Professional Documents
Culture Documents
(A PAPER SUMMARY)
BY
OKHUEGBE SAMUEL NOSAKHALE
EE300-0011/2018
INTRODUCTION
(WHY TRANSMISSION LINE)
Load Current
Transient Single-phase to ground faults are the most frequent faults that occur
on Extra-High-Voltage transmission systems. SPAR provides a means to improve
transient stability.
But re-closing on a permanent fault is undesirable and can cause potential
damage.
Conventional SPARs re-closes circuit breaker after a set fixed time delay(dead
time) following a protection trip order.
It is necessary to distinguish between permanent and transient faults and to use
an intelligent time varying auto reclosing scheme that can adaptively change
the dead time based on deionization of the fault path.
PHASE MEASUREMENT UNIT (PMU)
To help solve some of the challenges posed by the conventional distance relay and
SPAR, a phase measurement unit based solution where synchronized measurement
data from both ends of a transmission line is used to protect the line, is proposed.
Also an adaptive SPAR with variable dead time control in the case of transient fault
by determining secondary arc extinction.
It contains 4 main components; Fault detector and classifier, fault locator, decision making
unit, conventional protection scheme.
Fault classifier outputs for the 3 phases A, B, C
The Directional detector element measures the angle between the positive sequence
components of the phasor currents at the sending and receiving ends of the line
It also supervises the main fault classifier output,
EXTERNAL FAULT = Close to ZERO degrees
INTERNAL FAULT =180 degrees.
FAULT LOCATOR AND DECISION
MAKING UNIT
THANK YOU