ABB Group - 1 -
22-Jun-17
Distance Protection in SC Lines
Benefits of Series compensated lines
Improvement in stability margins
Improved load division on parallel paths
Reduction in transmission losses
Ability to regulate power flow
Reduction in the voltage drop on the system
during severe disturbances
ABB Group - 2 -
22-Jun-17
Distance Protection in SC Lines
Conventional spark gap-protected capacitor
L Bypass circuit-breaker R
Airgap
X11 XC X12
Protection Location
XSL XSR
ABB Group - 3 -
22-Jun-17
Distance Protection in SC Lines
MOV protected capacitor
Bypass circuit-breaker
L Airgap R
Metal Oxide Varistor (MOV)
X11 XC X12
Protection location
XSL XSR
ABB Group - 4 -
22-Jun-17
Distance Protection in SC Lines
Protection problems encountered
L CR
CL CR X12 = 100%
XC = 70%
X11 = 0%
R
C R
L CL
70 %
CR
Forward faults may appear to the distance relay in the reverse direction
Faulty-phase polarized directional measurement detects the fault in the
ABB Group - 7 -
wrong direction.
22-Jun-17
Pre-fault voltage
Fault voltage
U UM
Source
XS XL1
~
IF XC
X S X L1 X C
Source voltage
UM
Fault voltage
Source
XS XL1
~
IF XC
X C X S X L1
Zone 2L
L R
Zone 1L
X12
X11
XC Zone 1R
DL DR
Zone 2R
Zone 2L
L R
Zone 1L
G X12
X11
XC Zone 1R
DL DR
Zone 2R
ABB Group - 11 -
22-Jun-17
Distance Protection in SC Lines
Permissive overreach distance protection
L R
Permissive Zone LEFT
X12
X11
XC Permissive Zone RIGHT
DL DR
ABB Group - 12 -
22-Jun-17
Distance Protection in SC Lines
Influence of Protection in adjacent power
lines by the negative impedance
A1 L
X1
X
XC
A2 I1
X2 X11
I
X 11
A3 I1
I2
X3 I
I
DA1
XC
I3 I1
DL
DA2
DA3
X1
X C X 11
Z r1
I X r1
X r1 X 1 XC X 11 R
I1
I
X r2 X 2 XC X 11
I2
I
X r3 X 3 XC X 11
I3
Reactance Xr1, seen by the relay at station A1
I1 I 2 I 3 I
instantaneous zone
Distance Protection in SC Lines
Quadrilateral characteristic, cross-polarised
X12
X11
ZS
XC
ABB Group - 14 -
22-Jun-17
Distance Protection in SC Lines
Negative fault current
L R
I1 I2
XL11 XC XL21
XL10 XL20
XSL1 XSR1
XSL0 XSR0
Xa0 - X0M- XC
Xa0
X0M
Xa0
XC
}X
0M Xa0 - X0M- XC
XC
ABB Group - 16 -
22-Jun-17
Distance Protection in SC Lines
Current inversion phenomena
L R L R
L1 L1
L2 L2
Protection location
ABB Group - 17 -
22-Jun-17
Distance Protection in SC Lines
Double circuit series-compensated power
lines
The capacitor will compensate the self impedance in
the zero sequence network while the mutual
impedance will be the same as on non-compensated
power lines. The effect of the mutual impedance will
therefore be worse than for non-compensated double
lines.
If there exists negative impedance and negative fault
current at the same time and a good phase selection is
required for single pole autoreclosure, the distance
protection system will be faced with difficult
measurement problems.
ABB Group - 18 -
22-Jun-17
Distance Protection in SC Lines
Other problems
Subsynchronous transients and oscillations
Gap flashing transients
ABB Group - 19 -
22-Jun-17
Distance Protection in SC Lines
Series compensated lines and sub-synchronous
oscillations
A B C
~ Load
Series
capacitor Fault
X
Locus of transient
fault impedance
ABB Group - 20 -
A
22-Jun-17
Distance Protection in SC Lines
ABB Group - 21 -
22-Jun-17