You are on page 1of 14

Fuel Gas Sistem

Muh. Bahrul Amir

Sengkang, September 2015

PT. CONSOLIDATED ELECTRIC POWER ASIA


Fuel Gas system
atural gas system has two function :
ntrol mass flow of natural gas into the GT Combustion
mber.
uts off the flow of natural gas to the gas turbin under
in condition.
turbine fuel system supplies fuel to the combustion
r based on the power output required of the gas turbi
al gas supply system must be propided upstream
atural gas system to ensure that natural gas is availab
uantity required to meet operational demand.

Presentation title - 12/12/2012 - P


2
Fuel Gas system

Natural gas strainer

Natural gas strainer MBP11AT001 is located at


the upstream terminal point of supply. Its task is
to prevent the ingress of any coarse foreign
matter which may be present in the piping.

Presentation title - 12/12/2012 - P


2
Fuel Gas system

ilot gas flow measurement


A device is installed downstream of pilot gas
control valve MBP23AA151 for measuring and
recording pilot gas mass flow data
(MBP33CF101). The amount of pilot gas supplied
has a mayor impact on the humming of the gas
turbin

Presentation title - 12/12/2012 - P


2
Fuel Gas system

atural gas pressure relief valve

The natural gas pressure relief valve is part of the


gas lock and permits depressurization of the
piping sections between first

Presentation title - 12/12/2012 - P


2
Fuel Gas system

Natural gas Emergency Stop Valve (first


Its functionElement)
Shutoff is to enable or block the flow of natural gas to the
burner on start up and shutdown of the gas turbine. Its closed in
the event of faults which require immediate interuuption of the
supply of natural gas to the gas turbin. The natural gas ESV is
opened hydraulically and closed very rapidly by spring force.

Natural Gas diffusion burner Control Valve


(second
The shutoff
Natural Element)
gas diffusion burner control valve (NG DG CV)
controlling the mass flow of natural gas, also function as a shutoff
element.

Presentation title - 12/12/2012 - P


2
Fuel Gas system

Natural gas premix burner control valve


(second shutoff Element)
Natural gas premix burner control valve (NG PB CV)
MBP22AA151 is actuated in accordance with the
requirements of the gas turbine operating mode and
regulated the natural gas mass flow to premix burner.

Presentation title - 12/12/2012 - P


2
Fuel Gas system

ot gas control valve (second shutoff element)

Like the natural gas burner control valve, the pilot gas
control valve (PG CV) is a leak-tight and fail safe shutoff
valve which, in addition to controlling the mass flow of
pilot gas, is also part of the gas block. Pilot gas is used to
start the gas turbine. The pilot gas control valve regulates
the amount of natural gas that flow through the pilot gas
burner. The flow of pilot gas is set as a function of Nox
emission data, flame stability, and the humming behavior
of the gas turbine.

Presentation title - 12/12/2012 - P


2
Fuel Gas system
atural gas Temperature Monitoring

In the standard configuration, the natural gas


system is equipped with three resistance
thermometers MBP13CT101, MBP13CT102,
MBP13CT103 located in the natural gas supply line
upstream of the natural gas ESV. An alarm is
announciated if at least two of these three
thermometers indicated limit T. GAS.01 has been
exceeded. Natural gas temperature readings are
used by the gas turbine controller to correct the lift
setpoint for the premix and pilot gas control valve
Presentation title - 12/12/2012 - P
2
Fuel Gas system

gas control valve (second shutoff element)

Like the natural gas burner control valve, the pilot


gas control valve (PG CV) is a leak-tight and fail safe
shutoff valve which, in addition to controlling the
mass flow of pilot gas, is also part of the gas block.
Pilot gas is used to start the gas turbine. The pilot gas
control valve regulates the amount of natural gas
that flow through the pilot gas burner. The flow of
pilot gas is set as a function of Nox emission data,
flame stability, and the humming behavior of the gas
turbine.
Presentation title - 12/12/2012 - P
2
Fuel Gas system
atural gas Temperature Monitoring
In the standard configuration, the natural gas system is
equipped with three resistance thermometers MBP13CT101,
MBP13CT102, MBP13CT103 located in the natural gas supply
line upstream of the natural gas ESV. An alarm is
announciated if at least two of these three thermometers
indicated limit T. GAS.01 has been exceeded. Natural gas
temperature readings are used by the gas turbine controller
to correct the lift setpoint for the premix and pilot gas control
valve

Presentation title - 12/12/2012 - P


2
Fuel Gas system

tural gas pressure monitoring


The amount of natural gas that combusts in the gas turbine combustion
chamber is a function of the supply pressure of the gas, the lift of the
natural gas control valve and the combustion chamber pressure. Natural
gas pressure is measured upstream of the natural gas emergency stop
valve by pressure transducers MBP13CP101,102,103 and downstream of
the natural gas emergency stop valve by pressure transducer
Operating
MBP14CP101.
mode : If the natural gas pressure (MBP14cp101) downstream of the
natural emergency stop valve exceeds limits P.GAS.11, the
pretrip alarm NG pressure downstream of NG ESV TOO HIGH
>MAX is annuciated

Presentation title - 12/12/2012 - P


2
Fuel Gas system
Triggering of Trip
Triggering of trip becomes necessary if any operating condition accur
that poses an immediate Threat of the gas turbine. When the natural
gas system trip is triggered, the natural gas ESV And both control
valve simultaneously receive a close command. The circuit of the
hidrauliCally actuated valve that initiated trip are opened in response
to the close command and Valve are closed very rapidly by their
closing springs and than NG pressure relief valve is Opened.