Setting of Protection
Setting of Protection
Phase Overcurrent Protections
Selectivity
Time
Fault current
Setting of Protection
Phase Overcurrent Protections
reset
Setting of Protection
Overcurrent relays
Current selectivity
Time selectivity
Setting of Protection
Short circuit protection
Current setting shall be
Setting of Protection
Instantaneous stage for transformer
Setting shall be
Should not reach > 80% of transformer Complement to diff relay and buchholz
protection
Setting of Protection
Directional short circuit protection
Directional current relay shall have 60 degrees
angle lagging
Setting of Protection
Margin to equipment capacity
Setting of Protection
Earth fault relays in solidly earthed systems
Setting of Protection
Time setting of inverse type relays
Margin 100-150 ms for short circuit protection 150-200 ms for earth fault relays
Setting of Protection
Network for selectivity plan
Setting of Protection
Information required for selectivity plan
ABB Group - 13 25-Apr-14
System diagram
Maximum short circuit currents Minimum short circuit currents Maximum service currents Inrush currents for transformers, motors Relay characteristics Breaker characteristics
Setting of Protection
Setting of Protection
Phase and Ground over current protections
The phase over current protection offers both circuit local back-up protection and remote back-up protection for multi phase faults. They also offer protection for many faults involving ground if fault current is high enough to allow relay operation.
To cater to low current ground faults as a result of high ground fault resistance the ground over current protections are applied. They might also be applied, as main protection for high resistance faults where main protection does not offer required coverage.
Setting of Protection
Phase over current protections
Settings
The protection must not operate for highest load current during both normal and abnormal power system operation. The protection must operate for multiphase faults on the entire circuit under minimum plant conditions i.e. lowest fault current. The protection should not operate before the main protection of the protected circuit The protection must not operate before the circuit local backup protection clears a fault in an adjacent circuit.
Setting of Protection
Ground over current protections
Settings
The ground over current threshold should be set to ensure detection of all ground faults, but above any continuous residual current under normal system operation. Continuous residual current may arise because of
Unbalanced series impedances of un transposed transmission circuits Unbalanced shunt capacitance of transmission circuits Third harmonic current circulation.
Setting of Protection
Directional Over current relays-radial feeders
Setting of Protection
Directional over current relays