Octubre 2014
Index
General
Product presentation
Your needs & our offer
Switchgear
Protection, monitoring & control
Installation
General
Application Field
Ratings
References
Application Field
HV/MV MV/MV MV/LV Substations
Distribution & Generation
Utilities
Wind Power
Solar
Electrointensive Users
Railways
Airports
Oil & Gas
MMM (Mining, Minerals & Metals)
Heavy Load Industries
.
44
Ratings
Mining
Koniambo, Boddington Gold Mine, Aznalcollar.
Etc.
CBGS-0 - Schneider Electric - 2012
Product presentation
Architecture
Cubicle Types & Ratings
Architecture
1
LV Compartment
Busbar System
Main Compartment
1
2
3
4
88
Architecture
Low Voltage Compartment:
1. Interconnection LV wiring
2. C&M devices (optional)
Busbar System:
3. VT-s (option)
4. CT-s (option)
10
11
Your needs
Safety
Service
Continuity
Quality
&
Environment
CBGS0
CBGS-0 - Schneider Electric - 2012
12
Service Continuity
Simple design for a service life > 30 years
Simple & Robust = Reliable
Simple installation
Very short replacement time
Experience
+10.000 references worldwide
Optimized manufacturing & quality procedures
CBGS-0 - Schneider Electric - 2012
13
Safety
Simple design
Easy to understand & operate
Mechanical interlocks
Avoid false operations
Access to Cables only in earth position
Possibility to block earth position
14
OPEX
Civil Works
Small dimensions
No need of rear access
Installation
Fast and simple installation
No SF6 handling on site
Simple testing procedure
Maintenance
Maintenance Free in MV parts
Minimum maintenance for mechanisms
15
16
Switchgear
17
E2/M2/C2
Operating duty
O-0,3s-CO-15s-CO (up to 25kA)
O-0,3s-CO-3min-CO (for 31,5kA)
18
18
Disconnector
IEC 62271-102
3 position: closed-open-ready to earth
Earthing through CB (making capacity)
Reliable mechanical position indication
M0
Earthing through CB (E2)
19
19
Switch-disconnector
IEC 60265-1
3 position: closed-open-earthed
Reliable mechanical position indication
Breaking capacity: 630 A
Making capacity 50kA
20
Fuses
IEC 60282-2
Fuse-Switch combination
For AASS transformer protection
Recommended:
Fusarc CF type*,
Requisites
Dimensional standard DIN 43625
With thermal striker
21
Busbar system
1250/1600A
2000A
22
23
Current Transformers
Ring type
Busbar or circuit connection (A & B)
Outside SF6 tank
Not dielectrically stressed
IEC 60044-1*
Ring type
Low power CT
Reduced burden
Combined metering & protection
IEC 60044-1*
Low power CT
* For other specific standards ANSI, AS; BS, NBR, please contact us
24
24
Voltage Transformers
Characteristics:
Busbar or circuit connection (A & B)
Inductive Type
Phase-Earth connection
Shielded enclosure
IEC 60044-2*
* For other specific standards ANSI, AS; BS, NBR, please contact us
25
25
Schneider Offer
Sepam range
MiCOM range
* Other brands available
CBGS-0 - Schneider Electric - 2012
26
26
Installation
Power cables
1250 A (36kV) & 1600 A(24kV) installation layout
2000A installation layout
Civil works
Level adjustment
27
Power cables
Plug in connectors for incoming/outgoing cables
Outer cone EN 50181 (C type)
Up to 3 Cables (1600 A) + VT
Up to 6 cables (2000 A) + VT
Option to install surge arrestors
Reduced connection
28
A.
B.
C.
D.
E.
Incomer
Feeder
Bus section
Bus riser
Auxiliary Services
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Switchgear
Left side end panel
Level adjustment points
Situation of MV cables
Situation of VT cables
Fixing points
Relief area for SF6 gas (100mm)
Control cables routing (220x26mm open to right)
Minimum front operating aisle (1500mm)
Distance to the wall (100mm)
29
2000A Layout
A.
B.
C.
D.
E.
Incomer
Feeder
Bus section
Bus riser
Auxiliary Services
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Switchgear
Left side end panel
Level adjustment points
Situation of MV cables
Situation of VT cables
Fixing points
Relief area for SF6 gas (100mm)
Control cables routing (220x26mm open to right)
Minimum front operating aisle (1500mm)
Distance to the wall (100mm)
30
Civil works
31
Level adjustment
32
www.schneiderelectric.com