You are on page 1of 114

Detailed Energy Audit at

Confederation of Indian Industry


Shree Mega Power,
CII Godrej Green Business Centre, Hyderabad,
India
Beawar

At the outset
Thank you for

Opportunity
Support

Confederation of Indian Industry

Objective
SMP

Achieve Maximum Energy


Saving
Improve on a continuous
basis to achieve status of a
world class power plant

Confederation of Indian Industry

Methodolog
y
Data

Collection
Measurements
Discussion
And Now
Presentation
Confederation of Indian Industry

Past Energy Conservation


activities

Extensive use of VFD

Excellent monitoring system

Installation of lighting transformer

Individual isolation valve for


compressor cooling water

And many more


Committed Team
Confederation of Indian Industry

ROLE OF CII

Catalyst / Facilitator role

Supplement in-house activities

Identify energy saving proposals

All possible assistance

Monitoring

Vendor identification

Not fault finders !!


Confederation of Indian Industry

Operation of ACW pump


Design
Flow
- 2200 m3/hr
Pressure - 50 m
Rated power - 342 kW

Cooling tower

Equipment
cooling
Actual
Flow
- 1490 m3/hr
Pressure - 32 m
Power
- 220 kW
Confederation of Indian Industry

Operation of ACW pump

ACW pump installed to cater cooling


water needs of plants equipment

Three pumps installed for pumping water


to users from cooling tower

One in operation

VFD installed in one pump ( In Operation)

Water flow measurements, pressure


measurements and Temperature
measurements taken to assess efficiency
of the pumping system
Confederation of Indian Industry

Operation of ACW pump

Pump design:

Q : 2200 m3/hr

H : 50 m

kW : 342 kW

Actual:

Q : 1490 m3/hr

H : 32 m

kW : 220 kW

Confederation of Indian Industry

Operation of ACW pump

Pump being operated in lower speed

Changes happened in cooling water circuit

Pump efficiency:

63%

Pump operating in a low efficiency range

Bed ash cooler not in full operation

Operated at a lower range

Good potential to save energy by installing


a new pump for actual requirement
Confederation of Indian Industry

Operation of ACW pump

Recommendation:

Install a new pump for actual


requirement
Q : 1200 m3/hr, H : 35m, kW : 146 kW

VFD used in the earlier pump can be


used
About 70 kW can be saved
Annual Saving -

Rs 16.80 Lakhs

Investment

Rs 8.00

Lakhs
Payback

5 months

Confederation of Indian Industry

Install new correct size pump


for side filter water pumping

Water is constantly pumped to the side filter

About 150 m3/hr of water is being pumped

This water is tapped from the ACW pump


outlet

Pumped to sided filter at 3.2 bar

ACW flow : 1490 m3/hr

About 10% is being pumped to the side filter

Potential to save energy by installing a


correct head pump for side filter

Confederation of Indian Industry

Install new pump for side filter


water pumping

By installing a new pump, 10% of


flow of the ACW pump can be
avoided

VFD speed can be reduced

Recommendation:

Install separate pump for side filter


150

m3/hr, 15 m, 9.5 kW

Reduce 10% of flow in ACW pump


Reduce

speed of VFD

About 10 kW can be saved


Confederation of Indian Industry

Install new pump for side filter


water pumping

Annual Saving -

Rs 2.40 Lakhs

Investment

Rs 0.50

Lakhs
Payback

2 months

Confederation of Indian Industry

Operation of chillers (TG


chillers)
14.00C

8.00C

Chiller 3
Return
Water from
AHU

Chiller 2

11.80C

Supply to
AHU

Chiller 1

12.30C
130C

Chilled water pumps

Confederation of Indian Industry

Operation of chillers

3 chillers installed for catering air


conditioning load of TG building

Flow measurements taken:

All three in operation


Flow through chillers : 160 m3/hr

Return water from AHU is pumped to the


chillers

AHU return water temp0 : 150C


Chilled water temp0 from chiller 3 : 8.00C
Chilled water temp0 from chiller 2 : 11.80C
Chilled water temp0 from chiller 1 : 13.00C
Chilled water temp0 to AHU (after mixing) :
12.30C
Confederation of Indian Industry

Operation of chillers

Due to mixing of water temperature of


chilled water increases from 8.0 to 12.3 0C
Almost 40C is lost because of mixing of
water from

For every 10C temperature change, chiller


power consumption changes by 4%

In chiller 3, two compressors are in


operation
In chiller 1&2, only one compressor in
operation
Certain times compressors are loaded
only for 40 60%
Confederation of Indian Industry

