Division - Name - Date - Language

WHAT IS BUSWAY

Division - Name - Date - Language

TYPE OF BUSWAY
BY CONDUCTOR MATERIAL

COPPER OR ALUMINIUM

BY AMPERE CAPACITY

I-LINE I AND I-LINE II

BY GROUND SYSTEM

INTEGRAL GROUND OR INTERNAL GROUND

BY NUMBER OF CONDUCTORS IN BUSWAY

Division - Name - Date - Language

3 bars, 4 bars, 5 bars,

TYPE OF BUSWAY(continue)
BY DEGREE OF PROTECTION

IP 40, 41, 54, 55, 65, 66


IP definition - IEC 529-1989

First characteristic
numeral:
against ingress of solid
foreign objects

Second
characteristic
numeral:
against ingress of water
with harmful effects

Additional
letter
(optional):
against access to
hazardous parts
with:

Supplementary
information
specific to:
(optional)

0: Non-protected

0: Non-protected

A: Back of hand

1: >=50mm diameter

1: Vertically dripping

B: Finger

2: >=12.5mm diameter
3: >=2.5mm diameter

2: Dripping (15 degree C: Tool


tilted)
3: Spraying
D: Wire

H: High_voltage
apparatus
M: Motion during
water test
S:
Stationary
during water test
W:
Weather
condition

4: >=1.0mm diameter

4: Splashing

5: Dust protected

5: Jetting

6: Dust tight

6: Powerful jetting
7: Temporary immersion
8: Continuous immersion

Division - Name - Date - Language

TYPE OF BUSWAY(continue)
BY SHORT CIRCUIT RATING

Standard short circuit UL ratings: 3 cycles - feature CF25, CR25

High short circuit UL ratings: 3 cycles: CFH25, CPH25

High short circuit IEC ratings: 1 sec / 3 sec - IGB feature CFJ25, CPJ25

Division - Name - Date - Language

Cable VS Busway

Cable

Busway

Tx

M DB

Division - Name - Date - Language

Cable VS Busway

Busway

Division - Name - Date - Language

Cable VS Busway

MDB

Maintenance

DB

Division - Name - Date - Language

Cable VS Busway
Compact
Reduced dim.
Flexibility of
Changing install.

Easy operation

Division - Name - Date - Language

I- Line typical application (1,2)

Division - Name - Date - Language

10

I- Line typical application (3,4)

Division - Name - Date - Language

11

I-LINE BUSWAY
I-LINE I

Division - Name - Date - Language

I-LINE II

12

FEATURE
Rated voltage: 600V AC
3 and 4 Pole(100% neutral)
Copper and Aluminum conductors
I-LINE I : 225/250 to 600/630A
I-LINE II : 800A to 5000A

Ratings - from 800A to 5000A(CU) and 800A to 4000A(AL)


according to UL, IEC standard

Division - Name - Date - Language

13

FEATURES (continue)
Sandwich structure
IGB system
High IP ratings up to IP66
Easy Joint Pak
VISI-TITE One Bolt Joint
Totally Enclosed Housing
High short circuit current: J series

Division - Name - Date - Language

14

FEATURES(continue)
Housing thickness: 1.8mm in straight length and 2mm in fittings.
Housing made by Electro- galvanized steel
Paint - all steel enclosures use Polyester Epoxy electrostatic
powder finish Color: ANSI 49 gray
Universal fittings
Plug In Units - Square D MCCBs and MG MCCBs

Division - Name - Date - Language

15

I-LINE II

Division - Name - Date - Language

16

Sandwich Construction
Total enclosure, spread heating
through its housing
Low temperature rise enable
higher current rating
Save space, save money

Division - Name - Date - Language

17

IGB Integral ground bar


Ground bar material:electrical grade
aluminum
Wrap around construction with two
1/16 ground busbars
50% continuous current capacity
ground path, temp. raise not over
550C
IGB has 7-42% more cross sectional
area than a conventional 1/8 (3
mm) thick bar
80% less impedance

Division - Name - Date - Language

18

Mylar- Insulation
Excellent dielectric performance
Two layers Mylar wrap each bar
(only single layer needed according
to IEC standard )
B class: 130 degree
100% 7500VDC tested in 10 sec
before ship
Over 20 years of experience.

Division - Name - Date - Language

19

Conductors
High purity copper and Aluminum

Silver plated or tin plated over


entire length
Cross section greater than UL
standard. Bar size is largest in
all competitors.
Thickness is 6.36mm,1/4
Results: Low contact resistance,
low voltage drop,

Division - Name - Date - Language

20

EZ Joint Pak
Single bolt make the installation faster.
Small contact resistance; greater contact
area; reliable contact force
3mm(1/8) can be adjusted in joint
This can also take care of expansion
Pre-assembled on I Line II busway
and fittings.

