You are on page 1of 65

POWER SYSTEM

FAULTS
POWER SYSTEM FAULTS
Power substations as a target of study consists of some
elements like Transmission Lines, Bus Bars, Power
Transformers, Outgoing Feeders, and Bus Couplers.
Regardless of the design and the systematic preventive
maintenance procedures instituted, failures due to
abnormal or fault conditions do occur
Fault are intolerable power conditions (other than
steady-state or rated ones) to which the power system or
requirement are subjected.

General causes of power system
faults

1- Fault Current
Healthy insulation in the equipment is subjected to either transient
over voltages of small time duration due to switching and lightning
strokes, direct or indirect. Failure of insulation may be happened,
resulting in very high fault current. This current may be more than
10 times the rated or nominal current of the equipment.
2- Insulation Aging
Aging of power equipments may cause breakdown of its insulation
even at normal power frequency voltage.

General cause of power system
faults (contd)
3- External Causes
External object such as bird, kite, or tree branch are
considered as external cause of fault. These objects
may span one conductor and ground causing single
line to ground fault (phase-earth) or span two
conductors causing phase-phase fault


Fault Effects

The fault must be cleared as fast as possible. Many
equipments may be destroyed if the fault is not cleared
rapidly. The dangerous of the faults depends on the
type of the fault, as example the three phase short
circuit is the most dangerous fault because the short
circuit current is maximum. Some of the effects of short
circuit current are listed here under.
Fault Effects
1- Due to overheating and the mechanical forces
developed by faults, electrical equipments such as bus
bars, generators, transformers will be damaged
2- Negative sequence current arises from
unsymmetrical faults will lead to overheating.
3- Voltage profiles may be reduced to unacceptable
limits as a result of faults. A frequency drop may lead
to instability

Fault Types

Fault can be classified due t as:
1- Permanent
2- Transient
Or due to PARTICIPATED PHASES as
1- Phase-Earth
2- Phase-Phase
3- Phase-Phase-Earth
4- Three-Phase or Three-Phase-Earth

Broad categorization of Fault Types
Fault may be categorized broadly into 2 types:
Symmetrical or balanced faults
Asymmetrical or unbalanced faults
Broad categorization of Fault Types
Balanced (3) Faults
RARE :- Majority of Faults are Unbalanced
CAUSES :-
1. System Energisation with Maintenance Earthing
Clamps still connected.
2. 1 Faults developing into 3 Faults
Line - Line - Line (5%)
3 Phase; Ia + Ib + Ic = 0 and Va = Vb = Vc

Broad categorization of Fault Types
3 FAULTS MAY BE REPRESENTED BY 1 CIRCUIT
This is valid because system is maintained in a BALANCED state
during the fault
Voltages equal and 120 apart
Currents equal and 120 apart
Power System Plant Symmetrical
Phase Impedances Equal
Mutual Impedances Equal
Shunt Admittances Equal

Broad categorization of Fault Types
Unbalanced Faults
Unbalanced Faults may be classified into
SHUNT FAULTS and SERIES FAULTS.

SHUNT FAULTS:
Line to Ground
Line to Line
Line to Line to Ground

Broad categorization of Fault Types
Broad categorization of Fault Types
Causes :
1) Insulation Breakdown
2) Lightning Discharges and other Overvoltages
3) Mechanical Damage
During unbalanced faults, symmetry of system Is
lost therefore single phase representation is no
longer Valid

Broad categorization of Fault Types
SERIES FAULTS OR OPEN CIRCUIT:
Single Phase Open Circuit
Double Phase Open Circuit
Causes :
1) Broken Conductor
2) Operation of Fuses
3) Maloperation of Single Phase Circuit Breakers




Characteristics of Faults

A fault is characterized by:
Magnitude of the fault current
Power factor or phase angle of the fault current

The magnitude of the fault current depends upon:
The capacity and magnitude of the generating sources
feeding into the fault
Characteristics of Faults

The system impedance up to the point of fault or
source impedance behind the fault
Type of fault
System grounding, number and size of overhead
ground wires
Fault resistance or resistance of the earth in the case
of ground faults and arc
resistance in the case of both phase and ground faults

Characteristics of Faults
The phase angle of the fault current is dependent upon:
For phase faults: - the nature of the source and
connected circuits up to the fault location and
For ground faults: - the type of system grounding in
addition to above.


Necessity for fault calculations
Fault calculations are done primarily for the following:
To determine the maximum fault current at the point of
installation of a circuit breaker and to choose a
standard rating for the circuit breaker (rupturing)
To select the type of circuit breaker depending upon
the nature and type of fault.

Necessity for fault calculations
To determine the type of protection scheme to be
deployed.
To select the appropriate relay settings of the
protection scheme.
To co-ordinate the relay settings in the overall
protection scheme of the system

Necessity for fault calculations
The calculation is not only limited to present system
requirements but also meet:
The future expansion schemes of the system such as
addition of new generating units
Construction of new transmission lines to evacuate
power.
Construction of new lines to meet the load growth and
or Construction of interconnecting tie lines
Necessity for fault calculations
Basically, there are two approaches to fault
calculations. These are:
(a) Actual reactance or impedance method
(b) Percentage reactance or impedance method or per
unit (p.u) reactance or impedance method.
Machine and Transformer impedance or reactance are
always noted in percentage values on the nameplate.
Hence the latter method is considered for our
calculation.
Per Unit System
Power system quantities such as voltage,
current and impedance are often expressed in
per unit or percent of specified values.
Per unit quantities are calculated as:




Value Base
Value Actual
Value Per Unit =





Per Unit Values
base
pu
S
S
S
=
base
pu
I
I
I
=
base
pu
V
V
V
=
base
pu
Z
Z
Z
=
Z
Z
2
base
base
base
pu
V
S
Z
Z = =
pu
base
2
base
pu base
Z
S
V
Z Z = = Z
Conversion of Per Unit Values
Per Unit System
Per Unit System
Usually, the nominal apparent power (S) and
nominal voltage (V) are taken as the base values for
power (S
base
) and voltage (V
base
).
The base values for the current (I
base
) and
impedance (Z
base
) can be calculated based on the
first two base values.
100% Z
base
actual
%
=
Z
Z

The percent impedance
e.g. in a synchronous generator with 13.8
kV as its nominal voltage, instead of
saying the voltage is 12.42 kV, we say the
voltage is 0.9 p.u.

