 NW10N1 NW12N1 NW16N1 NW20N1 NW10H1 NW12H1 NW16H1 NW20H1 NW25H1 NW32H1 NW40H1 NW40bH1 NW50H1 NW63H1 NW10H2 NW12H2 NW16H2 NW20H2 NW25H2 NW32H2 NW40H2 NW40bH2 NW50H2 NW63H2 NW25H3 NW32H3 NW40H3 NW10L1 NW12L1 NW16L1 NW20L1 1000 30 40 35 30 40 30 40 40 40 40 25 40 40 40 40 40 40 KTC-13 1350 30 42 35 30 42 40 42 KTC-16 1600 KTC-20 2000 KTC-25 2500 KTC-30 3000 KTC-40 4000 KTC-50 5000

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

Masterpact

25 42 42 42 50 50 50

25 42 42 42 42 60 60 60 60 60

25 42 42 42 42 65 65 65 65 65

42

42

65 65 65 65 82

65 65 65 65 82

65 65 90 90

95 95

40 40 40

50 50 50

60 60 60 60 60

73 73 73 73 73

82 82 82 82 82

82 82 82 82 82

90 90 90 90 90 90 90

95 95

60

73

82 82 82

82 82 82

40 40

50 50 50 50

65 65 65 65

100 100

100 100

100 100

Schneider Electric

179

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking
Voltage: 660 V / 690 V
KHF NS800N NS800H NS800L NS1000N NS1000H NS1000L NS1250N NS1250H NS1600N NS1600H NS1600bN NS1600bH NS2000N NS2000H NS2500N NS2500H NS3200N NS3200H NT08H1 NT10H1 NT12H1 NT16H1 NT08L1 NT10L1 NW08N1 NW10N1 NW12N1 NW16N1 NW20N1 NW08H1 NW10H1 NW12H1 NW16H1 NW20H1 NW25H1 NW32H1 NW40H1 NW40bH1 NW50H1 NW63H1 NW08H2 NW10H2 NW12H2 NW16H2 NW20H2 NW25H2 NW32H2 NW40H2 NW50bH2 NW50H2 NW63H2 NW25H3 NW32H3 NW40H3 NW08L1 NW10L1 NW12L1 NW16L1 NW20L1 1000 28 28 75 28 28 35 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 25 25 28 28 28 28 28 28 28 28 28 28 28 KHF 1200 KHF 1450 KHF KHF KHF 2200/2500 3000/3400 4000/4500

Type of Canalis busbar trunking Trunking rating (in A at 35 C) Type of circuit breaker Compact Icc max. in kA ms.

30 38 35 30 38 30 38 30 38

30 48 35 30 48 30 48 48 48 48 48

30 42 60 40 60 40 60 40 60 40

60 40

Masterpact

38 38 38 38 25 25

38 38 38 38 25 25

38

38 38 38 38 38 38

38 38 38 38 38 38

65 65 65 65 65 92 92 92

65 65 65 65 100 100 100

65 65 100 100 100

28 28 28 28 28 28

38 38 38 38 38 38

38 38 38 38 38 38

28

38

38

85 85 85 85 85 92 92 92 92 92 92

85 85 85 85 100 100 100 100 100 100

85 85 100 100 100 100 100

28 28 28 28 28

38 38 38 38 38

38 38 38 38 38

100 100

100

180

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination Circuit breaker selection taking coordination into account
The use of current-limiting circuit breakers makes it possible to implement coordination techniques. This improves circuit breaker performance in terms of breaking capacity and continuity of service. Coordination techniques are described and recognised by the following standards: b product standards IEC 60947-1 and 60947-2 b installation standards IEC 60364, NF C15-100, etc.

Cascading
The use of a current-limiting circuit breaker upstream to reinforce the breaking capacity of a downstream circuit breaker.

Principle
Cascading
E40702

CB1

CB2 Isc = 65 kA

CB2 breaking capacity

Application for Compact NS range


Cascading
E40703

CB1 = NS400H

Reinforced break. cap. 70 kA

CB2 = NS160N (Breaking cap. = 35 kA)

Schneider Electric

181

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination
Discrimination
In the event of an electrical fault on one outgoing circuit, discrimination is the ability of the electrical installation to maintain the continuity of electrical power supplied to the other circuits not concerned by the fault. As a general rule, cascading and discrimination techniques are applied independently. Schneider has developed an exclusive system to conciliate cascading and discrimination. This system ensures discrimination up to the reinforced breaking capacity of the association of circuit breakers CB1 and CB2.

Principle
Cascading and reinforced discrimination
E40702

CB1

CB2 Isc = 65 kA

CB2 breaking capacity

Discrimination ensured up to the reinforced breaking capacity of CB2

Application for Compact NS range


Cascading and reinforced discrimination
E40704

CB1 = NS400H

Break. cap. renforced 70 kA CB2 = NS160N Isc = 65 kA

182

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination
Cascading, reinforced discrimination and reinforced protection of busbar trunking systems (BTS) This technique is the direct application of cascading and discrimination techniques to the protection of busbar trunking systems. For various upstream circuit breakers and upstream busbar trunking systems, the tables below give directly: b the level of short-circuit protection of the busbar trunking b the downstream circuit breaker and associated busbar trunking b the cascading breaking capacity of the downstream circuit breaker b the level of reinforced discrimination of the upstream and downstream circuit breakers b the level of reinforced protection of the downstream busbar trunking. Application to a Canalis distributed distribution system: b reinforcement of the breaking capacity of the NS 160N (CB2) up to 70 kA b discrimination between CB1 and CB2 ensured up to 70 kA b protection of Canalis KSA 16 busbar trunking up to 70 kA. Alimentation
E40705

CB1 = NS400H

KSA40 (400 A)

CB2 = NS160N

KSA16 (160 A)

70 kA

Example of a table corresponding to the above diagram.

Rated current of the upstream busbar trunking: 315 and 400 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS400N STR23SE/STR53UE KSA / KVA / KVC 315 and 400 A 45 NS100N TMD/STR22SE KSA 100 A NS160N KSA 160 A

NS400H STR23SE/STR53UE KSA / KVA / KVC 315 and 400 A 70 NS100N TMD/STR22SE KSA 100 A NS160N KSA 160 A

NS400L STR23SE/STR53UE STR23SE/STR53UE KSA KVA KVC KSA //KVA / /KVC 315 and 400 A 315 and 400 A 70 150 NS100N NS100H TMD/STR22SE TMD/STR22SE KSA KSA 100 A 100 A NS160H KSA KSA 160 A 160 A

NS400H

NS160N

Discrimination limit between upstream and downstream circuit breakers (kA) 45 Reinforced breaking capacity of the downstream circuit breaker (kA) 45 Reinforced protection of the downstream busbar trunking (kA) 45

45 45 45

70 70 70

70 70 70

70 150 70 150 70 25

70 150 70 150 70 70

Schneider Electric

183

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination Voltage: 380/415 V
E39614

source

upstream circuit breaker

reinforced cascading and discrimination between the 2 circuit breakers

level of protection of the upstream busbar trunking

upstream busbar trunking

downstream circuit breaker

reinforced protection of the downstream busbar trunking

downstream busbar trunking

Rated current of the upstream busbar trunking: 1600 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking NS1600N Micrologic 5.0 KTA-16 / KTC-16 1600 A 50 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A 500 - 630 A NS1600N Micrologic 5.0 KTA-16 / KTC-16 1600 A 50 NS100N 40 A KN 40 A TMD / STR22SE 63 A 100 A KN KN 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 50 Reinforced breaking capacity of the downstream circuit breaker (kA) 50 Reinforced protection of the downstream busbar trunking (kA) 50

50 50 50

50 50 50

45 50 50

40 50 50

50 50 50

50 50 50

50 50 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS1600H Micrologic 5.0 KTA-16 / KTC-16 1600 A 70 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A 500 - 630 A

NS1600H Micrologic 5.0 KTA-16 / KTC-16 1600 A 70 NS100N 40 A KN 40 A TMD / STR22SE 63 A 100 A KN KN 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 70 Reinforced breaking capacity of the downstream circuit breaker (kA) 70 Reinforced protection of the downstream busbar trunking (kA) 70

