Improved monitoring and protection

RCD-based protection plan

COMBT13FR-11/02

Contents
Protection of life and property
standard IEC 60479-1
standard IEC 60364
fire protection
Disturbances on distribution systems
earth-leakage currents
non-linear loads
overvoltage disturbances
Vigirex
four mesurement features
protection on disturbed distribution systems
Applications
EMC tests and voltage-dip immunity
measurement of fault currents with a DC component
RCD coordination
protection plans for different system earthing arrangements
load leakage currents
Vigirex - installation of toroids
protection of property

COMBT13FR-11/02

23

27
36

Protection of life and property


Standard IEC 60479-1
Impedance of the human body ZT
UC = Z T I D
ZT depends on:
the frequency
the touch voltage
the path through the body

ZT

ID

UC

Skin
(hand)
Internal
= ZT
resistance

E92455

Skin
(foot)

COMBT13FR-11/02

Protection of life and property


Standard IEC 60479-1
Impedance of the human body ZT
UC = ZT ID

ID

ZT depends on:
the frequency
the touch voltage
the path through the body

ZT

ID

UC

Skin
(hand)
Internal
= ZT
resistance

E92456

Skin
(foot)

The level of danger depends on:


the current ID
the duration of current flow

COMBT13FR-11/02

Protection of life and property


Standard IEC 60479-1
Time/current zones defining the effects of AC current
(15 Hz to 100 Hz)
Zone 1 : perception

Duration of current flow


T(ms)
10 000
5000

Zone 2 : unpleasant sensation


b

Zone 3 : muscular contractions


b (10 mA) let-go threshold

c1 c2 c3

2000
1000
500

200
100

b - c1

E92444

50
20
10
0.1 0.2
1
0.5 mA

COMBT13FR-11/02

Zone 4 : risk of ventricular fibrillation


(cardiac arrest)
c1 (30 mA)
: probability 0 %

c1 - c2 : probability ~ 5 %
2

5 10

100

500 2000 5000 (mA)


30 mA
1000
Current flowing through the body

c2 - c3 : probability ~ 50 %
> c3

: probability > 50 %

Protection of life and property


Standard IEC 60479-1
Critical current thresholds

E92450

mA

COMBT13FR-11/02

1A

Cardiac arrest

75 mA

Irreversible cardiac
fibrillation

30 mA

Breathing arrest

10mA

Muscular contraction

0.5 mA

Tingling

Protection of life and property


Standard IEC 60479-1
Effect of frequency
Current-sensitivity thresholds
(mA)
500

100
30
50

100

1000

(f)

E92451

DC

The human body is most sensitive to frequencies


in the 50 Hz / 60 Hz range

COMBT13FR-11/02

Protection of life and property


Standard IEC 60364
Standard IEC 60364 converts the current/exposure-time curves of
standard IEC 60479-1 into tables presenting the disconnecting-time
versus the nominal AC-voltage (Uo)
50 V < Uo 120 V

120 V < Uo 230 V 230 V < Uo 400 V Uo 400 V

Disconnecting time (s) AC

DC

AC

DC

AC

DC

AC

DC

TN or IT system

0.8

0.4

0.2

0.4

0.1

0.1

TT system

0.3

0.2

0.4

0.07

0.2

0.04

0.1

From table 41A of standard IEC 60364

COMBT13FR-11/02

Protection of life and property


Standard IEC 60364
Direct contact
"Contact of persons or livestock
with live parts of the installation"

Equivalent electrical circuit

COMBT13FR-11/02

E92459

E92458

Uc

Protection of life and property


Standard IEC 60364
Direct contact

Insulation

E95155

Out of reach

COMBT13FR-11/02

IP2X or IPXXB

ELV < 25 V

30 mA

10

Protection of life and property


Standard IEC 60364
Indirect contact
Contact of persons or
livestock with exposed
conductive parts in case
of a fault

Equivalent electrical circuit

E92454

E92460

Uc

COMBT13FR-11/02

11

Protection of life and property


E56887

Standard IEC 60364


Standard IEC 60364 defines three system earthing arrangements
to ensure:
Protection of persons against indirect contact
Protection against fire hazards
TT system
TN system
IT system
RCD protection is a fundamental part of the TT system

COMBT13FR-11/02

12

Protection of life and property


Standard IEC 60364
TT system
L1
L2
L3
N

The neutral point of the LV


transformer is directly
connected to an earth electrode
The exposed conductive parts
of the installation are connected
to a separate earth electrode

