Lecture 4: Transformers
Instructor: Dr. Gleb V. Tcheslavski Contact: gleb@ee.lamar.edu Office Hours: TBD; Room 2030 Class web site: MyLamar
Spring 2008
Some history
Historically, the first electrical power distribution system developed by Edison in 1880s was transmitting DC. It was designed for low voltages (safety and difficulties in voltage conversion); therefore, high currents were needed to be generated and transmitted to deliver necessary power. This system suffered significant energy losses! The second generation of power distribution systems (what we are still using) was proposed by Tesla few years later. His idea was to generate AC power of any convenient voltage, step up the voltage for transmission (higher voltage implies lower current and, thus, lower losses), transmit AC power with small losses, and finally step down its voltage for consumption. Since power loss is proportional to the square of the current transmitted, raising the voltage, say, by the factor of 10 would decrease the current by the same factor (to deliver the same amount of energy) and, therefore, reduce losses by factor of 100.
The step up and step down voltage conversion was based on the use of transformers.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
Preliminary considerations
A transformer is a device that converts one AC voltage to another AC voltage at the same frequency. It consists of one or more coil(s) of wire wrapped around a common ferromagnetic core. These coils are usually not connected electrically together. However, they are connected through the common magnetic flux confined to the core. Assuming that the transformer has at least two windings, one of them (primary) is connected to a source of AC power; the other (secondary) is connected to the loads. The invention of a transformer can be attributed to Faraday, who in 1831 used its principle to demonstrate electromagnetic induction foreseen no practical applications of his demonstration. Russian engineer Yablochkov in 1876 invented a lighting system based on a set of induction coils, which acted as a transformer.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
More history
Gaulard and Gibbs first exhibited a device with an open iron core called a 'secondary generator' in London in 1882 and then sold the idea to a company Westinghouse. They also exhibited their invention in Turin in 1884, where it was adopted for an electric lighting system. In 1885, William Stanley, an engineer for Westinghouse, built the first commercial transformer after George Westinghouse had bought Gaulard and Gibbs' patents. The core was made from interlocking E-shaped iron plates. This design was first used commercially in 1886. Hungarian engineers Zipernowsky, Blthy and Dri created the efficient "ZBD" closed-core model in 1885 based on the design by Gaulard and Gibbs. Their patent application made the first use of the word "transformer". Another Russian engineer Dolivo-Dobrovolsky developed the first three-phase transformer in 1889. Finally, in 1891 Nikola Tesla invented the Tesla coil, an air-cored, dual-tuned resonant transformer for generating very high voltages at high frequency.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
Core form
Shell form
Usually, windings are wrapped on top of each other to decrease flux leakage and, therefore, increase efficiency.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
Spring 2008
Spring 2008
Ideal transformer
We consider a lossless transformer with an input (primary) winding having Np turns and a secondary winding of Ns turns. The relationship between the voltage applied to the primary winding vp(t) and the voltage produced on the secondary winding vs(t) is
v p (t ) vs (t )
Np Ns
!a
(4.8.1)
Spring 2008
Ideal transformer
The relationship between the primary ip(t) and secondary is(t) currents is
i p (t )
1 ! is (t ) a Vp Vs Ip
(4.9.1)
!a
(4.9.2)
1 ! Is a
(4.9.3)
The phase angles of primary and secondary voltages are the same. The phase angles of primary and secondary currents are the same also. The ideal transformer changes magnitudes of voltages and currents but not their angles.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
10
Ideal transformer
One windings terminal is usually marked by a dot used to determine the polarity of voltages and currents. If the voltage is positive at the dotted end of the primary winding at some moment of time, the voltage at the dotted end of the secondary winding will also be positive at the same time instance. If the primary current flows into the dotted end of the primary winding, the secondary current will flow out of the dotted end of the secondary winding.
Spring 2008
11
Pin ! V p I p cos U p
The power supplied to the output circuits is
(4.11.1)
Pout ! Vs I s cos U s
Since ideal transformers do not affect angles between voltages and currents:
(4.11.2)
U p ! Us ! U
Both windings of an ideal transformer have the same power factor.