70 70 70

70 70 70

45 70 70

40 70 70

70 70 50

70 70 50

70 70 50

184

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 1200 to 1350 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS1250N Micrologic 5.0 KTA-12 / KTC-13 1200 and 1350 A 50 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A 500 - 630 A

NS1250N Micrologic 5.0 KTA-12 / KTC-13 1200 and 1350 A 50 NS100N 40 A KN 40 A TMD / STR22SE 63 A 100 A KN KN 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 50 Reinforced breaking capacity of the downstream circuit breaker (kA) 50 Reinforced protection of the downstream busbar trunking (kA) 50

50 50 50

50 50 50

45 50 50

40 50 50

50 50 50

50 50 50

50 50 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS1250H Micrologic 5.0 KTA-12 / KTC-13 1200 and 1350 A 70 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A 500 - 630 A

NS1250H Micrologic 5.0 KTA-12 / KTC-13 1250 and 1350 A 70 NS100N 40 A KN 40 A TMD / STR22SE 63 A 100 A KN KN 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 70 Reinforced breaking capacity of the downstream circuit breaker (kA) 70 Reinforced protection of the downstream busbar trunking (kA) 70

70 70 70

70 70 70

45 70 70

40 70 70

70 70 50

70 70 50

70 70 50

Rated current of the upstream busbar trunking: 1000 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking NS1000N Micrologic 5.0 KTA-10 / KTC-10 1000 A 50 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A 50 NS250N KSA 250 A 50 NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A 500 - 630 A 45 40 NS1000N Micrologic 5.0 KTA-10 / KTC-10 1000 A 50 NS100N 40 A KN 40 A 50 TMD / STR22SE 63 A 100 A KN KN 63 A 100 A 50 50

Discrimination limit between upstream and downstream 50 circuit breakers (kA) Reinforced breaking capacity of the downstream circuit breaker (kA) 50 Reinforced protection of the downstream busbar trunking (kA) 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS1000H Micrologic 5.0 KTA-10 / KTC-10 1000 A 55 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A 500 - 630 A

NS1000H Micrologic 5.0 KTA-10 / KTC-10 1000 A 55 NS100N 40 A KN 40 A TMD / STR22SE 63 A 100 A KN KN 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 70 Reinforced breaking capacity of the downstream circuit breaker (kA) 70 Reinforced protection of the downstream busbar trunking (kA) 55

70 70 55

70 70 55

45 70 55

40 70 55

70 70 50

70 70 50

70 70 50

Schneider Electric

185

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 1000 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS1000L Micrologic 5.0 KTA-10 / KTC-10 1000 A 150 NS100N/H NS160N/H TMD / STR22SE KSA KSA 100 A 160 A NS250N/H KSA 250 A NS400N/H NS630N/H STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A 500 - 630 A

NS100L Micrologic 5.0 KTA-10 / KTC-10 1000 A 150 NS100N/H 40 A KN 40 A TMD / STR22SE 63 A 100 A KN KN 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 150 Reinforced breaking capacity of the downstream circuit breaker (kA) 150 Reinforced protection of the downstream busbar trunking (kA) 50

150 150 70

150 150 150

150 150 150

150 150 150

150 150 50

150 150 50

150 150 50

Rated current of the upstream busbar trunking: 800 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking NS800N Micrologic 5.0 KVA-80 / KVC-80 800 A 50 NS100N NS160N NS250N NS400N STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A NS800N Micrologic 5.0 KVA-80 / KVC-80 800 A 50 NS100N 40 A KN 40 A TMD / STR22SE 63 A KN 63 A 100 A KN 100 A

TMD / STR22SE KSA KSA 100 A 160 A

KSA 250 A

Discrimination limit between upstream and downstream circuit breakers (kA) 50 Reinforced breaking capacity of the downstream circuit breaker (kA) 50 Reinforced protection of the downstream busbar trunking (kA) 50

50 50 50

50 50 50

35 50 50

50 50 50

50 50 50

50 50 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS800H Micrologic 5.0 KVA-80 / KVC-80 800 A 60 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A NS400N STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A

NS800H Micrologic 5.0 KVA-80 / KVC-80 800 A 60 NS100N 40 A KN 40 A TMD / STR22SE 63 A 100 A KN KN 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 70 Reinforced breaking capacity of the downstream circuit breaker (kA) 70 Reinforced protection of the downstream busbar trunking (kA) 60

70 70 60

70 70 60

35 70 60

70 70 50

70 70 50

70 70 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS800L Micrologic 5.0 KVA-80 / KVC-80 800 A 150 NS100N/H NS160N/H TMD / STR22SE KSA KSA 100 A 160 A NS250N/H KSA 250 A NS400N/H STR23SE / STR53UE KSA / KVA / KVC 315 - 400 A

NS800L Micrologic 5.0 KVA-80 / KVC-80 800 A 150 NS100N/H 40 A KN 40 A TMD / STR22SE 63 A 100 A KN KN 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 150 Reinforced breaking capacity of the downstream circuit breaker (kA) 150 Reinforced protection of the downstream busbar trunking (kA) 50

150 150 70

150 150 150

150 150 150

150 150 50

150 150 50

150 150 50

186

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 500 and 630 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS630bN Micrologic 5.0 KSA / KVA / KVC 630 A 20 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A

NS630bH Micrologic 5.0 KSA / KVA / KVC 630 A 29 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A

NS630bL Micrologic 5.0 KSA / KVA / KVC 630 A 150 NS100N/H NS160N/H TMD / STR22SE KSA KSA 100 A 160 A NS250N/H KSA 250 A

Discrimination limit between upstream and downstream circuit breakers (kA) 50 Reinforced breaking capacity of the downstream circuit breaker (kA) 50 Reinforced protection of the downstream busbar trunking (kA) 50

50 50 50

50 50 50

70 70 60

70 70 70

70 70 70

150 150 50

150 150 70

150 150 150

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS630bN Micrologic 5.0 KSA / KVA / KVC 630 A 29 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

NS630bH Micrologic 5.0 KSA / KVA / KVC 630 A 29 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

NS630bL Micrologic 5.0 KSA / KVA / KVC 630 A 150 NS100N/H TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 50 Reinforced breaking capacity of the downstream circuit breaker (kA) 50 Reinforced protection of the downstream busbar trunking (kA) 50

50 50 50

50 50 50

70 70 50

70 70 50

70 70 50

150 150 50

150 150 50

150 150 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS630N STR23SE/STR53UE KSA / KVA / KVC 500 and 630 A 45 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A

NS630H STR23SE/STR53UE KSA / KVA / KVC 500 and 630 A 70 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A NS250N KSA 250 A

NS630L STR23SE/STR53UE KSA / KVA / KVC 500 and 630 A 150 NS100H NS160H TMD / STR22SE KSA KSA 100 A 160 A NS250H KSA 250 A

Discrimination limit between upstream and downstream circuit breakers (kA) 45 Reinforced breaking capacity of the downstream circuit breaker (kA) 45 Reinforced protection of the downstream busbar trunking (kA) 45

45 45 45

45 45 45

70 70 70

70 70 70

70 70 70

150 150 70

150 150 70

150 150 70

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS630N STR23SE/STR53UE KSA / KVA / KVC 500 and 630 A 45 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

NS630H STR23SE/STR53UE KSA / KVA / KVC 500 and 630 A 70 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

NS630L STR23SE/STR53UE KSA / KVA / KVC 500 and 630 A 150 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 45 Reinforced breaking capacity of the downstream circuit breaker (kA) 45 Reinforced protection of the downstream busbar trunking (kA) 45

45 45 45

45 45 45

70 70 50

70 70 50

70 70 50

150 150 50

150 150 50

150 150 50

Schneider Electric

187

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 315 and 400 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS400N STR23SE/STR53UE KSA / KVA / KVC 315 and 400 A 45 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A

NS400H STR23SE/STR53UE KSA / KVA / KVC 315 and 400 A 70 NS100N NS160N TMD / STR22SE KSA KSA 100 A 160 A

NS400L STR23SE/STR53UE KSA / KVA / KVC 315 and 400 A 150 NS100H NS160H TMD / STR22SE KSA KSA 100 A 160 A

Discrimination limit between upstream and downstream circuit breakers (kA) 45 Reinforced breaking capacity of the downstream circuit breaker (kA) 45 Reinforced protection of the downstream busbar trunking (kA) 45