PE
Ru

E95152

Rn

COMBT13FR-11/02

13

Protection of life and property


Standard IEC 60364
Uo = 230 V

TT system
L1
L2
L3
N

Earth fault protection


Value of fault current
Id = Uo / (Rn + Ru)

400/230 V

= 230 / (10 + 10)


= 11.5 A
Metal exposed
conductive part

Id = 11.5 A

Ud =
115 V
Load

E95153

Rn
10

COMBT13FR-11/02

Ru
10

Ud = Ru x Id
= 10 x 11.5
= 115 V > UL = 50 V
The fault current creates
a dangerous touch voltage
The SCPD is not capable
of clearing this type of fault

14

Protection of life and property


Standard IEC 60364
Uo = 230 V

400/230 V

SCPD
25 A

TT system
L1
L2
L3
N

In = 5A

Metal exposed
conductive part

Load

E95154

Rn
10

COMBT13FR-11/02

Ru
10

Earth fault protection


Solution
The SCPD is not capable of
clearing this type of fault
(ST setting = 25 A)
The solution is a residual-current
device (RCD) designed for the
protection of persons
Tripping conditions
UCmax
UL
Ru x In < UL
(In is the setting for the RCD)
In = UL / Ru
= 50 /10
=5A
15

Protection of life and property


Standard IEC 60364
TT system
L1
L2
L3
N
PE

IPE = 0

At A

I1 + I2 + I3 + IN = IPE
Well designed network

IPE = 0

I1 + I 2 + I 3 + I N = 0

Rn

Ru

Current in the neutral


does not depend on current IPE
equal to unbalanced load
currents and/or 3rd order
harmonics (3 k)

E92457

COMBT13FR-11/02

IN = Iunbalance + I3 k

16

Protection of life and property


Standard IEC 60364
TT system
L1
L2
L3
N
PE

IPE 0

Faulty distribution system

IPE 0

I1 + I 2 + I 3 + I N 0

Current in the neutral


does not depend on current IPE
equal to unbalanced load
currents and/or 3rd order
harmonics (3 k)
E94409

Rn

Ru

IN = Iunbalance + I3 k

Measurement of current IPE can be used for protection of persons


(values depend on the earthing arrangement) and protection

against fire hazards. However, it is necessary


to detect the true IPE

COMBT13FR-11/02

17

Protection of life and property


Standard IEC 60364
"Deep" earth
the earth does not act as an insulator

Equivalent electrical circuit


"Deep" earth is equipotential in nature
whatever the distance!
11
1000 km

"Deep" earth

15

10

10

COMBT13FR-11/02

E92453

E92452

"Deep" earth

18

Protection of life and property


Fire protection
Risk analysis - the origins of fires in buildings
Study carried out in Germany between 1980 and 1990
Fire 37%

Lightning 1%

Explosions 1%

Cigarettes 6%

Other 7%

E92446

Accidents 7%

Electricity 41%

41% of fires are electrical in origin


this risk is far from negligible
it can be eliminated

COMBT13FR-11/02

19

Protection of life and property


Fire protection
Main cause
Ageing of the installation results in:
less effective insulation
the risk of very small leakage currents
Presence of humidity
Leakage
currents

Small
discharges

E92462

E92461

Carbonisation
of insulation
(dust)

There is a real risk of fire starting at leakage currents of 300 mA

COMBT13FR-11/02

20

Protection of life and property


Fire protection

E94550

I E C 6 0 3 6 4

Standard IEC 60364


Standard IEC 60364, section 3-32, defines premises presenting a
risk of fire (BE2) or explosion (BE3)
Standard IEC 60364, section 4-48, deals with premises where there
is a risk of fire
imposes use of a 500 mA RCD device
recommends use of a TT or IT system for the electrical installation
in such premises
prohibits use of a TN-C system

In TT, IT and TN-S systems, a 300 mA RCD eliminates the risk of fire

COMBT13FR-11/02

21

Protection of life and property


Fire protection
In the USA
The National Electrical Code (NEC) defines a TN-S system
the neutral conductor is not interrupted
the PE protective conductor is created by connecting the metal parts
of the equipment
The NEC considers that the TN-S system cannot control
the impedance of the insulation-fault loop

E92447

The NEC requires specific ground fault protection) (GFP) to protect


against fire hazards (maximum setting of 1200 A)