(4.11.3)
Spring 2008
12
;I s ! aI p
(4.12.1)
Therefore:
out
s I s cos U !
aI p cos U !
p p
I cos U !
in
(4.12.2)
The output power of an ideal transformer equals to its input power to be expected since assumed no loss. Similarly, for reactive and apparent powers:
Qout !
s s
I sin U !
s s
p p
(4.12.3)
Sout !
I !
p p
(4.12.4)
Spring 2008
13
Impedance transformation
The impedance is defined as a following ratio of phasors:
Z L ! VL I L
A transformer changes voltages and currents and, therefore, an apparent impedance of the load that is given by
(4.13.1)
Z L ! Vs I s
(4.13.2)
Z L ' ! Vp I p
which is
(4.13.3)
Vp
(4.13.4)
It is possible to match magnitudes of impedances (load and a transmission line) by selecting a transformer with the proper turn ratio.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
14
Spring 2008
15
I G ! I line ! Iload ! !
V Zline Zload
Spring 2008
16
Vload ! I load Z load ! 90.8 37.8r
(4 j 3) ! 90.8 37.8r
536.9r
! 454 0.9rV
The line losses are:
loss 2 ! I line Rline ! 90.82 0.18 ! 1484W
b) We will 1) eliminate transformer T2 by referring the load over to the transmission lines voltage level. 2) Eliminate transformer T1 by referring the transmission lines elements and the equivalent load at the transmission lines voltage over to the source side.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
17
10 ! 4 j 3 ! 400 j 300 1
Spring 2008
18
IG !
! 95.94 36.88r A
Knowing transformers turn ratios, we can determine line and load currents:
I line ! a1IG ! 0.1 95.94 36.88r
! 9.594 36.88 r A I load ! a2 Iline ! 10 9.594 36.88r
! 95.94 36.88 r A
Therefore, the load voltage is:
Note: transmission line losses are reduced by a factor nearly 90, the load voltage is much closer to the generators voltage effects of increasing the lines voltage.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
19
eind
dP ! dt
(4.19.1)
Here P is the flux linkage in the coil across which the voltage is induced:
P ! Ji
i !1
(4.19.2)
where JI is the flux passing through the ith turn in a coil slightly different for different turns. However, we may use an average flux per turn in the coil having N turns:
J !P N
Therefore:
ELEN 3441 Fundamentals of Power Engineering
(4.19.3)
eind
dJ !N dt
Spring 2008
(4.19.4)
20
J !
A portion of the flux produced in the primary coil passes through the secondary coil (mutual flux); the rest is lost (leakage flux):
1 v p (t )dt Np
(4.20.1)
J p ! Jm JLp
average primary flux mutual flux
(4.20.2)
Js ! J JLs
Average secondary flux
ELEN 3441 Fundamentals of Power Engineering
(4.20.3)
Spring 2008
21
v p (t ) ! N p
vs (t ) ! N s
d Js dJ dJ ! N s m N s Ls ! es (t ) eLs (t ) dt dt dt d Jm e p (t ) ! N p dt dJLs es (t ) ! N s dt
The primary and secondary voltages due to the mutual flux are:
(4.21.3)
e p (t ) Np
ELEN 3441 Fundamentals of Power Engineering
dJm es (t ) ! ! dt Ns
Spring 2008
dJ p
dJLp dJ ! Np Np ! ep (t ) eLp (t ) dt dt dt
(4.21.1)
(4.21.2)
(4.21.4)
(4.21.5)
22
e p (t ) es (t )
Np Ns
!a
(4.22.1)
That is, the ratio of the primary voltage to the secondary voltage both caused by the mutual flux is equal to the turns ratio of the transformer. For well-designed transformers:
(4.22.2)
v p (t ) vs (t )
ELEN 3441 Fundamentals of Power Engineering
Np Ns
}a
(4.22.3)
Spring 2008
23
Spring 2008
24
Ignoring flux leakage and assuming time-harmonic primary voltage, the average flux is: 1 1 m sin [ t ?Wb A J ! v p (t )dt ! (4.24.1) m cos [ tdt ! Np Np [Np If the values of current are comparable to the flux they produce in the core, it is possible to sketch a magnetization current. We observe: 1. Magnetization current is not sinusoidal: there are high frequency components; 2. Once saturation is reached, a small increase in flux requires a large increase in magnetization current; 3. Magnetization current (its fundamental component) lags the voltage by 90o; 4. High-frequency components of the current may be large in saturation. Assuming a sinusoidal flux in the core, the eddy currents will be largest when flux passes zero.