45 45 45

70 70 70

70 70 70

150 150 70

150 150 70

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS400N STR23SE/STR53UE KSA / KVA / KVC 315 and 400 A 45 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

NS400H STR23SE/STR53UE KSA / KVA / KVC 315 and 400 A 70 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

NS400L STR23SE/STR53UE KSA / KVA / KVC 315 and 400 A 150 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 45 Reinforced breaking capacity of the downstream circuit breaker (kA) 45 Reinforced protection of the downstream busbar trunking (kA) 45

45 45 45

45 45 45

70 70 50

70 70 50

70 70 50

150 150 50

150 150 50

150 150 50

Rated current of the upstream busbar trunking: 200 and 250 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking NS250N TMD / STR22SE KSA / KVA / KVC 200 and 250 A 36 NS100N TMD / STR22SE KSA-10 100 A NS250H TMD / STR22SE KSA / KVA / KVC 200 and 250 A 70 NS100N TMD / STR22SE KSA-10 100 A NS250L TMD / STR22SE KSA / KVA / KVC 200 and 250 A 150 NS100H TMD / STR22SE KSA-10 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 36 Reinforced breaking capacity of the downstream circuit breaker (kA) 36 Reinforced protection of the downstream busbar trunking (kA) 36

36 70 70

36 150 70

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS250N TMD / STR22SE KSA / KVA / KVC 200 and 250 A 36 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

NS250H TMD / STR22SE KSA / KVA / KVC 200 and 250 A 70 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

NS250L TMD / STR22SE KSA / KVA / KVC 200 and 250 A 150 NS100N TMD / STR22SE 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A

Discrimination limit between upstream and downstream circuit breakers (kA) 36 Reinforced breaking capacity of the downstream circuit breaker (kA) 36 Reinforced protection of the downstream busbar trunking (kA) 36

36 36 36

36 36 36

36 70 50

36 70 50

36 70 50

36 150 50

36 150 50

36 150 50

188

Schneider Electric

Complementary technical information

Coordination tables between Merlin Gerin with the circuit breaker and Telemecanique Canalis electrical busbar trunking Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 200 and 250 A
(cont.)

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit (calibre A) Downstream busbar trunking

NS250N TMD / STR22SE KSA / KVA / KVC 200 and 250 A 36 C60N 16/20 KLE 16 - 20 A C60N 25/40 KBA / KBB 25 - 40 A NC100L 25/40 KBA / KBB 25 - 40 A

NS250H TMD / STR22SE KSA / KVA / KVC 200 and 250 A 70 C60H 16/20 KLE 16 -20 A C60H 25/40 KBA / KBB 25 - 40 A NC100L 25/40 KBA / KBB 25 - 40 A NC100LH 25/40 KBA / KBB 25 - 40 A

Discrimination limit between upstream and downstream circuit breakers (kA) 25 Reinforced breaking capacity of the downstream circuit breaker (kA) 25 Reinforced protection of the downstream busbar trunking (kA) 25

25 25 25

36 36 36

40 40 40

40 40 40

50 50 50

70 70 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS250N TMD / STR22SE KSA / KVA / KVC 200 and 250 A 36 C60N 40 A KN 40 A C60N 63 A KN 63 A NC100L 40 A KN 40 A NC100L 63 A KN 63 A

NS250H TMD / STR22SE KSA / KVA / KVC 200 and 250 A 70 C60H 40 A KN 40 A C60H 63 A KN 63 A NC100L 40 A KN 40 A NC100L 63 A KN 63 A NC100LH 40 A KN 40 A NC100LH 63 A KN 63 A

Discrimination limit between upstream and downstream circuit breakers (kA) 25 Reinforced breaking capacity of the downstream circuit breaker (kA) 25 Reinforced protection of the downstream busbar trunking (kA) 25

25 25 25

36 36 36

36 36 36

40 40 40

30 30 30

50 50 50

50 50 50

70 70 50

70 70 50

Rated current of the upstream busbar trunking: 160 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit (calibre A) Downstream busbar trunking NS160N TMD / STR22SE KSA 160 A 36 C60N 16/20 KLE 16 - 20 A C60N 25/40 KBA / KBB 25 - 40 A NC100L 25/40 KBA / KBB 25 - 40A NS160H TMD / STR22SE KSA 160 A 70 C60H 16/20 KLE 16 - 20 A C60H 25/40 KBA / KBB 25 - 40 A NC100L 25/40 KBA / KBB 25 - 40 A NC100LH 25/40 KBA / KBB 25 - 40 A

Discrimination limit between upstream and downstream circuit breakers (kA) 25 Reinforced breaking capacity of the downstream circuit breaker (kA) 25 Reinforced protection of the downstream busbar trunking (kA) 25

25 25 25

36 36 36

40 40 40

40 40 40

50 50 50

70 70 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking

NS160N TMD / STR22SE KSA 160 A 36 C60N 40 A KN 40 A C60N 63 A KN 63 A NC100L 40 A KN 40 A NC100L 63 A KN 63 A

NS160H TMD / STR22SE KSA 160 A 70 C60H 40 A KN 40 A C60H 63 A KN 63 A NC100L 40 A KN 40 A NC100L 63 A KN 63 A NC100LH 40 A KN 40 A NC100LH 63 A KN 63 A

Discrimination limit between upstream and downstream circuit breakers (kA) 25 Reinforced breaking capacity of the downstream circuit breaker (kA) 25 Reinforced protection of the downstream busbar trunking (kA) 25

25 25 25

36 36 36

36 36 36

40 40 40

40 40 40

50 50 50

50 50 50

70 70 50

70 70 50

Schneider Electric

189

266

Compact NS

Schneider Electric

Compact

Catalogue numbers

Presentation Functions and characteristics Installation recommendations Dimensions, volumes Connection Electrical diagrams Additional characteristics

1 11 143 165 205 221 251

NSA80H-MA NSC100N NS100/160/250N/H 1P/2P NS100/160/250N complete fixed/FC device NS100/160/250H complete fixed/FC device NS100/160/250L complete fixed/FC device NS100/160/250N/H/L fixed/FC device based on separate components Installation and connection Accessories NS400/630 complete fixed/FC device NS400/630 fixed/FC device based on separate components Installation and connection Accessories NB50/100 NB250N NB400N/NB600N NSA125/160 complete fixed/FC device Accessories NS125E NS100/400 NS630b to NS1600 fixed manually operated NS630b to NS1600 fixed electrically operated Accessories for NS630b to NS1600 fixed devices NS630b to NS1600 manually operated withdrawable devices NS630b to NS1600 electrically operated withdrawable devices Accessories for NS630b to NS1600 withdrawable devices Common accessories for NS630b to NS1600 withdrawable devices NS1600b to NS3200 fixed, front-connected, manually operated device Accessories for NS1600b to NS3200

268 270 272 274 276 277 278 279 280 285 287 288 290 294 298 298 300 301 302 304 309 311 312 314 315 316 318 320 321

267

Compact NS

Schneider Electric

Catalogue numbers

NSA125/160: complete fixed/FC device NSA160N/E and NSA125/160NA

Compact NSA160N with built-in trip unit


Compact NSA160N (36 kA at 380/415 V) Rating 3P 3d TM16D 28239 TM25D 28238 TM32D 28237 TM40D 28236 TM50D 28235 TM63D 28234 TM80D 28233 TM100D 28232 TM125D 28231 TM160D 28230 Compact NSA160E (16 kA at 380/415 V) Rating 3P 3d TM16D 28209 TM25D 28208 TM32D 28207 TM40D 28206 TM50D 28205 TM63D 28204 TM80D 28203 TM100D 28202 TM125D 28201 TM160D 28200 Rating Compact NSA125NA Compact NSA160NA 3P 28263 28261 4P 4d 28259 28258 28257 28256 28255 28254 28253 28252 28251 28250
E21016

Compact NSA160E with built-in trip unit


4P 4d 28229 28228 28227 28226 28225 28224 28223 28222 28221 28220 4P 28264 28262
E21016

