Technical Seminar on Busduct Handling,

Installation, Testing and Maintenance

Material Storage & Protection


- Water / Dust Precaution
Water/ dust will provide alternative path /
heating point
Damage insulation
Latent hazard of short circuit
Solution
Double packing (plastic bag+carton box)
Apply rain coat after installation each day
Proper storage management
2

Factory Precaution
Double packing (plastic bag+carton box)

Factory Precaution
Double packing (plastic bag+carton box)

Site Recommendation
Apply rain coat after installation each day

Protecting the end

Using proper Plastic Shield


5

Proper Storage

Storage in Dirty and Open Area

Storage in Dry and Clean Warehouse

Site Storage

Wetted Floor
7

Good Example of Busduct Storage

Stored in Dry & Clean Place,


Raise Crate with wooden Blocks

Provide Curb to Protect


Vertical Busduct
8

6. Installation Procedure
Video of Installation (about 8 minutes)

Quality Project Management Services


Provided by Schneider
Product Training
Site Measurement
Optimum busduct routing design
Detail shop drawing preparation
On site technical support
Training on installation procedure
Missing Link and Remedial Units
Joint inspection (not contractual service)

10

Missing Links / Remedial Units


Missing link reserve 1 pc of busduct for final measurement
Increase accuracy of busudct dimension
Save time for rectifying installation mistake
Streamline the installation

Missing Link

11

Missing Link

12

Contractor-Supplier Interaction
Project Start

Technical support
and routing deisgn

After sales services


and missing links

AutoCad Drawing

Installation support

Project
Management
Support

We are not only a


busduct supplier

BRASS and
manufacturing
instruction

Fabrication
13

Vertical Spring Hanger

Release of Locknut

14

Installation Arrangement Horizontal Hanger

15

Installation Arrangement Horizontal Hanger

16

Testing & Commissioning


A.Factory Test
Factory Test 7500V dc Hi-pot
Test
100% test before delivery
Insulation = 10M/ ft
(IEC require 1M/ ft )
Check weak point of insulation

17

Testing & Commissioning


B. On Site Test
Mega test before any energizing
NEMA:
M =100/ Length of Busduct in Ft (1000V)
Reading of individual busduct normally
> 10 M

18

System coordination with other trades


Try to design the systems to move water
services for busduct system
Eliminate the water hazard from burst or leaked
pipes / drains

19

System coordination with other trades

Water Drip from


Ceiling

20

System coordination with other trades

Large Drain Pipe


Overhead

21

11. Maintenance Issues


Routine inspection
Vertical spring hanger adjustment & Bowing
Symptom
Thermal checking/ scanning
Spare part provision

22

Routine Inspection
Insulation test recommended by NEMA
Check at least 1 per year
Check after electrical short circuit or ground
fault
Visual inspection on joints and terminals
Remove damp or clean dust when necessary
Check tighten torque of joint bolt if necessary
Check any cracks, loosen/ broken parts

23

Trouble Shooting
Recommend spare parts
1 pair of flanged ends for each busduct
rating used
A number of plug-in units
24-hours services hotline provided by
Schneider Busway
Contact local Schneider office

24