Spring 2008
25
Core-loss current
Core-loss current is: 1. Nonlinear due to nonlinear effects of hysteresis; 2. In phase with the voltage. The total no-load current in the core is called the excitation current of the transformer:
iex ! im ih e
ELEN 3441 Fundamentals of Power Engineering
(4.25.1)
Spring 2008
26
Fp ! N p i p
(4.26.1) (4.26.2)
Fs ! N s is
Fnet ! N p i p N sis ! J
(4.26.3)
where is the reluctance of the transformer core. For well-designed transformer cores, the reluctance is very small if the core is not saturated. Therefore:
net
ELEN 3441 Fundamentals of Power Engineering
! N p i p N s is } 0
Spring 2008
(4.26.4)
27
Ns 1 N p i p } N s is } ! is N p a
An ideal transformer (unlike the real one) can be characterized as follows: 1. 2. 3. 4. The core has no hysteresis or eddy currents. The magnetization curve is The leakage flux in the core is zero. The resistance of the windings is zero.
ip
(4.27.1)
Spring 2008
28
Spring 2008
29
eLp (t ) ! N p
dJLp dt
(4.29.1)
Since much of the leakage flux pass through air, and air has a constant reluctance that is much higher than the core reluctance, the primary coils leakage flux is:
JLp ! P N p i p
permeance of flux path
(4.29.2)
Therefore:
di p d 2 eLp (t ) ! N p N p i p
! N pP P dt dt
Spring 2008
(4.29.3)
30
(4.30.1)
eLp (t ) ! Lp eLs (t ) ! Ls
di p dt dis dt
(4.30.2)
Secondary coil:
(4.30.3)
The leakage flux can be modeled by primary and secondary inductors. The magnetization current can be modeled by a reactance XM connected across the primary voltage source. The core-loss current can be modeled by a resistance RC connected across the primary voltage source. Both currents are nonlinear; therefore, XM and RC are just approximations.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
31
Spring 2008
32
Spring 2008
33
1 GC ! RC
The susceptance of the magnetizing inductor is:
(4.33.1)
1 BM ! XM
ELEN 3441 Fundamentals of Power Engineering
(4.33.2)
Spring 2008
34
YE ! GC jBM !
1 1 j RC XM
(4.34.1)
I oc YE ! Voc
(4.34.2)
The angle of the admittance in the open-circuit test can be found from the circuit power factor (PF):
(4.34.3)
Spring 2008
35
(4.35.1)
Spring 2008
36
Z SE
VSC ! I SC
(4.36.1)
(4.36.2)
37
Z SE !
VSC 0r VSC ! U r I SC U r I SC
(4.37.1)
Z SE ! Req jX eq Z SE ! R p a 2 RS j X p a 2 X S
(4.37.2) (4.37.3)
it is possible to determine the total series impedance referred to the primary side of the transformer. However, there is no easy way to split the series impedance into primary and secondary components. The same tests can be performed on the secondary side of the transformer. The results will yield the equivalent circuit impedances referred to the secondary side of the transformer.
Spring 2008
38
Spring 2008
39
Z SE !
! 38.4 j192;
Therefore:
Spring 2008
40
(4.40.1)
Usually, two base quantities are selected to define a given per-unit system. Often, such quantities are voltage and power (or apparent power). In a 1-phase system:
Pbase , Z base
ELEN 3441 Fundamentals of Power Engineering
base
(4.40.2)
(4.40.3)
41
Ones the base values of P (or S) and V are selected, all other base values can be computed form the above equations. In a power system, a base apparent power and voltage are selected at the specific point in the system. Note that a transformer has no effect on the apparent power of the system, since the apparent power into a transformer equals the apparent power out of a transformer. As a result, the base apparent power remains constant everywhere in the power system. On the other hand, voltage (and, therefore, a base voltage) changes when it goes through a transformer according to its turn ratio. Therefore, the process of referring quantities to a common voltage level is done automatically in the per-unit system.