Operation of chillers

Good potential to save energy by avoiding


this chilled water mixing

Operate only two chillers and have one in


stand by

Additional savings since pumping of water


to 3rd chiller will be avoided

Improved temperature conditions in user


space

Better user comfort


Confederation of Indian Industry

Operation of chillers

Recommendation:

Avoid temperature loss due to mixing


of chilled water
Operate only two chillers with same
set points

21 kW can be saved

Annual Saving -

Rs 5.00 Lakhs

Confederation of Indian Industry

Increase set point of the


chillers
Chiller set point set at a very low

temperature

Lower the chiller temperature, chiller


consumes more energy to achieve the
temperature
Supply & return air temperature in the AHU
also studied

70C

Supply air temperature : 13 140C


Return air temperature : 19 240C

Chiller set point can be increased and can be


operated without affecting the user comfort
Confederation of Indian Industry

Increase set point of the


chillers

Recommendation:

Increase the set point of the chiller


9

- 100C

Temperature setting of the chiller


according to the ambient condition
A

simple automation system can be put in


place

12 kW can be saved
Annual Saving -

Rs 2.88 Lakhs

Confederation of Indian Industry

Convert 3 way valve to 2


way valve and install VFD for
3 way valves installed at the chilled
chilled
water
pumps
water lines to the VFD

Not in operation (not fully commissioned)

Installed to control the temperature of


the user space

Disadvantage of 3 way valve

Recirculates back to return line through


bypass

Recirculation is wastage of pump power


consumption
Confederation of Indian Industry

Convert 3 way valve to 2


way valve and install VFD for
Presently there is not temperature
chilled water pumps

control as such

Supply air temperature : 13 14 0C

Return air temperature : 19 24 0C

Room temperature maintained at a lower


side

Good potential to save energy by


maintaining correct temperature at the
user space
Confederation of Indian Industry

Convert 3 way valve to 2


way valve and install VFD for
Recommendation:
chilled
water
pumps

Replace or dummy the third port (bypass


port) of all three port valves
Recirculation

reduces, back pressure increases

Install VFD for each pump

Operate the VFD in closed loop based on


Pump

discharge pressure

Operate based on the temperature setting

Confederation of Indian Industry

Convert 3 way valve to 2 way


valve and install VFD for chilled
water pumps
Annual Saving -

Rs 1.68 Lakhs

Investment

Rs 2.50

Lakhs
Payback

18 months

Confederation of Indian Industry

Install VFD for the AHUs

Presently, no temperature control


available for the user space
Latest trend installing VFD for the air
handling units with feed back control
Feed back return air temperature
Maintain the temperature at 23 24oC
Advantages

Precise maintenance of temperature


Reduction in AHU power consumption
Reduction in chiller load
Confederation of Indian Industry

Install VFD for the AHUs

Recommendation:

Install VFD for all AHUs


Return air temperature can be given
as feed back
Annual Saving -

Rs 2.40 Lakhs

Investment

Rs 4.00

Lakhs
Payback

20 months

Confederation of Indian Industry

Install new pumps for


DMCC pumps

Four DMCC pumps installed for bed


ash coolers

Two for each unit


One

in operation in each unit

Flow & head measured to ascertain


the efficiency of the pumps
Unit 2
Unit 1
Flow
Flow
- 335
3
m
/hr
3
m /hr
Pressure
Pressure - 35 m
Power
Power
kW
63 kW
Efficiency
Confederation of Indian Industry
Efficiency - 59%

325
- 35 m
- 60
- 60%

Install new pumps for


DMCC pumps

Good potential to save energy by


installing new pumps of correct size
& efficiency for the application
Recommendation:

Install new pumps for DMCC pumps


Q : 250 m3/hr, H : 35m, kW : 38 kW

47 kW can be saved
Annual Saving -

Rs 11.28 Lakhs

Investment

Rs 3.50

Lakhs
Payback

4 months

Confederation of Indian Industry

Arrest Leakages in Flue


Combustion analysis has been carried out at
Gas Path

various location along the flue gas path

Before APH

After APH

After ESP

Parameters measured

Excess O2, CO, CO2 & Temperature

Measurements repeated on two different days

16 February 2012

20 February 2012
Confederation of Indian Industry

Arrest Leakages in Flue


Gas
Path
Flue gas
analysis carried out on February
16, 2012 at various locations as shown
below:
Boiler 1

