OF TRANSFORMER OIL
NUMBER
4. TRANSFORMER RATING
5. VOLTAGE RATIO
B] HISTORICAL INFORMATION
1. DATE OF COMMISSIONING
2. DATE OF LAST OIL FILLING
3. DATE OF LAST OIL FILTRATION/ DETANKING /
TOPPING UP / TRANSFORMER REPAIRS
4. DATE OF SAMPLING
5. OIL VOLUME IN SYSTEM
6. ANY ABNORMALITY IN WORKING
C] OPERATIONAL
NEW TRANSFORMERS
OF A HEALTHY TRANSFORMER
1. Benchmark Results
2. Permissible Limit
3. IS Ratio Method
4. Muller’s Ratio Method
5. Key Gas Method
6. TCG Content
7. Rate of Rise of Gas
Code of range of ratios
C2H2 CH4 C2H4
C2H4 H2 C2H6
< 0.1 0 1 0
0.1 – 1 1 0 0
1–3 1 2 1
>3 2 2 2
BEFORE & AFTER HEAT RUN TEST
• Here t is duration of heat run test in hours, (X)2 and (X)1 are
concentrations of gas X, after and before the test.
• 5 th criteria may only be used if increase in gas concentration of C2H4
& C2H6 BHRT & AHRT are > 10 Sa
INTERPRETATION
33 kV
DATE OF COMM. 1984
RATIOS : 2 0 2
H2 240
CH4 26
C2H2 202
C2H4 51
C2H6 3
CO 199
CO2 64
Fault diagnosis : Presence of severe electrical
discharges
Observation : Total winding was damaged
significantly