Introduction:
In this week we have been able to visit two sites:
Green Plaza and Alex West under supervision of
eng./M.Gomaa and eng./M.labib respectively.
We could learn some practical informations about water and gas
systems which have been used in these sites.
1-Green Plaza:
In this site we could be familiar with the water system as well as
CO2 system.
For water system there are three types of pipe material have
been used : Steel,PVC,HDPE .
Flexible joints are used for under ground pipes to avoid changes
in elevation.
In order to protect each building separatelly a zone control
valve have been used for each building.
flow
tamper detector
switch
test &drain
valve
OS&Y valve
There are three pumps used in this site:electric driven and
deisel driven centrifugal pumps plus a jocky pump used for
pressure maintenance.(network pressure = 8bar)
A flexible joint is used to prevent vibration transmission from
pumps to the tank
Main pressure relief is used with the deisel driven pump .
Types of Detectors:
• Wireless smoke detector
• Photoelectric smoke detector
• Ionization type smoke detector
• Heat detector
• Combined heat & smoke detector
Kitchen system:
Kitchens are protected by using potassium carbonates.
• This system is being activate using a fusible link connected to
a pin in the cylinder valve through a wire in thin tube.
• A shut off valve can be used to stop the flammable gas
through cylinders control board.
2-Alex West:
In this site we could be more familiar with the water system and its
installation.
• The type of pipe used is seemless steel pipes.
• The optimum distance between the upright sprinklers and the
ceiling is 10:15 Cm.
• Minimum distence between the sprinkler and the wall is 70 Cm.
• Pipes with diameters of 2 in max.can be fitted with threads.
other dia. is fitted by welding.
• An OS&Y valve ,Strainer and alarm check valve are used as a Z.C.V.
Third week report
Introduction:
In this part of our training we became aware with the main
components of FM200 systems as well as water-foam solution
system.