Compact NSA125/160NA switch

550E5060.fm/78

Schneider Electric

Catalogue numbers

Accessories NSA160N/E and NSA125/160NA

Vigi module 0.03/3A


Bottom connectors
E20793
R

Top connectors

3P 4P 3P 4P

28000 28001 28002 28003

Connection accessories
Long terminal shields (1 pair)
E18607

3P 4P

28034 28035

Electrical auxiliaries
Auxiliary contacts (changeover)
E18608

OF or SD OF or SD low level

29450 29452

Voltage releases
AC 50/60 Hz
E21394

DC

Voltage (V) 48 110/130 220/240 380/415 440/480 Voltage (V) 24 48 125 250

MX 28070 28071 28072 28073 28074 MX 28075 28076 28077 28078

MN 28080 28081 28082 28083 28084 MN 28085 28086 28087 28088

Rotary handles
Door-mounted rotary control
E31293

Extended black handle Red handle on yellow front


ON I
trippe d
5...8

28059 28058

reset

O OFF

Miscellaneous
DIN rail and riser for Multi 9 devices 28041

Schneider Electric

550E5060.fm/79

Catalogue numbers

Source changeover Compact NS100 to NS630 and Compact C801 to C1251

Manual source changeover


Mechanical interlocking
For toggle controlled circuit-breakers
E21288

NS100...250 NS400...630

29354 32614

For rotary handled circuit-breakers


E18780

NS100...250 NS400...630 C801...1251

29369 32621 46946

Key lock interlocking


For rotary handled or remote controlled circuit breakers 2 locks, 1 key Ronis 1351.500 Profalux KS5 B24 D4Z 41950 42878
E23851

Remote controlled source changeover


Plate + IVE
Source "normal"/source "replacement" (identical voltages) 24 to 250 V DC
E33419

48 to 415 V AC 50/60 Hz 480 V 60 Hz 29350 29349 29352 4 x 29450 29365 (2) (2) 32610 32609 29352 4 x 29450 29365 (2) (2) 1 x 32618

NS100...250/NS100...250 Plate + IVE (1) Plate IVE Auxiliary switches 2 OF + 2 SDE Spare wiring system (device/IVE) Back sockets option add: Only long RC Plug in base option add: Plug in kit NS400...630/NS100...630 Plate + IVE (1) Plate IVE Auxiliary switches 2 OF + 2 SDE Spare wiring system (device/IVE) Back sockets option add: Only long RC Plug in base option add: Plug in kit Adaptator kit for NS100...250 C801...1251/C801...1251 Plate + IVE (1) Plate IVE Auxiliary switches 3 OF + 1 SD Contact SDE for Compact with T remote control Motormech. For ats spare wiring (device/IVE) Back sockets option

29351 29349 29356 4 x 29450 29365 (2) (2) 32611 32609 29356 4 x 29450 29365 (2) (2) 1 x 32618

46955 46949 46956 2 x 44901 2 x 46962 46873 (2) 220/240 V AC 50/60 Hz 29470 29363 29376 29472 29363 29378 29474 29363 29379

46954 46949 46957 2 x 44901 2 x 46962 46873 (2) 380/415 V AC 50/60 Hz 480 V 60 Hz 29471 29364 29377 29473 29364 29380 29475 29364 29381

Control unit option


110/127 V AC 50/60 Hz
E33420
GERIN MERLIN
multi P25M 9

0 . OFF

GERIN MERLIN
multi P25M 660V AC3-IEC292-1 9

0 . OFF

660V AC3-IEC292-1

Test

Test

ACP + control unit BA (1) Plate ACP Control unit BA ACP + control unit UA (1) 29448 Plate ACP 29447 Control unit UA 29446 ACP + control unit UA150 (1) (communication option) Plate ACP Control unit UA150

Wiring cable between BA/UA and ACP/IVE


29368 29368 (1) the supply voltages BA/UA control unit, ACP plate, IVE and the remote control must be identical whatever the source changeover type. (2) see products pages.

Connection accessories
Downstream coupling accessories
E23851

Source "normal"/source "replacement" NS100...250/NS100...250 250 A NS400...630/NS400...630 630 A

3P 4P 3P 4P

29358 29359 32619 32620

550E5065.fm/114

Schneider Electric

Catalogue numbers

Source changeover (cont.) Compact NS100 to NS630 and Compact C801 to C1251 (cont.)

Typical composition of remote controlled source changeover


Remote controlled source changeover
1 normal device N (1) + 1 replacement device R (2) + 2 remote controls (3) + 1 plate with interlocking (4) with IVE (5) and its wiring (8) + 2 plug-in kits (if plug-in version) + 1 adaptor kit for NS100...250 plug-in (if NS400...630 with NS100...250) + auxilary switches (6) 2 x (1 OF + 1 SDE) for Compact NS100...630 2 x (3 OF + 1 SD) for Compact C801...1251 + 1 downstream coupling accessory (7) for Compact NS100...630 (option) + long RC (if back connection)
E33422

IVE voltages and remote controls are identical.

Associated control unit


GERIN MERLIN
multi P25M 9

0 . OFF

GERIN MERLIN
multi P25M 660V AC3-IEC292-1 9

0 . OFF

660V AC3-IEC292-1

Test

Test

1 source changeover without associated control unit + 1 ACP (9) with BA control unit (10) Or + 1 ACP (9) with UA control unit (11) Or + 1 ACP (9) with UA150 control unit (11)

E33423

IVE voltages + remote control + ACP + BA or UA are identical.

Schneider Electric

550E5065.fm/115

550E5065.fm/116

Schneider Electric

Catalogue numbers

NS125E Complete fixed/FC device and accessories

Complete device
Compact NS125E with standard thermal-magnetic trip unit TM-D
Compact NS125E (16 kA at 380/415 V) Rating 3P 3d TM16D 34636 TM25D 34635 TM40D 34634 TM63D 34633 TM80D 34632 TM100D 34631 TM125D 34630 Vigicompact NS125E (16 kA at 380/415 V) Rating 3P 3d TM16D 34676 TM25D 34675 TM40D 34674 TM63D 34673 TM80D 34672 TM100D 34671 TM125D 34670 4P 3d 34646 34645 34644 34643 34642 34641 34640 4P 4d 34656 34655 34654 34653 34652 34651 34650
E21284

push to trip

Im 4 Ir .9 .85 .8 .98 .7 .63 xIn 1 .95 3 8 2 1.5 xIr 10 5 6 Ir Im

Vigicompact NS125E MH with trip unit TM-D


4P 3d 34686 34685 34684 34683 34682 34681 34680 4P 4d 34696 34695 34694 34693 34692 34691 34690
E21279

push to trip

Installation and connection


RC device = FC device + RC kit
Short RC kit 3P 4P Comprising: Mixed RC kit 3P 4P Comprising: 29237 29238 29235 29235 29239 29240 29235 29236 29235 29236
E16992

Kit 3P Kit 4P

6 short RCs 8 short RCs

3x 4x

Kit 3P Kit 4P

4 short RCs 2 long RCs 4 short RCs 4 long RCs

2x 1x 2x 2x

Accessories
Connection accessories
Rear connections
E18579

2 short 2 long

29235 29236

Bare cable connectors


E18572

Snap-on, for cable 1.5 to 95 mm2 Clips for bare-cable connector Distribution connectors for six 1.5 to 35 mm2 cables with interphase barriers

Set of 3 Set of 4 Set of 10 Set of 3 Set of 4

29242 29243 29241 29248 29249

E18589

Terminal extensions
E18600

Right-angle terminal extensions Set of 3 Set of 4 Straight terminal extensions Set of 3 Set of 4

29261 29262 29263 29264 31563 31564

E18601

Spreaders
E186599

3P 4P Supplied with 2 (or 3) interphase barriers

550E5080.fm/160

Schneider Electric

Catalogue numbers

NS125E (cont.) Accessories

Connection accessories (cont.)


