intertripping Function
Intertripping is designed to transfer protection commands originating, in most cases, from distance protection relay contacts to ONE remote location through a communication medium. Communication between the intertripping equipment is a bidirectional point-to-point communication
Poste lectrique A Ligne HT
Poste lectrique B
Protection relay
Protection relay
intertripping Function
Functioning in voice frequency mode on Power line carrier
Line Trap H.V. TRANSPORT NETWORK
Services Services
intertripping Criteria
Reliability/Dependability : Since the communication can be altered by noise due to the high voltage environment, the intertripping signal shall be transmitted in a way to minimize the risk of losing a command that would lead to the non functioning of the fault clearance process. This value is expressed as the Probability of Missing command Pmc.
intertripping Criteria
All intertripping equipment shall meet as a minimum, the security, dependability and transfer time criteria defined by an IEC standard IEC 60834-1
DIP5000 Requirements
Faster transfer time Increase reliability and security Increase monitoring capabilities Increase the number of commands
10
10
Faster transfer time : The fault clearance process is reduced saving expensive HV equipment.
Protection Mode Tra nsfer Time With E1 Interfa ce 4 or 8 comma nds 1 ms 1 ms 1.5 ms Relia bility (Pmc) Security (Puc) Worst ca se
- Increase the safety of your electrical network 11 > Titre de la prsentation - Date - Rfrences 11
- Increase the safety of your electrical newtork 12 > Titre de la prsentation - Date - Rfrences 12
13
13
Possibility to select alarms in case of too high transmission time or high BER or Programmable alarms contacts on lengthy command 512 events 1 ms stamping allowing fault analysis and tracking
- Increase the safety of your electrical network 14 > Titre de la prsentation - Date - Rfrences 14
Configuration on line, off line, downloaded on site to the local and remote DIP5000 with PC ( digital interface only )
Medium Range Laser 1310 nm e.g 60 km with fiber 9/25m - 0.25 dB/km Long range Laser 1550 nm e.g 110 km with fiber 9/25m - 0.25 dB/km
Electrical interfacesj
V11/RS422 G703.1 (64 Kbit/s) G703.6 (E1 2 Mbit/s) Analogue interface for pilot wires or communication
with Power line carrier
Voice frequency interface for communication on pilot wires or leased line or communication with Power line carrier (PLC ) ( 4 wires interface ) . Up to 4 independant commands No requirement for extra bandwitdh when used with PLC ( silent mode )
17
17
You can use electrical converter OCM 5000 optical to electrical converter to fit with your substation constraints
50km
50km
50km
DIP5000
OCM5000 V11 Or V24
Up to 8 Commands DIP5000
Up to 4 Commands
Analogue 4 wires
Customer is able to qualify its link with 1. Test mode with trip transfer 2. loop back function
You can easily modify your interfaces or upgrade from copper to optical interface
DIP5000 Architecture
Technical data
22
22
Input / Output logic combination capacity Firmware Up gradable on site by simple download 24 to 250 VDC power supply with power supply duplication as an option Up to 8 independent fast solid state relay output + 1 copy contact for each output : Rating Max 2A, cut off power 120 W
Equipment is CE compliant.
DIP5000 Architecture
New features
25
25
to connect the AREVA TMS 5000 monitoring software to monitor a DIP 5000 network alarm status on a real time basis
Intranet network
Alternate
path V11 or G703
Main path
27
27
DIP5000 References
References
28
28
MORE THAN 1500 UNITS IN OPERATION SINCE Year 2000 IN OPERATION IN MORE THAN 15 COUNTRIES FOR UP TO 500 KV NO RECORD OF FALSE OR UNWANTED COMMAND DUE TO THE EQUIPMENT
- A RELIABLE PRODUCT IN USE IN MORE THAN 15 COUNTRIES 29 > Titre de la prsentation - Date - Rfrences 29
DIP5000 Conclusion
Conclusion
30
30
Conclusion
DIP 5000 is the best way to
Increase the safety of the electrical network
Fastest transfer time Highest level of reliability and security Enhanced monitoring capabilities Built in optical interface Up to 8 independent commands TESTED as per latest IEC and ANSI EMC requirement
Intuitive commissioning Powerful HMI Plug in board for easy hardware upgrade
- The Reference in terms of intertripping equipment 31 > Titre de la prsentation - Date - Rfrences 31