Basics of Low Voltage System & Circuit Breakers Typical Transformer specifications Rating Primary Voltage Secondary Voltage %ge Impedance Vector Group 1000 11 440 5 DYn11 kVA kV Volts %
1000 440 16
kVA Volts %
A&D / BD-CD
June 04
So the fault level at T/F terminals works out to be 27.8 kA Similarly the fault level at the generator terminal works out to be 8.7 kA
Folienthema/Folie 3/Jahreszahl
A&D / BD-CD
June 04
A&D / BD-CD
June 04
A&D / BD-CD
June 04
A&D / BD-CD
June 04
5. ICC Rated short time withstand capacity for non automatic breakers (expressed as rms value)
Folienthema/Folie 7/Jahreszahl
Test sequence
ICU = O t CO ICS = O t CO t - CO
(t = 3 min) (t = 3 min)
A&D / BD-CD
June 04
Types of breakers
1. Medium of arc quenching - Oil - Air, - Vacuum 2. Principle of operation - Current zero type of breakers - Current limiting breakers
Folienthema/Folie 8/Jahreszahl
A&D / BD-CD
June 04
4 ms
10 ms t
A&D / BD-CD
June 04
A&D / BD-CD
June 04
What is Cascading ? Cascading refers to the technique of series connection of protective devices,which results in enhanced breaking capacity.
A&D / BD-CD
June 04
Folienthema/Folie 11/Jahreszahl
What is Cascading ?
Isc = 40 kA
Folienthema/Folie 12/Jahreszahl
VL160X, 100A, 40 kA
Cascading Chart
VF100 VL160x VL160x VL160 VL250 VL250 VL400 VL400 VL630 VL800
18 kA 40 kA 70 kA 40 kA 70 kA 40 kA 70 kA 40 kA 70 kA 40 kA 70 kA 45 kA 70 kA 45 kA 70 kA 45 kA 70 kA 50 kA 70 kA
100A 100A 100A 160A 160A 160A 160A 200A 200A 250A 250A 315A 315A 400A 400A 630A 630A 800A 800A 40 kA 50 kA 40 kA 50 kA 45 kA 50 kA 45 kA 50 kA 45 kA 50 kA 50 kA 50 kA 40 kA 70 kA 70 kA 45 kA 70 kA 45 kA 70 kA 50 kA 70 kA 45 kA 70 kA 45 kA 70 kA 50 kA 70 kA 45 kA 70 kA 45 kA 70 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA
Folienthema/Folie 13/Jahreszahl
45 kA
A&D / BD-CD
June 04
What is Discrimination ?
Discrimination implies that the protective devices closest to the point of fault will operate in the quickest possible manner to avoid any wide spread shut down.
A&D / BD-CD
June 04
Folienthema/Folie 14/Jahreszahl
What is Discrimination ?
Isc = 40 kA
Folienthema/Folie 15/Jahreszahl
VL160X, 100A, 40 kA
Types of Discrimination
1. Current based 2. Time based 3. Energy based 4. Logic based (ZSI)
Folienthema/Folie 16/Jahreszahl
A&D / BD-CD
June 04
Discrimination Chart
Br.Cap. (Icu) 5SX4 10 kA Release Ratings TM upto 20A 3.8 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 5SX4 10 kA TM 25 / 32A 3.0 kA 9.1 kA 9.1 kA 9.1 kA 9.1 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 5SX4 10 kA TM 40 - 63A 2.1 kA 4.8 kA 4.8 kA 4.8 kA 4.8 kA 6.5 kA 6.5 kA 6.5 kA 6.5 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
Downstream MCB / MCCB frame VF100 18 kA TM 100A VL160x 40 kA TM 100A VL160x 40 kA TM 160A VL250 40 kA VL250 40 kA
18 kA 40 kA 70 kA 40 kA 70 kA 40 kA 70 kA 40 kA 70 kA 45 kA 70 kA 45 kA 70 kA 45 kA 70 kA 50 kA 70 kA
100A 100A 100A 160A 160A 200A 200A 250A 250A 315A 315A 400A 400A 630A 630A 800A 800A
12 kA 12 kA 18 kA 18 kA 18 kA 18 kA 18 kA 18 kA 18 kA 18 kA 18 kA 18 kA 18 kA 18 kA 25 kA 25 kA 25 kA 25 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 25 kA 25 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 32 kA 32 kA 32 kA 32 kA 40 kA 40 kA 40 kA 40 kA 26 kA 26 kA 26 kA 40 kA 40 kA 40 kA 40 kA
Folienthema/Folie 17/Jahreszahl
26 kA
A&D / BD-CD
June 04