Crimp lugs
Set of 3 Set of 4 For cable 150 mm2 Set of 3 Set of 4 For cable 185 mm2 Set of 3 Set of 4 Supplied with 2 (or 3) interphase barriers Short (1 pair)
E18618

For cable 120 mm2

29252 29256 29253 29257 29254 29258

E18602

Terminal shields
3P 4P 3P 4P Set of 6 29321 29322 29323 29324 29329

Long (1 pair)

Interphase barriers
E18606

Electrical auxiliaries - test kits


Auxiliary contacts (changeovers)
E18608

OF or SD or SDE or SDV SDE adapter for trip unit TM

29450 29451

Voltage releases
Voltage (V) 48 110/130 208/277 380/480 525/600 DC Voltage (V) 12 24 30 48 60 125 250 MN 220/240 V AC with time delay Composed of: MN 250 V DC Delay unit 220/240 V 50/60 Hz AC 50/60 Hz MX 29385 29386 29387 29388 29389 MX 29382 29390 29391 29392 29383 29393 29394 MN 29405 29406 29407 29408 29409 MN 29402 29410 29411 29412 29403 29413 29414 29422 29414 29427
E18609

Rotary handles
Direct rotary handle
ON I

O OFF

Standard black handle Red handle on yellow front MCC conversion accessory CNOMO conversion accessory Standard extended rotary handle Red handle on yellow front
ON I

29337 29339 29341 29342 29338 29340

E18611

Extended rotary handle


ON I

E18612

O OFF

OFF

Accessories
E18620
ON I

Locking devices Key locks Indication auxiliary

pr

of

al

ux

O OFF

Ronis 1351.500 Profalux KS5 B24 D4Z 1 early-break contact 2 early-make contacts

29344 41940 42888 29345 29346

Locks
Toggle locking device for 3 padlocks
Removable Fixed 29370 29371

Schneider Electric

550E5080.fm/161

Catalogue numbers

NS100/400 with "tarif jaune" connection

Complete fixed/FC device without accessories


Compact NS with trip unit STRAB
Compact NS NS100N STRAB NS160N STRAB NS250N STRAB NS400N STRAB Rating 100 160 240 400 4P 34562 34563 34564 34565 Basic frame 29008 30408 31408 32408 Trip unit 34550 34551 34554 34557
E22078

push to trip

STR
90 %Ir 105 alarm

22 DE
z test

50/60H

Im Ir .9 .85 .8 .98 .7 .63 xIn 1 .95 3 8 2 1.5 xIr 10 4 5 6 Ir Im

Comprising: NS100N + STRAB100 NS160N + STRAB160 NS250N + STRAB240 NS400N + STRAB400

Vigicompact NS with trip unit STRAB


Vigicompact NS NS100N STRAB NS160N STRAB NS250N STRAB NS400N STRAB Rating 100 160 240 400 4P 34572 34573 34574 34575 Basic frame 29008 30408 31408 32408 Trip unit 34550 34551 34554 34557 Vigi module MH/MB 29211 29211 31536 32456
E22087

push to trip

Comprising: NS100N + STRAB100 + MH NS160N + STRAB160 + MH NS250N + STRAB240 + MH NS400N + STRAB400 + MB

550E5080.fm/162

Schneider Electric

Catalogue numbers

NS100/400 "tarif jaune" connection (cont.)

Complet fixed/FC device without accessories


Compact NS with normal trip unit
Compact NS100N Rating TM40D TM63D TM80D TM100D Compact NS160N Rating TM80D TM100D TM125D TM160D Compact NS250N Rating TM125D TM160D TM200D TM250D Compact NS400N STR23SE 4P 3d 29643 29642 29641 29640 4P 3d 30643 30642 30641 30640 4P 3d 31643 31642 31641 31640 4P 3d 32694 4P 4d 29653 29652 29651 29650 4P 4d 30653 30652 30651 30650 4P 4d 31653 31652 31651 31650 4P 4d 32694
E22086

4P 3d+N/Z

push to trip

STR
90 %Ir 105 Im
4 5 6 8 2 1.5 10 xIr

22 DE
test

z 50/60H
Ir Im

Im Ir .85 .8 .7 .63
.8 .7 .63 1 .85 Ir

4
.9

5 6 8

alarm 3

.9

3 .95 .95 .98


1 .98 2

Ir Im

1.5

10 xIr

xIn

xIn

29661 29660 4P 3d+N/Z 30663 30662 30661 30660 4P 3d+N/Z 31663 31662 31661 31660 4P 3d+N/Z 32694

Vigicompact NS with normal trip unit


Compact NS100N Rating TM40D TM63D TM80D TM100D Compact NS160N Rating TM80D TM100D TM125D TM160D Compact NS250N Rating TM125D TM160D TM200D TM250D Compact NS400N STR23SE 4P 3d 29943 29942 29941 29940 4P 3d 30943 30942 30941 30940 4P 3d 31943 31942 31941 31940 4P 3d 32734 4P 4d 29953 29952 29951 29950 4P 4d 30953 30952 30951 30950 4P 4d 31953 31952 31951 31950 4P 4d 32734
E22087

4P 3d+N/Z

push to trip

29961 29960 4P 3d+N/Z 30963 30962 30961 30960 4P 3d+N/Z 31963 31962 31961 31960 4P 3d+N/Z 32734

Schneider Electric

550E5080.fm/163

Catalogue numbers

NS100/400 "tarif jaune" connection (cont.)

Interpact INV100 to INV630 standard version


Interpact INV100 Interpact INV160 Interpact INV200 Interpact INV250 For Compact NS100 For Compact NS160 For Compact NS250 For Compact NS250 4P 31161 31165 31163 31167
E51001

Interpact INV320 Interpact INV400

For Compact NS400 For Compact NS400

4P 31169 31171

E51002

Spare viewport
E51003

For INV100 to 250 For INV320/400

31089 31090

Combination with Compact NS devices


INV100 to 250 - NS250 combination assembly INV320/400 - NS250 combination assembly Front alignment base for INV320/400 - NS250 combination assembly INV320/400 - NS400 combination assembly 31066 31067 31064 31068
E51004

Flexible connection assembly, vertical INV100 to 250 to horizontal NS250 Flexible connection assembly, vertical INV320/400 to horizontal NS250 Flexible connection assembly, vertical INV100 to 250 to vertical NS250, side-by-side Flexible connection assembly, vertical INV320/400 to vertical NS400, side-by-side Flexible connection assembly, vertical INV320/400 to vertical NS250, side-by-side

31069 31092 31071 31072 31093

E51005

550E5080.fm/164

Schneider Electric

Catalogue numbers

NS100/400 "tarif jaune" connection (cont.)

Installation and connection with or without the visible break function


Conventional installation
Combination assembly Upstream and downstream connection INV100 to 250 4 snap-on bare cable NS100/160/250 connectors for cables:

1.5 to 95 mm2 ; y 160 A 10 to 185 mm2 ; y 250 A

INV320/400 - NS100/160/250

INV320/400 - NS400

10 clips for bare cable connector 4 right-angle terminal extensions 2 long terminal shields 4 bare cable connectors : For 1 cable, 35 mm2 to 300 mm2 For 2 cables, 35 mm2 to 240 mm2 4 right-angle terminal extensions 2 long terminal shields 4 snap-on bare cable 1.5 to 95 mm2 ; y 160 A connectors for cables: 10 to 185 mm2 ; y 250 A 10 clips for bare cable connector 4 right-angle terminal extensions 2 long terminal shields 4 bare cable connectors : For 1 cable, 35 mm2 to 300 mm2 For 2 cables, 35 mm2 to 240 mm2 4 right-angle terminal extensions 2 long terminal shields

2x 2x 1x 2x 1x 1x 1x 1x 1x 1x 1x 1x 1x 1x 2x 2x 2x 1x

29243 29260 29241 29262 29324 32480 32482 32485 32565 29243 29260 29241 29262 29324 32480 32482 32485 32565

Installation in cabinet or enclosure


Combination assembly (mounting in duct) Flexible connection assembly (mounting in cubicle) Upstream and downstream connection INV100 to 250 4 snap-on bare cable NS100/160/250 connectors for cables: INV320/400 - NS100/160/250 2 short terminal shields 4 bare cable connectors :

1.5 to 95 mm2 ; y 160 A 10 to 185 mm2 ; y 250 A For 1 cable, 35 mm2 to 300 mm2 For 2 cables, 35 mm2 to 240 mm2 1.5 to 95 mm2 ; y 160 A 10 to 185 mm2 ; y 250 A For 1 cable, 35 mm2 to 300 mm2 For 2 cables, 35 mm2 to 240 mm2

2x 2x 1x 1x 1x 1x 1x 1x 1x 2x 2x 1x

29243 29260 29322 32480 32482 32563 29243 29260 29322 32480 32482 32563

2 short terminal shields 4 snap-on bare cable connectors for cables: INV320/400 - NS400 2 short terminal shields 4 bare cable connectors :