APH Inlet

APH
Outlet

ESP
Outlet

Side

Left

Righ
t

Left

Righ
t

Left

Righ
t

O2, %

4.92

5.28

4.84

6.04

5.39

5.26

CO, ppm

29

22

24

27

24

29

CO2, %

14.0
9

13.9
1

14.1
5

13.1
3

13.6
7

1440

Temp,
Deg-C

277

290

138

134

135.
6

130

Confederation
IndianIndustry
Industry
Confederation
ofofIndian

Arrest Leakages in Flue


Gas
Path
Flue gas
analysis carried out on February
20, 2012 at various locations as shown
below:
Boiler 1

APH Inlet

APH
Outlet

ESP
Outlet

Side

Left

Righ
t

Left

Righ
t

Left

Righ
t

O2, %

3.84

2.47

4.77

4.68

4.82

5.04

CO, ppm

34

21

26

23

27

27

CO2, %

15.0
1

16.2
3

14.2

14.3
1

14.1
8

13.9
8

Temp,
Deg-C

286.
8

261

150

131.
8

142.
4

129.
8

Confederation
IndianIndustry
Industry
Confederation
ofofIndian

Arrest Leakages in Flue


Gas
Path
Flue gas
analysis carried out on June 27,
2012 at various locations as shown below:
Boiler 2

APH Inlet

APH
Outlet

ESP
Outlet

Side

Fron
t

Rear

Left

Righ
t

Left

Righ
t

O2, %

4.5

4.2

3.8

3.1

4.2

3.8

CO, ppm

48

29

29

37

41

37

CO2, %

14.3

14.8

15.1

15.7

14.7

15

Temp,
Deg-C

266

270

158

143

143

137

Confederation
IndianIndustry
Industry
Confederation
ofofIndian

Arrest Leakages in Flue


Gas
Path
Air leakages
estimated in Unit 1

There is an increase in O2 level on right hand side of


the APH

Significant decrease in flue gas temperature

Clear indication of air leakage into the system

Effect of air leakage

Reduction in heat recovery and hence reduction in


opening efficiency of boiler

Increase in ID fan power consumption

Confederation of Indian Industry

Arrest Leakages in Flue


Gas Path
By arresting the air leakages

Reduction in power consumption of


each of the ID fan by 5.5 kW

Equivalent reduction in petcoke


consumption
210 Tonne/annum

Confederation of Indian Industry

Arrest Leakages in Flue


Gas Path

Annual Savings
Lakhs
Investment
Lakhs
Payback period

Rs. 19.00

Rs. 12.00

8 months

Confederation of Indian Industry


Confederation of Indian Industry

Boiler feed pump


154 kg/cm2

5.69 kg/cm2

ECO
263.1 Tph
3(2 )

523 TPH

170.3 kg/cm2
HP 2

HP 1

259.1 Tph

7.52 MW for four pumps

Control Station
Pr diff 7 kg/cm2

Confederation of Indian Industry

Multistage stage pressure


reduction drag valve

Confederation of Indian Industry


Confederation of Indian Industry

Boiler Feed Pump


Further reduce the pressure drop across the control

station

Limitation stable operation of the plant

Best pressure drop maintained 4 kg/cm2

% Reduction in pressure drop 1.5 %

Corresponding reduction in Power Consumption in the pump

During the study tried to measure the leakage


through the recirculation valve

Unable to measure

Temperature measurement clear indication of


recirculation

Confederation of Indian Industry

Boiler Feed Pump

Approximate estimation about 3-5% of flow


Install multi stage pressure reduction drag
valve

Pressure reduction happens in multiple stages

More than 8-12 stages

Highly reliable

Minimize the leakage as low as possible

Typical
reduction
3%
Annual
Savingsin power consumption
Rs. 54.00

Lakhs
Investment
Lakhs

Confederation of Indian Industry

Rs. 60.00

Fan Performance

PA fan
Description

PA fan
-2A

PA fan
-2B

PA fan
-1A

PA fan
-1B

Flow (m3/sec)

34.90

34.76

35.49

32.98

Head mmWC

1157

586.7

1121

1206

Power
Consumption in
kW

565.5

586.7

586

597.5

Efficiency %

82.35

74.67

70.06

68.7

Confederation of Indian Industry

Fan Performance

SA fan
Description

SA fan
-1A

SA fan
-1B

SA fan
-2A

SA fan
-2B

Flow (m3/sec)

