REB500

Industrial IT enabled
1 Breaker
solutions
2003 ABB. All rights reserved. - 1
2003-03-18
REB500 1 Breaker solutions Variant 1

Variant 1 T-Zone / STUB Protection


3 Bay Units
BU BU BU
1 2 3
BB1 BB2 Protection Functions:
X Y BBP, BFP, EFP
If Q6 is closed, the zone is
Q6 Q6
protected via LP / TP
Q6 is open, the LP / TP can
LP TP not protect the zone anymore
=>
L1 L2

REB500 will take over this


part as differential & current
directional comparison
protection with all its
2003 ABB. All rights reserved. - 2

advantages =>
CT saturation / external faults
This is more reliable than OC
2003-03-18
REB500 1 Breaker solutions Variant 2

T-Zone / STUB Protection


3 Bay Units
Variant 2
Protection Functions:
BU BU BU BBP, BFP
1 2 3
BB1 BB2
X
=> see variant 1 but without
Y
EFP
Q6 Q6

LP TP

L1 L2
2003 ABB. All rights reserved. - 3
2003-03-18
REB500 1 Breaker solutions Variant 3

T-Zone Protection
Variant 3 5 Bay Units
Protection Functions:
BU BU BU
1 2 3
BBP, BFP, (EFP is integrated
BB1 BB2
X
in coupler function)
Y
T-Zone is always protected via
REB500
BU BU
4 5 Only 1 BU more per line
LP TP
instead of a complete
separate differential protection
L1 L2
2003 ABB. All rights reserved. - 4
2003-03-18
REB500 1 Breaker solutions Variant 4

T-Zone Protection
Variant 4 8 Bay Units
Protection Functions:
BU BU BU BU BU BU
1 2 3 4 5 6 BBP, BFP, (EFP is integrated
BB1 BB2
X Y in coupler function)
T-Zone is always protected via
REB500
BU BU
7 8
Only 1 BU more per line
LP TP instead of a complete
separate differential protection
L1 L2
2003 ABB. All rights reserved. - 5
2003-03-18
REB500 1 Breaker solutions Variant 5

Variant 5 1 Breaker scheme is


handled as 2 single
L1 L1
busbars
=> 2 bay units per
BU BU BU
Diameter
1 2 3

L2

BU BU BU
L2 4 5 6
2003 ABB. All rights reserved. - 6
2003-03-18
REB500 1 Breaker solutions with EFP

RT1 RT2

BBI BBII

CB A CT1 CT2 CB B CT3 CB C

1
RT = Remote trip

Trip All All


CBs CB A RT 1 CB B RT 2 CB C CBs Remarks
Fault BBI BBII

CB A closed and
1 1.STEP 1.STEP 2.STEP 2.STEP
faulty
2003 ABB. All rights reserved. - 7
2003-03-18
REB500 1 Breaker solutions with EFP

RT1 RT2

BBI BBII
CB A CT1 CT2 CB B CT3 CB C

2
RT = Remote trip

Trip All All


CBs CB A RT 1 CB B RT 2 CB C CBs Remarks
Fault BBI BBII

2 1.STEP 1.STEP 2.STEP 2.STEP


2003 ABB. All rights reserved. - 8

Un- Un- CB A Open


2 End fault
delayed delayed
2003-03-18
REB500 1 Breaker solutions with EFP

RT1 RT2

BBI BBII
CB A CT1 CT2 CB B CT3 CB C

3
RT = Remote trip

Trip All All


CBs CB A RT 1 CB B RT 2 CB C CBs Remarks
Fault BBI BBII

3 1.STEP* 2.STEP 1.STEP 2.STEP 2.STEP B CLOSED AND


2.STEP FAULTY
2003 ABB. All rights reserved. - 9

1.STEP* A CLOSED AND


2.STEP 2.STEP 2.STEP 1.STEP
FAULTY

* If ext. prot. selective


2003-03-18
REB500 1 Breaker solutions with EFP

RT1 RT2

BBI BBII
CB A CT1 CT2 CB B CT3 CB C

4
RT = Remote trip

Trip All All


CBs CB A RT 1 CB B RT 2 CB C CBs Remarks
Fault BBI BBII

4 2.STEP 2.STEP 1.STEP 2.STEP 1.STEP


2003 ABB. All rights reserved. - 10

Un- Un- B Open


4 End fault
delayed delayed
2003-03-18
REB500 1 Breaker solutions with EFP

RT1 RT2

BBI BBII
CB A CT1 CT2 CB B CT3 CB C

5
RT = Remote trip

Trip All All


CBs CB A RT 1 CB B RT 2 CB C CBs Remarks
Fault BBI BBII

5 1.STEP 2.STEP 1.STEP* 2.STEP C CLOSED AND


2.STEP FAULTY
2003 ABB. All rights reserved. - 11

B CLOSED AND
2.STEP 2.STEP 1.STEP 2.STEP 1.STEP*
2.STEP FAULTY

* If ext. prot. selective


2003-03-18
REB500 1 Breaker solutions with EFP

RT1 RT2

BBI BBII
CB A CT1 CT2 CB B CT3 CB C

6
RT = Remote trip

Trip All All


CBs CB A RT 1 CB B RT 2 CB C CBs Remarks
Fault BBI BBII

Un- Un- C Open


6 End fault
delayed delayed
2003 ABB. All rights reserved. - 12
2003-03-18
REB500 1 Breaker solutions with EFP

RT1 RT2

BBI BBII
CB A CT1 CT2 CB B CT3 CB C

6
RT = Remote trip

Trip All All


CBs CB A RT 1 CB B RT 2 CB C CBs Remarks
Fault BBI BBII

6 2.STEP 2.STEP 1.STEP 1.STEP


2003 ABB. All rights reserved. - 13

Un- Un- C Open


6 End fault
delayed delayed
2003-03-18
REB500 1 Breaker solutions with EFP

RT1 RT2

BBI BBII

CB A CT1 CT2 CB B CT3 CB C

RT = Remote trip

Trip All All


CBs CB A RT 1 CB B RT 2 CB C CBs Remarks
Fault BBI BBI
I
2003 ABB. All rights reserved. - 14

CB C closed and
7 2.STEP 2.STEP 1.STEP 1.STEP
faulty
2003-03-18
REB500 1 Breaker solutions STUB
BB 1
x Busbar 1 protected by REB500

Transformer protection

1 1/2 breaker system,


one ct per circuit breaker,
Endfault protection within REB500 no ct per feeder (Line, Transformer)
x

Isolator closed: Protected by line protection.


Isolator open: Protected by REB500
STUB
protection
2003 ABB. All rights reserved. - 15

Busbar 2 protected by REB500

BB 2
2003-03-18
REB500 1 Breaker solutions T-Zone
BB 1

x Busbar 1 protected by REB500

Transformer protection

1 1/2 breaker system,


T-Zone
protection one ct per circuit breaker,
one ct per feeder (Line, Transformer)
x

Endfault protection within REB500

Protected by REB500 Protected by line protection

T-Zone
protection
2003 ABB. All rights reserved. - 16

Busbar 2 protected by REB500

BB 2
2003-03-18
2003 ABB. All rights reserved. - 17
2003-03-18