Spring 2008
42
The generator is rated at 480 V and 10 kVA. a) Find the base voltage, current, impedance, and apparent power at every points in the power system; b) Convert the system to its per-unit equivalent circuit; c) Find the power supplied to the load in this system; e) Find the power lost in the transmission line (Region 2).
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
43
Sbase1 10000 I base1 ! ! ! 20.83 A Vbase1 480 Vbase1 480 Z base1 ! ! ! 23.04; I base1 20.83
The turns ratio of the transformer T1 is a1 = 0.1; therefore, the voltage in the transmission line region is
Vbase2
Spring 2008
44
Vbase
Spring 2008
45
b. To convert a power system to a per-unit system, each component must be divided by its base value in its region. The generators per-unit voltage is
VG , pu
Z line, pu
ELEN 3441 Fundamentals of Power Engineering
46
Z load , pu
The per-unit equivalent circuit c. The current flowing in this per-unit power system is
I pu !
V pu Ztot , pu
Spring 2008
47
Spring 2008
48
Spring 2008
49
P, , S
pu ,base2 ! P, , S
pu,base
V pu ,base2 ! V pu ,base Vbase Vbase
Sbase Sbase
(4.49.1)
(4.49.2)
R, X , Z pu ,base2
(4.49.3)
Spring 2008
50
38.4 j192 ! 0.012 j 0.06 pu Z SE , pu ! 3200 159000 ! 49.7 pu RC , pu ! 3200 00 ! 12 pu X M , pu ! 3200
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
51
Spring 2008
52
VR !
Vs ,nl Vs , fl Vs , fl
100% !
Vp a Vs , fl Vs , fl
100%
(4.52.1)
In a per-unit system:
VR !
V p , pu Vs , fl , pu Vs , fl , pu
100
(4.52.2)
Where Vs,nl and Vs,fl are the secondary no load and full load voltages.
Spring 2008
53
Vp a
! Vs Req I s jX eq I s
(4.53.1)
Spring 2008
54
A transformer operating at a unity power factor: It is seen that VR > 0 A transformer operating at a leading power factor: If the secondary current is leading, the secondary voltage can be higher than the referred primary voltage; VR < 0.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
55
(4.55.1)
Note: the same equation describes the efficiency of motors and generators. Considering the transformer equivalent circuit, we notice three types of losses: 1. Copper (I2R) losses are accounted for by the series resistance 2. Hysteresis losses are accounted for by the resistor Rc. 3. Eddy current losses are accounted for by the resistor Rc. Since the output power is The transformer efficiency is
Pout ! Vs I s cos U s
Vs I s cos U L! 100% PCu Pcore Vs I s cos U
Spring 2008
(4.55.2)
(4.55.3)
56
a. Find the equivalent circuit of this transformer referred to the high-voltage side. b. Find the equivalent circuit of this transformer referred to the low-voltage side. c. Calculate the full-load voltage regulation at 0.8 lagging power factor, at 1.0 power factor, and at 0.8 leading power factor. d. Plot the voltage regulation as load is increased from no load to full load at power factors of 0.8 lagging, 1.0, and 0.8 leading. e. What is the efficiency of the transformer at full load with a power factor of 0.8 lagging?
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
57
U oc ! cos 1
Rc ! XM
Spring 2008
58
U SC ! cos 1
Spring 2008
59
Spring 2008
60
I S ,rated !
Since:
Vp a
I s ! 65.2 cos 1 (0.8) ! 65.2 36.9 r A At PF = 0.8 lagging, current Vp ! 2300r 0.0445 65.2 36.9 r
j0.0645 65.2 36.9 r
! 234.85 0. 40rV and a The resulting voltage regulation is, therefore:
VR ! ! V p a VS , fl VS , fl 100%
Spring 2008
61
Spring 2008
62
Spring 2008
63
Spring 2008
64
Vp a
RC
The output power of the transformer at the given Power Factor is:
L!