34.58

44.70

37.16

36.85

Head mmWC

639

660

583

575

Power
Consumption in
kW

303

448.5

363.9

356.8

75.27

67.88

64.85

64.86

Efficiency %

Confederation of Indian Industry

Performance SA fan

Observations

Suction side pressure

SA fan -1 A

- 60 mmWC

SA fan -1 B

- 95 mmWC

Sa fan -2 A

-68 mmWC

SA fan -2B

-66 mmWC

Suction side pressure drop is higher

It will result in corresponding increase in fan


power consumption

Confederation of Indian Industry

Performance SA fan

Recommendations

Install correct size of duct for SA fan


Flow requirement is same for SA and PA fan
35 m3/hr
Duct size at suction - different for SA and PA
fan

For PA fan (3.34 0.832) = 2.78 m2


For SA fan (2.53 0.7)
= 1.77 m 2

Reduce the suction side pressure drop for


all the fans
Maintain pressure drop up to -20 mmWC at
suction side
Annual
Savings
Rs. 30.00
Total saving of 125 kW

Lakhs
Investment

Confederation of Indian Industry

???

Fan Performance

ID fan
Description

ID fan
-1A

ID fan
-1B

ID fan 2A

ID fan
-2B

116.67

118.81

109.44

105.12

298

311

259

260

Power Consumption in
kW

536.8

528.2

401.3

342.3

Efficiency %

66.81

72.19

76.94

86.98

Flow (m3/sec)
Pressure mmWC

Confederation of Indian Industry

ID Fan performance

-220 mmWC

35mmWC

40 mmWC

ID 2A
401. 3 kW
= 76.94%

Confederation of Indian Industry

40 mmWC

Optimize the performance of


Secondary Dust Extraction
fan
-420 mmWC June 30, 2012
-92 mmWC June 30, 2012

Bag Filter

-510 mmWC +5 mmWC

-370 mmWC
119.49 kW
= 89%
P = 328 mmWC

Confederation of Indian Industry

Optimize the performance of


Secondary Dust Extraction fan

Pressure loss across the damper is


140 mmWC
P across the bag filter: 328 mmWC
Purging cycle is timer based.
Recommendation

Open the damper 100%


Install the VFD for the fan
Control the flow with VFD
Feedback

signal from P across bag filter

Confederation of Indian Industry

Optimize the performance of


Secondary Dust Extraction fan

Recommendations

Operate the purging cycle based


on P across bag filter
Maintain the P across bag filter
90-120 mmWC

Power savings of 75 kW
Annual Savings
Lakhs
Investment
Lakhs
Confederation of Indian Industry
Payback period
-

Rs. 6.75
Rs. 10.00
18

Avoid the Damper loss in Lime


Mill Blower

Pressure loss
across the damper
is 140 mmWC
Recommendation

-319 mmWC

-470 mmWC 254 mmWC

121.22 kW
= 94%

Open the damper


100%
Install the VFD for
the fan
Control the flow
with VFD

Confederation of Indian Industry

Avoid the Damper loss in Lime


Mill Blower

Power savings of 24 kW
Annual Savings
Lakhs
Investment
Lakhs
Payback period
months

Rs. 2.16

Rs. 8.00

45

Confederation of Indian Industry

Avoid leakage in Service


Air System

Total 2 Compressors Screw


Compressor

Users

1 in service and other in standby


Flyash loading into the bunker
Lime loading into the bunker

Methodology

Kept one compressor running and


stopped all the users

Confederation of Indian Industry

Avoid leakage in Service


Air System

Observation

51.16 % - Loading
48.84 % - Unloading

Operating Hours 6000


Kept a margin of 5 % leakage
Clear indication of huge leakage

Confederation of Indian Industry

Avoid leakage in Service


Air System

Recommendation

Arrest all the leakages


Install drain valve which operates on
condensate level and not on timer
based.
Currently

