You are on page 1of 52

HV SYSTEM

The power station CONTROL ROOM

STEP UP
TRANSFORMER LV SWITCHGEAR

AC & DC
HV- BREAKER AUXILIARY
SYSTEMS CONTROL
SYSTEMS

2 1
AUX. PROTECTION
TRANSF.
GOVERNOR
GENERATOR
1 BREAKER 2
STATIC
STARTER

PT’s
&
CT’s
SYNCHRONIZING

SYNCHRONOUS EXCITATION
TURBINE GENERATOR SYSTEM

STAR
POINT EXCITATION
CUBICLE TRANSFORMER
Overview of Electrical Systems

• Generators •EHV protections


• Excitation System •Black Start DG set
• Transformers •DC Systems
• MV Switchgear •415 V Systems
• EHV Switchgear •Fire protection
systems
• Generator
•Switchyard
protections
Equipments
General Classification

ELECTRICAL SYSTEMS

AC 50 Hz SUPPLY SYSTEM D/C SYSTEM

220 KV 3 PHASE FOR BULK 220 V FOR UPS &


POWER TRANSMISSION EMERGENCY SYSTEMS
10.5 KV,15.75 KV 3 PHASE
GENERATOR OUTPUT 24 V FOR SOLENOIDS,
VOLTAGE CONTROLLERS
6.6 KV 3 PHASE FOR STATION
AUXILLIARIES 48 V DC IN SWITCHYARD

415 V 3 PHASE FOR LOW VOLTAGE


AUXILLIARIES

240 V SINGLE PHASE SUPPLY


GENERAL SINGLE LINE DIAGRAM
Turbo generator
Excitation system Generator details

–Providing variable DC current with


short time overload capability GAS TURBINE GENERATOR :
170.12 MVA,10.5kV,field voltage
–Controlling terminal voltage,MVAR 410 V,stator current-9354 A- 2
and PF with suitable accuracy No
STEAM TURBINE
–Ensure stable operation with
network and / or other machines GENERATOR : 188.23 MVA,
15.75kV,field voltage 432 V,stator
–Keep machine within permissible current-6900 A- 1 No
operating range Air cooled, 3000 RPM, 2 pole,
double star.
–Contribution to transient stability
subsequent to a fault. Four coolers in the generator for
cooling the air.
–Communicate with the power plant
control system
GT Generator

• Apparent power • 170.12MVA


• Active Power • 144.6MW
• Current • 9354A
• Voltage • 10.5KV+/-5%
• Speed • 3000rpm
• Frequency • 50Hz
• Power Factor • 0.85
• Stator Winding • YY
• Rated Field current • 833A
• Rated Field Voltage • 410V
STG Generator

• Apparent power • 188.23MVA


• Active Power • 160MW
• Current • 6900A
• Voltage • 15.75KV+/-5%
• Speed • 3000rpm
• Frequency • 50Hz
• Power Factor • 0.85
• Stator Winding
• YY
• Rated Field current
• 798A
• Rated Field Voltage
• 432V
Steam Turbine Generator
If Synchronous Ug
Machine Grid

Excitation
System

Controller

The automatic voltage control system


High voltage line Characteristic of Static Excitation System:
+ direct measuring of field -current, -voltage
Unit step up transformer
+ superior dynamic performance
(fast response)
Excitation transformer
+ field voltage reversing feature

+ very effective field discharge


AVR
Sensing PT
+ Ceiling factor not limited

+ field ground dedection availabel


SM
+ superior MTBF, MTTR
Thyristor Converter

Synchronous machine - Sliprings

Static Excitation System


Brush less excitation system

• Just positive ceiling voltage


capability

• Exciter response limited by the


exciter machine time constant
(>200ms)

• Field discharge with natural time


constant

• Supply from PMG possible


providing supporting of short
circuit currents

• Relative large size of exciter


machine for low speed generators

• No sliprings (less maintenance


and dust)
Neutral terminal

• Grounding transformer
used to reduce fault
currents.
• The 100% stator earth
fault detection is also done
through this transformer
Starting system