2 short terminal shields

Schneider Electric

550E5080.fm/165

550E5080.fm/166

Schneider Electric

Catalogue numbers

NS630b to NS1600 fixed manually operated Complete device

Front-connected circuit breaker with Micrologic 2.0 control unit


Compact NS type N
Icu = 50 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 3P 33460 33466 33472 33478 33482 3P 33461 33467 33473 33479 33483 3P 33462 33468 33474 4P 33463 33469 33475 33480 33484 4P 33464 33470 33476 33481 33485 4P 33465 33471 33477
E59545

Compact NS type H
Icu = 70 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600

Compact NS type L
Icu = 150 kA at 220/415 V NS630b NS800 NS1000

Front-connected circuit breaker with Micrologic 5.0 control unit


Compact NS type N
Icu = 50 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 3P 33546 33552 33558 33564 33568 3P 33547 33553 33559 33565 33569 3P 33548 33554 33560 3P 33486 33487 33488 33489 33490 4P 33549 33555 33561 33566 33570 4P 33550 33556 33562 33567 33571 4P 33551 33557 33563 4P 33491 33492 33493 33494 33495
E59545

Compact NS type H
Icu = 70 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600

Compact NS type L
Icu = 150 kA at 220/415 V NS630b NS800 NS1000

Front-connected switch-disconnector
NS630b NS800 NS1000 NS1250 NS1600
E59546

Nota : select in addition the connection accessories, device accessories and auxiliaries, control-unit accessories and communications option, as required.

550E5100.fm/2

Schneider Electric

Catalogue numbers

NS630b to NS1600 fixed manually operated (cont.) Complete device (cont.)

Front-connected circuit breaker with Micrologic 2.0 A control unit


Compact NS type N
Icu = 50 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 3P 33223 33233 33243 33253 33263 3P 33228 33238 33248 33258 33268 3P 33497 33498 33499 4P 33227 33237 33247 33257 33267 4P 33229 33239 33249 33259 33269 4P 33500 33501 33502
E47313

Compact NS type H
Icu = 70 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600

Compact NS type L
Icu = 150 kA at 220/415 V NS630b NS800 NS1000

Front-connected circuit breaker with Micrologic 5.0 A control unit


Compact NS type N
Icu = 50 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 3P 33323 33333 33343 33353 33363 3P 33328 33338 33348 33358 33368 4P 33327 33337 33347 33357 33367 4P 33329 33339 33349 33359 33369
E47313

Compact NS type H
Icu = 70 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600

Compact NS type L
Icu = 150 kA at 220/415 V 3P 4P NS630b 33516 33519 NS800 33517 33520 NS1000 33518 33521 Nota : select in addition the connection accessories, device accessories and auxiliaries, control-unit accessories and communications option, as required.

Schneider Electric

550E5100.fm/3

Catalogue numbers

NS630b to NS1600 fixed manually operated (cont.) Device based on separate components
Compact NS type N
Icu = 50 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 3P 33220 33230 33240 33250 33260 3P 33221 33231 33241 33251 33261 3P 33222 33232 33242 Without ammeter Basic protection Selective protection Selective + earth-fault protection Selective + earth-leakage protection 2.0 5.0 6.0 7.0 33504 33511 4P 33224 33234 33244 33254 33264 4P 33225 33235 33245 33255 33265 4P 33226 33236 33246 With ammeter (option A) 33505 33512 33513 33514

Basic circuit breaker


E59547

Compact NS type H
Icu = 70 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600

Compact NS type L
Icu = 150 kA at 220/415 V NS630b NS800 NS1000

+ Micrologic control units

Basic switch-disconnector
Compact NS type NA
NS630b NS800 NS1000 NS1250 NS1600 3P 33420 33422 33424 33426 33428 4P 33421 33423 33425 33427 33429
E59548

Connections for circuit breakers and switch-disconnectors


Front connection
630/1000 A 1250 A 630/1000 A type L 1600 A Top Bottom Top Bottom Top Bottom 3P 33598 33599 33600 33601 33602 33603 3P 33604 33605 33606 33607 4P 33608 33609 33610 33611 33612 33613 4P 33614 33615 33616 33617
E59549

Rear connection
Vertical Horizontal Top Bottom Top Bottom

Note: to order a complete device, order: b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector b connections b accessories (for the device, the connection, the control unit) and communication option as required.

550E5100.fm/4

Schneider Electric

Catalogue numbers

NS630b to NS1600 fixed electrically operated Device based on separate components


Compact NS type N
Icu = 50 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 3P 33270 33280 33290 33300 33310 3P 33271 33281 33291 33301 33311 3P 33272 33282 33292 Without ammeter Basic protection Selective protection Selective + earth-fault protection Selective + earth-leakage protection 2.0 5.0 6.0 7.0 33504 33511 4P 33274 33284 33294 33304 33314 4P 33275 33285 33295 33305 33315 4P 33276 33286 33296 With ammeter (option A) 33505 33512 33513 33514

Basic circuit breaker


E59550

U?
I O
push push OFF ON

ed discharg

O OFF

Compact NS type H
Icu = 70 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 Note: the characteristics of the motor mechanism module for electrical operation are specified separately by selecting a part number from the table at the bottom of this page.

Compact NS type L
Icu = 150 kA at 220/415V NS630b NS800 NS1000

+ Micrologic control units

Basic switch-disconnector
Compact NS type NA
3P 4P NS630b 33440 33441 NS800 33442 33443 NS1000 33444 33445 NS1250 33446 33447 NS1600 33448 33449 Note: the characteristics of the motor mechanism module for electrical operation are specified separately by selecting a part number from the table at the bottom of this page.
E59551

U?
I O
push push OFF ON

ed discharg

O OFF

Connections for circuit breakers and switch-disconnectors


Front connection
630/1000 A 1250 A 630/1000 A type L 1600 A Top Bottom Top Bottom Top Bottom Top Bottom Top Bottom 3P 33598 33599 33600 33601 33602 33603 33604 33605 33606 33607 4P 33608 33609 33610 33611 33612 33613 33614 33615 33616 33617
E59549

Rear connection
Vertical Horizontal

Motor mechanism module


AC 50/60 Hz DC
Communicating 33697 33698 33699 33700 Standard Communicating Standard 48 V 33691 33698 24-30 V 33690 100-130 V 33687 33694 48-60 V 33691 220-240 V 33688 33695 100-130 V 33692 380-415 V 33689 33696 200-250 V 33693 Note: to order a complete device, order: b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector b connections b accessories (for the device, the connection, the control unit) and communication option as required. Schneider Electric

550E5100.fm/5

Catalogue numbers

NS630b to NS1600 manually operated withdrawable devices Device based on separate components
Compact NS type N
Icu = 50 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 3P 33320 33330 33340 33350 33360 3P 33321 33331 33341 33351 33361 3P 33322 33332 33342 Without ammeter Basic protection Selective protection Selective + earth-fault protection Selective + earth-leakage protection 2.0 5.0 6.0 7.0 33504 33511 4P 33324 33334 33344 33354 33364 4P 33325 33335 33345 33355 33365 4P 33326 33336 33346 With ammeter (option A) 33525 33532 33533 33534

Basic circuit breaker


E47311

Compact NS type H
Icu = 70 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600

Compact NS type L
Icu = 150 kA at 220/415 V NS630b NS800 NS1000

+ Micrologic control units

Basic switch-disconnector
Compact NS type NA
NS630b NS800 NS1000 NS1250 NS1600 3P 33430 33432 33434 33436 33438 4P 33431 33433 33435 33437 33439
E59685

Basic chassis and connections


Chassis
630/1250 A 1600 A 630/1000 A type L 3P 33722 33723 4P 33725 33726
E59652

+ connection
3P Front connection Top Bottom 33727 33728
E59584

4P 33733 33734

E59585

Rear connection Vertical Horizontal

Top Bottom Top Bottom

33729 33730 33731 33732

33735 33736 33737 33738

Note: to order a complete device, order: b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector b chassis and connections b accessories (for the device, the connection, the control unit) and communication option as required.

