You are on page 1of 33

|  



î L M
Flux density
B [T]
N
` A

î
       
x   
      
   

J 
nduction motor cannot start
by itself. This problem is
solved by introducing three
phase system      
nstead of using one coil only , three coils are used arranged in one
axis with orientation of 120o each other. The coils are R-R1 , Y-Y1
and B-B1. The phases are measured in this sequence R-Y-B. .e Y
lags R by 120o , B lags Y by 120o.
F  

e L

a 
F  
e L2 Load
a 
F  
e L3
a


The three winding can be represented by the above circuit. n this


case we have six wires. The emf are represented by eR , eY, eB.
E m sin !÷
E m sin(!÷-120 ‰)
‰
E m sin(!÷-240 )
The circuit can be simplified as follows, where R1 can be
connected to Y and Y1 can be connected to B. n this case
the circuit is reduced to 4 wires.
2  

RB1 R Î Y Î B

‰ ‰ 2   
 m [sin ÷ sin( ÷ å 120 ) sin( ÷ å 240 )] 
 
 

a [sin !t Î sin !t ü cos 120 ‰ cos !t ü sin 120 ‰ 2  

 sin t ü cos 240 ‰å cos t ü sin 240 ‰] 

a [sin !t 05 sin !t 0.866 cos !t 0.5 sin !t Î 0.866 m !t ]


0
Since the total emf is zero, R and B1 can be connected together, thus
we arrive with delta connection system.

2

2

L



onduo
L e







2

ÚSince the total emf is zero, R and B1 can be ?
 
connected together as in Fig.A , thus we arrive
with delta connection system as in Fig. C. ? 
ÚThe direction of the emf can be referred to the

emf waveform as in Fig. B where PL is +ve (R1- 
R), PM is ±ve (Y-Y1) and PN is ±ve (B-B1). 
?
ÚR1, Y1 and B1 are connected together. 
ÚAs the e.m.f generated are assumed in —
positive direction , therefore the current

directions are also considered as flowing

in the positive direction. —
ÚThe current in the common wire (MN)
is equal to the sum of the generated   —Ñ — —
3
currents. i.e —R+—Y+—B . 
—
ÚThis arrangement is called four ±wire
star-connected system. The point N  
refers to star point or neutral point.
eneao Load
The instantaneous current in loads L1 , L2 and L3 are


—
i  a sin !t 

L neonduo

i  a sin(!tè120 )
‰ 
  
—
‰ 
i    sin( tè240 )
 —

i i Î i Î i


L3 L2 L
 a [sin t Î sin( t å 120‰) —Ñ — —

Î sin( t å 240‰)] 0
|   

For balanced loads, the fourth wire carries no current , so it can
be dispensed
!!

 2!

L

  "#
 
  L

L

  #
!!

geneao a b  ba aned
o  oad
nstantaneous currents¶ waveform for —R, —Y and —B in
a balanced three-phase system.
      
Ú*RY, *YB and *BR are called line voltage Ñ

R
Ú*R, *Y and *B are called phase voltage $Ñ
$ Ñ


From Kirchoff voltage law we have $ $ Y
$
    Î (  ) B


 
 Î ( 
) *B -*Y
*RY
*BR
Ñ   å Ñ    (å Ñ )
-*R *R
n phasor diagram
-*B
*Y

*YB
For balanced load *R , *Y and
*B are equaled but out of phase

*R = *Po30 ; *RY = *Lo30 ; *B -*Y


*RY
*BR
*Y = *Po-90 ; *YB = *Lo-90 ;
-*R *R
*B = *Po150 ; *BR = *Lo150 ;
-*B
therefore *Y

Ñ 2 Ñ cos 30   3 Õ
*YB

Ñ 2  cos 30   3 Õ

 2 cos 30   3 Õ
then

  3 Õ

and

  Õ


ÚÑ,  and  are called line current 1
Ú1, 2 and 3 are called phase current

3 
From Kirchoff current law we have $
$%
 Ñ  1 å  3  1  ( å  3 )
2 

 2 1  2 Î ( 1 ) R
1
 B  3 å  2   3  (å  2 )
-2 -3
B
n phasor diagram
3 2

-1
Y
Since the loads are balanced, the magnitude of currents are
equaled but 120o out of phase. i.e 1 =2=3 ,=P Therefore:-

R = Lo30 ; 1 = *Po30 ;
Y = Lo-90 ; 2 = *Po-90 ;
B = Lo150 ; 3 = *Po150 ;
Where P is a phase current and L is a line current
R
‰
 2 1 cos 30 ( 3) Õ 1
‰
  2  2 cos 30  ( 3 )  Õ -2 -3


2  3 cos 30 ‰
 3  Õ
B

3 2
Thus R=Y=B = L
-1
Y
ùence

  3  Õ Õ
î

n a three-phase four-wire system the line voltage is 400*


and non-inductive loads of 5 kW, 8 kW and 10 kW are
connected between the three conductors and the neutral.
Calculate: (a) the current in each phase
(b) the current in the neutral conductor.
400
*oltage to neutral Õ    230
3 3

ÕÑ 10 4
Current in 10kW resistor Ñ    43.5 
Õ 230

Õ 8 103
Current in 8kW resistor  34.8 
Õ 230

Õ
5 103
Current in 5kW resistor 
21. 
Õ 230
R
N* N

Bù Yù

B* Y* Nù


B Y

Resolve the current components into horizontal and vertical


components.
  cos 30‰ 
cos 30 086634.8 21.  11.3 

   Ñ å  cos 60‰å   cos 60  43.5 å 0.5(34.8  21.)  13.0 


2 2
        1132  13.0 2  1.2 
A delta ±connected load is arranged as in Figure below.
The supply voltage is 400* at 50ùz. Calculate:
(a)The phase currents;
(b)The line currents.