• SFC manufacturer-AEG Germany


• Rating-2.9 MW
• Modes of operation:washing at 600 rpm
• Boiler purging at 900 rpm
• Unit black start at link circuit current 2.7 MW 1360 RPM
• Power operation at max dragging 2.9 Mw 2100 RPM
Transformers

• Generator transformer
• Unit auxiliary transformer
• Excitation Transformer
• MV/LV Transformers
• Lighting Transformers
Generator transformer UAT
• Three Phase, 153.5 MVA, • Rating 25 MVA 10.5/6.9
BHEL make. kV
• Delta Star, neutral solidly • Cooling: ONAN/ONAF
grounded.
• Quantity of oil-13095
• 10.5/230 kV.
liters
• Cooling-
ONAN/ONAF/OFAF • On load tap changer at 12
• Off circuit Tap changer at positions
five positions
• Oil quantity:-39715 liters
Busduct and UAT

Gen. Transformer
System
• There are two Unit Transformers connected thru
GT, 10.5 KV Bus.
• These two Transformer make 2no. 6.6KV bus ( 11
&12 BBE) which in turn make another 2 bus thru
Ties.(OCA- A&B)
• A total 4no 6.6KV bus exists which are
interconnected thru Ties and Bus coupler.
• DG is also connected to OCA (A&B) bus thru
6.6KV Breakers.
6.6KV BUS SYSTEM
Changeover Schemes

Changeover Schemes are divided in Two Group:


A. With Paralleling
B. Without Paralleling
Here there are Four Types of Schemes under these
Categories:
• MANUAL Changeover
• FAST Changeover
• SLOW Changeover
• BLACKOUT Condition
Manual Changeover Scheme

Features:

• It is a planned changeover.
• Thru Operator Intervention.
• No Interruption in Voltages.
• Thru Synchronizing Relay
Manual Changeover Scheme
Scope:

1. Bus coupler at OCA


2. UAT Incomer ( BBE01&2)
3. DG Breaker 1&2
4.Tie Breaker at OCA( Tie1 &2)
Manual Changeover Scheme

Example :

U1-B/C-U2 Changeover:
--Proven scheme
--Either of Breaker can be closed thru ECB.
--Choice of Breaker tripping is done thru Trip
selection switch.
Fast Changeover Scheme

Feature:
• This is only for OCA Bus coupler.
• This changeover occurs when Voltage sink is
likely to occur.
• OCA Bus coupler will close in Auto without any
time delay. No manual Intervention possible.
• This changeover will take place in less than
200millisecond, hence chances of supply
interruption is very less.
Slow Changeover Scheme

Features:
• This is a backup of Fast changeover.
• Bus coupler will close in auto after certain
Time delay and fulfillment of certain
condition
• Chances of unit survival depends on
situation
Black Out Condition

Normally blackout condition means:


• 1. All GCB and HVCB open.
• 2. Both Unit Incomer Breakers Open
• 3. No Auxiliary Power at station.
At this moment our attempt to restore the
Auxiliary power as soon as possible.
Black Out Condition

Under this Condition:


• DG set will take start in Auto
• All Aux. Feeders at OCA Bus will Trip
• Both DG Breakers will closed in Auto.
• Priority Transformer feeders will close in Auto,
also their LT Incomers(except PCC)
• Tie feeders at OCA and PCC will not Trip
• This all will be done thru Logics As:
Black Out Condition Contd.

If due to any reason DG fail to start or DG Breaker


does not close in Auto :
• Start DG Manually
• Close the DG Breakers one by one
• Close the Priority feeders one by one.
Black Out Condition --Normalisation

2. Thru GT1 and GT2 Transformer :


• Back charge the transformer and close the U1 and
U2 breaker thru manual Changeover. D1 and D2
will trip respectively in auto.
3. Thru Unit Start Up.
• Start Gas Turbine1/2 in Black Start mode. U1/U2
Breaker will close and D1/D2 will Trip in Auto.
Black Out Condition
Others:
• During D1/D2 close condition—
• Only Priority feeders can be closed- i.e ODA A
&B Breaker( Only emergency section, ODC I/c-
A&B, and Common transformer breaker.)
• Other than Priority 6.6 KV fdr , no 6.6 KV fdr can
be closed
• 415V,ODA-B/C D&E , CW &Chlorination fdr.,
OSF MCC, Nox and Misc MCC can not be closed.
Supply to Switchyard

