Professional Documents
Culture Documents
1
Klas C. Haglid, P.E., R.A., CEM - Bio
• ASHRAE Distinguished Service Award
• 2011 ASHRAE Handbook, HVAC Applications and Management, Chapter 37,–
Author, Klas C. Haglid P.E. R.A.
• ASHRAE Standard 189.1, Corresponding Member
• GPC 32P - Sustainable, High Performance Operations & Maintenance, Voting
Member, Contributing, Co-Author
• Technical Committee 5.5 - Air-To-Air Energy Recovery, Handbook Subcommittee
Chairman, Past Chairman
• Technical Committee 7.6 - System Energy Utilization, Voting Member
• Technical Committee 7.8 - Owning and Operating Costs of Commercial Buildings,
Past Chairman
• ASHRAE Standard 84-1991R, Voting Member
• Reviewed draft of ASHRAE Standard 84-1991R and provided engineering details for
efficiency calculations.
2
Challenge
• Complying with ASHRAE Std. 62.1-2010 to
improve IAQ while increasing energy efficiency
ASHRAE Std. 90.1 can be accomplished with:
– Displacement Ventilation
– Demand Controlled Ventilation
– Energy Recovery Ventilator
– Variable Speed Drives
3
ASHRAE Std. 62.1-2010
• Ventilation for Acceptable Indoor Air Quality
– How to determine minimum prescriptive
ventilation rates
– How to use Demand Side Ventilation to meet
ASHRAE Standard 62.1-2010
4
Definitions
• “acceptable indoor air quality: air in
which there are no known contaminants at
harmful concentrations as determined by
cognizant authorities and with which a
substantial majority (80% or more) of the
people exposed do not express
dissatisfaction.” –ASHRAE Standard 62.1-2010 pg. 3
5
6.1.1 Ventilation Rate Procedure
• The following procedure for determining the
minimum prescriptive ventilation rates can be
used on any zone type.
• 6.1.1 Takes into consideration:
– Space type
– Number of Occupants
– Floor Area
– Typical contaminant sources and source strength
6
Ventilation Rate Procedure -
Breathing Zone Outdoor Airflow
• Vbz = RpPz + RaAz where:
7
Office Example
What is the prescriptive design for outdoor air (cfm) of a 1500 square foot office
with 12 occupants?
8
School Example
What is the prescriptive design for outdoor air (cfm) of a 1100 square foot
classroom with 30 students?
9
General Manufacturing Example
(Excludes Heavy Industrial and processes using chemicals)
What is the prescriptive design for outdoor air (cfm) of a 50,000 square foot coat
hanger production facility with 20 machinists?
Notice the Area outdoor air rate (Ra) increased for a manufacturing facility.
10
Ventilation Rate Procedure –
Zone Outdoor Airflow
• Voz = Vbz/Ez
(Partial Table)
11
Methods of Providing Outdoor
Air to Zone
• Dilution Ventilation
• Displacement Ventilation
12
Dilution Ventilation
It’s important to design ventilation system to have maximum air
distribution. This will help eliminate dead space and short circuiting of
air flow
13
Dilution Ventilation
• Typical in U.S. construction
14
Displacement Ventilation
Diagram shows good air circulation providing fresh air on one end of room and
exhaust pulling air out on the other end to maximize removing contaminant
concentrations
15
Displacement Ventilation (DV)
• Uses natural convection to provide “Buoyancy-
assisted forced ventilation”
16
Displacement Ventilation
• Using displacement ventilation and then measuring
air quality of the space is an effective way to improve
IAQ
17
Demand Controlled Ventilation
(DCV)
• “any means by which the breathing zone
outdoor airflow (Vbz) can be varied to the
occupied space or spaces based on the actual
or estimated number of occupants and/or
ventilation requirements of the occupied
zone.” – ASHRAE Std. 62.1-2010 pg. 4
18
Example of DCV Methods
Fan
Relays
EA
ERV
SOA
CO2 Sensor
comes on over
700 ppm and ERV- Energy Recovery
turns off under Ventilator
600 ppm
People EA- Exhaust Air
19
DCV
• CO2 concentrations in outdoor air generally range from 300 to 500
ppm
• ASHRAE std. 62.1 2007 and 2010 recognize 700 ppm of CO2 above
outdoor ambient levels or 1000 to 1200 ppm to be acceptable air
quality for an indoor space. Reference page 37 of Appendix C
• DCV can reduce runtime from 168 hours per week to 30 hours per
week for a classroom. That is an 82% reduction in runtime.
20
Summary of Ventilation Rates
• Determine prescriptive design ventilation rate for zone
by using Ventilation Rate Procedure
21
Not All ERVs Are the Same
• ERV Features to Compare:
– Airflow Arrangement
• Thermal Effectiveness
– Pressure Drop
– Fan Efficiency
– Maintenance
– Sound Levels
22
Heat Exchanger Airflow Arrangement
ASHRAE states:
• Counter-flow heat exchangers are theoretically
capable of achieving 100% Sensible Effectiveness*
24
Example
• What is the percent difference in BHP required
to run a ventilation system if alternative 2 has
a 50% increase in static pressure from
alternative 1?
• Altenative 1 Conditions:
– CFM = 8,000
– SP = 1” in wg
– BHP = 5
– RPM = 1000
25
Example Continued
• Rearranging Eq (2):
– RPM2 = SP2/SP1 x RPM1
– RPM2 = 1.5/1 x 1000 = 1225
Eq (3):
BHP2 = BHP1 x ( RPM2/RPM1)3
BHP2 = 5 x ( 1225/1000)3 = 9.2 BHP
9.2-5/5 = 84% Increase
26
High Efficiency Fans
• Typical fan efficiency can range from 5 to 10 W/cfm
BTUs Recovered
EER =
Watts of Fan Power
27
Efficiency is Essential
160
140
120
100 High Eff. ERV
80 Typical ERV
60
40 Typical ERV has an
EER of around 10.
20 High efficiency ERV
0 can be well above
Effectiveness (%) Fan Power (W) EER (BTU/W) 120.
28
Maintenance Costs are Essential
• There’s more to a product than its initial costs and
efficiency – Maintenance costs can make or break your
bottom line
• Look for :
• Corrosion resistant equipment
• Minimal moving parts
• Low static pressure
• Use appropriate filter type for equipment
29
Tools to Meet ASHRAE Std. 62.1 and Improve IAQ
While Increasing Energy Efficiency, ASHRAE Std. 90.1
• Displacement Ventilation
• Demand Controlled Ventilation
– CO2 controls or other contaminant monitoring sensors
• ERV
– Counter flow heat exchanger
– Low Pressure Drops
– High efficiency fans
• Variable Speed Drives
– Air balancing
– Better control
30