drain is kept crack open

Annual Saving -

Rs 17.00 Lakhs

Confederation of Indian Industry

Avoid leakage in Conveying


Air System

Total 4 Compressors Screw


Compressor

Users

2 in service and others in standby


Flyash conveying from ESP, APH to
silo

Methodology

Kept one compressor running and


stopped all the users

Confederation of Indian Industry

Avoid leakage in Conveying


Air System

Observation

11.11 % - Loading
88.89 % - Unloading

Operating Hours 8000


Kept a margin of 5 % leakage
Clear indication of huge leakage

Annual Saving -

Rs 1.44 Lakhs

Confederation of Indian Industry

Avoid leakage in Lime Conveying


Air System

Total 4 Compressors - Reciprocating

Users

2 in service and others in standby


Flyash conveying from ESP, APH to
silo

Methodology

Kept one compressor running and


stopped all the users

Confederation of Indian Industry

Avoid leakage in Lime Conveying


Air System

Observation

12.50 % - Loading
87.50 % - Unloading

Operating Hours - 4000


Kept a margin of 5 % leakage
Clear indication of huge leakage
Annual Saving -

Rs 1.48 Lakhs

Confederation of Indian Industry

Optimize Instrument Air Operating


Pressure

Total 3 Screw Compressor

Operating Range

1 in Service & 2 in standby


VFD installed manual mode
5.8 6.5 kg/ cm2
Average 6.15 kg/ cm2

Users

All pneumatic instruments


Maximum pressure required by the
user is 4.5 kg/cm2
Dome valve operation 5 kg/ cm2
Confederation of Indian Industry

Optimize Instrument Air Operating


Pressure

Recommendation

Take VFD into auto mode and set the


pressure to 5.2 kg/cm2.
Presently Compressor is
Loading

- 96 %
Unloading - 4 %

New average operating pressure will


be 5.2 kg/ cm2
Unloading can be avoided

Confederation of Indian Industry

Optimize Instrument Air Operating


Pressure

Savings

By avoiding unloading
By reducing pressure
kW

Annual Saving -

- 1.74 kW
- 31.89

Rs 8.00 Lakhs

Confederation of Indian Industry

Optimize Service Air Operating


Pressure

Total 3 Screw Compressor

Operating Range

1 in Service & 1 in standby


VFD installed manual mode
6.5 - 7.5 kg/ cm2
Average 7 kg/ cm2

Operating hours
Users

- 4000 hrs

Lime feeding into bunker


Flyash feeding into bunker
These user need only 2 kg/ cm 2
Confederation of Indian Industry

Optimize Service Air


Operating Pressure

Recommendation

Take VFD into auto mode and set the


pressure to 4.5 kg/cm2.
Install a new receiver tank of higher
capacity
This

will avoid frequent loading and


unloading
Can cater to sudden requirement also

Savings

Power
-65 kW
Annual Saving
-

Rs 7.80 Lakhs

Confederation of Indian Industry

Install VFD for Loop Seal Blower in


boiler-1

Total 2 Blowers

Operation

Runs on full load


Discharge valve full open
Power consumption 68 kW

Boiler -2 Runs with similar blower but with


VFD (manual mode)

1 in service and other in standby

Power consumption 28 kW

Measurement could not be done because of


non-availability of points
Here comparative study is done with
blower of Boiler-2
Confederation of Indian Industry

Install VFD for Loop Seal Blower in


boiler-1

Recommendation

Install VFD
Run

in auto mode based on the pressure


requirement
Run on manual mode similar to Boiler-2

Savings 40 kW
Annual Saving -

Rs 9.60 Lakhs

Confederation of Indian Industry

ELECTRICAL

Confederation of Indian Industry

Optimize the Loading of Ash


Handling Plant Distribution
Transformers
6.6kV
Existing system

DT-1 2.5 MVA


339.61 KVA
13.5% Load

DT-2 2.5 MVA


439.25 KVA
17.57% Load

0.433kV
Confederation of Indian Industry

Optimize the Loading of Ash


Handling Plant Distribution
Transformers

Transformer losses:

DT 1: 3.36 kW
DT 2: 3.61 kW

Since loading is less, load can be


transferred to a single transformer
Loss in one transformer operation

4.922 kW

Net saving : 2.05 kW

Confederation of Indian Industry

Optimize the Loading of Ash


Handling Plant Distribution
Transformers
6.6kV
Proposed
system

DT-1 2.5 MVA


778.86 KVA
31.07% Load

DT-2 2.5 MVA

0.433kV
Confederation of Indian Industry

Optimize the Loading of Ash


Handling Plant Distribution
Transformers

Recommendation:

Operate only one transformer


Switch

load from the other transformer

Total Savings 2.05 kW


Annual Saving -

Rs 0.49 Lakhs

Investment

Confederation of Indian Industry

Nil

Optimize the Operation of dry


type Distribution Transformers

6
Dry
type
distribution
transformers cater to the loads
in 3 meter. Observations in:

DT-5 (2 MVA)

DT-6 (2 MVA)