COMBT13FR-11/02

22

Disturbances on distribution systems


Earth-leakage currents
Cable leakage capacitance
continuous leakage current
called
"natural leakage current"

Load leakage capacitance


continuous leakage current
called
"intentional leakage current"
L1

COMBT13FR-11/02

E92463

E92449

23

Disturbances on distribution systems


Non-linear loads
Harmonic currents
non-linear loads cause harmonic currents,
as a result, the intentional leakage currents are "amplified"
Amplitude
%
100
80
60
40

E92464

20
0

COMBT13FR-11/02

E94410

VSD

IH

11

13

Harmonic
order

24

Disturbances on distribution systems


Non-linear loads

UPS

COMBT13FR-11/02

E92465 - E92499

Fault currents
fault currents have DC components

PE

25

Disturbances on distribution systems


Overvoltages (surges)
Lightning and switching overvoltages cause high transient currents
in distribution-system leakage capacitances
A
6
10
4
2
Ir1

E94412

0
-2
-4

0Current

COMBT13FR-11/02

in the PE
0,02

0,04

E94167

-6
T(s)

26

Vigirex
Four mesurement features
Reduced tolerances

Rms
measurement

Frequency filtering

E94411

Inverse time

Vigirex implements four functions to:


analyse leakage currents to avoid nuisance tripping
trip immediately when required for the protection of persons

COMBT13FR-11/02

27

Vigirex
Four mesurement features
Filtering of harmonic frequencies
frequency converters create leakage currents

with high harmonic components

In
15 x
30 mA

ihf

Ich ihf = ihf

5x
30 mA

a /a

E94413

1x
30 mA

50/60 Hz

1000 Hz

these currents are not dangerous


the RCD must not trip

PE

10 KHz

Ich = 0

ihf

E94414

Eliminate
nuisance tripping

M
1

Analyse leakage currents

COMBT13FR-11/02

28

Vigirex
Four mesurement features

Eliminate
nuisance tripping

RMS measurement
non-linear loads can cause leakage currents with high
form factors 1
I
+ In

1
2

E94415

T (ms)

In

RMS measurement is the means to react only

to dangerous currents

Analyse leakage currents

COMBT13FR-11/02

29

Vigirex
Four mesurement features
Reduced tolerances
Eliminate
nuisance tripping

RCDs never operate below 50% of In


RCDs always operate at 100% of In
In
2

0.8 In

In
Standard RCD
I fault

Non-operation

Operation

E94416

Vigirex

Vigirex has a non-operating current equal to 80% of In,

i.e. better immunity to both natural and intentional leakage currents


Analyse leakage currents

COMBT13FR-11/02

30

Vigirex
Four mesurement features
Inverse time

T (s)

Eliminate
nuisance tripping

energisation of loads

with filters can create major


inrush currents 2

0,3
0,15

0,1

these currents must not trip

the RCD

0,04

0,01
E94417

Vigirex does not trip


2

10

Analyse leakage currents

COMBT13FR-11/02

31

Vigirex
Four mesurement features
Ensure
effective
protection
of persons

Inverse time

T (s)
1

dangerous faults can occur

0,3
0,15

Vigirex, combined

0,1
0,04

1
0,01
1

E94418

10

with a Compact NS, has an


instantaneous total break
time that complies
with table B1 of standard
IEC 60947-2, appendix B 2

Schneider guarantees the break time for a Vigirex combined with circuit
breakers rated up to 630 A, even for the 30 mA threshold

COMBT13FR-11/02

32

Protection on disturbed distribution systems


EMC tests and voltage-dip immunity
Vigirex goes beyond the maximum requirements of standard IEC 60947-2
for EMC immunity
Test standard
Electrostatic-discharge
immunity test
Radiated EM-field
immunity test
Surge immunity test

Voltage-dip
immunity test

Standardised test as per IEC 60947-2


8 kV contact
8 kV in air
10 V/m
80 to 1000 MHz modulated at 1 kHz
- On supply > 100 V AC
4 kV line-to-earth, 4 kV line-to-line
- On supply < 100 V AC
2 kV line-to-earth, 1 kV line-to-line
- On DC supply
0.5 kV line-to-earth, 0.5 kV line-to-line
- On input/output (I/O)
2 kV line-to-earth, 1 kV line-to-line
1.2/50 s wave, open circuit
8/20 s short circuit
Single-phase supply: Us 85 V
Three-phase supply: Us 70%

