Professional Documents
Culture Documents
Impedance Protection
The year of Profitable Growth
Power Automation
Progress. It‘s that simple.
Generator Protection
Overcurrent and Impedance
Protection
Power Automation 2
Power Transmission and Distribution
Summary
Power Automation The short circuit is a heavy fault for a generator. In that case the short-circuit protection is a standard protection for a
generator. The electromotive force (e.m.f.) supplies at the moment of a short circuit the following current :
Progress. It‘s that simple.
1,1 UN
IK(3) with: UN - nominal voltage
3 Xd" Xd“ - subtransient reactance
This subtransient short-circuit current is reduced with the typical time constants of a generator. The type of the excitation has
an important influence on the magnitude of the short circuit current. In the case of a short circuit near the terminals the
voltage is low and the voltage regulator starts to increase the excitation. A higher current is the result.
Dimensioning the co-ordination of the voltage regulator and excitation system (including excitation winding) based on a short
circuit current for a time of 8-10s is appr. 1,8 of the nominal generator current.
The settings of an overcurrent time relay is appr. 1,3 - 1,4 x IN . If the short- circuit current can be lower after a time an
undervoltage seal-in must be activated.
The short-circuit current depends on the fault type.
The ratio is ISC(1) : ISC(2) : ISC(3) = 5:3:2. In the case of a no load field voltage and a full load field voltage the range of the
short-circuit current is appr. 1:2,5.
For a turbo generator the following steady state short-circuit currents are
typically:
three-phase fault: ISC (0,8 ... 2)IN
phase-to-phase fault: ISC (1,2 ... 3)IN
single-phase fault: ISC (2 ... 5)IN
(earthing of the generator star point)
If the generator is earthed with a low ohmic resistor the short-circuit
current is limited to the nominal current.
Power Automation 3
Power Transmission and Distribution
L1
3phase short circuit
L2
L3
Single phase short
Interturn fault circuit
Phase to phase short circuit (Resistor limits the
fault current)
Power Automation 4
Power Transmission and Distribution
- t
2 Ιk' '
2 Ι' - Ι e T' d
k k
2 Ιk
- t
2 Ι' 'k e Tg
Combinations:
Driving Voltages Up < Up < Up
Power Automation 5
Power Transmission and Distribution
Power Automation 6
Power Transmission and Distribution
0,5 1
I >, t
G
I >, t
I >>, t I >, t
t
I > - Generator
Dt I > - Network Dt:grading time
I >> (approx. 0,3 s)
l
Protection is connected on the star-point-CT (proof against internal faults - at open
circuit breaker too)
Pick-up value I>; Ipick-up (1,2.....1,4) IN, G
Co-ordination of grading time with the network protection
I>>-stage: responsible for faults near or within the generator with a short tripping
time (0,1 s)
Busbar connection: reverse interlocking is recommended for radial network
Unit transformer connection: Ipick-up > 1,5 I SC(3, G) t 0,1 s
Power Automation 8
Power Transmission and Distribution
T-Seal-in
The same
characteristic
is used
Grading time
Power Automation 10
Power Transmission and Distribution
generator voltage.
(Used at generator-transformer schemes) 0,25 1,0 U/UNG
Note:
To avoid an overfunction in the case of an fuse failure (voltage circuit
interruption), there is recommended a blocking via an external m.c.b. or
the internal fuse - failure -monitor function.
Power Automation 11
Power Transmission and Distribution
Impedance Protection
Power Automation
Progress. It‘s that simple.
t
I>
tNetz +D t
Z<
Z1 0,7X T
0,1s
Z1
G
XG XT
Z<
Power Automation 12
Power Transmission and Distribution
Z< ZT ZL Z< ZT IK
1 1 I K2
Z Meas Z T ZL ZMeas Z T 1 ZL
Ratio 2 Tr Ratio 2 Tr I K1
Power Automation 13
Power Transmission and Distribution
L1 L1
L2 L2
L3 L3
X2
t t(I>)
X1B
X1 t(Z2)
Power Automation 15
Power Transmission and Distribution
ZG ZT
ZL
I > (ZG)
t ZT (backward)
ZG ZL
Z
2. Stage (ZT) ZT
Power Automation 16