Switchyard
EHV Control and Switchgear
• Circuit Breaker
• Isolator
• Current Transformer
• Capacitive Voltage Transformer
• Lightning Arrestor
• PLCC equipment
• Bus Switching Schemes
• Disturbance recorder
• Event logger
• Remote telemetering units
Line diagram
Bus Switching Schemes
Double main and Transfer bus scheme
Main Bus-2
Main Bus-1

Bus Coupler
Transfer
Bay

Transfer Bus

3 Generators 4 Transmission
lines
PLCC System
Substation A Substation B
Wave trap

CVT
Tx Tx
Rx Rx
Electrical Protections
• Generator and transformer protections
• 6.6 kV Protections
– Station transformer protections
– Motor protections
– Transformer protections
• 220 kV Protections
– Line protections
– Bus bar protection
– Breaker failure protection
VT Panel Protection Panel Terminal Box
Protection
Panel
Numerical Relays
Backside of relays
Tripping Matrix

Tripping Relay
Generator Protection:
Protection Functions (1)

27 81O
59 81U

87G
87G Generator differential
50/51 Over current protection
50 51V 51V/21 Voltage dependent backup
51
21 50/51N Stator earth fault
67N 50N
51N
59N Neutral displacement
67N Sensitive directional E/F
59N 27TN 27TN 100% Stator E/F
27 & 59 Under & over voltage
81U/O Under & over frequency
Generator Protection:
Protection Functions (2)

24 32R Reverse power


32L Low forward power
32O Overload power
RTD
40 Field failure
46 Negative phase seq.
40 46 24 Overfluxing
32R
32L
27/50 Dead Machine (GUESS)
320
38/26 RTD Thermal protection
Interconnection
df/dt rate of change of frequency
dVø Voltage vector shift

MiCOM-P340-42
Settings

• Reverse Power Frequency • -3.3 %


• Under frequency
• Overfrequency • 47.5 & 47.0 Hz
• 51.5 & 52 Hz
• Rotor earth fault • 5Kohm and 40 Kohm
• Stator earth fault • 14ohm
• Over Voltage • 127V/ 143V
• Under Voltage • 70V
• Over Current • 125%
• Under Excitation • 5.04V
• • 1.1-1.4
Overflux
• 25%
• Generator Differential • 33%
• Overall Differential • 33%
• REF • 5V
• Stator earth fault(95%) • 51% , 1.5Sec
• Unbalanced Load
STG GRP
6.6 kV Protections
• Station transformer protections
– Three phase Over current protection.
– Earth fault protection.
– Restricted earth fault protection.
• Motor protection
– IDMT over current protection
– Earth fault protection
• Transformer protection
– IDMT over current protection
– Earth fault protection
EHV Protections
• Line protections
• Transformer protections
• Generator Protections
• Bus bar protection
• Breaker failure protection
Line protections
• Main I Distance protection (21-1)
• Main II Distance protection (21-2)
• Breaker failure relay.
• Trip circuit supervision relay
• Trip coil supervision relay.
• Fault locator
• Disturbance recorder
Distance Protection
Zone 3: 200%,1000mS
Zone 2: 120%,300mS
Zone 1: 80%, 0mS

A B
220 kV Transformer protections
• Transformer Differential protection.(87)
• Three phase over current protection. (51)
• Earth fault relay (Phase current balance)
• Breaker failure relay.
• Bucholz relay
• Winding temperature relay
• Oil temperature relay
• Pressure relief device
DC SYSTEM
DC Systems
• 220 Volts DC Gas Turbine batteries
• 220 and 24 Volts Station batteries
• 432 Volts UPS batteries
• 220 Volts Emergency Lighting batteries
• 48 V Switchyard Battery systems
415 Volts System
• GT MCCs
– All the LT auxiliaries of Gas turbine including:
• Auxiliary lube oil pump
• Generator cooling water pump motors
• GT cooling water pump motors
• Ventilation fans
• Battery chargers
• Jacking oil pump motor

You might also like