Professional Documents
Culture Documents
Lightning Overvoltages
Basics of Lightning
1.
Lightning
Lightning Flash
Minimum one stroke
Average 3 to 5 strokes
Maximum upto 40 strokes.
Current magnitude reduces progressively.
Zs
I0 = Z Z . I s
0
s
= Z
0
Zs
~ Is
. Is
Z0
if Zs <<1
Zs 3000
Object
Z0
Tower
100 - 150
OHGW
400
Ph Condr
330 - 400
UHV
LT lines
6 Effects of Lightning
(i) Strokes to power system components
- generate hazardous overvoltages.
- Back flashover/flashover line insulation insulation
System outage.
- Failure of transformer insulation system outage
severe losses
- Loss of life and property.
V0 Battery Voltage.
Conductor AB
Refer Figure 1
When switch closes on point A, it (A) rises to potential V0
due to source
For the whole conductor to attain potential V0, it
(conductor) needs to be charged.
Charge flows from source along conductor Current
Flow of current causes magnetic field
Energy WB stored in magnetic field (B=magnetic flux
density)
1
WB
2 0
2
B
dv
allspace
0
2
WE
E
dv
Z all space
Thus conductor AB can be represented as comprising of
(a) a continuous distribution of inductance along length
and (b) a continuous distribution of capacitance from
every element of conductor to ground.
9. Refer Figure 2
10
or
di V
dt
L
1
or V idt
c
Even if i is constant, V as t
If i (as in case of L alone) V much
the line
b)
Z0
V0
0
376
0
LC
0 0
(400)
3 x10 8 m / s C 0
= velocity of light
1
LC
1
WB ( L.x).I 2
2
I
V0
(C.x) ( L.x) I
C
2
2
This voltage at B becomes V0 +V0 = 2V0 and current
becomes zero.
Above explained as
(a) Voltage at B =
Incident Voltage Wave + Reflected Voltage Wave
= Vi + Vr
= V0+ V0 = 2V0
= Vr = V0
(b) Current at B =
Incident Current Wave + Reflected Current Wave
= Ii + Ir = 0
Ir = - Ii
13
When a travelling voltage wave arrives at open end of a
transmission line voltage gets doubled (due to reflection)
This is almost always Not Desirable !
14. Case A
Consider that a resistance R0 equal to Z0 is connected to
ground from B. See figure 4.
V0
I0
As soon as voltage wave V0 arrives at B,a current
R0
flows into R0
Voltage remains absolutely stable at V0 as current I0 steady
flows into R0
Matched Termination
Case B
Consider that the point B is solidly connected to earth
Figure 5
Voltage at B collapses to 0
Incident voltage wave =V0 =Vi
Total Voltage =0
Reflected voltage wave = Vr
Vi + Vr = Total Voltage =0
Vr = -Vi = -V0
For Currents
r (current) = - r (Voltage)
Z0
1
Z0
VB = Vi + Vr = V0 + r .V0
= V0 + V0 = 2V0
VB Vi Vr
V0 r .V0
V0 V 0 0
Le
Ce
1
Le .C e
22. Voltages
- Incident voltage = VT = IS. ZT
- Reflection coefficient at tower footing
RTF Z T
r
RTF Z T
Assume : ZT = 100, RTF = 10
T = 10-100 = -0.82
10+100
- Voltage VT reaches tower foot after a time of 0.3 s from
instant of lightning strike (t=0)
23 Currents
Stroke Current IS
At tower footing, replaced current IR is given by
ITF = IS - T . IS
= IS +0.82 IS
24. Examples
E1 : Assume IS = 100 KA = Ir
VTF = 100kA x 100 = 10000 kV (10 MV)
If IS is a Step current, VTT will be a step voltage of 10 MV
can cause backflashover of insulator string definitely.
Assume that there is no back flashover.
10 MV reaches tower foot after T i.e. 0.3s.
Due to reflection (-0.82 VTT), voltage reduces to 0.18 VTT
i.e. 1.8 MV at foot.
Reflected wave reaches tower top after another T i.e. 0.3
s i.e. totally after 0.6 s of strike.
Example 2:
Assume overhead ground wire (400 surge impedance) on
both side (effective surge impedance of 400 / 2 = 200 )
IS divides between tower & OHGWs in either side.
Z 0H
2
IT
Z 0 H 100
2
.I S
400
1
.
0.67.I S
400
2
100
2
Example 3 :
In practice, lightning currents have rise times of 3s to
15s.
Rarely, fast length fronts of 1 s are believed to occur.
Effect of this is very important Front time of VTT is also
1 s.
OABC
Example 5
Consider, in E 1 to E 4 above :
RTF = 20
r = 20-100 = - 0.67
20+100
Instead of voltage collapsing to 1.8 MV ( E 1 to 3) and
0.9 MV (in E 4), here it collapses to the very high values
of 3.3 MV (E 1 to E 3) and 1.65 MV (in E 4).
Back flashovers will greatly increase.
Example 6
If RTF is 7.5
r = 7.5-100 = -086
7.5 +100
There will be correspondingly reduced voltages &
reduced probability of back flashover. However, the
reduction in back flashover rate is not very great.
25 Summary
In summary good grounding practice, with RTF < 10
is essential to reduce Back Flashover rate and hence
lightning performance of transmission lines.
THANK YOU