Professional Documents
Culture Documents
Handbook Structure
© ABB Group - 1 -
28-Mar-18
Control System Structure
Equipment included in control
system
Auxiliary supplies
Protection system
Metering equipment
Control and regulation
Signaling and event recording
Operation
© ABB Group - 2 -
28-Mar-18
Control System Structure
CT location
Fault signalling
Annunciator system
Event recorder
Disturbance recorder
SCADA
© ABB Group - 20 -
28-Mar-18
Control System Structure
Inerlocking
Documentation
Electrical design documents
Operation and maintenance manuals
Erection manuals
© ABB Group - 22 -
28-Mar-18
CBIP manual on Protection
of Generators, generator Location of CTs and
transformers and 220kV VTs in Substations
and 400 kV networks
© ABB Group - 23 -
28-Mar-18
Control System Structure
1.0 GENERAL
2.1
• The CTs shall be placed near the circuit breakers (CBs) and on the line
side
• The detection zones of line relays and busbar relays start at the CTs. It
is advantageous if these two points are close to each other.
• It is usual to locate the CTs on the line side after the CBs
• To get the line current the secondary current of the two CTs are summated
© ABB Group - 29 -
28-Mar-18
Control System Structure
2.2.5 One and a Half Breaker Station
- Paralleling of two CTs to the main line protection is not required. This
gives better transient response
• CVTs can also be used as coupling capacitors for power line carrier
(PLC)
• They are then to be located at the line side of the line traps and line
earthing switches(as shown in Fig.5)
• For 400kV level it is recommended that each line bay is provided with
CVTs all the three phases
© ABB Group - 32 -
28-Mar-18
Control System Structure
• Even for 220kV substations it is preferable to provide three phase
CVTs in each phase for each line bay
• Three phase VTs / CVTs on the busbars provide input for directional
relays and reference voltage for synchronization