Vigirex tests
8 kV contact
15 kV in air
12 V/m
80 to 1000 MHz modulated at 1 kHz
- For all supplies (*)
4 kV line-to-earth, 4 kV line-to-line
- On supply < 100 V AC
4 kV line-to-earth, 4 kV line-to-line
- On DC supply
2 kV line-to-earth, 1 kV line-to-line
- On input/output (I/O)
2 kV line-to-earth, 1 kV line-to-line
1.2/50 s wave, open circuit
8/20 s short circuit
Single-phase supply: Us 85 V

(*) for V AC < 48 V, the Vigirex relay does not have a supply transformer

COMBT13FR-11/02

33

Protection on disturbed distribution systems


Measurement of fault currents with a DC component
Classification of faults and types of RCDs
Fault

If
T

If

If

E94419

Loads

Linear - frequent

Non-linear - frequent

Non-linear - rare

Examples

Lamps
AC motors
Capacitors

Dimmers, soft starters (*)


Variable-speed drives

Variable-speed drives
with accessible
braking resistors

RCD

Type AC

Type A

Type B

(*) Type AC
is sufficient

COMBT13FR-11/02

For power distribution, a type A RCD is required for effective


protection against insulation fault

34

Protection on disturbed distribution systems


Measurement of fault currents with a DC component
Combination of different types of RCDs

type A
Vigirex
RCD1

type A
RCD

type A or
type AC RCD

300 mA
inst

type A
Vigirex
RCD1

type B
RCD2

300 mA
60 ms

type A
RCD2

E94441

Class II
insulation

Different types of RCDs may be combined as long as none


of the devices are blocked by the fault current

COMBT13FR-11/02

35

Applications
RCD coordination
Discrimination rules
CB1

two conditions:

RCD1

1
2

CB2

E94442

RCD2

COMBT13FR-11/02

In (RCD1) > 2 In (RCD2)


t (RCD1) > t (RCD2) + t (CB2)
(including the interrupting time)

To implement condition 2 , it is necessary to know the total break


time guaranteed for the CB2 + RCD2 combination or to run tests
on the combination

36

Applications
Coordination of

RCDs

Discrimination rules
CB1

two conditions:

RCD1

CB2

E94442

RCD2

COMBT13FR-11/02

In (RCD1) > 2 In (RCD2)


setting (RCD1) setting (RCD2) +1

Condition 2 is automatically obtained for (RCD2) +1 if RCD2


is combined with a circuit breaker/switch disconnector from
the
Multi 9 or Compact ranges

37

Applications
Coordination of

RCDs

Discrimination rules with a Vigirex upstream


CB1

two conditions:

Vigirex

1
2

RCD1

In (RCD1) > 1.5 In


setting (RCD1) setting (RCD2) +1

Condition 2 is automatically obtained for (RCD2) +1 if RCD2


is combined with a circuit breaker/switch disconnector from
the
Multi 9 or Compact ranges

CB2

E94442

RCD2

COMBT13FR-11/02

38

Applications
Protection plans for different system earthing arrangements
TT system
I n

CB1
RCD1
2,5 A

5A

1s

E94479

CB2

E94478

RCD2
UL = 50 V
RT = 10

COMBT13FR-11/02

In current setting on upstream RCD


standardised rules (maximum): In = 5 A

t = 1 s

39

Applications
Protection plans for different system earthing arrangements
TT system
IL

CB1
RCD1
Vigi 3 A

NS250

60

t(ms)

0,3

vigi MH

T R

10

vigi

NS 250
200 /440 V - 5

0,55 1,5 A

3A 5A

1s

N 1 3 5

In(A)

HS 0,03 (t = 0)

2 4 6

E94478

E94479

CB2

310

150

I n

Process
ILA

20 VSDs
ILB

ILA = 150 mA
ILB = 400 mA
IL = 550 mA

COMBT13FR-11/02

In current setting on upstream RCD


t = 1 s

standardised rules (maximum): In = 5 A

leakage-current IL withstand (min.): In 2 IL = 1.1 A In = 3 A


Example. NS250 Vigi 3 A

40

Applications
Protection plans for different system earthing arrangements
TT system
Vigirex
MERLIN GERIN