550E5100.fm/6

Schneider Electric

Catalogue numbers

NS630b to NS1600 electrically operated withdrawable devices Device based on separate components
Compact NS type N
Icu = 50 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600 3P 33370 33380 33390 33400 33410 3P 33371 33381 33391 33401 33411 3P 33372 33382 33392 Without ammeter Basic protection Selective protection Selective + earth-fault protection Selective + earth-leakage protection 2.0 5.0 6.0 7.0 33504 33511 4P 33374 33384 33394 33404 33414 4P 33375 33385 33395 33405 33415 4P 33376 33386 33396 With ammeter (option A) 33525 33532 33533 33534

Basic circuit breaker


E47312

U?
I O
push push OFF ON

d discharge

O OFF

Compact NS type H
Icu = 70 kA at 220/415 V NS630b NS800 NS1000 NS1250 NS1600

Note: the characteristics of the motor mechanism module for electrical operation are specified separately by selecting a part number from the table at the bottom of this page.

Compact NS type L
Icu = 150 kA at 220/415 V NS630b NS800 NS1000

+ Micrologic control units

Basic switch-disconnector
Compact NS type NA
3P 4P NS630b 33450 33451 NS800 33452 33453 NS1000 33454 33455 NS1250 33456 33457 NS1600 33458 33459 Note: the characteristics of the motor mechanism module for electrical operation are specified separately by selecting a part number from the table at the bottom of this page.
E59686

U?
I O
push push OFF ON

ed discharg

O OFF

Chassis and connections


Chassis
630/1250 A 1600 A 630/1000 A type L 3P 33722 33723 4P 33725 33726
E59652

+ connection
3P Front connection Top Bottom Rear connection Vertical Horizontal 33727 33728 Top Bottom Top Bottom 33729 33730 33731 33732
E59584

4P 33733 33734 33735 33736 33737 33738

E59585

Motor mechanism module


AC 50/60 Hz DC
Communicating 33837 33838 33839 33840 Standard Communicating Standard 48 V 33831 33838 24-30 V 33830 100-130 V 33827 33834 48-60 V 33831 220-240 V 33828 33835 100-130 V 33832 380-415 V 33829 33836 200-250 V 33833 Note: to order a complete device, order: b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector, b chassis and connections b accessories (for the device, the connection, the control unit) and communication option as required.

Schneider Electric

550E5100.fm/7

Catalogue numbers

Accessories for NS630b to NS1600 fixed devices

Connection accessories
Front connection Rear connection 33640 33641

Bare-cable connectors + 1 connector shield for 4 cables (240 mm2)


E59558

3P (3 parts) 4P (4 parts)

1 long connection shield


E59578

3P 4P

33628 33629

Vertical-connection adapters
E59559

3P (3 parts) 4P (4 parts)

33642 33643

Cable lug adapters


E59560

3P (3 parts) 4P (4 parts)

33644 33645

Interphase barriers
E79151

3P/4P top (3 parts) 33646 3P/4P bottom (3 parts) 33646

3P/4P top (3 parts) 33648 3P/4P bottom (3 parts) 33648

Arc chute screen


E74437

3P 4P

33596 33597

Brackets for mounting on a horizontal surface


3P/4P (2 parts) 33647

Spreaders
E598561

3P 4P

33622 33623

3P 4P

33622 33623

Cable lug kits


240 mm2
E47820

300 mm2

3P (6 lug kit) 4P (8 lug kit) 3P (6 lug kit) 4P (8 lug kit)

33013 33014 33015 33016

Electrical auxiliaries
Indication contacts
(1) 6 A - 240 V 29450 (1) Low level 29452 Up to 3 OF, 1 SD and 1 SDE can be connected (the SDE contact is standard for electrically operated devices).

OF, SD, SDE


E59574

Instantaneous voltage releases


MX
E59575

MN

Delay unit for MN R (non-adjustable)

Rr (adjustable)

12 V DC 24-30 V AC/DC 48-60 V AC/DC 100-130 V AC/DC 200-250 V AC/DC 240-277 V AC 380-480 V AC

33658 33659 33660 33661 33662 33663 33664

33668 33669 33670 33671 33673

33684 33685

33680 33681 33682 33683

Installation accessories
Escutcheon (small cut-out) for manually operated device with toggle
E59576

33717

Escutcheon for: - device with toggle (large cutout) - device with rotary handle - electrically operated device

33718

E59582

Blanking plate
33858
E59588

(1) See Compact NS.

550E5100.fm/8

Schneider Electric

Catalogue numbers

Accessories for NS630b to NS1600 withdrawable devices

Connection accessories
Vertical-connection adapters for front-connected chassis
E59559

3P (3 parts) 4P (4 parts)

33642 33643

Cable lug adapters for front-connected chassis


E59560

3P (3 parts) 4P (4 parts)

33644 33645

Interphase barriers for rear-connected chassis


3P/4P (3 parts)
E59579

33768

Spreaders for front-connected and rear-connected chassis


E598561

3P (3 parts) 4P (4 parts)

33622 33623

Cable lug kits


240 mm2
E47820

300 mm2

3P (6 lug kit) 4P (8 lug kit) 3P (6 lug kit) 4P (8 lug kit)

33013 33014 33015 33016

Chassis accessories
Auxiliary terminal shield (CB)
E59589

3P 4P

33763 33764

Safety shutters (VO)


E59649

3P 4P

33765 33766

Electrical auxiliaries
SD trip indication contact for manually operated devices
6 A - 240 V Low level 33800 33803 33799 33802 33801 33804

SDE fault indication contact for manually operated devices


6 A - 240 V Low level

OF ON/OFF indication contacts


6 A - 240 V Low level Up to 3 OF contacts per device
E59655

CE, CD, CT carriage switches


6 A - 240 V Low level Up to 3 CE, 1 CT, 2 CD per device
E59656

33170 33171

Instantaneous voltage releases


MX
E59657

MN

Delay unit for MN R (non-adjustable)

Rr (adjustable)

12 V DC 24-30 V AC/DC 48-60 V AC/DC 100-130 V AC/DC 200-250 V AC/DC 240-277 V AC 380-480 V AC

33809 33810 33811 33812 33813 33814 33815

33819 33820 33821 33822 33824

33684 33685

33680 33681 33682 33683 47071 47072 47900

Auxiliary terminals for chassis alone


3 wire terminal (30 parts) 6 wire terminal (10 parts) Jumpers (10 parts)

Schneider Electric

550E5100.fm/9

Catalogue numbers

Accessories for NS630b to NS1600 withdrawable devices (cont.)

Chassis locking
Keylocking in disconnected position
Profalux
E59650

Ronis

1 lock 1 lock + 1 lock with same key profile 2 locks (with different key profiles) 1 lock 1 lock + 1 lock with same key profile 2 locks (with different key profiles)

33773 33774 33775 33776 33777 33778 33779 33769 33770 33771 33772 33786 33787
(1)

Option for locking in connected, disconnected and test positions Keylock kit (without keylocks) Profalux Ronis Castell Kirk

Door interlock
E59651

Right side of chassis (VPECD) Left side of chassis (VPECG)

Racking interlock (VPOC)


33788
E59653

Mismatch protection (VDC)


33767
E59654

Installation accessories
Escutcheon
33857
E46668

Transparent cover for escutcheon


33859
E59587

Blanking plate
33858
E59588

(1) No charge.

550E5100.fm/10

Schneider Electric

Catalogue numbers

Accessories for NS630b to NS1600 fixed and withdrawable devices

Locking for manually operated devices


Removable toggle locking system
Locking by 3 padlocks
E59562

44936

Fixed toggle locking system


Locking by 3 padlocks
E68390

32631

Rotary handle for manually operated devices


Devices with direct rotary handles
Handle
E59563
I on
trippe d

reset

0 OFF

Conversion accessory Locking by keylocks

Black Red/yellow front CNOMO OFF position OFF and ON positions

Keylock kit (without keylocks)

33863 33864 33866 Ronis 33870 33872 33868 33890

Profalux 33869 33871 33868

Mechanical interlocking
For 2 devices with extended rotary handles
E70744

Devices with extended rotary handles


Handle
E59564
I on
d trippe

Black Red/yellow front Telescopic (for chassis-mounted devices)

33878 33879 33880

reset

0 OFF

ON

tripped

reset

OFF

Control accessories
2 advanced indication contacts (6 A - 240 V) Early break Early make 33882 33883
E59573

Locking and accessories for electrically operated devices


Pushbutton locking
By transparent cover + padlocks
E59577

33897

Locking in OFF position


By Profalux keylocks
E59580

By Ronis keylocks Keylock kit (without keylocks)

1 lock 1 lock + 1 lock with same key profile 1 lock 1 lock + 1 lock with same key profile For Profalux keylocks For Ronis keylocks For Kirk keylocks For Castell keylocks

