Professional Documents
Culture Documents
Systems
EPR-2-1
J.CHIKAPHONYA 5/27/19 1
introduction
Two main types of voltages in use
◦ Direct current
◦ Alternating current
J.CHIKAPHONYA 5/27/19 2
introduction
Alternating current system is varsetile since it
can be used by both A.C. and D.C.
Consumers.
D.C. supply can be obtained from the A.C. by
J.CHIKAPHONYA 5/27/19 3
Standard Voltages
Extra low voltages:
◦ Up to 30 Vrms (A.C.) and 50 V (D.C.)
Low Voltage:
◦ 250 V or less.
Medium Voltages:
◦ 251 to 650 V
High Voltage:
◦ 651 to 3000 V
Extra-High voltages:
◦ More than 3000 V
J.CHIKAPHONYA 5/27/19 4
Standard Voltage
It is impractical for the supply authorities to
maintain the same constant voltage at the
terminals of their customers due to voltage
drops in the distribution system as the loads
vary.
J.CHIKAPHONYA 5/27/19 5
Standard Voltage
The acceptable variation under the electricity
regulation is ± 10% of the declared voltage.
The permitted variation in frequency is ± 1%
of declared frequency.
J.CHIKAPHONYA 5/27/19 6
The 3 Phase Electricity Supply
System
There are 4 distinct stages of a 3 phase
electricity system:
◦ Generation
◦ Transmission
◦ Distribution
◦ Utilisation
J.CHIKAPHONYA 5/27/19 7
The 3 Phase Electricity Supply
System
J.CHIKAPHONYA 5/27/19 8
Generator
Voltage is generated at 11KV (Malawi)
The generator has 2 main Parts:
◦ Startor
◦ Rotor
But to fully operate, the generator needs two
additional parts
◦ Exciter
◦ Prime mover
J.CHIKAPHONYA 5/27/19 9
Generator
Electrical
PRIME output
ROTOR STATOR
MOVER (a.c.
voltage)
EXCITER
(dc
source)
J.CHIKAPHONYA 5/27/19 10
Principle of operation of a
synchronous generator
Generator works on electromagnetic
induction principle which is based on
Faradays law
J.CHIKAPHONYA 5/27/19 11
J.CHIKAPHONYA 5/27/19 12
Principle of operation of a
synchronous generator
The rotor winding is continuously fed from a
dc source through brushes and slip rings
The direct current flowing in the rotor
J.CHIKAPHONYA 5/27/19 13
Principle of operation of a
synchronous generator
The stator conductors are placed at 120° to
each other, therefore the flux does not cut
the cut the conductors simultaneously but at
equal intervals
The emf induced in one winding is identical
J.CHIKAPHONYA 5/27/19 14
J.CHIKAPHONYA 5/27/19 15
Transmission
Electricity is generated at 11KV, 22KV, and
33KV( in Malawi its is at 11KV)
This generated voltage is stepped up by large
J.CHIKAPHONYA 5/27/19 16
Distribution
The Transmission voltages are subsequently
reduced to distribution voltages of 33KV and
11KV for primary and secondary distribution
systems respectively
The 11 KV is further reduced to 400V for non
J.CHIKAPHONYA 5/27/19 17
Substation arrangement for
11KV/400V
The substation can provide a number of
supply systems, namely
◦ 3 phase, 4 wire supply system
◦ 3 phase, 3 wire supply system
J.CHIKAPHONYA 5/27/19 18
Single phase supply system
Mainly used for domestic consumers
Consists of any one of the live wires and a
neutral wire
J.CHIKAPHONYA 5/27/19 19
A.C. 3 phase, 4 wire system
J.CHIKAPHONYA 5/27/19 20
A.C. 3 phase, 4 wire system
Consists of 3 single phase circuits with a
common earthed conductor know as the
neutral.
The transformer secondary windings are
connected in star.
The star point is then earthed and connected
to the neutral
J.CHIKAPHONYA 5/27/19 21
A.C. 3 phase, 4 wire system
All three phase supplies are connected to the
three live conductors.
Lighting, heating and other single phase
J.CHIKAPHONYA 5/27/19 22
A.C 3 Phase , 3 wire system
J.CHIKAPHONYA 5/27/19 23
A.C 3 Phase , 3 wire system
Used in large loads which do not present
problems in load balancing over the three
phases eg motors.
However, its main disadvantage is that no
J.CHIKAPHONYA 5/27/19 24
Star and delta connection
◦ If three phase windings are kept independent,
then six wires are needed to connect a supply
source (such as a generator) to a load (such as a
motor)
◦ To reduce the number of wires, these windings are
interconnected in two ways
Star connection
Delta connection
◦ Sources of three phased supplies are usually
connected in star where as 3phased transformer,
motor windings and other loads are connected in
either star or delta
Star connection
Star connection
Outlets from each load are joined together to
form neutral point (star point)
Voltages V V and V are called phase
R, Y B
voltages (VP), or line to neutral voltages.
Voltages VRY, VYB and VBR are called Line
voltages.
Voltage and current relationship in
star connection
Delta Connection
The end of one load is connected to the start
of the next load
Voltage and current relationship in
delta connection
Line Voltages VRY, VYB and VBR are the
respective phase voltages (VP).
Power in a 3 Phase Balanced load
P= I2R
In A.C. circuits, we will need to define R in
J.CHIKAPHONYA 5/27/19 34