! 98.03
65
Spring 2008
66
Spring 2008
67
The autotransformer
Sometimes, it is desirable to change the voltage by a small amount (for instance, when the consumer is far away from the generator and it is needed to raise the voltage to compensate for voltage drops). In such situations, it would be expensive to wind a transformer with two windings of approximately equal number of turns. An autotransformer (a transformer with only one winding) is used instead. Diagrams of step-up and step-down autotransformers:
Series winding Series winding
Common winding
Common winding
Output (up) or input (down) voltage is a sum of voltages across common and series windings.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
68
The autotransformer
Since the autotransformers coils are physically connected, a different terminology is used for autotransformers: The voltage across the common winding is called a common voltage VC, and the current through this coil is called a common current IC. The voltage across the series winding is called a series voltage VSE, and the current through that coil is called a series current ISE. The voltage and current on the low-voltage side are called VL and IL; the voltage and current on the high-voltage side are called VH and IH. For the autotransformers:
VC N ! C VSE N SE
(4.68.1)
N C I C ! N SE I SE VL ! VC VH ! VC VSE
ELEN 3441 Fundamentals of Power Engineering
I L ! I C I SE I H ! I SE
Spring 2008
69
N SE N SE VH ! VC VC ! VL VL NC NC
Therefore: The current relationship will be:
(4.69.1)
VL NC ! VH N C N SE
(4.69.2)
I L ! I SE
Therefore:
N SE N SE I SE ! I H IH NC NC
I L NC N SE ! IH NC
(4.69.3)
(4.69.4)
Spring 2008
70
Sin ! VL I L Sout ! VH I H
It is easy to show that
where SIO is the input and output apparent powers of the autotransformer. However, the apparent power in the autotransformers winding is
SW ! VC I C ! VSE I SE
Which is:
(4.70.4)
SW ! VL I L I H
! VL I L VL I H
! VL I L VL I L
NC N SE ! S IO N SE N C N SE N C
Spring 2008
(4.70.5)
71
S IO N SE N C ! SW N SE
(4.71.1)
The last equation described the apparent power rating advantage of an autotransformer over a conventional transformer.
SW is the apparent power actually passing through the windings. The rest passes from primary to secondary parts without being coupled through the windings. Note that the smaller the series winding, the greater the advantage!
Spring 2008
72
SW ! S IO
N SE 28 ! 5 ! 1.015MVA N SE NC 28 110
Therefore, the autotransformer would have windings rated at slightly over 1 MVA instead of 5 MVA, which makes is 5 times smaller and, therefore, considerably less expensive. However, the construction of autotransformers is usually slightly different. In particular, the insulation on the smaller coil (the series winding) of the autotransformer is made as strong as the insulation on the larger coil to withstand the full output voltage.
The primary disadvantage of an autotransformer is that there is a direct physical connection between its primary and secondary circuits. Therefore, the electrical isolation of two sides is lost.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
73
b. The max series winding current: The secondary apparent power: c. The power rating advantage:
I SE ,max
or
ELEN 3441 Fundamentals of Power Engineering
74
Variable-voltage autotransformers
The effective per-unit impedance of an autotransformer is smaller than of a conventional transformer by a reciprocal to its power advantage. This is an additional disadvantage of autotransformers.
Spring 2008
75
3-phase transformers
The majority of the power generation/distribution systems in the world are 3-phase systems. The transformers for such circuits can be constructed either as a 3-phase bank of independent identical transformers (can be replaced independently) or as a single transformer wound on a single 3-legged core (lighter, cheaper, more efficient).
Spring 2008
76
Four possible connections for a 3-phase transformer bank are: 1. 2. 3. 4. Y-Y Y-( (- ( (-Y
Spring 2008
77
VLP VJ P ! 3
The secondary phase voltage is
(4.77.1)
VLS ! 3VJ S
The overall voltage ratio is
(4.77.2)
(4.77.3)
Spring 2008
78
Spring 2008
79
VLP VJ P ! 3
The secondary phase voltage is
(4.79.1)
VLS ! VJ S
The overall voltage ratio is
(4.79.2)
(4.79.3)
Spring 2008
80
Spring 2008
81
VJ P ! VLP
The secondary phase voltage is
(4.81.1)
VLS ! 3VJ S
The overall voltage ratio is
(4.81.2)
(4.81.3)
The same advantages and the same phase shift as the Y-( connection.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
82
VJ P ! VLP
The secondary phase voltage is
(4.82.1)
VLS ! VJ S
The overall voltage ratio is
(4.82.2)
VLP VJ P ! !a VLS VJ S
No phase shift, no problems with unbalanced loads or harmonics.