Simplified:
Concerns about using phase or line voltages are
removed in the per-unit system
Actual values of R, X
C
and X
L
for lines, cables, and
other electrical equipment typically phase values.
It is convenient to work in terms of base VA (base
volt-amperes)
,
3
3
B
B
B
B B B
V
S
I
I V S
=
=
( )
B
B
B
B
B
B B B
S
V
I
V
Z
Z I V
2
3 /
3
= =
=
Usually, the 3-phase S
B
or MVA
B
and line-to-line V
B
or kV
B

are selected
I
B
and Z
B
dependent on S
B
and V
B

The impedance of individual generators &
transformer, are generally in terms of
percent/per unit based on their own ratings.
Impedance of transmission line in ohmic
value
When pieces of equipment with various
different ratings are connected to a system, it
is necessary to convert their impedances to a
per unit value expressed on the same base.
( )
O
O
-
|
|
.
|

\
|
= = Z
V
S
Z
Z
Z
old
B
old
B
old
B
old
pu
2
( )
O
O
-
|
|
.
|

\
|
= = Z
V
S
Z
Z
Z
new
B
new
B
new
B
new
pu
2
new
B
new
B
V base voltage new &
S base power new on the impedance unit per new the be
new
pu
Z
old
B
old
B
V base voltage &
S base power on the impedance unit per the be
old
pu
Z
1
2
Change of Base
2
|
|
.
|

\
|
|
|
.
|

\
|
=
new
B
old
B
old
B
new
B
old
pu
new
pu
V
V
S
S
Z Z
|
|
.
|

\
|
=
old
B
new
B
old
pu
new
pu
S
S
Z Z
From (1) and (2), the relationship between the old
and the new per unit value
If the voltage base are the same,
Change of Base

2
) (
2
) (
) (
) (
) ( ) (
* *
new base
old base
old base
new base
old pu new pu
KV
KV
MVA
MVA
Z Z =
Other base quantites :-
kA in
kV . 3
MVA
Current Base
Ohms in
MVA
) (kV
Z Impedance Base
b
b
b
b
2
b
b
= =
= =

Per Unit Values = Actual Value


Base Value
Current Unit Per
) (kV
MVA
. Z
Z
Z
Z Impedance Unit Per
KV
KV
kV Voltage Unit Per

MVA
MVA
MVA MVA Unit Per
b
a
p.u.
2
b
b
a
b
a
p.u.
b
a
p.u.
b
a
p.u.

= =
= = =
= =
= =
If Z
T
= 5%
with Secondary S/C
5% V
(RATED)
produces I
(RATED)
in Secondary.
V
(RATED)
produces 100 x I
(RATED)
5
= 20 x I
(RATED)
If Source Impedance Z
S
= 0
Fault current = 20 x I
(RATED)

Fault Power = 20 x kVA
(RATED)

Z
T
is based on I
(RATED)
& V
(RATED)

i.e. Based on MVA
(RATED)
& kV
(RATED)

is same value viewed from either side of transformer.

(1) To calculate the p.u impedance and % impedance
of a transmission line at 100 MVA
base Line voltage 330 KV
Line length 200 Kms
Line resistance /Km = 0.06 ohms/Km
Line reactance /Km = 0.4 ohms/Km


Z = R + jX
For the 200kms line length
Z = 200 (0.06 + j 0.4)
= 12 + j 80
|Z| = \ [(12)
2
+ (80)
2
] = 80.895 ohms

Zp.u = Z x MVA base
(KV)
2
base

= 80.895 x 100
(330)
2
= 0.0743 p.u
%Z = 0.074 x 100
= 7.43


(2)To calculate the p.u impedance to a 100 MVA base
Given four generators; 90MVA, 11KV of 15%
impedance each connected to step up transformers
of 90MVA 11KV/330KV of 14% impedance. Calculate
the fault current at F.

Assumed MVA = 100
%Z generators = 15 on 90 MVA base
or Z
g
p.u = 0.15 on 90 MVA base

Z
g
p.u on 100 MVA base will be:
(Z
g
p.u)
base2
= (Z
g
p.u)
base1
x MVA base2
MVA base1
(Z
g
p.u)
100
= 0.15 x 100
90
= 0.167

%Z transformers = 14 on 90 MVA base
or Z
t
p.u = 0.14 on 90 MVA base

Z
t
p.u on 100 MVA base will be:
(Z
t
p.u)
base2
= (Z
t
p.u)
base1
x MVA base2
MVA base1
(Z
t
p.u)
100
= 0.14 x 100
90
= 0.156

The system reduces as follows

Z
total
= 0.323
4
= 0.08075
Total p.u impedance at F = 0.08075 = Z
total

Fault MVA at F = Base MVA
Z
total

= 100 MVA
0.08075
= 1238.4 MVA

Current at F = Fault MVA x (10)
3
u
\3 x system voltage (KV) at point of fault

= 1238.4 x (10)
3

\3 x 330
= 2166.638Amps

MORE EXAMPLES IN YOUR LECTURE BOOK,
PLEASE.

You might also like