1 General Provisions
Pumped
Capacitors Batteries
Hydro*
Compressed Magnetic
Fuel cells
Air coils
Flywheels
Central
Central Control
Control
Not applicable to emergency generation operating in parallel less than five minutes per
calendar month while the system is in normal system state;
Voltage Connection level is not considered in the determination of the Storage Type
• Similar characteristics to a PPM: full new set of technical requirements coming from the NC and
not yet in the FGC
• Not an isolated chapter in the FGC => not the approach of having a “full grid code for storage”
Use of references to technical requirements to PPM or PGM, when appropriate : to limit
double writing of the same rule
To refer indirectly to the NC RfG, when the PPM or PGM articles are referring to the RfG
Specific Sub-Section devoted for storage, to add readability in the FGC
Limited to technical requirements
12
RfG Reference Requirement Adaptation
Admissible maximum power reduction with
[Art. 13-4] Not applicable
falling frequency
Use of automatic disconnection and
[Art. 13 (2)(b)] Not applicable
reconnection (LFSMO)
Limited frequency sensitive mode –
[Art. 13 (2)] Yes
Overfrequency
[Art 13-6] Logical interface to cease active power injection Yes
Conditions for automatic connection to the
[Art 13.7] Yes
network
[Art. 15(2)(c)] Limited frequency sensitive mode –
Yes*
Underfrequency
[Art 15.6(e)] Ramping Limits Yes*
* Optional requirement
RfG Reference Requirement Adaptation
Vs RfG
[Art 15.2.(a)] Time period for frequency stability to be Yes
reached
[Art 21 (3)(a-c)] Reactive power capabilities Yes
[Art 15 (2) (d)] FSM requirements Reference to
the general
framework
[Art 15.2.(e)] Specifications of the Frequency Restoration Reference to
Control the general
framework