ELEN 3441 Fundamentals of Power Engineering
(4.82.3)
Spring 2008
83
S1J ,base !
Sbase 3
(4.83.1)
Therefore, the base phase current and impedance of the transformer are
IJ ,base !
(4.83.2)
Z base
V !
S1J ,base
(4.83.3)
Spring 2008
84
VL ,base ! VJ ,base
If the windings are in Y:
(4.84.1)
(4.84.2)
I L ,base
(4.84.3)
The application of the per-unit system to 3-phase transformer problems is similar to its application in single-phase situations. The voltage regulation of the transformer bank is the same.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
85
Z base !
3 VJ ,base Sbase
Spring 2008
86
Z eq , pu ! 0.01 j 0.07 pu
Therefore, the high-side impedance in ohms is:
VR !
VJ P aVJ S aVJ S
100%
The rated phase current on the primary side can be found as:
Spring 2008
87
208 VJ S ! ! 120V 3
When referred to the primary (high-voltage) side, this voltage becomes
VJP ! aVJS Req IJ jXeqIJ ! 138000r114.2 1.208cos1(0.8) j 800 1.208cos1(0.8) !14490 j690.3 ! 145062.73rV
The voltage regulation, therefore, is
VR !
VJ P aVJ S aVJ S
100
! 5.1%
Spring 2008
88
VR !
Spring 2008
89
Transformer ratings
Transformers have the following major ratings: 1. Apparent power; 2. Voltage; 3. Current; 4. Frequency.
Spring 2008
90
v (t ) ! VM sin [t
J (t ) !
An increase in voltage will lead to a proportional increase in flux. However, after some point (in a saturation region), such increase in flux would require an unacceptable increase in magnetization current!
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
91
Jmax
Vmax ! [N p
(4.91.1)
Therefore, to maintain the same maximum flux, a change in frequency (say, 50 Hz instead of 60 Hz) must be accompanied by the corresponding correction in the maximum allowed voltage. This reduction in applied voltage with frequency is called derating. As a result, a 50 Hz transformer may be operated at a 20% higher voltage on 60 Hz if this would not cause insulation damage.
Spring 2008
92
Spring 2008
93
v(t ) ! VM sin [t U
The maximum flux reached on the first half-cycle depends on the phase of the voltage at the instant the voltage is applied. If the initial voltage is
(4.93.1)
(4.93.2)
and the initial flux in the core is zero, the maximum flux during the first half-cycle is equals to the maximum steady-state flux (which is ok):
Jmax
VM ! [Np
(4.93.3)
v(t ) ! VM sin [t
ELEN 3441 Fundamentals of Power Engineering
(4.93.4)
Spring 2008
94
Jmax
1 ! Np
T [
T [
2VM ! [N p
(4.94.1)
Which is twice higher than a normal steady-state flux! Doubling the maximum flux in the core can bring the core in a saturation and, therefore, may result in a huge magnetization current! Normally, the voltage phase angle cannot be controlled. As a result, a large inrush current is possible during the first several cycles after the transformer is turned ON. The transformer and the power system must be able to handle these currents.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008
95
Additional information, such as perunit series impedance, type of cooling, etc. can also be specified on the plate.
Spring 2008
96
Instrument transformers
Two special-purpose transformers are uses to take measurements: potential and current transformers. A potential transformer has a high-voltage primary, low-voltage secondary, and very low power rating. It is used to provide an accurate voltage samples to instruments monitoring the power system. A current transformer samples the current in a line and reduces it to a safe and measurable level. Such transformer consists of a secondary winding wrapped around a ferromagnetic ring with a single primary line (that may carry a large current )running through its center. The ring holds a small sample of the flux from the primary line. That flux induces a secondary voltage. Windings in current transformers are loosely coupled: the mutual flux is much smaller than the leakage flux. The voltage and current ratios do not apply although the secondary current is directly proportional to the primary. Current transformers must be short-circuited at all times since very high voltages can appear across their terminals.
ELEN 3441 Fundamentals of Power Engineering
Spring 2008