33902 33904 33903 33905 33898 33899 47517 47518 33895

Operation counter CDM


E59581
9 0039

Schneider Electric

550E5100.fm/11

Catalogue numbers

Accessories for NS630b to NS1600 fixed and withdrawable devices

Communications options
For fixed devices
Modbus COM Eco Modbus COM module Digipact COM Manually operated 33702 33703 33705 Manually operated 33842 33714 33845 33852 33855 Electrically operated 33708 33709 33711 Electrically operated 33848 33713 33851 33852 33855
E59553

For moving part


Modbus COM Eco Modbus COM module Digipact COM

+ chassis
Modbus Digipact

Accessories for Micrologic control units


Long-time rating plug (enhanced accuracy by limiting the setting range)
alarm long time

tr
(s)

E59658

Ir

.8 .9 .7 .95 .6 .98 .5 1 .4 x In

2 1 .5

8 12 16 20 24
Ir @6

Standard Low setting High setting Without long-time protection

0.4 to 1 x Ir 0.4 to 0.8 x Ir 0.8 to 1 x Ir OFF

33542 33543 33544 33545

External sensors
External sensor for neutral + earth-fault protection (TCE) CT rating: 400/1600 A
E59659

33576

Rectangular sensor for earth-leakage protection 280 mm x 115 mm


E59660

33573

E59659

Source ground return (SGR) earth fault protection External sensor (SGR) MDGF summing module

33579 48891

External power supply module


24-30 V DC 48-60 V DC 125 V DC 110 V AC 220 V DC 380 V DC 54440 54441 54442 54443 54444 54445
E59661

Test equipment
Mini test kit
33594
E59921

Portable test kit


33595
E59554

Spare parts
Toggle extension
E23865

46996

550E5100.fm/12

Schneider Electric

Catalogue numbers

Accessories for NS630b to NS1600 fixed and withdrawable devices


(cont.)

Mechanical interlocking for source changeover


Interlocking using connecting rods for Compact electrically operated devices
Complete assembly with 2 adaptation fixtures + rods 2 Compact fixed devices 2 Compact withdrawable devices
FFO hsup

33910 33913

E72941

NO h sup

FFO

O
d e gr ahcs id

FFO hsup

NO h sup

FFO

O
d e gr ahcs id

Interlocking using cables for Compact electrically operated devices


Complete assembly with 2 adaptation fixtures + cables 2 Compact fixed devices 2 Compact withdrawable devices 1 Compact fixed + 1 Compact withdrawable device
FFO hsup

33911 33914 33915

E72942

NO h sup

FFO

O
d e gr ahcs id

FFO hsup

NO h sup

FFO

O
d e gr ahcs id

Schneider Electric

550E5100.fm/13

Catalogue numbers

NS1600b to NS3200 fixed, frontconnected, manually operated device

Circuit breaker
Compact NS type N
Icu = 85/70 kA to 220/415 V NS1600b NS2000 NS2500 NS3200
OFF OFF

3P 34000 34006 34012 34018 3P 34001 34007 34013 34019 Without ammeter

4P 34003 34009 34015 34021 4P 34004 34010 34016 34022 With ammeter (option A) 33505 33512 33513 33514

E59555

Compact NS type H
Icu = 125/85 kA to 220/415 V NS1600b NS2000 NS2500 NS3200

+ Micrologic control units

Basic protection Selective protection Selective + earth-fault protection Selective + earth-leakage protection

2.0 5.0 6.0 7.0

33504 33511

Switch-disconnector
Compact NS type NA
NS1600b NS2000 NS2500 NS3200
OFF OFF

3P 34024 34027 34030 34033

4P 34025 34028 34031 34034

E59556

Optional vertical connection adaptor


1600/2500 A Note: standard for 3200 A. 3P (3 parts) 4P (4 parts) 33975 33976

Electrical auxiliaries
Indication contacts
OF, SD, SDE
E59574

6 A - 240 V Low level Up to 3 OF, 1 SD and 1 SDE can be connected.

29450 29452

(1) (1)

Instantaneous voltage releases


MX
E59575

MN

Delay unit for MN R (non-adjustable)

Rr (adjustable)

12 V DC 24-30 V AC/DC 48-60 V AC/DC 100-130 V AC/DC 200-250 V AC/DC 240-277 V AC 380-480 V AC

33658 33659 33660 33661 33662 33663 33664

33668 33669 33670 33671 33673

33684 33685

33680 33681 33682 33683

Locking
Removable toggle locking system
Locking by 3 padlocks
E59562

33996

Fixed toggle locking system


Locking by 3 padlocks
E68390

32631

(1) See Compact NS.

550E5100.fm/14

Schneider Electric

Catalogue numbers

Accessories for NS1600b to NS3200

Communications option
Modbus COM
E59557

33986 Eco Modbus COM module 33988 Digipact COM


OFF OFF

33987

Accessories for Micrologic control units


Long-time rating plug (enhanced accuracy by limiting the setting range)
alarm long time (s) 4

tr

Ir

E59658

.8 .9 .7 .95 .6 .98 .5 1 .4 x In

2 1 .5

8 12 16 20 24
Ir @6

Standard Low setting High setting Without long-time protection

0.4 to 1 x Ir 0.4 to 0.8 x Ir 0.8 to 1 x Ir OFF

33542 33543 33544 33545

External sensors
External sensor for neutral + earth-fault protection (TCE) CT rating: 1000/4000 A
E59659

34036

Rectangular sensor for earth-leakage protection 470 mm x 160 mm


E59660

33574

E59659

Source ground return (SGR) earth fault protection External sensor (SGR) MDGF summing module

33579 48891

External power supply module


24-30 V DC 48-60 V DC 125 V DC 110 V AC 220 V DC 380 V DC 54440 54441 54442 54443 54444 54445
E59661

Test equipment
Mini test kit
33594
E59921

Portable test kit


33595
E59554

Spare parts
NS3200 toggle extension for replacement 33997

Installation accessories
Escutcheon
33929
E88640

Interphase barriers (3 parts)


33998
E88639

Schneider Electric

550E5100.fm/15

Catalogue numbers

Communication bus accessories and display modules

Display modules
DMB300
Monochrome display module
E67954

Max. 4 breakers

50894

DMC300
Color display module
E67955

Max. 16 breakers

50895

Spare parts
DMC300PCM: DMC300 memory card 50959

RS 485 Modbus pre-wired system


RS 485 Modbus junction block
CJB306: 6 SubD 9 pins connectors junction block
E67958

50963

RS 485 Modbus connector


CSD309: 9 pins SubD with screw terminals
E67959

50964

RS 485 Modbus cables


CDM303: display module pre-wired cable, 3 m length
E67960

50960

E79015

CCP303: Masterpact or Compact pre-wired cable (4 RS 485 wires + 2 power wires) 3 m length 50961 CCS303: Masterpact or Compact pre-wired cable (Modbus slave) 3 m length 50962

CCR301: RS485 roll cable (2 RS 485 wires + 2 power wires) 60 m length


E67961

50965

Digipact Bus pre-wired system


Data concentrator DC150
Auxiliary supply voltage
E79014

110-240 V AC, 50/60 Hz and 115-125 V DC

50823

Junction block
Junction block for internal Bus
E67956

50778

Cables
Cable for internal bus
E67957

20-meter roll (0.75 mm2) 100-meter roll (0.75 mm2)

50779 50780

Converter
RS 485/RS 232 (ACE909) 12 V DC power supply included RS 485/RS 232 RS 485/Ethernet RS 485/Ethernet (SMS compatible) RS 485/Ethernet (Micrologic Transparent Ready available 2003) (1) See catalogue Telemecanique. (2) See catalogue PowerLogic System. 59648 TSX SCA72 174 CEV 300-10 EGX 200/400 33507
(1) (1) (2)

550E5100.fm/16

Schneider Electric

Schneider Electric Industries SAS


89 boulevard Franklin Roosevelt F - 92500 Rueil Malmaison (France) Tel : +33 (0)1 41 29 85 00 http://www.schneider-electric.com As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

This document has been printed on ecological paper.


Design: Schneider Electric - Ameg. Photos: Schneider Electric. Printed:

BTP550E

mm-aaaa

ABTED000000EN 2002 - Schneider Electric - All right reserved