IL

I n

0,55 0,7 A 2,5 A 1 A 55 A


A

CB1

1 ss

RCD1
RH99 1A
B
E94479

NS250
A

E94478

In current setting on upstream RCD


Process
ILA

20 VSDs
ILB

ILA = 150 mA
ILB = 400 mA
IL = 550 mA

COMBT13FR-11/02

t = 1 s

standardised rules (maximum): In = 5 A

leakage-current IL withstand (min.): In 1.5 IL = 825 mA In = 1 A


Example. Vigirex RH99

41

Applications
Protection plans for different system earthing arrangements
TT system
IL

I n

In2

CB1
RCD1

0,55 1,5 A 3 A 5 A

1s

300 mA

CB2

E94478

RCD2
RCD2
300 mA - s

COMBT13FR-11/02

E94479

60 ms

In current setting on upstream RCD


standardised rules (maximum): In = 5 A t = 1 s
leakage-current IL withstand (min.): In 2 IL = 1.1 A In = 3 A
discrimination rules
In1 In2 x 2 = 600 mA In = 1 A
t1 > t2 + break time CB2

42

Applications
Protection plans for different system earthing arrangements
TT system
In2

NS250

RCD1
Vigi
3 A - 150 ms

150
150

t(ms)

0,3

vigi MH
10

T R

vigi

NS 250
200 /440 V -5

0,55 1,5 A 3 A 5 A

150 ms 1 s

N 1 3 5

In(A)

HS 0,03 (t = 0)

CB2

310

60

I n

2 4 6

300 mA
E94479

CB1

IL

60 ms
E94478

RCD2

RCD2
C60 Vigi if s 300 mA
RCD1
NS250
Vigi

COMBT13FR-11/02

In current setting on upstream RCD


standardised rules (maximum): In = 5 A t = 1 s
leakage-current IL withstand (min.): In 1,5 IL = 825 mA In = 3 A
discrimination rules (Schneider)
In1 In2 x 2 = 600 mA In = 1 A
setting RCD1 setting RCD2 + 1

43

Applications
Protection plans for different system earthing arrangements
TT system
Vigirex
MERLIN GERIN

In2

IL

I n

0,3 0,55 0,7 A 1 A 5 A

CB1
RCD1
RH99
1 A - 150 ms

150 ms 1 s

300 mA

CB2

RCD2

E94478

C60 Vigi
If s 300 mA

COMBT13FR-11/02

E94479

60 ms

In current setting on upstream RCD


standardised rules (maximum): In = 5 A t = 1 s
leakage-current IL withstand (min.): In 1.5 IL = 825 mA In = 1A
discrimination rules
In In x 1.5 = 450 mA In = 0.5 A
setting RCD1 setting RCD2 + 1

44

Basic principle

Applications
Protection plans for different system earthing arrangements
RCD at the head

RCD1

RCD2

In < 5 A

UL = 50UVL

1RT

In < 10 A

5RT

In < 5 A
RCD3

10 RT

Standardised rule An RCD must be installed at the head of the installation and at the
head of each group of separately earthed exposed conductive parts
Settings: current setting In < UL/RT
delay T < 1s
Implementation
In3 < 50 V = 5 A, In2 < 50 V = 10 A, In1 < min 50 , 50 V = 5 A
10
5
10 5
COMBT13FR-11/02

45

Applications
Protection plans for different system earthing arrangements
TT system
Typical leakage currents following a first fault
System leakage capacitance (F) First-fault current

In setting

70 mA

300 mA

360 mA

1A

30

2.17 A

5A

Standardised rule
IEC 60364-5-53: The RCD current settings must be greater than twice
the first-fault current

COMBT13FR-11/02

46

Applications
Load leakage currents
Equipment

Leakage currents IL are due to the natural or intentional capacitances


installed between the phases and earth
cable leakage currents
Differential-mode capacitance Common-mode capacitance
Standard cable (not shielded) 20 pF/m

150 pF/m

Shielded cable

200 pF/m

E94472

30 pF/m

leakage currents of computer equipment


Computer equipment

Standard IEC 60950

Maximum leakage current (mA)