2 MVA transformer used to


cater the load for CEP and other
LT motors.
Confederation of Indian Industry

Optimize the Operation of dry


type Distribution Transformers
6.6kV

DT-6 2 MVA
277.2 KVA
13.8% Load

DT-5 2 MVA
431.8 KVA
21.59% Load

0.433kV
Confederation of Indian Industry

Optimize the Operation of dry type


Distribution Transformers

Transformer losses:

DT 5: 3.88 kW
DT 6: 3.33 kW

Since loading is less, load can be


transferred to a single transformer
Loss in one transformer operation

5.45 kW

Net saving : 1.77 kW

Confederation of Indian Industry

Optimize the Operation of dry


type Distribution Transformers

Recommendation

Shift
the
entire
load
transformer to the DT-5.

Isolate the primary


transformer and

DT-6

the

DT-6

Energise the transformer once in 30 days


for 8 hours to avoid the moisture problem

of

of

(Or)

Change over from DT-5 to DT-6 and vice


versa on a monthly basis and perform
maintenance in the isolated transformer.
Confederation of Indian Industry

Optimize the Loading of Ash


Handling Plant Distribution
Transformers

Recommendation:

Operate only one transformer


Switch

load from the other transformer

Total Savings 1.77 kW


Annual Saving -

Rs 0.42 Lakhs

Investment

Confederation of Indian Industry

Nil

Switching off the idle running


Transformer

In Dry type distribution


transformers DT-3 and DT-4,

DT-3 is taking the entire load with the


bus coupler ON and DT-4 is off load.

However, the DT-4 is Idle charged


and hence the magnetizing loses or
the no load losses are prevalent.

Confederation of Indian Industry

Switching off the idle running


Transformer

Idle running transformer

No load loss

Typically for a 2 MVA transformer, the noload losses are 2.5 to 3 kW

It is observed that the Transformer DT-4 (2


MVA) in 3-meter is idle running and can be
turned off

A saving of at least 2.5 kW can be achieved


by turning off the idle running transformer
Confederation of Indian Industry

Switching off the idle running


Transformer

Annual Saving

Investment

Nil

Rs 0.60 Lakhs

Confederation of Indian Industry

Optimize the Loading of Coal


Handling Plant Distribution
Transformers
There are 4 Distribution Transformers in
Coal Handling Plant.

DT-1 and DT-2 are operating with bus


coupler off.

While for DT-3 and DT-4, DT-3 is taking the


entire load while the DT-4 is de-energized.

Excellent initiative and has to be applied to


DT-1 and DT-2 as well since the majority of
load is conveyers which are lightly loaded.
Confederation of Indian Industry

Optimize the Loading of Coal


Handling Plant Distribution
Transformers
6.6kV
Existing system

DT-1 2 MVA
397.33 KVA
19.8% Load

DT-2 2 MVA
110.6 KVA
5.5% Load

0.433kV
Confederation of Indian Industry

Optimize the Loading of Coal


Handling Plant Distribution
Transformers

Transformer losses:

DT 1: 3.72 kW
DT 2: 4.00 kW

Since loading is less, load can be


transferred to a single transformer
Loss in one transformer operation

4.25 kW

Net saving : 3.47 kW

Confederation of Indian Industry

Optimize the Loading of Coal


Handling Plant Distribution
Transformers
6.6kV
Proposed
system

DT-1 2 MVA
507.93 KVA
25.3% Load

DT-2 2 MVA

0.433kV
Confederation of Indian Industry

Optimize the Loading of Coal


Handling Plant Distribution
Transformers

Total Savings 3.47 kW

Annual Saving -

Rs 0.83 Lakhs

Investment

Confederation of Indian Industry

Nil

Install auto star delta star


converters in identified motors

Loading of motors studied

Majority of motors 50 to 85%


loaded

Some motors under loaded

Poor power factor

High voltage dependent losses

Low efficiency
Confederation of Indian Industry

Following are lightly loaded motors

Install auto star delta star


Rating
Actual
%
Motor in identified
KW
KW
Load
converters
Chain conveyer 2
motors
18.5
5.83
31.5
for unit-1
Chain conveyer 1
for unit-2

18.5

4.28

23.1

Belt Conveyer 1A

45

9.14

20.3

Belt Conveyer 2A

22

2.86

13

Belt Conveyer 4A

37

6.53

17.6

Belt Conveyer 5A

22

5.45

24.7

Belt Conveyers 1B,2B,3B,4B and 5B are OFF during the


measurements.
Confederation of Indian Industry

Recommendation
Install auto star delta star

converters
in identified motors
Install auto star delta star converter
for motors loaded <40%