Division - Name - Date - Language

21

Visitite Bolt
Single bolt connection
double

head

visible

torque indication

No

torque wench required

Torque

Division - Name - Date - Language

requirements 70 lb-ft (+- 10 lb-ft)

22

Joint Cover
Within the same ampere range, all I Line busway
lengths & fitting are fully compatibility

Feeder, Plug-in & Riser use the standard universal


tie channels (Joint Cover), helping to speed up the
installation process

Division - Name - Date - Language

23

ELBOW
I Line busway allows the use of the same accessories to
fit all lines, simplifying pre-installation labor

Division - Name - Date - Language

24

I-LINE II accessories

Expansion fitting (Indoor only)

Unfused reducer

Division - Name - Date - Language

25

Hanger

Flat Hanger

Edgewise Hanger

Spring Hanger

Division - Name - Date - Language

26

I- Line II quick selection


Application
Transformer to LV
panel;
Panel to panel
Vertical electrical
distribution;
(in electrical well)
Horizontal electrical
distribution to the
downstream
switches

Division - Name - Date - Language

Busway
type (Cu)

PIU distance

IP ratings
Outdoor:
IP66(COFxxxxG)
Indoor:
IP40/41; IP54/55
IP65

CF (feeder)

No

CR (riser)

Single side;
Indoor:
Gap 610 mm/ 2 ft IP40/41; IP54/55

CP (plug-in)

Double sides;
Indoor:
Gap 610 mm/ 2 ft IP40/41; IP54/55

27

I-LINE II Conclusion
Standard : UL, IEC 439
General : 600V, 3-phase, 4-wire with 50% capacity integral ground bus
Housing : steel and aluminum.
Joint : EZ joint-pak (removable).
Bolt : two-headed
Busbars : tin plated aluminum or silver flashed copper.
Insulation : Class B rated 130 0c polyester film or epoxy powder coated.
Plug-in opening : 5 dead front each side of 10 foot lengths.
Support : Indoor -every 3m. For horizontal, 4.88m. For vertical
: Outdoor -every 1.5m.
Voltage drop : lower than competitor.
Plug-in unit safety : Must connect ground bus before the phase bars
Can not open the cover when the switch is ON.

Division - Name - Date - Language

28

I- Line I

Division - Name - Date - Language

29

DESCRIPTION
Ratings
225,400,600A is UL standard current ratings
250,400,630A is IEC standard current ratings
4 poles with integral ground which is Aluminum.
Requires support every 3 meters(horizontally flatwise), 1.5
meters(horizontally edgewise) and 4.8 meters(vertically)

Division - Name - Date - Language

30

I line I - Construction
Steel housing : 1.8 mm electro-galvanized steel
Epoxy electrostatic powder coated
Ground bar /housing made of aluminum and only on TOP *
Ground bar rated for 50 % of phase
Air separated bars inside the housing
There is insulated fiberglass supports for the bars

Division - Name - Date - Language

31

I line I - Conductors

Silver flashed copper or tin plated aluminum conductor across


full length.
Two sizes - 0.94 for 200 A and 2 for 400/600A
Thickness is same 1/4 like I line II
Insulation is Mylar like I line II , with two layers of 7.5 mil each

Division - Name - Date - Language

32

Plug in Units
Plug in Units with Square D breakers
Fusible plug in units

Division - Name - Date - Language

33

PIU for Square D Circuit Breaker


MCCB Type
PFA - 15 - 100 A
PKA- 125- 250 A
PBLA - 250 - 400 A
PTMA - 500 - 1000 A
Horizontal or vertical
PTPA - 1200 - 1600 A
Suffix: *H/V

Division - Name - Date - Language

Bolt On Connection - Specify


Bolt on Connection

mounting .

34

Square D PIU - features


Meet with UL standard
Mounted with Square D MCCB
Up to 1600A
3 pole
5 frame size: PF,PK,PBL,PTM,PTP
More interrupting capacity can be selected: A,H,C,I type
Steel housing ( 1.8 / 2 / 2.5mm thickness )
Door cover with reliable interlock
PIU jaw connection technology laboratory tested and customer proven for over
20 years
High visibility ON-OFF indication on cover
Bracket allows unit to be padlocked in off position
Hook stick operated mechanism
Transparent shield over Line side parts - that means safety & visible

Division - Name - Date - Language

35

Perry Units - PIU with MG breakers


Why Perry PIU
- 4 Pole option available
- MG brand
- Co-ordination with other MG
products
- Earth leakage protection with
VIGI

Division - Name - Date - Language

36

Perry Units
Range upto 630 A
Three frame sizes
PFNS upto 100A ( smaller size ) PNS upto 250 A
PBNS : 300 A to 630 A
Offered with three types of Breakers from MG
NSD type upto 630 A : only 3 pole 35KA breaking capacity
NSN type upto 630 A : Both 3 and 4 pole varying breaking capacity
NSH type upto 630 A : Both 3 and 4 Pole 70 KA breaking capacity

Division - Name - Date - Language

37

PIU features - safety


Totally enclosed conductors.
Polarized Plug In Units.
All Plug In Units have door interlocks.
Ground jaw connect with busway before phase jaws
PIU mounts correctly by design.

Division - Name - Date - Language

40

PIU features - easy to install

Hook swing
installation

Division - Name - Date - Language

41

ADVANTAGE OF SQUARE D BUSWAY


STEEL HOUSING FOR EXTRA PROTECTION AGAINST
MECHANICAL DAMAGE.
LOW VOLTAGE DROP.
MORE SAFETY ON INSTALL THE PLUG-IN UNIT.
TAP OFF UNIT UP TO 1600 A.
MANY IP RATING.
FAST SHOP DRAWING.
FAST DELIVERY

Division - Name - Date - Language

42

SQUARE D BUSWAY

Division - Name - Date - Language

43

SQUARE D BUSWAY

Division - Name - Date - Language

44

SQUARE D BUSWAY

Division - Name - Date - Language

45

SQUARE D BUSWAY

Division - Name - Date - Language

46