1
'†
& &

 '3 2
2'2† 2
& 3
 2'!†

[(  400
1 4
1 100

1 is in phase with *RY since there is only resistor in the branch


n branch between YB , there are two components , R2 and X2
 400
2    6.32 
2 2
20  60 R

$Ñ

2
Ñ 2 Î 2
2
20 2 Î 60 2
1
-3
 2   60 
î tan å1
 tan å1    1‰34' ) 

 Ñ2   20 

n the branch RB , only capacitor in 

$ Ñ ) *
it , so the XC is -90 out of phase. 
$ 
)
3
Ñ 400
3 1 /( 2  50  30  10 6 ) 90 ‰ 2


3. A 90
[(  R  1 å  3

 2 12 Î 2 1  3 cos Î  32 î=30o


1
 2 4.02 Î 24.0 3. cos 30 2
Î 3.  56.3

 .5  

î = 1o 34¶ -60o= 11o 34¶ 


) *
Y  2 å 1 î

2 -1
2  22 Î 2 1  2 cos Î 12

2 2
 2  6.32   24.0 6.32 cos 11 34' 4.0   105.5
 10.3 
Y
î = 180-30o-11o 34¶ = 138o 34¶

B 3 å 2


2  32 Î 2  3  2 cos Î  22
-2
 2 6.322 Î 23. 6.32cos138 26'Î3. 2 18.5

 4.3  2
î


) *

) * )
3

2
Õ  

Active power per phase = Õ Õ x power factor


Total active power= 3 ÕÕ x power factor

Õ  3 Õ  Õ cos J
f L and *L are rms values for line current and line voltage
respectively. Then for delta ([) connection: *P = *L and P
= L/ 3. therefore:
Õ 3  cos

For star connection (a) : *P = *L/ 3 and P = L. therefore:

Õ 3  cos
A three-phase motor operating off a 400* system is developing
20kW at an efficiency of 0.8 p.u and a power factor of 0.82.
Calculate:
(a)The line current;
(b)The phase current if the windings are delta-connected.
(a) Since ——   ÷÷  u  — u ÷÷
—÷  u  — u ÷÷
÷÷  u  — u ÷÷

3 ë . 
20 ë1000
0.8  And line current =L=40.0A
3 ë  ë 400 ë 0.82
(b) For a delta-connected winding
`—  ÷ 40.0
Õ  ÷ 23.1
3 3
Three identical coils, each having a resistance of 20† and
an inductance of 0.5 ù connected in (a) star and (b) delta
to a three phase supply of 400 *; 50 ùz. Calculate the
current and the total power absorbed by both method of
connections.
First of all calculating the impedance of the coils
R P  20† X P  2 ë 50 ë 0.5  15 †

1 XP 
 ÑÕ   Õ  ÑÕ   Õ oJ
2 2
where tan  
 RP
Õ

2 2  15 
1 ‰
20 Î 15  tan   15883
 20 

cos J cos 83‰ 0.1264


Star-connection

2†
&
& 400 / 3

+


+ +
& 2† 2†

Since it is a balanced load


400  231
 231   1.46A
3  158
Power absorbed
Õ 3  cos J 3  400  1.46  0.1264 128W
Star connection

&
+
2† 2†

+
& & 2† +

 400
  400   4.38A
Z 158

Õ  3  cos J 3  400  4.38  0.1264 383W


A balanced three phase load connected in star, each phase consists
of resistance of 100 † paralleled with a capacitance of 31.8 F.
The load is connected to a three phase supply of 415 *; 50 ùz.
Calculate: (a) the line current;
(b) the power absorbed;
(c) total k*A;
(d) power factor .
 

*L 415
*P    240*
3 3
Admittance of the load
1 1 1
YP   where XP 
R P XP j!

1 1
  j!   j2  50  31.8  10 6
 (0.01  j0.01)S
RP 100
Line current
 Õ Õ Õ 240(0.01 Î  0.01) 2.4 Î  2.4 3.3945‰
*olt-ampere per phase
A     240 ë 3.39o 45 ‰ 814 .4o 45 ‰

Active power per phase ÕÕ  814.4 cos 45‰ 56

Total active power A 3  56 1.28 kW


[(

Ñeactive power per phase Ñ j814.4 sin 45 ‰ j56

Total reactive power Ñ j3  56 j1.28 kW

[( Total volt-ampere  3 ë 814 .4  2.44 k*A

[(
Power Factor = cos = cos 45 = 0.0 (leading)
A three phase star-connected system having a phase voltage of
230* and loads consist of non reactive resistance of 4 †, 5 †
and 6† respectively.
Calculate:(a) the current in each phase conductor
(b) the current in neutral conductor
and (c) total power absorbed.

230
 4† 5.5A
4
230
 5† 46A
5
230
 6† 38.3A
6
38.3 A

5.5 A

[( 46 A

X-component = 46 cos 30 + 38.3 cos 30 - 5.5 = 15.5 A


Y-component = 46 sin 30 - 38.3 sin 30 = 3.9 A

Therefore  N  15.5 2  3.9 2  16A

[(  230 5.5 Î 46 Î 38.3 32.61kW

You might also like