You are on page 1of 10

MEP ENGINEERING DESIGN

www.ny-engineers.com
Cooling Tower System Replacement

 Cooling Tower System Replacement:


• Architects, engineers and other professionals in the green construction industry can add great value to their professional record by
becoming LEED Green Associates and Accredited Professionals. Green buildings are a strong trend in the construction industry globally, and
professionals with LEED credentials can gain a significant competitive advantage.
• Open-circuit or direct contact cooling towers are the most common type, where water is supplied to the tower after gathering heat, and
sprinkled on the upper side while a fan establishes an upward airflow. This causes part of the water to evaporate, lowering its overall
temperature. Although this method is effective, it comes with several limitations:
• Extra water must be supplied to compensate for evaporation losses.
• Since water is in direct contact with the atmosphere, it must be constantly treated to avoid the accumulation of particles and bacteria.
• Although open circuit cooling towers are simple, they are not the most efficient option available: there are alternatives offering
enhanced energy efficiency and simpler maintenance. The cooling tower and its associated water pump normally represent around 15% of
energy consumption in chilled water systems. Therefore, any upgrades that increase their energy efficiency offer an attractive financial return.
Closed-Circuit Cooling Towers with Adiabatic
Cooling

• A closed-circuit cooling tower is also based on the principle of evaporative cooling, but the water used by processes or
chillers is never in direct contact with the atmosphere; instead, it circulates through a coil inside the cooling tower, and
water from a separate supply is sprinkled to achieve the evaporative cooling effect. When adiabatic cooling is deployed,
most of the heat rejecting is achieved with only the fan; water sprinklers are controlled precisely so the amount of water
supplied is exactly as needed to complement the natural cooling effect of air.
• Adiabatic cooling offers various advantages over conventional open-circuit cooling towers:
• Water is kept free from particles. This allows pumps, chillers and other system components to operate more efficiently,
while increasing their service life.
• Water treatment and maintenance costs are greatly reduced. The water volume that requires treatment is significantly lower
than in open-circuit cooling towers.
• Intermittent use of sprinklers saves both water and energy.
• In general, adiabatic cooling can reduce operating costs by up to 30 percent, compared with conventional open-circuit
cooling towers.
Plate Heat Exchangers with Open-Circuit
Cooling Towers
• An alternative to adiabatic cooling is to keep the conventional cooling tower, but isolating it
from the process or chiller plant with a plate heat exchanger. In simple terms, the heat
exchanger separates the water circuit in two segments:
• In the first segment, water circulates between the heat exchanger and the process or chiller
from which heat is removed.
• In the second segment, water moves between the cooling tower and the heat exchanger.
• This way, heat can be released outdoors without mixing both streams of water.
• Since the heat exchanger is already isolating the cooling tower from the rest of the system, a
conventional open-circuit tower can be used. In fact, combining a closed-circuit cooling
tower and a heat exchanger is redundant and a waste of money
Additional Enhancements to Cooling
Tower Systems
• Cooling towers can be upgraded to higher-performance systems, but it is also possible to upgrade individual system
components to further enhance energy efficiency and operating flexibility.
• Speed Control for Fans and Pumps
• Both conventional cooling towers and adiabatic coolers use a fan to establish the required airflow. When the system is
operating under part-load conditions, fan speed can be reduced to achieve significant energy savings. This is accomplished
with a variable frequency drive (VFD), a device that adjusts the supply voltage and frequency to reduce motor speed below
its nameplate value.
• In open discharge fans, like those of cooling towers, the power savings achieved are proportional to fan speed cubed. This
means that a cooling tower fan operating at 80% speed would only be consuming 51.2% of its rated power (80% x 80% x
80%).
• To improve energy savings further, a VFD can be used to control the water pump as well. Using a control system, the speed
of both motors can be coordinated to match the cooling load precisely, minimizing overall energy consumption.
Waterside Economizer: Heat Exchanger
Between Water Circuits in a Chiller Plant
• In the case of chiller plants, it is possible to increase overall efficiency by installing
another heat exchanger, but in this case between the condenser water circuit and
chilled water circuit. This type of heat exchanger is called a waterside economizer,
and it may allow removal of heat from the chilled water circuit before it reaches the
chiller, which must only provide the extra cooling effect that isn’t possible with the
heat exchanger.
• It is important to note that this approach is only possible under certain weather
conditions, and its effectiveness is diminished as relative humidity increases. For
example, a waterside economizer is a much better investment in New York City than
in South Florida.
NEMA Premium Motors

• Fan and pump motors are responsible for most of the energy consumption in cooling towers and their respective water
circuits, and there are plenty of applications where they operate for 24 hours a day. Therefore, it is possible to achieve
significant energy savings by replacing these motors with higher-efficiency models.
• Motors in the USA have three efficiency levels, where NEMA Premium indicates the highest performance. For example,
the average efficiency levels of a 460 V, 15 HP, 1800 rpm, totally-enclosed fan-cooled motor are be the following, according
to NEMA:
• Standard Efficiency: 86.6%
• Energy Efficient: 91.1%
• Premium Efficiency: 92.4%
• In this case, upgrading from standard to premium efficiency would represent an increase of 5.8 percent. Yearly savings
increase in proportion to the total hours a motor is used each year, which is typically high in the case of cooling towers.
Concluding Remarks
• Cooling towers play a very important role in both commercial and industrial settings. In large commercial facilities, water-
cooled chillers are far superior to their air-cooled counterparts for air conditioning; although air-cooled chillers don’t need a
cooling tower, the energy efficiency advantage of water-cooled chillers compensates the extra cost. In industrial settings,
water is a practical and highly available cooling medium, and cooling towers are a cost-effective way of removing heat from
water for recirculation.
• Complementing a cooling tower with a heat exchanger simplifies maintenance by isolating cooling water from the
environment, and adiabatic coolers offer this plus enhanced energy efficiency. If such an upgrade is complemented with
high efficiency motors and VFDs for speed control, maximum system efficiency can be achieved.
• High performance is easier to achieve when HVAC systems are first installed, and can be more expensive for existing
installations. Hiring a qualified engineering firm for design, consulting and supervision ensures that cooling towers and
other building system are specified correctly, while considering energy efficiency and total cost of ownership.

US OFFICE WEBSITE
275 WEST 39TH STREET, 2ND www.ny-engineers.com
FLOOR NEW YORK, NY 10018.
REQUEST A PROPOSAL
INDIA OFFICE
Michealt@ny-engineers.com
C-1010, TEERTH TECHNOSPACE,
BEHIND MERCEDES BENZ PRESS INQUIRIES
SHOWROOM,
MUMBAI-BANGALORE HIGHWAY, Ravindra@ny-engineers.com
BANER, PUNE, MAHARASHTRA
411045.

You might also like