Advantages

%age loading improves

Power factor improves

Efficiency improves
Confederation of Indian Industry

Delta & Star Motor Connection


L1
IL = 3 Ip

VL

VP =
3

L1

VL

VL = V P
L2

L2

L3

L3

Delta connection

Star connection

Confederation of Indian Industry

Install auto star delta star


Operating efficiency
increases
converters
in identified
motors

At least 10% can be saved


3.4 kW can be saved

Annual Saving -

Rs 0.51 Lakhs

Investment

Rs 2.25

Lakhs
Simple Payback -

53 Months

Confederation of Indian Industry

Optimize Lighting Voltage

Detailed lighting load measurement carried


out in 3 meter lighting and Unit 2 ACC of the
plant

Dedicated Lighting transformers are installed


in Various locations

Excellent initiative by Plant team

Lighting Voltage observed in the range of


240V

It was observed that in all the lighting feeders,


2 lighting transformers are installed and are
running in parallel with less loading on both.
Confederation of Indian Industry

Optimize Lighting Voltage

One lighting transformer can be


isolated to improve the loading
and also maintain a minimum tap.

Optimum Voltage for lamps is 210215V

Higher Voltage results

Higher Power consumption

Increased failure rate of lamps


Confederation of Indian Industry

Optimize Lighting Voltage


S.N
o

Area

Voltage
(V)

Load
(kW)

Unit-1 Main LDB TF1

239

15.15

Unit-1 Main LDB TF2

241

23.23

Unit-2 Main LDB TF1

241

13.3

Unit-2 Main LDB TF4 above


2 transformers are operating 240
8.86bus coup
The
in parallel with

Confederation of Indian Industry

Optimize Lighting Voltage

10% reduction in Voltage

10%
reduction
consumption

in

Power

Insignificant drop in illumination

level
A total of approximately 6.54 kW can
be saved
by optimizing
the voltage of
Annual Saving Rs 0.78 Lakhs
the lighting transformers in those
Investment
NIL
areas.
Simple Payback -

Months

Confederation of Indian Industry

Lighting Optimisation

Light Pipe

Good potential to install in ware house and in office areas

Lighting movement sensors

Good potential to install in areas of low movement


MCCs
Wash

rooms

Confederation of Indian Industry

Lighting Optimization

LUX Sensors

Lights continue to glow even during day time

Potential to install LUX sensors to street lights and focus lights

Operated based on LUX levels

Timers for Street lights

Lights continue to glow even during day time

Potential to install timers for street lights and operate street lights based on timings

Confederation of Indian Industry

Observations

Confederation of Indian Industry

Harmonics Measurements

Harmonics are produced


linear equipment

due

to

non

Variable frequency drives

DC drives

UPS, Computers, etc

Switching Devices Diode, Thyristor, rectifier

Welding units

IEEE recommendations

THD-V < 5% up to 33 kV

THD-I < 15%

Harmonics
are
measured
distribution transformers
Confederation of Indian Industry

at

all

Harmonics Measurements

Current harmonics observed above


the recommended values at the
transformers with vfd motors.

Effects of harmonics

Failure of capacitor banks

Mal functioning of relays & false


tripping of breakers

Over heating of motors & transformers

Confederation of Indian Industry

Harmonics Measurements

Tag #

THD-V%

THD-I%

AHP DT-1

0.3

1.2

AHP DT-2

0.3

1.1

ESP UNIT 1 DT

3.6

45.2

ESP UNIT 2 DT

2.0

50.8

ACC UNIT 1 DT 1

8.1

30.9

ACC UNIT 1 DT 2

7.6

31.3

ACC UNIT 2 DT 1

6.7

32.8

ACC UNIT 2 DT 2

9.0

29.8

Confederation of Indian Industry

Harmonics Measurements
Tag #

THD-V%

THD-I%

DRY TF-1

4.2

29.9

DRY TF-3

0.7

2.7

DRY TF-5

4.6

29.8

DRY TF-6

3.9

41.7

CHP DT-1

0.3

0.6

CHP DT-2

0.3

5.1

CHP DT-4

0.3

0.2

*Dry TF-4 is not in line and TF-2 incomer to panel is


locked.
*CHP DT-3 is not in line.
Confederation of Indian Industry

Harmonics Measurements
Latest technologies are there with
reduced harmonics
Drives come with in built filter