All equipment

0.25

PC

Type A fixed or mobile

3.5

Computer room

Type B fixed

3.5 or 5% In

requirement for RCD protection - an RCD must not trip

for these natural currents, yet must protect life and property

COMBT13FR-11/02

47

Applications
Load leakage currents
Implementation of RCDs

E94473

ID63
30 mA

for RCDs protecting power outlets, In = 30 mA,

IL must therefore not exceed 15 mA


PC

IL = 3.5 mA

In?
xm

xn

Example. Maximum of 4 PCs per set of outlets

for RCDs upstream of a set of loads on a TT system

calculate current IL

E94474

RCD current setting In must be greater than 2 IL


IL2

IL1

check that In < UL / RT

IL = m IL2 + n IL

COMBT13FR-11/02

48

Applications
Vigirex - installation of toroids
6 In

E94484

< 15 mA

Recommendations
centre the conductors
respect the operational current In of the toroid, corresponding
to a 30 mA operating threshold, on a 6 In overload

E94523

Improve immunity to disturbances


use a toroid with a larger diameter
delay the protection function (< 1s)
install a magnetic sleeve

E94524

Toroid mounting on multi-conductor cable with PE


run the PE back down through the toroid

COMBT13FR-11/02

49

Applications
Protection of property
Protection of motors (TN-S system)

Vigirex

MERLIN GERIN

E94458

a low insulation fault can cause a short-circuit


an RCD with a current setting between 3 and 30 A avoids this risk

COMBT13FR-11/02

50

Applications
Protection of property
Protecting downstream
Monitored
Monitored system
system

A
T

PEN

E94481

PE

N
PE
PE

Toroid T measures all the fault currents downstream of A


the neutral is not earthed downstream of A
the system earthing arrangement is TT or TN-S
TT/ RCD - MS
TN-S RCD - BS / RS-type GFP
Protection of life and property

COMBT13FR-11/02

a few A
a few 100 A

51

Applications
Protection of property

COMBT13FR-11/02

PEN

PE source

PE

E94482

Protecting upstream

52

Applications
Protection of property
Protecting upstream
Monitored system

A
T

N amont
PEN

PEamont
source
PE

PE
PE
E94482

NPEN
amont

Toroid T measures all the fault currents upstream of A


the neutral is not earthed upstream of A
the downstream system earthing arrangement is TN-S, the upstream
system earthing arrangement is TN-C

COMBT13FR-11/02

53

Applications
Protection of property
Protecting upstream
Monitored system

COMBT13FR-11/02

PEN
N
amont

PEN amont

PE amont

PE

E94482

54

Applications
Protection of property
Protecting upstream
Monitored system

A
T

PEN
PE

E94482

PE source

RCD - BS / RS-type GFP


The fault current is a few 100 A

COMBT13FR-11/02

55

Applications
Protection of property
Protecting upstream
Monitored system

A
T

N amont

PEN amont

PE source
amont
PE

PE
PE

E94482

2nd source

Protection and/or decoupling of sources

COMBT13FR-11/02

56

Applications
Protection of property
Protecting upstream
Monitored system

PEN
T

PE

E94482

PE source

SGR

COMBT13FR-11/02

57

Applications
Protection of property
Protecting upstream
Monitored system

PE amont

PEN amont
N
T

PE

PE

E94482

N amont
PEN

SGR

Note. SGR-type GFP measures the upstream and downstream currents

COMBT13FR-11/02

58

Applications
Protection of property
Protecting upstream
Monitored system

A
T

N amont
PEN

PEamont
source
PE

PE
PE
E94482

NPEN
amont

Toroid T measures all the fault currents upstream of A


the neutral is not earthed upstream of A
the downstream system earthing arrangement is TN-S, the upstream is TN-C
RCD - BS / RS-type GFP
The fault current is a few 100 A Nota : GFP de type SGR mesure les
courants
amont etGFP
aval measures the upstream and downstream currents
Note.
SGR-type
Protection and/or decoupling of sources

COMBT13FR-11/02

59

Applications
Protection of property
Restricted Earth Fault (REF)
Generator
Protected
zone

Unprotected
zone

Generator
shutdown
PE

PEN
L

E94483

N
PE

Purpose
protection of generators
Upstream system earthing arrangement is TN-C
RS-type GFP or RCD - BS
COMBT13FR-11/02

60

Applications
Protection of property
Restricted Earth Fault (REF) - Multisource diagram
Generator no. 1

Generator no. 2

Protected
zone

Unprotected
zone

PE

PEN

PE

PEN
L
N
E94384

PE

Purpose
continuity of service (parallel-connected generators)
elimination of a generator if an insulation fault occurs
RS-type GFP or RCD - BS
COMBT13FR-11/02

61