Recommend to install filters if any


of

these problems occur after

carrying

out detailed study

Confederation of Indian Industry

Avoid damper loss in Lime


conveying blower

Total 3 Blowers

Operation

1 in service and 2 in standby


Runs on VFD (manual mode) based on
the requirement

Pressure was measured across the


discharge damper

Pressure difference of 100 mmWC was


observed

Confederation of Indian Industry

Avoid damper loss in Lime


conveying blower

Recommendation

Damper losses should be max of


20mmWC

Savings 80mmWC to be reduced

Confederation of Indian Industry

Condenser Vacuum
System
CII and Plant team conducted a detailed ACC

vacuum audit for Both the Units


Vacuum Drop

Major concern in the Plant


Day time Vacuum : (0.7 0.75 kg/cm2)
Even observed 0.65 kg/cm2 during peak summer
temperatures

Specific Steam Consumption

Depends on the vacuum conditions


Under favorable conditions( Vacuum 0.80 kg/cm2)

470 TPH 480 TPH steam is needed for 148 MW

Under unfavorable conditions

510 TPH to 515 TPH

Confederation of Indian Industry

Condenser Vacuum
System

Audit Findings

Condenser Vacuum

Day Time Vacuum : 0.7- 0.75 kg/cm2


Starts decreasing after 5:00 7:00 PM
Sole reason is that air temperature
starts favoring
Function of Load and cooling
opportunity provided by condenser

Load characteristics

Governed by external demand


Confederation of Indian Industry

Condenser Vacuum
System

Cooling Opportunity in Air Cooled


Condenser at a particular load

Depends upon ambient air


temperature
Heat transfer area provided

Steam Ejectors at both the units

Handling higher infiltrated air and


condensate flow
Helium test also conducted for the
plant
Confederation of Indian Industry

Air Cool Condenser


arrangement
Exhaust Line

Steam Distribution Line

55 deg C

48 deg C

55 deg C

55 deg C

55 deg C

48 deg C

59 deg C

56 deg C

59 deg C

60 deg C

60 deg C

60 deg C

Confederation of Indian Industry

Air Cool Condenser


arrangement
Temperature in the second row

During unfavorable conditions

Always lower and shows subcooling during


favorable conditions
Indicates lesser flow going through second
stage
Last stage also behaves abnormally sometimes
Heat exchanger area does not remains
sufficient
Situation of low vacuum occurs

Its highly recommended to check the steam


distribution in second and last stages
Confederation of Indian Industry

Performance of steam
ejector
Measured flow through ejector condenser 415 m3/hr
Temperature difference

Inlet 45.75 deg C


outlet 47.4 deg C

steam flow through ejector based on heat balance 996 kg/hr

Very high compared to design

Some times two ejectors operated

Vacuum maintained during favourable condition outside temp -19-20


deg C

Operating 0.17 kg/cm2 (a)

Design 0.15 kg/cm2 (a)

Confederation of Indian Industry

Performance of steam
Observation
-1
ejector

Cold reheat tapping temperature -

335 Deg C

Auxiliary steam header temp

220 Deg C

Significant drop in temperature of steam

Need to ensure there is no attemperation

Quantity of steam consumption in ejector will increase with


reduction in super heat / saturation steam supply

Size of pipe line may contribute only to some extent

If temp drop is due to heat loss there would be reduction in


pressure as well at the inlet of ejector

Confederation of Indian Industry

Performance of steam
Observation
-2
ejector

Install a vacuum pump parallel to steam jet ejector


Power generation potential from cold reheat to
condensing

210 units

Avoiding 1 ton/hr of cold reheat will result in overall


reduction in steam consumption of about 0.75 ton/hr

Estimated power consumption of vacuum pump approx


90 kW

Steam requirement for 90 kW 0.3 ton/hr

Confederation of Indian Industry

Performance of steam
Observation
-2
ejector

Net benefit

approx 0.5 ton/hr

Majority of major power plants in installed with


Vacuum pumps

Install the vacuum pump in parallel to existing


ejector

Confederation of Indian Industry

Summary of Findings
No. of
Projects

Parameter
Total Annual Saving

Rs. in Lakhs

24

187

Annual Saving without


investment

14

86

Annual saving with


investment

10

101

10

110

Investment required
Simple payback period

Confederation of Indian Industry

13 Months

To Sum-up
Shree Mega Power, Already several
efforts taken towards energy efficiency
Several projects on anvil

Confederation of Indian Industry

Thank you

Confederation of Indian Industry

You might also like